Bard WA301, WA361 User Manual

477.32 Kb
Loading...

 

WALL MOUNTED

INSTALLATION

PACKAGED

INSTRUCTIONS

AIR CONDITIONER

 

Models: WA301, WA361

 

 

MIS-656

Bard Manufacturing Company

Manual No.:

2100-192M

Bryan, Ohio 43506

Supersedes:

2100-192L

Since 1914...Moving ahead just as planned.

File:

Volume III, Tab 16

Date:

05-13-02

 

© Copyright 2002

Contents

Getting Other Information and Publications

 

Start Up

 

For more information,

 

Important Installer Note........................................

13

contact these publishers ........................................

1

Crankcase Heaters ..............................................

13

 

 

Service Hints ........................................................

13

Wall Mount General Information

 

Sequence of Operation ........................................

13

Air Conditioner Wall Mount Model Nomenclature ..

2

Compressor Control Module ................................

13

Shipping Damage ..................................................

5

Adjustments .........................................................

14

General ..................................................................

5

Pressure Service Ports ........................................

14

Duct Work ..............................................................

5

 

 

Filters .....................................................................

5

Troubleshooting

 

Fresh Air Intake ......................................................

6

Fan Blade Setting Dimensions ............................

15

Condensate Drain ..................................................

6

Removal of Fan Shroud .......................................

15

 

 

Refrigerant Charge ..............................................

15

Installation Instructions

 

Pressure Table .....................................................

16

Wall Mounting Information .....................................

7

Optional Accessories ...........................................

17

Mounting the Unit...................................................

7

 

 

Top Outlet Only ......................................................

7

 

 

Wiring — Main Power ............................................

7

 

 

Wiring — Low Voltage Wiring .................................

8

 

 

Figures

 

 

Tables

 

 

 

Figure 1

Unit Dimensions ...................................

3

Table

1

Electrical Specifications ........................

2

Figure 2

Blower Damper Assembly.....................

6

Table

2

Dimensions of Basic Unit ......................

3

Figure 3

Mounting Instructions ...........................

9

Table

3

Electric Heat Table ................................

4

Figure 4

Electric Heat Clearances ......................

9

Table

4

Operating Voltage Range .....................

8

Figure 5

Wall-Mounting Instructions .................

10

Table

5

Thermostat Wire Size ...........................

8

Figure 6

Wall-Mounting Instructions .................

10

Table 6

Wall Thermostat and

 

Figure 7

Common Wall-Mounting Installations . 11

 

 

Subbase Combinations ........................

8

Figure 8

Low Voltage Wiring .............................

12

Table

7

Fan Blade Dimensions .......................

15

Figure 9

Start Up Label .....................................

13

Table

8

Suction Line Temperatures .................

15

Figure 10

Fan Blade Setting ...............................

15

Table

9

Indoor Blower Performance ................

15

 

 

 

Table 10

CFM and ESP.....................................

15

 

 

 

Table

11

Maximum ESP of Operation

 

 

 

 

 

 

Electric Heat Only ...............................

16

 

 

 

Table 12

Cooling Pressure ................................

16

 

 

 

Table

13

Optional Accessories ..........................

17

i

Getting Other Information and Publications

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

National Electrical Code .......................

ANSI/NFPA 70

Standard for the Installation ...............

ANSI/NFPA 90A

of Air Conditioning and

 

Ventilating Systems

 

Standard for Warm Air ........................

ANSI/NFPA 90B

Heating and Air

 

Conditioning Systems

 

Load Calculation for .............................

ACCA Manual J

Residential Winter and

 

Summer Air Conditioning

 

Duct Design for Residential ................

ACCA Manual D

Winter and Summer Air

 

Conditioning and Equipment

 

Selection

 

FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:

ACCA

Air Conditioning Contractors of America

 

1712 New Hampshire Avenue NW

 

Washington, DC 20009

 

Telephone: (202) 483-9370

 

Fax: (202) 234-4721

ANSI

American National Standards Institute

 

11 West Street, 13th Floor

 

New York, NY 10036

 

Telephone: (212) 642-4900

 

Fax: (212) 302-1286

ASHRAE American Society of Heating Refrigerating,

and Air Conditioning Engineers, Inc.

