Broan RMIP45, RMIP33 User Manual

0 (0)
Broan RMIP45, RMIP33 User Manual

INSTALLATION INSTRUCTIONS

HB0031

MODELS RMIP33 AND RMIP45

! INTENDED FOR DOMESTIC COOKING ONLY !

READ AND SAVE THESE INSTRUCTIONS

INSTALLER: LEAVE THIS MANUAL WITH HOMEOWNER. HOMEOWNER: USE AND CARE INFORMATION ON PAGES 12 AND 13.

Broan-NuTone LLC, 926 West State Street, Hartford, WI 53027 (1-800-637-1453) NuTone Inc., 4820 Red Bank Road, Cincinnati, OH 45227 (1-800-543-8687)

Broan-NuTone Canada Inc., 1140 Tristar Drive, Mississauga, ON L5T 1H9 (1-888-882-7626)

REGISTER YOUR PRODUCT ON LINE AT: www.broan.com/register

V05861 rev G

! WARNING

! WARNING

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING*:

1.Use this unit only in the manner intended by the 1. SMOTHER FLAMES with a close-fitting lid,

manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.

2.Before servicing or cleaning unit, switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.

3.Installation work and electrical wiring must be done by qualified personnel in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

4.Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

cookie sheet or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. IF THE FLAMES DO NOT GO OUT IMMEDIATELY, EVACUATE AND CALL THE FIRE DEPARTMENT.

2.NEVER PICK UP A FLAMING PAN – You may be burned.

3.DO NOT USE WATER, including wet dishcloths or towels – This could cause a violent steam explosion.

4.Use an extinguisher ONLY if:

A.You own a Class ABC extinguisher and you know how to operate it.

B.The fire is small and contained in the area where it started.

C.The fire department has been called.

D.You can fight the fire with your back to an exit.

* Based on “Kitchen Fire Safety Tips” published by NFPA.

CAUTION

1.For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

5.When cutting or drilling into wall or ceiling, do not 2. To avoid motor bearing damage and noisy and/or

 

appropriate for the size of the surface element.

8.

Because of the high exhausting capacity of this

 

 

unit, you should make sure enough air is entering

 

damage electrical wiring and other hidden utilities.

 

 

 

the house to replace exhausted air by opening a

 

 

window close to or in the kitchen.

 

 

unbalanced impellers, keep drywall spray,

6.

Ducted fans must always be vented to the

 

construction dust, etc. off power unit.

 

outdoors.

 

 

3.

Your insert motor has a thermal overload which will

7.

Do not use this unit with any solid-state speed

 

automatically shut off the motor if it becomes

 

control device other than RMIPWC optional wall

 

overheated. The motor will restart when it cools

 

mounted control.

 

 

 

down. If the motor continues to shut off and restart,

8.

To reduce the risk of fire, use only metal ductwork.

 

have the insert serviced.

9.

This unit must be grounded.

 

 

4.

The minimum hood distance above cooktop must

 

 

 

 

 

not be less than 24”. A maximum of 30” above

 

 

 

 

 

cooktop is highly recommended for best capture of

TO REDUCE THE RISK OF A RANGE TOP

 

cooking impurities.

GREASE FIRE:

 

 

5.

Two installers are recommended because of the

a)

Never leave surface units

unattended

at high

 

large size and weight of this unit.

 

settings. Boilovers cause

smoking and

greasy

6.

To reduce the risk of fire and to properly exhaust

 

spillovers that may ignite. Heat oils slowly on low or

 

air, be sure to duct air outside – Do not exhaust air

 

medium settings.

 

 

 

into spaces within walls or ceiling or into attics,

b)

Always turn hood ON when cooking at high heat or

 

crawl space or garage.

 

when cooking flaming foods.

 

7.

This product is equipped with a thermostat which

 

 

 

 

 

may start blower automatically. To reduce the risk

c) Clean ventilating fans frequently. Grease

should

 

of injury and to prevent power from being switched

 

not be allowed to accumulate on fan or filter.

