Ariston 41-116-38, 47-116-67, 47-116-66, 41-116-37, 41-116-36 User Manual

0 (0)

CLAS HE EVO

CLAS HE EVO System

InstallationandServicingInstructions

CONDENSING WALL-HUNG

GAS BOILER

G.C.N.:47-116-65 (24 kW)

G.C.N.:47-116-66 (30 kW)

G.C.N.:47-116-67 (38 kW)

G.C.N.:41-116-36 (18 kW)

G.C.N.:41-116-37 (24 kW)

G.C.N.:41-116-38 (30 kW)

CountryofDestination.GB/IE

INDEX

 

Overview.......................................................................................................

3

General Information...................................................................................

4

Advice for the Installer...............................................................................

4

CE Labelling...................................................................................................

4

Data Plate Symbols.....................................................................................

4

Safety Regulations ......................................................................................

5

Product description.................................................................................

6

Control Panel.................................................................................................

6

Overall View...................................................................................................

7

Overall Dimension ......................................................................................

8

Minimum Clearances .................................................................................

8

Technical Information................................................................................

9

Installation................................................................................................

11

Reference Standards ...............................................................................

11

Installing the Boiler..................................................................................

14

Gas Connection.........................................................................................

15

Water Connection ....................................................................................

15

Instructions for Opening the Casing and Performing an

 

Internal Inspection..............................................................................

15

Underfloor heating..................................................................................

16

Water circuit diagram..............................................................................

17

Connecting the Flue................................................................................

18

Fitting the Coaxial Flue (Ø 60/100 Horizontal)...............................

19

Fitting the 5” Flue (Ø 80/125 Horizontal / Vertical).......................

20

Fitting the Coaxial Flue (Ø 60/100 Vertical).....................................

21

Fitting the Twin Pipe (Ø 80/80)............................................................

22

Electrical Connections............................................................................

25

Peripheral Unit Connection..................................................................

25

Room Thermostat Connection ............................................................

26

Outdoor Sensor Connection ................................................................

26

Cylinder connection................................................................................

26

Internal mechanical time clock

 

Internal RF receiver for Ariston programmable

 

room thermostat ..................................................................................

27

Electrical Diagram ....................................................................................

28

Commissioning .......................................................................................

32

Initial Preparation.....................................................................................

32

Electricity Supply......................................................................................

32

Filling the Heating System ....................................................................

32

Filling of the DHW System.....................................................................

32

Gas Supply ..................................................................................................

32

Water Treatment .......................................................................................

32

First Igniton Operation...........................................................................

33

Ignition procedure...................................................................................

34

Test Function and Combustion Analysis..........................................

35

AUTO Function ..........................................................................................

37

Boiler Protection Devices...................................................................

38

Boiler Protection Devices ......................................................................

38

Table summarising error codes...........................................................

38

Anti-Frost Device ......................................................................................

39

Settings - Adjustment - Problem Identification Menus

 

Accessing the Menus ..............................................................................

40

Maintenance

 

General Comments..................................................................................

47

Operational Test........................................................................................

47

Draining procedures ...............................................................................

47

Cleaning the primary exchanger........................................................

47

Cleaning the trap......................................................................................

47

Maintenance Guide

 

General Access ..........................................................................................

48

Electrical Unit.............................................................................................

49

Hydraulic Unit............................................................................................

52

Main Heat Exchanger..............................................................................

60

Burner Unit .................................................................................................

61

Fan Unit........................................................................................................

64

Gas Valve......................................................................................................

65

Annual Maintenance...............................................................................

66

Benchmark Commissioning Checklist ..............................................

68

Benchmark Service Interval Record...................................................

69

overview

These instructions are suitable for CLAS HE boilers :

Do not forget the Log Book!

The Benchmark Scheme

Benchmark places responsibilities on both manufacturers and installers.The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.

Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.

To The Installer

As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.

Please ensure that your customer is aware of the correct operation of the system, boiler and controls.

ARISTON recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.

CUSTOMER CARE

ARISTON, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service.

Advice on installation or servicing can also be obtained by contacting the ARISTON Technical and Customer Service Departments at High Wycombe.