1791 Tullie Circle, N.E.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA

National Fire Protection Association

 

Batterymarch Park

 

P.O. Box 9101

 

Quincy, MA 02269-9901

 

Telephone: (800) 344-3555

 

Fax: (617) 984-7057

Manufactured under the following U.S. patent numbers:

5,485,878; 5,301,744; 5,002,116; 4,924,934; 4,875,520; 4,825,936

Manual 2100-192

Page 1

FILTER OPTIONS
X - One Inch Throwaway (Standard)
W- One Inch Washable
P - Two Inch Pleated

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE

MODEL NUMBER

WA 36 1 – A 10 X X X X X A

CONTROL MODULES

CAPACITY

 

30

-

2 1/2 Ton

 

36

-

3 Ton

REVISIONS

KW

VOLTS & PHASE

A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3

VENTILATION OPTIONS

X - Barometric Fresh Air Damper

(Standard)

B - Blank-off Plate

M - Motorized Fresh Air Damper V - Commercial Room Ventilator

-

 

 

COIL OPTIONS

 

 

X- Standard

 

 

1 - Phenolic Coated Evapora-

COLOR OPTIONS

tor

X - Beige (Standard)

2 - Phenolic Coated Con-

1

- White

denser

2

- Mesa Brown

3 - Phenolic Coated Evapora-

4

- Buckeye Gray

tor

5

- Desert Brown

and Condenser

6

- Dark Bronze

 

OUTLET OPTIONS

X- Front (Standard)

T - Top on WA30 and WA36

Models

Motorized with Exhaust

E - Economizer (Internal - Fully Modulating with Exhaust

R - Energy Recovery Ventilator -

NOTE: For 0KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of with Exhaust

model number.

TABLE 1

ELECTRICAL SPECIFICATIONS

 

 

 

3

1

2

2

3

 

1

 

2

 

2

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

Minimum

External

Field

 

 

 

 

 

No.

 

Field

 

Fuse or

Ground

 

Rated

Minimum

External

Ground

Circuit

Circuit

Power

 

Field

Fuse or

Power

Ampacity

Breaker

Wire Size

Wire Size

 

Volts &

Power

Circuit

Circuit.

Wire

Wire

 

 

 

 

 

 

 

 

 

 

 

Model

CKT

CKT

CKT

 

CKT

CKT

 

CKT

CKT

 

CKT

Phase

Circuits

Ampacity

Breaker

Size

Size

 

 

 

 

 

 

 

 

 

 

A

B

A

 

B

A

 

B

A

 

B

WA301-A00, A0Z

 

1

24

35

8

10

---

---

---

 

---

---

 

---

---

 

---

A05

230/208-1

1

31

35

8

10

---

---

---

 

---

---

 

---

---

 

---

A10

1

57

60

6

10

---

---

---

 

---

---

 

---

---

 

---

A15

 

1 or 2

83

90

4

8

55

26

60

 

30

4

 

10

8

 

10

WA301-B00, B0Z

 

1

17

20

12

12

---

---

---

 

---

---

 

---

---

 

---

B09

230/208-3

1

32

35

8

10

---

---

---

 

---

---

 

---

---

 

---

B15

 

1

50

50

8

10

---

---

---

 

---

---

 

---

---

 

---

WA301-C00, C0Z

 

1

10

15

14

14

---

---

---

 

---

---

 

---

---

 

---

C09

460-3

1

17

20

12

12

---

---

---

 

---

---

 

---

---

 

---

C15

 

1

26

30

10

10

---

---

---

 

---

---

 

---

---

 

---

WA361-A00, A0Z

 

1

27

35

8

10

---

---

---

 

---

---

 

---

---

 