 

on accidentally, switch power off at service panel

d)

Use proper pan size. Always use cookware

 

and lock or tag service panel.

 

 

 

 

 

 

9.

To reduce the risk of fire and electrical shock, the

 

 

 

 

 

Broan Elite models RMIP33 and RMIP45 must be

 

 

 

 

 

installed only with Broan interior blower models P5

 

 

 

 

 

or P8; Broan exterior models 331H, 332H, 335 or

 

 

 

 

 

336; Broan in-line blowers models HLB3, HLB6,

 

 

 

 

 

HLB9, HLB11. Other blowers cannot be substituted.

 

 

 

 

 

(Blowers sold separately).

 

 

 

 

10.

Use with approved cord-connection kit only.

 

 

 

 

11.

Please read specification label on product for

 

 

 

- 2 -

further information and requirements.

 

 

 

 

- RMIP33 AND RMIP45 INSERT SYSTEM -

INTERIOR BLOWERS

Model 647

 

Model 643

(7” Rd wall cap)

 

(8” Rd wall cap)

 

Model 634 or 644

Model 415

(roof cap)

8” Rd

 

adjustable

7” Rd adjustable

 

elbow (optional)

elbow (optional)

 

 

 

 

8” Rd

Model 407

 

standard

(7” Rd x 24’’

 

duct

section)

 

 

7” Rd metal

 

8” Rd metal

 

flexible duct

flexible duct

 

(optional)

(optional)

 

 

Model 412

Model 413

Model 459

transition

transition

transition

(31/4” x 10” to 7”)

(31/4” x 10” to 8”)

(31/4” x 14” to 8”)

 

 

Adapter and damper 31/4’’ x 14’’

Adapter and damper 31/4’’ x 10’’

 

(supplied with P8 blower)

(supplied with P5 and P8 blowers)

 

 

Flow deviator (supplied with P5 and P8 blowers)

RML3336S, RML3342S,

RML4548S, RML4554S or

RML4560S

Custom Hood Liner (optional)

 

RBFIP Series

 

Baffle Filters

 

(Optional)

RMIPWC

Model P5

Wall control

(Optional)

single-blower

 

(500 cfm)

RMP Series Backsplash (Stainless Steel wall covering with warming shelves. Optional)

RMIP33 OR RMIP45

INSERT

Rough-in kit

(supplied with P5 and P8 blowers)

Model P8 dual-blower (900 cfm)

NOTE: The dual blower P8 can be installed either with 7’’ round or 8’’ round ductwork.

For optimal air and quiet sound performance, use 8’’round ductwork.

HL0067

- 3 -

 

- RMIP33 AND RMIP45 INSERT SYSTEM -

IN-LINE AND EXTERIOR BLOWERS

Model 437

 

Model 441

 

(10” Rd wall cap)

(High capacity roof cap)

Model HLB9 (800 cfm)

 

or HLB11 (1100 cfm)

Model 335 (1200 cfm)

 

or 336 (1500 cfm)

 

in-line blower

 

Model 331H (600 cfm) exterior blower

 

(includes two 8” x 12” to

 

or 332H (900 cfm)

 

10’’ round transitions)

 

exterior blower

 

 

Model 441

 

 

(10” Rd wall cap)

 

 

Model HLB6 (600 cfm) in-line blower

(includes two 4½” x 18½” to 10’’ round transitions)

Model 418 10” Rd adjustable elbow

Model HLB3 (280 cfm) (optional) in-line blower

(includes one 8” to 10” round transition)

10” Rd metal flexible duct (optional)

RMIPWC Wall control (Optional)

RBFIP Series Baffle filters (Optional)

RMP Series Backsplash (Stainless Steel wall covering with warming shelves. Optional)

 

Model 421

 

(10” Rd. vert.

 

in-line damper)

Model 410

Recommended

for use with

(10” Rd duct

exterior blowers

- 2ft. sections)

RML3336S, RML3342S,

RML4548S, RML4554S or

RML4560S

Custom Hood Liner (optional)

RMIP33 OR RMIP45

INSERT

332KR in-line and exterior blower rough-in kit - Purchase separately.