TECHNICAL DEPARTMENT

CUSTOMER SERVICE DEPARTMENT

Tel:

0333 240 7777

Tel:

0333 240 8777

Fax:

01494 459775

Fax:

01494 459775

GUARANTEE

The manufacturer’s guarantee is for 5 years from the date of purchase. The guarantee is invalidated if the appliance is not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an efficient after sales service, please register the guarantee online at www.ariston.co.uk

CAUTION

In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.

In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations, reference should also be made to the current ETCI rules for electrical installation.

All GAS SAFE registered installers carry a GAS SAFE ID card, and have a registration number. Both should be recorded in your boiler Log Book. You can check your installer is GAS SAFE registered by calling GAS SAFE directly on:- 0800 408 5500.

Improper installation may cause damage or injury to individuals, animals and personal property for which the manufacturer will not be held liable. To ensure efficient and safe operation it is recommended that the boiler is serviced annually by a competent person.

If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent person.

This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland

3

overview

Advice for the installer

The installation and first ignition of the boiler must be performed by qualified personnel in compliance with current national regulations regarding installation, and in conformity with any requirements established by local authorities and public health organisations.

After the boiler has been installed, the installer must ensure that the end user receives the declaration of conformity and the operating manual, and should provide all necessary information as to how the boiler and the safety devices should be handled.

This appliance is designed to produce hot water for domestic use. It should be connected to a heating system and a distribution network for domestic hot water, both of which must be compatible with its performance and power levels.

The use of the appliance for purposes other than those specified is strictly forbidden. The manufacturer cannot be held responsible for any damage caused by improper, incorrect and unreasonable use of the appliance or by the failure to comply with the instructions given in this manual.

Installation, maintenance and all other interventions must be carried out in full conformity with the governing legal regulations and the instructions provided by the manufacturer. Incorrect installation can harm persons, animals and possessions; the manufacturing company shall not be held responsible for any damage caused as a result. The boiler is delivered in a carton. Once you have removed all the packaging, make sure the appliance is intact and that no parts are missing. If this is not the case, please contact your supplier.

Keep all packaging material (clips, plastic bags, polystyrene foam, etc.) out of reach of children as it may present a potential hazard.

In the event of a fault and/or malfunction, turn the appliance off, turn off the gas cock and do not attempt to repair it yourself. Contact a qualified professional instead.

Before any maintenance or repair work is performed on the boiler, make sure you have disconnected it from the electricity supply by switching the external bipolar switch to the “OFF” position and removing the fuse.

All repairs, which should only be performed using original spare parts, should be carried out by a qualified professional. Failure to comply with the above instructions could compromise the safety of the appliance and invalidate all liability on the part of the manufacturer.

In the event of any maintenance or other structural work in the immediate vicinity of the ducts or flue gas exhaust devices and their accessories, switch the appliance off by switching the external bipolar switch to the “OFF” position and shutting off the gas control valve. When the work has been completed, ask a qualified technician to check the efficiency of the ducting and the devices.

Turn the boiler off and turn the external switch “OFF” to clean the exterior parts of the appliance.

Clean using a cloth dampened with soapy water. Do not use aggressive detergents, insecticides or toxic products. If the appliance is used in full compliance with current legislation, it will operate in a safe, environmentally-friendly and cost-efficient manner.

If using kits or optional extras, make sure they are authentic.

CE labelling

The CE mark guarantees that the appliance conforms to the following directives:

-2009/142/CEE

relating to gas appliances

-2004/108/CEE

relating to electromagnetic compatibility

-92/42/CEE

relating to energy efficiency

-2006/95/CEE

relating to electrical safety

Symbols used on the data plate

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

4

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

MAX

 

 

MIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

14

 

 

 

 

 

 

 

 

9

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

60/80°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

17

18

 

 

10

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend :

1.Brand

2.Manufacturer

3.Boiler model - Serial number

4.Commercial reference

5.certification number

6.Destination country - gas category

7.Gas setting

8.Installation type

9.Electrical data

10.Maximum domestic hot water pressure

11.Maximum heating pressure

12.Boiler type

13.NOx class / Efficiency

14.Input rating nominal heating

15.Power ouput heating

16.DHW specific flow rate

17.Boiler output efficiency

18.Input rating nominal DHW

19.Gases which may be used

20.Minimum ambient temperature for use

21.Max. central heating temperature

22.Max. domestic hot water temperature

4

overview

Safety regulations

Key to symbols:

Failure to comply with this warning implies the risk of personal injury, in some circumstances even fatal

Failure to comply with this warning implies the risk of damage, in some circumstances even serious, to property, plants or animals.