---

A05

230/208-1

1

31

35

8

10

---

---

---

 

---

---

 

---

---

 

---

A10

1

57

60

6

10

---

---

---

 

---

---

 

---

---

 

---

A15

 

1 or 2

83

90

4

8

55

26

60

 

30

4

 

10

8

 

10

WA361-B00, B0Z

 

1

20

25

10

10

---

---

---

 

---

---

 

---

---

 

---

B09

230/208-3

1

32

35

8

10

---

---

---

 

---

---

 

---

---

 

---

B15

 

1

50

50

8

10

---

---

---

 

---

---

 

---

---

 

---

WA361-C00, C0Z

 

1

10

15

14

14

---

---

---

 

---

---

 

---

---

 

---

C09

460-3

1

17

20

12

12

---

---

---

 

---

---

 

---

---

 

---

C15

 

1

26

30

10

10

---

---

---

 

---

---

 

---

---

 

---

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

2 Based on 75° copper wire. All wiring must conform to the National Electrical Code and all local codes.

3 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.

Manual 2100-192

Page 2

192-2100 Manual

3 Page

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIMENSIONS OF BASIC UNIT (NOMINAL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

Depth

Height

 

Supply

 

 

Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

(W)

(D)

 

 

(H)

A

 

 

 

B

 

 

C

 

 

B

E

 

 

F

G

I

J

 

K

 

 

 

L

M

 

 

N

 

 

 

O

 

 

 

P

 

 

Q

 

R

S

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA30

38.200

17.125

70.563

7.88

 

 

27.88

 

13.88

27.88

40.00

18.50

25.75

17.93

26.75

28.75

29.25

27.00

2.75

 

39.19

22.75

9.14

4.19

12.00

5.00

WA36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DIMENSIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONTVIEW

SIDE VIEW

BACK VIEW

MIS-1262

* Optional top outlet (factory installed only) for WA30 and WA36 models only.

192-2100 Manual

4 Page

TABLE 3

ELECTRIC HEAT TABLE

 

 

WA301-A

 

 

WA301-B

 

WA301-C

 

WA361-A

 

 

WA361-B

 

WA361-C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

240V-1

208V-1

240V-3

208V-3

460V-3

240V-1

208V-1

240V-3

208V-3

460V-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

20.8

17,065

18.1

12,800

---

---

---

---

---

---

20.8

17,065

18.1

12,800

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.0

33.3

27,300

28.8

20,475

---

---

---

---

---

---

33.3

27,300

28.8

20,475

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.0

41.6

34,130

36.2

25,600

---

---

---

---

---

---

41.6

34,130

36.2

25,600

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.0

---

---

---

---

---

---

---

---

---

---

62.5

51,200

54.1

38,400

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.0

---

---

---

---

14.4

20,500

12.5

15,360

7.2

20,475

---

---

---

---

14.4

20,500

12.5

15,360

7.2

20,475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.0

---

---

---

---

21.7

30,600

18.7

23,030

10.8

30,700

---

---

---

---

21.7

30,600

18.7

23,030

10.8

30,700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.0

---

---

---

---

 

 

 

 

18.0

51,200

---

---

---

---

36.2

38,400

31.2

38,400

18.0

51,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.

The refrigerant system is completely assembled and charged. All internal wiring is complete.

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.

Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

Refer to Table 10 for maximum static pressure available for duct design.

Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of 1 inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.

A 1/4 inch clearance to combustible material for the first 3 feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.

Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.

CAUTION

Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.

Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2 through RG-5 or RFG-2 through RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.

FILTERS

A 1 inch throw away filter is suppled with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1 inch washable filter and a 2 inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2 inch filter by loosening 2 screws in each bracket assembly and sliding the brackets apart to the required width and retightening the 4 screws.

Manual 2100-192

Page 5

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the service panel.

If the unit is equipped with the fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.

All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.

The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.

FIGURE 2

FRESH AIR DAMPER ASSEMBLY

BLADE IS LOCKED

CLOSEDFOR

SHIPPING

MIS-938

Manual 2100-192

Page 6

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.