HL0068

- 4 -

 

1. SELECT BLOWER OPTION AND INSTALL DUCTWORK

Either an interior or exterior blower or in-line blower may be used with this insert.The insert model RMIP33 or RMIP45 must be installed with blower models P5, P8, HLB3, HLB6, HLB9, HLB11, 331H, 332H, 335 or 336 only. Other blowers cannot be substituted. (Blowers sold separately).

Plan where and how the ductwork will be installed. Access to the top of the hood is preferred for connection of ductwork. As an alternative, flexible metal ductwork may be used.

If installing in-line blower, refer to instructions packed with in-line blower and follow steps 1 up to 8, 13, 14, 16, 17, 19 and up of this manual.

Install proper-sized ductwork, elbows and roof or wall cap for the type of blower you are installing. Use round ductwork, with a short section (about 4’ expanded) of flexible metal duct (optional) for attachment to the transition. Use screws to attach flexible metal duct to the rigid duct. Use 2” duct tape to seal duct joints.

The minimum hood distance above cooktop must not be less than 24”. A maximum of 30” above cooktop is highly recommended for best capture of cooking impurities.

Distances over 30” are at the installer and users discretion.

Roof cap

7” or 8” round ducts with 7” or 8” round

metal flex. duct (optional)

3 1/4”x 10”to 7”or 8”transition or 3 1/4”x 14”to 8”transition

Insert with

Wall interior blower cap

24” minimum

above cooking surface

HH0038A

MODEL P5 (SINGLE) OR

P8 (DOUBLE) INTERIOR BLOWER

TYPICAL DUCTWORK

Exterior blower

 

 

 

 

 

 

 

 

 

 

Roof cap

 

 

 

 

 

 

10” round duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10” round metal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flex. duct

 

10” round metal

 

 

 

 

 

 

 

 

 

 

 

 

 

flex. duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(optional)

 

(optional)

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Insert with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exterior blower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Insert

 

 

 

 

 

 

 

 

 

24” minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24” minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above

 

 

 

 

 

 

 

 

 

cooking surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cooking surface

 

 

 

HH0039A

 

HH0058A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL 331H, 332H, 335 OR

 

MODEL HLB3, HLB6, HLB9 OR HLB11

336 EXTERIOR BLOWER

 

 

 

IN-LINE BLOWER

TYPICAL DUCTWORK

 

 

TYPICAL DUCTWORK

2. PREPARE THE INSTALLATION

Make sure that the following items are included:

-Insert

-Accessories:

Filters (3 for RMIP33 model, 4 for RMIP45 model)

Bag of parts including:

(4)lock nuts, (1) wire clamp, (8) no. 8 x 3/4” standard screws, (2) wire connectors,

(2) no. 6 x 1/2” standard screws, (8) no. 8 x 3/8” screws. Discard items not used. Parts sold separately:

-Interior blower Model P5 includes blower, rough-in kit, flow deviator and 31/4” x 10” adapter

-Interior blower Model P8 includes blower, rough-in kit, flow deviator and 31/4” x 10” adapter and 31/4” x 14” adapter

-In-line blower assembly HLB3, HLB6, HLB9 or HLB11 (all include transition)

-In-line blower rough-in plate model 332KR, required for all In-line or Exterior Blowers

-Exterior blower assembly 331H, 332H, 335 or 336

-Halogen lights 120V, 50W, PAR 20 (2 for RMIP33 model and 3 for RMIP45 model)

-Custom hood liner Model RML3336S, RML3342S, RML4548S, RML4554S or RML4560S (optional)

-Backsplash RMP Series (optional)

-RMIPWC Remote control (optional)

-Baffle filters RBFIP Series (optional)

-Transitions, ducts (rigid and flexible), elbows, dampers, wall and roof caps. Refer to page 3 and 4 for a complete list of venting options and model numbers.

NOTE: During installation, protect countertop and/or cooktop.

