Air-Cooled Condensers

DESCRIPTION

Capacities to 10 Tons

9AB Air-Cooled Condensers available in nominal capacities of 5, 7% and 10 tons are designed for verti­ cal installations with horizontal air flow. They may be located in any area having unobstructed air circula­ tion; the low silhouette permits installation in varied ground or roof locations. Each unit consists of a direct drive motor (or motors), fan (or fans), fan guards, motor mounts, condenser coil with integral subcooling circuit, wind deflector, and electrical junction box. Weather Armor* enclosures (which are also provided for 09DC016) have a baked enamel finish which pro­ vides maximum weather protection.

Capacities 15 Tons and Over

09DC Air-Cooled Condensers are available in 15-, 20-, 25-, 30and 40-ton sizes. The 25-, 30and 40-ton sizes are designed for use in multiples to give capacities of 50, 60 and 80 tons. Each size has three direct drive fans, three motors and motor mounts, three guards, a junction box, and a condenser coil with integral sub­ cooling circuit. The 20-, 25-, 30and 40-ton units, all using vertical air flow, may have 2 or 3 circuits, each with an integral subcooling circuit. Each circuit may be used as a separate condenser for a single system. Double-weight, hot dipped, galvanized steel enclosures give maximum protection.

FEATURES

Multiple Fans and Motors provide inexpensive, re­ liable system control in intermediate seasons. Standby protection is provided in case one fan motor fails.

Subcooling permits greater liquid lift in vertical risers without liquid flashing. Special coil circuiting cools liquid refrigerant below the saturated condensing temperature, extending system capacity without in­ creasing motor horsepower.

Direct Drive Fans require no tensioning device or pulleys. Alignment problems, belt maintenance, and friction loss are eliminated.

Three Types of Head Pressure Control (Accessory) are available to maintain a refrigeration load by hold-

ing a minimum head pressure and reducing condenser capacity at low outdoor temperatures.

1.Motormaster Electronic Control (9AB6, 8, 12 and 09DC016, single-phase) modulates condenser fan motor speed from zero to full rpm.

2.Fan Cycling Control cycles one fan (9AB8, 12) or

two fans (09DC) for control during intermediate seasons.

3. Head Pressure Control Damper (09DC024, 084), mounted below unit at the uncontrolled fan section, further reduces capacity.

• Winter Start Control — Optional package permits start-up of compressor regardless of low temperatures.

© Carrier Corporation 1966

•SINGLE FEATURE SHEET AVAILABLE

Form 9AB, 09DC-2P

PHYSICAL DATA

UNIT

 

 

9 AB

 

 

 

 

09DC

 

 

09DC054

 

09DC064

09DC084

 

 

 

 

 

 

 

 

 

 

(T wo

 

(Two

(Two

 

6

8

12

016

024

 

028

034

044

 

 

 

 

028’s)

 

034*s)

044’s)

 

 

 

 

 

 

 

 

 

 

 

 

RATING (tons)*

 

6.8

10.5

13.8

15.8

22.1

 

28.0

35.8

46.7

56.0

 

71.7

93.4

NET WEIGHT (lb)t

 

215

315

410

550

854

 

904

1225

1600

1808

 

2450

3200

FAN (Prop.), No.

 

1

2

2

3

3

 

3

3

3

6

 

6

6

Prop. Diom (in.)

 

22

22

22

22

26

 

30

30

32

30

 

30

32

Rpm

 

1120

1120

1 120

1120

1140

 

1140

1140

1140

1140

 

1140

1140

Cfm

 

4400

6600

8800

13,000

18,200

 

25,200

28,200

31,000

50,400

 

56,400

62,000

MOTORS, No. ... Hp

 

1.. Vs

2...Vs

2... Vs

3...V

3...%

 

3 . 1

3...1

3...1

6...1

 

6...1

6...1

COILS, Type

 

 

3-row

 

 

3-row

 

 

 

4-row

3-row

4-row

No.

 

 

1

 

 

2

 

 

2

 

4

4

Face Area (sq ft)

 

9 0

13 5

18 0

26.2

35.4

 

39 0

49.6

60.4

78 0

 

99 2

120.8

DIMENSIONS (ft-in.)

 

 

 

 

 

 

 

 

 

9-lOV.

 

 

 

 

Length (each)

A

3-7Vs

5-2 Vs

6-8Vs

6-9Vs

9- 7 %

 

9- 1 %

9- 7V.

9- 1 %

 

9- 7 %

9-lOV.

 

9-lOVst

 

9-lOVst

 

 

 

 

 

 

 

 

 

 

 

 

 

Width (module)

B

3-1 Vs

3-1 Vs

3-1 Vs

4-6 V.

3-1IV.

 

3-1IV.

4-lOV.

6- OV.

3-1IV.

 

4-lOV.

6- OV.

Height, w/o Legs

C

3-2Vi6

3-2 Vs

3-2Vs

1-8V.

2- 4 Vs

 

2- 4 Vs

3- iVs

3- r/s

2- 4 Vs

 

3- iVs

3- r/s

Adj Stand (in.)

D

 

lOV or

16 V.

12Vsor 19Vs

16 or 24

 

16 or 24

18 or 26

20 or 28

16 or 24

 

18 or 26

20 or 28

Data common to 1- and 2-module units.

*Tons of refrig effect at 30 F temp diff with 1 20 compr heat rejec­ tion factor for R-22.

tWithout damper or refrigerant.

iFor three-circuit coil.

**Use 50/50 split for single circuit. 09DC034 coil 40/40/20 split may be field modified into 40/60 split.

tt80% liquid, 20% vapor at 90 F. NOTES:

1.For 09DC024 thru 084, use maximum adjustable stand height when using a damper section.

2.Certified dimension drawings available on request.

DIMENSIONS

9AB6,8,12

09DC016, 024, 028,

024,028.034,044

024,028

034

044

 

034, 044

50/50

63/37

40/40/20

38/38/24

 

COIL SPLIT

COIL SPLIT

COIL SPLIT

COIL SPLIT

5/„ ODF LIQUID OUTLET

 

 

 

 

(09DC0I6 ONLY)

 

 

 

 

AIR FLOW

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

KNOCKOUT

 

 

 

 

 

OUTLET

 

1/2-024,028

ODF

7/^' ODF Vg" ODF

7/g ODF

 

7/"-034, 044

 

 

 

'''a' ODE

 

 

 

 

S3 SPACE FOR AIR FLOW

RIGHT END VIEWS

 