2.On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

WARNING

Fire hazard can result if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.

2.The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 28-1/2" x 8-1/2" dimensions for sizing. However, it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 30" x 10". See Figures 3 and 4 for details.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.

4.Mount bottom mounting bracket, if used.

5.Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.

9.On side by side installations, maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

TOP OUTLET ONLY

1.Remove airframe angles from the back of the unit.

2.Coat angles with two 1/8" beads of silicone as shown. Silicone is shipped in the control panel. See Figure 6.

3.Secure angles to the top of the unit with 14 screws provided. Use of prepunched holes provided. Do not

relocate. See Figure 6.

4.After installation duct work, seal around airframe and duct work to provide a rain tight seal.

5.It is strongly recommended, but not required, that this unit be installed under a soffit area large enough to shield the top of the unit. See Figure 7.

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

Manual 2100-192

Page 7

The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TABLE 4

OPERATING VOLTAGE RANGE

TAP

RANGE

 

 

 

 

240V

253

-

216

 

 

 

 

208V

220

-

187

 

 

 

 

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.)

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 10.

TABLE 5

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

Wire

Distance

VA

FLA

Gauge

In Feet

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

TABLE 6

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

Predominate Features

 

 

 

8403-002

8404-003

1 stage heat, 1 stage cool

T87F3111

Q539A1220

System: heat-off-cool

Fan: auto-on

8403-041

---

1 stage heat, 1 stage cool

T8034C

 

System: heat-off-cool

Fan: auto-on

8403-019

8404-012

1 stage cool, 2 stage heat

T874C1760

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

 

8403-021

8404-012

2 stage cool, 2 stage heat

T874D1934

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

 

8403-049

---

2 stage cool, 2 stage heat

1F93-380

 

Electronic 7 day programming

 

 

 

8403-043

---

1 stage heat, 1 stage cool

CM-200

System: heat-off-cool

Fan: auto-on

 

Manual 2100-192

Page 8

FIGURE 3

MOUNTING INSTRUCTIONS

4 9/

16

MIS-311

NOTE: It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation.

FIGURE 4

ELECTRIC HEAT CLEARANCE

MIS-277

Side section view of supply air duct for wall mounted unit showing 1/4 inch clearance to combustible surfaces.

WARNING

A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.

It is important to insure that the 1/4 inch minimum spacing is maintained at all points.

Failure to do this could result in overheat-

ing

the combustible material and may

result in

fire.

Manual 2100-192

Page 9

FIGURE 5

WALL-MOUNTING INSTRUCTIONS

SEE FIGURE3 – MOUNTING INSTRUCTIONS

MIS-548

FIGURE 6

WALL-MOUNTING INSTRUCTIONS

SEE UNIT DIMENSIONS, FIGURE 1,

FOR ACTUAL DIMENSIONS

SEE FIGURE 1 FOR

DUCT DIMENSIONS

MIS-549

Manual 2100-192

Page 10

FIGURE 7

 

 

COMMON WALL-MOUNTING INSTALLATIONS

 

 

 

 

MIS-550

Manual

2100-192

Page

11

FIGURE 8

LOW VOLTAGE WIRING

 

MIS-1373C

Manual

2100-192

Page 12

START UP

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil with a dishwasher detergent.

CRANKCASE HEATERS

All units are provided with some form of compressor crankcase heat.

All single and three phase models have an insertion well-type heater located in the lower section of the compressor housing. This is a self-regulating type heater that draws only enough power to maintain the compressor at a safe temperature.

Some form of crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor, causing oil pump out on compressor start up and possible valve failure due to compressing a liquid.

The decal in Figure 9 is affixed to all outdoor units detailing start up procedure. This is very important. Please read carefully.

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.

2.Check all power fuses or circuit breakers to be sure they are the correct rating.

