Fire Alarm Systems | W HS Wall mount Multi candela Horn Strobes
W HS Wall mount Multi candela Horn
Strobes
www.boschsecurity.com
u Sleek modern aesthetics
u Multiple voltages (12 VDC or 24 VDC) u Voltage test points
u Eight strobe candela options and three horn volume options
u Universal mounting base
The Cooper Wheelock Exceder Series Horn Strobes feature a sleek modern design that incorporates high reliability and high-efficiency optics to minimize current draw. The reduced current draw allows for a greater number of devices on the two wire notification appliance circuit. This, in combination with eight candela options in one appliance, no tools needed for changing settings, voltage test points, 12 V or 24 V DC operation, the universal mounting base, and multiple mounting options results in a reduced cost of ownership.
These horn strobes provide eight candela settings and three sound settings on each appliance. All the switches to change these settings can be set without a tool and are located behind the appliance to prevent tampering.
The separate universal mounting base can be easily mounted to five industry standard back box types. They can also be pre wired to allow full testing of the circuit wiring before the appliance is installed and the surface finished. These wall mounting horn strobes also feature voltage test points for taking readings with a volt meter for troubleshooting or AHJ inspection.
Certifications and approvals
Cooper Wheelock holds these Listings and Approvals:
Region |
Certification |
|
|
|
|
USA |
UL |
ULSZ: Audible-signal Appliances |
|
|
(ANSI/UL 464), UUKC: Signaling Appli- |
|
|
ances and Equipment for the Hearing Im- |
|
|
paired (ANSI/UL 1971) |
|
CSFM |
see our website |
Canada |
ULC |
UEESC: Visual and Visual-audible Signal |
|
|
Appliances, Fire Alarm (CAN/ULC-S525, |
|
|
CAN/ULC-S541, CAN/ULC-S526, ULC- |
|
|
S527), ULSZC: Audible Signal Applian- |
|
|
ces and Accessories, Fire Alarm (CAN/ |
|
|
ULC-S525, ULC-S527) |
|
|
|
Installation/configuration notes
Compatibility
Horn:
These horns provide a selectable Continuous or Code 3 horn tone when connected directly to the Fire Alarm Control Panel (FACP). They can also provide a synchronized Code 3 Horn tone when used in
2 | W HS Wall mount Multi candela Horn Strobes
conjunction with an FACP that incorporates the Cooper Notification sync protocol, a Cooper Notification Sync Module, or the Cooper Notification Power Supply. The Horn Appliances can be field set for High (HI), Medium (MED), or Low (LO) dBA sound output.
Strobe:
These strobes provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with an FACP that incorporates the Cooper Notification sync protocol, a Cooper Notification Sync Module, or the Cooper Notification Power Supply. They are designed to flash at 1 flash per second minimum over their Regulated Voltage Range.
Notice
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
Compatible Products
The following Bosch Security Systems, Inc. products are compatible with the Cooper Wheelock Exceder Series Horn Strobes:
Category |
Product ID |
Product Description |
Control Panels |
FPA-10001 |
Analog Addressable Fire |
|
|
Panels |
|
FPD-70241 |
Conventional or |
|
|
Addressable2 FACP |
|
D10024A3 |
Analog FACP |
|
D80243 |
Analog FACP |
|
D91243 |
Addressable FACP |
|
D70243 |
Conventional or |
|
|
Addressable2 FACP |
|
D70223 |
Conventional FACP |
Modules |
SM 12/24 R |
Synchronization module |
|
|
(red) |
|
DSM 12/24 R |
Dual synchronization |
|
|
module (red) |
Power Supplies |
FPP-RNAC-8A-4C1 |
Remote Notification |
|
|
Appliance Circuit (RNAC) |
|
|
Power Supply |
|
PS 24 8MC1 |
Power supply with built-in |
|
|
synchronization protocol |
1 These products have built in Cooper Notification synch protocol.
2 When used with a D7039 Multiplex Expansion Module, the FPD 7024 or the D7024 become addressable FACPs.
3 For synchronization, use the SM or DSM modules with these control panels.
Mounting Considerations
The Universal Mounting Base supplied with each horn strobe can be pre-wired. With the supplied Contact Cover in place, the pre wired circuit can be checked for continuity before the horn strobes are mounted. The horn strobes snap onto the pre-installed Universal Mounting Bases with the Contact Covers removed and can be secured to the base with an optional securing screw. The Universal Mounting Base flush mounts on single-gang, double-gang, 4 in. square, 4 in. octal,
3.5 in. octal, and 100 mm European-type back boxes.
Wiring Considerations
The wiring terminals on the Universal Mounting Base accept two appliance wires with diameters between 12 AWG and 18 AWG (ISO 4 mm2 and 0.75 mm2) at each terminal.
Parts included
Quant. Component
1Horn Strobe appliance
1Universal mounting base
1Contact cover
1Hardware pack
•Two pan head mounting screws
•One securing screw
1Literature – Installation Instructions
Technical specifications
Electrical
Horn and Strobe Current Draw5
24 V nominal (16.0 V to 33.0 V range)
Voltage |
Volume |
Current Draw |
Type |
Setting |
|
|
|
|
DC: |
High: |
15 cd: 82 mA, 15/75 cd: 95 mA, |
|
|
30 cd: 102 mA, 75 cd: 148 mA, |
|
|
95 cd: 176 mA, 110 cd: 197 mA, |
|
|
135 cd: 242 mA, 185 cd: 282 mA |
|
|
|
|
Medium: |
15 cd: 73 mA, 15/75 cd: 83 mA, |
|
|
30 cd: 87 mA, 75 cd: 139 mA, |
|
|
95 cd: 163 mA, 110 cd: 186 mA, |
|
|
135 cd: 230 mA, 185 cd: 272 mA |
|
|
|
|
Low: |
15 cd: 65 mA, 15/75 cd: 75 mA, |
|
|
30 cd: 87 mA, 75 cd: 139 mA, |
|
|
95 cd: 157 mA, 110 cd: 184 mA, |
|
|
135 cd: 226 mA, 185 cd: 267 mA |
|
|
|
FWR: |
High: |
15 cd: 133 mA, 15/75 cd: 138 mA, |
|
|
30 cd: 138 mA, 75 cd: 216 mA, |
|
|
95 cd: 258 mA, 110 cd: 289 mA, |
|
|
135 cd: 357 mA, 185 cd: 384 mA |
|
|
|
|
Medium: |
15 cd: 112 mA, 15/75 cd: 126 mA, |
|
|
30 cd: 126 mA, 75 cd: 201 mA, |
|
|
95 cd: 247 mA, 110 cd: 272 mA, |
|
|
135 cd: 340 mA, 185 cd: 378 mA |
|
|
|