Bryan Boilers RV450, RV350, RV400 User Manual

RV SERIES FORCED DRAFT INDIRECT
WATER HEATERS (RV350 - RV450 )
EFFECTIVE DATE:
REPLACES:
3/15/04
7/24/03
NOTES:
1. ALL DIMENSIONS ARE IN INCHES. THOSE IN PARENTHESES ARE CENTIMETERS.
2. LOCATION DIMENSIONS ARE ALL ±1/2".
3. GAS TRAIN, CONTROL AND BURNER CONFIGURATION WILL VARY DEPENDING ON JOB SPECIFICATIONS & CONDITIONS.
4. DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONSULT FACTORY FOR CERTIFIED DIMENSIONS.
5. ALL FLANGES ARE 150# UNLESS OTHERWISE NOTED.
6. SEE FORMS 1594 AND 1595 FOR FLOW RATES AND PRESS. DROPS OF 2 AND 4 PASS HEAT EXCHANGERS.
1
4 1/2"
D
A
25 1/2"
(64.8)
B
20"
(50.8)
50"
(127.0)
9 1/4"
(23.5)
PLAN VIEW
14
8
17
3
5
G
SUPPLY
7
H
C
SERVICE AREA
9"
(22.86)
32"
(81.3)
10
J
(SEE DETAIL 1)
2
2 1/8"
3" NPT
4 PASS EXCH. HEAD (STD.)
6 1/4"
2 PASS EXCH. HEAD (OPT.)
(121.9)
48"
BURNER
MINIMUM TUBE REMOVAL CLEARANCE
16
(SEE NOTE #6)
(SEE NOTE #6)
DETAIL 1
1/2" NPT DRAIN
4" NPT
4
20
9
87 1/2"
(222.3)
18
15
19
REAR VIEW
1. PROBE TYPE L.W.C.O.-
2. FORCED DRAFT BURNER
3. RELIEF VALVE
4. EXPANSION TANK (LOOSE)
5. CONTROL TAPPINGS 3/4" NPT
BOILER MODEL
A-LENGTH OVER JACKET
B-FLUE LOCATION
C-FLUE DIAMETER
D-LENGTH OVER BASE
G-SUPPLY / RETURN NOZZLE SIZE
H-BURNER EXTENSION
J-HT. EXCH. REMOVAL CLR.
BRYAN BOILERS
90"
(228.6)
STOP VALVE
12
6. JACKET ACCESS PANELS
7. PRESS./TEMP. GAUGE
8. CLNOUT./INSP. OPNG.-1 1/2"NPT
9. ELEC. ENCLOSURE-
RETURN
6
33 1/2"
(85.1)
LEFT SIDE VIEW
12. FILL VALVE
13. OIL PUMP LOCATION
14. LIFTING LUGS
15. DRAIN CONNECTION 2" NPT10. VENT/EXP. TANK CONN. 1" NPT 20. DRAIN VALVE (BY OTHERS)
RV350WT RV400WT
98"
(248.9)
16"
(40.6)
16"
(40.6)
130 1/2"
(331.5)
4" FLG
(10.2) (15.2)
CONSULT FACTORY FOR BURNER EXTENSION APPLICATIONS
101"
(256.5)
783 NORTH CHILI AVE
PERU, INDIANA 46970
G
FRONT VIEW
16. INDIRECT HEAT EXCHANGER
17. HEIGHT OVER SUPPLY
18. FLAME OBSERVATION PORT
19. COMB. CHAMBER DRAIN 1" NPT
111"
(281.9)
18 3/4"
(47.6)
16"
(40.6)
143 1/2"
(364.5)
6" FLG
114"
(289.6)
:
.
O
N
R
E
D
R
O
ORDER REV. NO.:
FORM NO.:
1769
80 1/8"
(203.5)
RV450WT
120 1/2"
(306.1)
18 3/4"
(47.6)
16"
(40.6)
153 1/4"
(389.3)
6" FLG
(15.2)
124"
(315.0)
13
BRYAN BOILERS
RV SERIES FORCED DRAFT
INDIRECT WATER HEATERS
BOILER MODEL RV350 RV400 RV450
INPUT MBH 3,500 4,000 4,500
(KW) 1,025.5 1,172.0 1,318.5
OUTPUT* MBH 2,800 3,200 3,600
(KW) 820.4 937.6 1,054.8
BOILER HORSEPOWER HP 84 96 108
(KW) 819.7 936.8 1,053.9
TUBE DIAMETER INCHES 1.50 1.50 1.50
(CM) 3.81 3.81 3.81
NUMBER OF TUBES 47 55 61
PRESSURE VESSEL
VOLUME GAL 146 169 181
(L) 552.6 639.7 685.1
Form # >> 1769
Date >> 4/5/2004
HEATING SURFACE SQ FT 419 490 544
(SQ M) 38.9 45.5 50.6
INDIRECT HEAT EXCHANGER
UTF2-68-(#) OR INCHES 92 105 115
UTF4-64-(#) (CM) 233.7 266.7 292.1
OPERATING WEIGHT LBS 9,317 9,729 10,309
(KG) 4,226.3 4,413.1 4,676.2
SHIPPING WEIGHT LBS 8,100 8,320 8,800
(KG) 3,674.2 3,774.0 3,991.7
RELIEF VALVE TYPICAL - 30 PSIG (206.8 KPA)
QUANTITY (1) 740 (1) 740 (2) 741
SIZE INCHES 2 x 2½ 2 x 2½ 1½ x 2
(CM) 5.08 x 6.35 5.08 x 6.35 3.81 x 5.08
CAPACITY-TOTAL MBH 5,250 5,250 5,800
(KW) 1,538.2 1,538.2 1,699.4
RELIEF VALVE TYPICAL - 125 PSIG (861.8 KPA)
QUANTITY (1) 174A (1) 174A (1) 174A
SIZE INCHES 1¼ x 1¼ 1¼ x 1¼ 1½ x 1½
(CM) 3.17 x 3.17 3.17 x 3.17 3.81 x 3.81
CAPACITY-TOTAL MBH 5,370 5,370 6,460
(KW) 1,573.4 1,573.4 1,892.8
* Output based on nominal 80% of input. Actual combustion efficiencies will vary and are fuel dependant. (#) - - Indicates length of exchanger.