- 5 -

3. INSTALL BACKSPLASH (OPTIONAL)

It is recommended to install the backsplash before the custom hood insert. The custom hood will cover the backsplash top mounting screws. In order to be able to install the backsplash, make sure you have at least 18’’ clearance between bottom of custom hood and range control panel or cooktop. (See instructions packed with backsplash.)

4. CUSTOM HOOD PREPARATION

! WARNING

When building a custom hood, always follow all applicable construction codes and standards.

The custom hood frame must be sized to the shape and total weight of the insert assembly. Refer to the table below for total weight of the insert, according to the type of blower choosen.

INSERT MODEL

WITH P5 INT. BLOWER

WITH P8 INT. BLOWER

WITH IN-LINE OR EXT. BLOWERS (ROUGH-IN PLATE ONLY)

RMIP33

41 LB

49 LB

27 LB

RMIP45

49 LB

57 LB

35 LB

Start with the custom hood base, because its position will determine the height of the insert. We recommend the base of the custom hood should be 3/4 inch thick plywood. If an optional custom hood liner will be installed, we recommend the sides and front of the custom hood to be 3/4 inch thick, assuming standard cabinet widths. If the optional custom hood liner will not be installed, the custom hood side and front thickness is at the installer’s discretion.

Run power cable to installation location. Stub out a 4 foot length of electrical cable below the custom hood.

If the RMIPWC optional remote control will be installed, run electrical cable from the insert to the remote control location. Stub out a 6 inch length from the remote control wall location. Refer to the remote control installation instruction.

Backsplash

(Optional)

Plywood base thickness: 3/4”

4” for liner installation

24” to 30” above cooking surface

Standard 36” h. cooktop

HH0037A

5. SUGGESTED CUSTOM HOOD INTERNAL FRAMEWORK

The mounting holes for the 2 top stud supports are located at 119/16” up from the insert base. The on center distance between the 2 studs is 301/4” for the RMIP33 insert model and 421/4” for the RMIP45 insert model.

The mounting holes for the rear stud support are located at 11/2” up from the insert base. See illustration beside.

Once the custom hood base and frame are done, finalize the custom hood.

1 1/2”

HH0040A

- 6 -

6. INSTALL CUSTOM HOOD LINER (OPTIONAL)

The liners are specially designed to protect the exterior base of the custom hood. To order, refer to the table below to find the right liner model number for your insert and width of custom hood. To view specific model information, including depths for each liner models, visit www.broan.com or contact Technical Support (phone number listed on front cover). To install, see instruction packed with custom hood liner.

The liner must be installed before the insert.

NOTE: On some liners models, front liner piece may overlap front insert flange. If so, remove the front liner piece, assemble insert, and reassemble front liner piece.

 

LINER MODEL

INSERT MODEL

CUSTOM HOOD

 

 

 

NOMINAL WIDTH

 

 

RML3336S

RMIP33

36’’

 

 

RML3342S

RMIP33

42’’

 

 

RML4548S

RMIP45

48’’

 

 

RML4554S

RMIP45

54’’

 

 

RML4560S

RMIP45

60’’

 

 

 

 

 

HA0038A

7. INSTALL THE RMIPWC REMOTE CONTROL (OPTIONAL)

The electrical connection for the remote control is located in front of the insert. Perform this connection before the insert installation. For installation details, see installation instructions included with the RMIPWC remote control.

HL0044

8. CUT THE HOLE IN CUSTOM HOOD BASE

 

 

If it is not done yet, cut a hole in the bottom of the cabinet, using

 

 

the dimensions shown beside.

 

 

 

 

INSERT MODEL NUMBER

A

 

 

3 1/2''

 

 

 

RMIP33

321/2’’

 

 

 

RMIP45

441/2’’

 

 

 

NOTES: 1. The notch shown in the inset must be cut only if the

 

 

RMIPWC optional remote control will be installed.

 

17 1/16''

16 3/8''

2. The recommended distance

from the back to

the

2 1/4''

A

rearmost cutout edge is 21/4’’ minimum.