Install the appliance on a solid wall which is not subject to vibration.

Noisiness during operation.

When drilling holes in the wall for installation purposes, take care not to damage any electrical wiring or existing piping.

Electrocution caused by contact with live wires. Explosions, fires or asphyxiation caused by gas leaking from damaged piping. Damage to existing installations. Flooding caused by water leaking from damaged piping.

Perform all electrical connections using wires which have a suitable section.

Fire caused by overheating due to electrical current passing through undersized cables.

Protect all connection pipes and wires in order to prevent them from being damaged.

Electrocution caused by contact with live wires. Explosions, fires or asphyxiation caused by gas leaking from damaged piping. Flooding caused by water leaking from damaged piping.

Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force.

Electrocution caused by contact with live wires which have been installed incorrectly. Damage to the appliance

caused by improper operating conditions.

Use suitable manual tools and equipment (make sure in particular that the tool is not worn out and that its handle is fixed properly); use them correctly and make sure they do not fall from a height. Replace them once you have finished using them.

Personal injury from the falling splinters or fragments, inhalation of dust, shocks, cuts, pricks and abrasions.

Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.

Use electrical equipment suitable for its intended use (in particular, make sure that the power supply cable and plug are intact and that the parts featuring rotary or reciprocating motions are fastened correctly); use this equipment correctly; do not obstruct passageways with the power supply cable, make sure no equipment could fall from a height. Disconnect it and replace it safely after use.

Personal injury caused by falling splinters or fragments, inhalation of dust, knocks, cuts, puncture wounds, abrasions, noise and vibration. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.

Make sure any portable ladders are positioned securely, that they are suitably strong and that the steps are intact and not slippery and do not wobble when someone climbs them. Ensure someone provides supervision at all times.

Personal injury caused by falling from a height or cuts (stepladders shutting accidentally).

Make sure any rolling ladders are positioned securely, that they are suitably strong, that the steps are intact

and not slippery and that the ladders are fitted with handrails on either side of the ladder and parapets on the landing.

Personal injury caused by falling from a height.

During all work carried out at a certain height (generally with a difference in height of more than two metres), make sure that parapets are used to surround the work area or that individual harnesses are used to prevent falls. The space where any accidental fall may occur should be free from dangerous obstacles, and any impact upon falling should be cushioned by semi-rigid or deformable surfaces.

Personal injury caused by falling from a height.

Make sure the workplace has suitable hygiene and sanitary conditions in terms of lighting, ventilation and solidity of the structures.

Personal injury caused by knocks, stumbling etc.

Protect the appliance and all areas in the vicinity of the work place using suitable material.

Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.

Handle the appliance with suitable protection and with care.

Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.

During all work procedures, wear individual protective clothing and equipment.

Personal injury caused by electrocution, falling splinters or fragments, inhalation of dust, shocks, cuts, puncture wounds, abrasions, noise and vibration.

Place all debris and equipment in such a way as to make movement easy and safe, avoiding the formation of any piles which could yield or collapse.

Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.

All operations inside the appliance must be performed with the necessary caution in order to avoid abrupt contact with sharp parts.

Personal injury caused by cuts, puncture wounds and abrasions.

Reset all the safety and control functions affected by any work performed on the appliance and make sure they operate correctly before restarting the appliance.

Explosions, fires or asphyxiation caused by gas leaks or an incorrect flue gas exhaust. Damage or shutdown of the appliance caused by out-of-control operation.

Before handling, empty all components that may contain hot water, carrying out any bleeding if necessary.

Personal injury caused by burns.

Descale the components, in accordance with the instructions provided on the safety data sheet of the product used, airing the room, wearing protective clothing, avoid mixing different products, and protect the appliance and surrounding objects.