3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On all 230 volt units there is a one minute off delay on the blower motor. 460 volt models do not have an off delay. On a call for heating, circuit R-W1 make at the thermostat pulling in heat contact for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

FIGURE 9

START UP LABEL

IMPORTANT

Theseproceduresmustbefollowed at initial start up and at any time power has been removed for 12 hours or longer.

To prevent compressor damage which may result from the presence of liquid refrigerant in the compressor crankcase:

1.Make certain the room thermostat is in the "off" position (the compressor is not to operate).

2.Apply power by closing the system disconnect switch. This energizes the compressor heater which evaporates the liquid refrigerant in the crankcase.

3.Allow 4 hours or 60 minutes per poind of refrigerant in the system as noted on the unit rating plate, whichever is greater.

4.After properly elapsed time, the thermostat may be set to operate the compressor.

5.Except as required for safety while servicing, do not open system disconnect switch.

7961-061

Manual 2100-192

Page 13

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout

Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute

(30 seconds)

DOB = 123 second DOM

1.0 minute

(60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds)

DOB = 132 second DOM

3.0 minute (180 seconds)

DOB = 138 second DOM

4.0 minute (240 seconds)

DOB = 144 second DOM

5.0 minute (300 seconds)

DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

Manual 2100-192

Page 14

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 10

FAN BLADE SETTING

TABLE 7

FAN BLADE DIMENSION

Model Dimension A

WA301

WA361 1.25

REMOVAL OF FAN SHROUD

1.Disconnect all power to unit.

2.Remove the screws holding both grills, one on each side of unit, and remove grills.

3.Remove screws holding fan shroud to condenser and bottom – 9 screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in Table 8.

TABLE 8

SUCTION LINE TEMPERATURES

 

Rated

95° F

82° F

Model

Airflow

OD Temp.

OD Temp.

 

 

 

 

WA301

1,100

55 - 57

64 - 66

 

 

 

 

WA361

1,100

57 - 59

62 - 64

The suction line temperatures in Table 8 are based upon 80ºF dry bulb/67ºF wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 9

INDOOR BLOWER PERFORMANCE

CFM AT 230 VOLTS

 

 

WA301, WA361

 

 

 

 

 

 

E.S.P.

High Speed

Low Speed

 

 

 

 

In H2O

Dry Coil

Wet Coil

Dry Coil

Wet Coil

.0

1,395

1,315

950

935

.1

1,340

1,270

930

915

 

 

 

 

 

.2

1,285

1,190

910

885

.3

1,205

1,100

855

830

 

 

 

 

 

.4

1,110

1,000

800

755

 

 

 

 

 

.5

1,005

870

---

---

 

 

 

 

 

TABLE 10

RATED CFM AND ESP

 

1

1

 

Model

Rated

Rated

Recommended

CFM

ESP

Airflow Range

WA301

1,000

.40

930 - 1,300

WA361

1,100

.30

930 - 1,350

1Rated CFM and ESP on high speed tap

Manual 2100-192

Page 15

TABLE 11

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

Front Outlet

Top Outlet

 

 

 

 

 

 

Low

High

Low

High

KW

Speed

Speed

Speed

Speed

A00

.50

.50

.50

.50

A05

.50

.50

.45

.50

A08

.50

.50

---

---

A10

.45

.50

.35

.50

A15

.35

.40

---

---

 

 

 

 

 

B00

.50

.50

.50

.50

B06

.40

.50

---

---

B09

.50

.50

.40

.45

B15

.30

.45

---

---

 

 

 

 

 

C00

.50

.50

.50

.50

C06

.50

.50

---

---

C09

.40

.50

.40

.45

C15

.35

.45

---

---

 

 

 

 

 

TABLE 12

COOLING PRESSURE – OUTDOOR TEMPERATURE °F

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

120

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg DB

Low Side

74

77

79

81

82

84

85

85

86

87

88

 

62 deg WB

High Side

218

232

247

262

277

292

306

325

341

357

373

WA301

80 deg DB

Low Side

80

82

84

86

88

89

91

91

92

93

94

67 deg WB

High Side

223

238

253

268

284

300

316

333

350

366

383

 