 

min.

 

 

 

 

 

HD0084

 

9. INSTALL BLOWER (INTERIOR OR EXTERIOR BLOWER)

INTERIOR BLOWER:

Follow all subsequent steps of this manual.

EXTERIOR BLOWER:

Refer to instructions packed with exterior blower and follow steps 13, 14, 16, 17, 19 and

 

up of this manual.

- 7 -

10. REMOVE THE KNOCK-OUT OPENING (INTERIOR BLOWER)

Remove the knockout on rough-in plate. See picture below.

CAUTION

When using P5 blower, remove the 10’’ wide knockout (smaller part). If using P8 blower, remove the knockout corresponding to the ducting installed (10’’ or 14’’ adapter/damper).

14’’

KNOCKOUT

10’’

KNOCKOUT

HD0077

Removing vertical knockout opening on rough-in plate

11. INSTALL THE DEVIATOR (INTERIOR BLOWER)

Install the deviator as shown.

NOTE: To prevent the deviator from sliding out of the rough-in plate, put some tape on the deviator base after sliding it into the rough-in plate (provided with the P5 and P8 blower) opening. If installed correctly, the deviator will protrude about 1/8” above the rough-in plate.

HD0087

12. INSTALL THE ADAPTER (INTERIOR BLOWER)

Using two (2) no. 6 x 1/2’’ screws provided with insert, secure the adapter to the top of the rough-in plate. Remove tape from damper flap. Seal the adapter to the rough-in plate by using duct tape.

HD0005

 

HD0006

- 8 -

13. CONNECT WIRING (ALL BLOWERS)

! WARNING

Risk of electrical shock. Electrical wiring must be done by qualified personnel in accordance with all applicable codes and standards. Before connecting wires, switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally.

Position insert below the installed custom hood. Pull cable through hole in top of insert.

INTERIOR BLOWER: Remove the cable knock-out on the top of the rough-in plate. Remove rough-in plate wiring cover. Place the wire clamp in the knock-out hole, insert the cable through the wire clamp in the rough-in plate wiring box. Tighten the wire clamp to secure the cable.

Connect cable into wiring box using provided wire connectors.

Connect wires as follow: BLACK to BLACK, WHITE to WHITE and

GREEN or BARE wire under ground screw. DO NOT FORGET TO

CONNECT THE GROUND. Reinstall wiring cover.

HD0007

 

1

 

1) Ground screw

IN-LINE OR EXTERIOR BLOWER: Remove rough-in plate wiring cover and connect wiring (see instructions included with in-line or exterior blower).

14. INSTALL THE ROUGH-IN PLATE (ALL BLOWERS)

INTERIOR BLOWER: Carefully install the rough-in plate inside the top of the insert with four

(4) lock nuts. See picture beside.

HD0042

IN-LINE OR EXTERIOR BLOWER: Refer to instructions included with rough-in kit. Secure the rough-in plate inside the top of the insert with (4) lock nuts.

15. INSTALL THE TRANSITION (INTERIOR BLOWER)

Slide the transition over the adapter/damper. Seal the transition to the adapter/damper by using duct tape.

HD0091

- 9 -

16. DUCTING CONNECTION (ALL BLOWERS)

A.When there is access to the top of the hood, connect ductwork and seal connections with duct tape after Step 17 Install the insert.

B.When there is no access to the top of the hood, carefully pull down the metal duct through the custom hood base hole. Slide this duct over the transition (interior blower) or over the flange of the rough-in plate (in-line or exterior blower). Make sure the adapter/damper assembly enters the ducting. Seal the connection with duct tape.

HD0092

CAUTION

Take care not to kink ducting when installing insert (step 17).

17. INSTALL THE INSERT

 

If an optional wall control will be

 

installed, refer to its installation

 

instructions now. When

done,

 

continue the insert installation.

 

Install the insert inside the custom

 

hood and secure to the frame

 

by using the no. 8 x 3/4” mount-

 

ing screws provided. Start with

 

4 screws on top and finish with

 

2 on rear side. (See figure

 

beside for mounting screw spe-

REAR

cific locations.)