 

85 deg DB

Low Side

85

88

91

93

95

96

97

96

99

100

101

 

72 deg WB

High Side

231

246

262

278

294

310

327

345

362

379

396

 

75 deg DB

Low Side

70

72

74

76

78

79

80

81

82

83

84

 

62 deg WB

High Side

224

242

259

275

290

304

316

328

339

351

363

WA361

80 deg DB

Low Side

75

77

79

81

83

85

86

87

88

89

90

67 deg WB

High Side

229

248

265

272

297

311

325

337

348

360

373

 

 

85 deg DB

Low Side

80

83

85

87

89

91

92

94

95

96

98

 

72 deg WB

High Side

238

257

275

292

307

322

336

349

360

373

386

Low side pressure ± 2 psig

High side pressure ± 5 psig

Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled "refrigerant charge" elsewhere in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

Manual 2100-192

Page 16

TABLE 13

OPTIONAL ACCESSORIES

MODEL DESCRIPTION

WA301-A

WA301-B

WA301-C

WA361-A

WA361-B

WA361-C

EHWA03-A05

Heater Packages

1

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

EHWA03-A08

Heater Packages

1

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

EHWA03-A10

Heater Packages

1

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

EHWA03-A15

Heater Packages

1

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

EHWA03-B06

Heater Packages

1

 

X

 

 

X

 

 

 

 

 

 

 

 

 

 

EHWA03-B09

Heater Packages

1

 

X

 

 

X

 

 

 

 

 

 

 

 

 

 

EHWA03-B15

Heater Packages

1

 

X

 

 

X

 

 

 

 

 

 

 

 

 

 

EHWA03-C06

Heater Packages

1

 

 

X

 

 

X

 

 

 

 

 

 

 

 

 

EHWA03-C09

Heater Packages

1

 

 

X

 

 

X

 

 

 

 

 

 

 

 

 

EHWA03-C12

Heater Packages

1

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

EHWA03-C15

Heater Packages

1

 

 

X

 

 

X

 

 

 

 

 

 

 

 

 

BOP-3

Blank Off Plate

 

X

X

X

X

X

X

BFAD-3

Barometric Fresh Air Damper

X

X

X

X

X

X

 

 

 

 

 

 

 

 

MFAD-3

Motorized Fresh Air Damper

X

X

X

X

X

X

CRV-3

Commercial Ventilator with Exhaust

X

X

X

X

X

X

 

 

 

 

 

 

 

 

EIFM-3

Economizer with Exhaust

X

X

X

X

X

X

 

 

 

 

 

 

 

 

WERV-A3B

Energy Recovery Ventilator

X

X

 

X

X

 

 

 

 

 

 

 

 

 

WERV-C3B

Energy Recovery Ventilator

 

 

X

 

 

X

 

 

 

 

 

 

 

 

CMA-5

Time Delay Relay (TDR)

X

X

X

X

X

X

 

 

 

 

 

 

 

 

CMA-6

Low Ambient Control

X

X

 

X

X

 

 

 

 

 

 

 

 

 

 

CMA-8

TDR + HPC

 

X

X

X

X

X

X

 

 

 

 

 

 

 

 

 

CMA-10

LPC + HPC + TDR

 

X

X

X

X

X

X

 

 

 

 

 

 

 

 

CMA-13

LPC + HPC + TDR + LAC

X

X

 

X

X

 

 

 

 

 

 

 

 

 

 

CMC-15

Start Kit

 

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

WMCB-05A

Circuit Breaker Kit

 

X

 

 

X

 

 

 

 

 

 

 

 

 

 

 

WMCB-02B

Circuit Breaker Kit

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

WMPD-01C

Pull Disconnect Kit

 

 

 

X

 

 

X

 

 

 

 

 

 

 

 

 

WMCB-03B

Circuit Breaker Kit

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

Manual 2100-192

Page 17