HD0085

TOP

 

 

 

CAUTION

Take care not to kink ducting or pinch electrical cable when installing insert.

18. INSTALL THE BLOWER (INTERIOR BLOWER)

The blower must be installed to the rough-in plate using (6) no. 8 x 3/8” screws for the single blower unit and (8) no. 8 x 3/8” screws for the dual blower unit. Remove the cover from the blower assembly. Remove the impeller(s) by pulling them out gently (see pictures below).

HD0021

 

HD0022

- 10 -

18. INSTALL THE BLOWER (INTERIOR BLOWER) (CONT’D)

Install (4) no. 8 x 3/8’’ screws into the location as shown in the pictures below (single blower or dual blower). Do not tighten screws down fully, leave a 1/8” gap. Hang blower unit onto blower plate (screws through the large part of the keyhole). Slide the blower to its position (screws in the small part of the keyhole). Tighten the (4) screws.

HD0044

Single blower (P5)

HD0045

Dual blower (P8)

Secure the blower by installing 2 more no. 8 x 3/8’’ screws for the P5 blower and 4 more no. 8 x 3/8’’ screws for P8 into the locations shown in the pictures below (single blower or dual blower). Reinstall impeller(s) and cover.

HD0080

Single blower (P5)

FOR DUAL BLOWER UNIT, MAKE SURE THE IMPELLERS ARE CORRECTLY INSTALLED, THE INSERT WILL NOT WORK PROPERLY IF REVERSED. Both impellers are different in the dual blower, one rotates clockwise and the other counterclockwise. Each wheel and motor have an arrow and a number on them, you have to match them correctly (see drawing beside).

HD0023

HD0081

Dual blower (P8)

FRONT

1

2

HD0023

! WARNING

Never plug the 2-prong blower cord to the 3-prong power supply cord.

Plug the power supply to the 3-prong male connector (A) and the blower unit into the 2-prong female receptacle (B) inside the insert.

A

B

HE0022

- 11 -

19. LIGHT BULBS

This insert uses 50W halogen lamps (120V, 50W, PAR 20) (Purchase separately). Install the lamps by rotating them clockwise into their socket holder.

20. INSTALL FILTERS

It is recommended to install side filters first and finish with center one(s). 1.Insert upper end of filter into the insert (finger sized cup side).

2.Raise lower end of filter to position it into grease rail inside of hood and pull. 3.While pulling the filter, slide it under the inner retaining piece.

Replacement filters are available from your dealer. See inside label insert for size and part number.

1

2

3

HD0086

HD0031

1

 

1) Finger sized cup

Baffle Filters

Baffle filters are available as an option. To order them, refer to the table below to find the right filter kit number for your insert. To install them, refer to instruction sheet included with baffle filter kit.

KIT NO.

INSERT MODEL

RBFIP33

RMIP33

RBFIP45

RMIP45

HD0011

21. USE AND CARE

BAFFLE FILTER (TYPICAL)

Grease filters and impeller(s).

The grease filters, impeller(s) and grease rail should be cleaned frequently. Use a warm detergent solution. Grease filters and impeller(s) are dishwasher safe.

Remove greasse filters by pushing them towards the back of hood and rotating downward. Stainless steel cleaning: How to maintain its « BRIGHT LOOK »

Do:

-Regularly wash surfaces with clean cloth or rag soaked with warm water and mild soap or liquid dish detergent.

-Always clean in the direction of original polish lines.

- Always rinse well with clear water (2 or 3 times) after cleaning. Wipe dry completely.

-You may also use a specialized household stainless steel cleaner.

Don’t:

-Do not use any steel or stainless steel wool or any other scrapers to remove stubborn dirt.

-Do not use any harsh or abrasive cleansers.

-Do not allow dirt to accumulate.

-Do not let plaster dust or any other construction residues reach the insert. During construction or renovation, cove the hood to make sure no dust sticks to stainless steel surface.- 12 -

21. USE AND CARE (CONT’D)

Avoid: when choosing a detergent

-Any cleaners that contain bleach will attack stainless steel.

-Any products containing : chloride, fluoride, iodide, bromide will deteriorate surfaces rapidly.

-Any combustible products used for cleaning such as acetone, alcohol, ether, benzol, etc., are highly explosive and should never be used close to a range.

22. OPERATION

Always turn your blower on before you begin cooking to establish an air flow in the kitchen. Let the blower run for a few minutes to clear the air after you turn off the range. This will help keep the whole kitchen cleaner and brighter.

 

 

 

 

 

 

 

 

 

 

HC0007

2

1

3

1)ON/OFF blower switch

2)Blower speed control

3)Halogen light switches

BLOWER

The blower is operated using two (2) controls or with the RMIPWC optional wall control.

Use the red, lighted on/off switch to start and stop the blower. When turned on, the blower will operate at the previous setting of the speed control.

Turn the speed control knob clockwise to decrease blower speed - counterclockwise to increase speed.

COOKTOP LIGHTING (HALOGEN)

A double set of ON/OFF switches controls the halogen lights.

The fron rocker controls the center light (for 45’’ inserts).The rear rocker controls both side lights (each switch controls one light for 33’’ insert). Select one, two or three lights for best cooking lighting.

Use PAR 20, 50W halogen bulbs (Purchase separately).

HEAT SENTRY

This unit is equipped with a Heat Sentry thermostat. This thermostat is a device that will turn on or speed up the blower if it senses excessive heat above the cooking surface.

1)If blower is OFF - it turns blower ON to HIGH speed.

2)If blower is ON at a lower speed setting – it turns the blower up to HIGH speed.

! WARNING

The HEAT SENTRY can start the blower even if the insert is turned OFF. In this case, it is impossible to turn the blower OFF with blower switch. If you must stop the blower, do it from the main electrical panel.

When the temperature level drops to normal, the blower will return to its original setting.

Test all insert switches. If a RMIPWC remote control is installed, test all its switches.

Finalize the custom hood.

RMIPWC REMOTE CONTROL (OPTIONAL)

An optional remote control is also available to operate your hood insert. For installation details, see installation instructions included with the RMIPWC remote control.

NOTE: When the RMIPWC remote control is connected to the insert, the control switches on the insert are no longer operational.

HC0006

1

2

3

1) Light switch

3) Blower speed control

2) Blower ON/OFF switch

 

- 13 -

WARRANTY

BROAN-NUTONE LLC ONE-YEAR LIMITED WARRANTY

Broan-NuTone LLC warrants to the original consumer purchaser of its products that such products will be free from defects in materials or workmanship for a period of one year from the date of original purchase. THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

During this one-year period, Broan-NuTone LLC will, at its option, repair or replace, without charge, any product or part which is found to be defective under normal use and service.

This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse, negligence, accident, improper maintenance or repair (other than by Broan-Nutone LLC), faulty installation or installation contrary to recommended installation instructions.

The duration of any implied warranty is limited to the one-year period as specified for the express warranty. Some states or provinces do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.

BROAN-NUTONE LLC’S OBLIGATION TO REPAIR OR REPLACE, AT BROAN-NUTONE LLC’S OPTION, SHALL BE THE PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. BROANNUTONE LLC SHALL NOT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE. Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state or province to another. This warranty supersedes all prior warranties.

To qualify for warranty service, you must (a) notify Broan-NuTone LLC at the addresses or telephone number stated below, (b) give the model number and part identification and (c) describe the nature of any defect in the product or part. At the time of requesting warranty service, you must present evidence of the original purchase date.

Broan-NuTone LLC, 926 West State Street, Hartford, WI 53027 (1-800-637-1453) NuTone Inc., 4820 Red Bank Road, Cincinnati, OH 45227 (1-800-543-8687)

Broan-NuTone Canada Inc., 1140 Tristar Drive, Mississauga, ON L5T 1H9 (1-888-882-7626)

SERVICE PARTS

RMIP33 AND RMIP45 MODELS

 

 

 

 

 

2

KEY

PART

DESCRIPTION

MODEL

NO.

NUMBER

33

45

 

 

 

1

V03493

RANGEMASTER LOGO

1

1

 

2

V03686

FILTER CLIP

3

4

 

3

V03435

THERMOSTAT

1

1

 

4

V03501

SPEED CONTROL

1

1

 

5

V02512

SCREW NO. 8-32 x 1/2’’, QUADREX

2

2

 

6

V02773

MALE CONNECTOR

1

1

 

7

V02772

FEMALE CONNECTOR

1

1

 

8

V03505

TERMINAL STRIP

1

1

 

9

V00673

LOCK NUT NO 8-32

2

2

 

10

V02264

SOCKET LAMP

2

3

14

11

V03502

SPST DOUBLE SWITCH (HAL. LIGHT)

1

1

12

V03503

SPSTLIGHTEDSINGLESWITCH(BLOWER)

1

1

 

13

V03504

SPEED CONTROL BUTTON

1

1

 

14

V05865

MICROMESH FILTERS 9.250’’ x 12.500’’

3

2

HL0043

V05866

MICROMESH FILTERS 11.130’’ x 12.500’’’’

-

2

 

 

 

 

V02544

HALOGEN LAMP PAR 20 50W

3

4

 

 

V05861

INSTALLATION MANUAL

1

1

 

 

 

PARTS BAG ((4) lock nut no. 10-32, (1)

 

 

 

 

V03888

wire clamp LP16-AP, (2) wire connectors

1

1

 

 

no. 74B, (8) no. 8 x 3/4” screws, (8) no. 8

 

 

 

 

 

 

 

 

x 3/8” screws, (2) no. 6 x 1/2" screws)

 

 

 

 

1

 

 

4

 

6

 

5

7

8

3

 

 

 

 

 

9

13

12

11

10

 

 

- 14 -

SERVICE PARTS

SINGLE BLOWER/ROUGH-IN

(Model P5)

1

2

3

4

5 7

6

8

9

HL0021

20

21

23 22

19

17 18

16 15

14

13

6

12

11

10

KEY

PART NUMBER

DESCRIPTION

QTY

NO.

 

 

 

1

V13296

ADAPTER AND DAMPER 3 1/4’’ x 10’’

1

2

V03500

AIR DEFLECTOR

1

3

V12997

SINGLE BLOWER ROUGH-IN PLATE ASSEMBLY

1

4

V03577

FOAM 1/2” X 1/2” X 12”

1

5

V02160

CAPACITOR 15MFD

1

6

V01869

MACHINE SCREW NO. 6-32 X 1/4”

4

7

V01857

WIRE COVER

1

8

V01582

LOCK NUT NO. 6-32

1

9

V14973

SINGLE BLOWER ASSEMBLY

1

10

V01810

IMPELLER RING

1

11

V03400

BLOWER IMPELLER 7.094” X 3.375” CW

1

12

V01766

MOTOR 165W CW

1

13

V00871

WASHER 3/16”ID X 3/4 OD

3

14

V02001

MOTOR GROMMET G-431-1

3

 

V01831

8” TIE WRAP

2

15

V11705

MOTOR MOUNT

1

 

V11614

WIRE NO. 18 TEW BROWN X 10”

1

16

V01927

METRIC SCREW M4 X 6MM PAN QDRX

4

17

V03495

STRAIN RELIEF FOR BLOWER POWER CORD

1

18

V03494

36” BLOWER POWER CORD

1

19

V13230

OUTLET BOX COVER

1

20

V03496

POWER CORD, 120 VOLTS

1

21

V00660

STRAIN RELIEF FOR POWER CORD

1

22

V05520

SCREW NO. 8 X 3/8”, T/B, NO. 8 HEAD

2

23

V00613

SCREW NO. 10-32 X 3/8, TF, GREEN

2

- 15 -

Loading...
+ 33 hidden pages