Personal injury caused by acidic substances coming into contact with skin or eyes; inhaling or swallowing harmful chemical agents. Damage to the appliance or surrounding objects due to corrosion caused by acidic substances.

If you detect a smell of burning or smoke, keep clear of the appliance, disconnect it from the electricity supply, open all windows and contact the technician.

Personal injury caused by burns, smoke inhalation, asphyxiation.

5

product description

Control panel

1

2

3

4

5

6

Legend :

1.Display

2.Domestic Hot Water temperature adjustment button +/-

(only for Clas HE EVO models)

3.MODE button

(Operation mode selection (summer/winter)

4.Pressure gauge

5.Auto Function and/or Comfort Function enable/disable button

(Comfort function only for Clas HE EVO models)

6.ESC button - reserved for technical assistance

7.“encoder” programming knob - reserved for technical assistance

8.OK button - reserved for technical assistance

9.ON/OFF button

10.TIME CLOCK (CLAS HE Evo System models optional)

11.RESET button

12.Heating temperature adjustument button +/-

Digits indicating:

- boiler status and temperature indication (°C)

- error code signals (Err) - menu settings

Technical assistance request

Flame detected with indication of power used or indication of operation shutdown

Heating operation set

Heating operation active

12

 

 

 

 

 

 

11

 

2

1

24

23

 

 

 

3

 

 

 

 

 

4

12

 

22

 

 

5

 

 

 

 

10

 

 

 

 

18

8

 

 

 

 

 

 

 

 

 

21

 

6

 

 

 

I

20

 

7

9

 

 

 

19

 

9

 

6

 

 

17

 

 

10

 

16

 

 

 

 

 

 

 

 

11

 

14

15

 

 

 

12

13

 

 

 

 

 

 

 

 

9

8

7

 

 

 

 

 

Hot water operation set

 

 

 

 

 

Hot water operation active

 

 

 

 

 

Hot Water Comfort activated

 

 

 

 

 

Boiler off with antifreeze function active

 

 

 

 

 

Antifreeze function activated

AUTO

AUTO function activated

(Temperature regulation activated)

 

 

 

 

 

 

 

 

 

 

Clip-in solar connected (optional)

 

 

 

 

 

 

 

 

 

 

 

Note: A radio frequency (RF) Programmable Room Thermostat is available from Ariston stockists.

The Receiver unit can be fitted in the time clock position (10)

6

Ariston 41-116-38, 47-116-67, 47-116-66, 41-116-37, 41-116-36 User Manual

product description

Overall view

CLAS HE EVO

CLAS HE EVO SYSTEM

 

1

 

1

 

 

24

 

24

2

23

2

23

 

 

3

 

3

 

4

22

4

22

21

21

 

 

5

 

5

 

6

20

6

20

 

 

7

 

7

 

8

 

 

 

9

19

9

19

 

 

10

 

10

 

12

16

12

15

 

 

 

14

 

14

1.

Flue connector

 

 

2.

Manual air vent

 

 

3.

Main heat exchanger

 

 

4.

Detection electrode

 

 

5.

C.H. Return temperature probe

 

 

6.

C.H. Flow temperature probe

 

 

7.

Silencer

 

 

8.

Secondary heat exchanger

 

 

9.

Gas valve

 

 

10.

Trap

 

 

12.

C.H. Pressure relief valve

 

 

14.

C.H. Circuit filter

 

 

16.

Circulation pump with air release valve

 

 

17.

D.H.W. Flow switch

 

 

18.

Diverter valve

 

 

19.

Low Water Pressure Switch

 

 

20.

Modulating fan

 

 

21.

Ignition electrodes

 

 

22.

Ignitor

 

 

23.

Thermal fuse

 

 

24.

Combustion analysis test point

 

 

 

 

 

7

product description

Overall Dimensions

200

 

200

 

 

120

120

 

CLAS HE EVO

 

 

F

 

 

 

 

65

67

67

65

28

 

180

150

315 mod. 24

385 mod. 30/38

 

200

 

200

 

25

120

120

 

 

 

 

 

 

CLAS HE EVO SYSTEM

 

770

 

 

 

 

 

F

 

 

 

 

132

67

65

28

 

 

A.Central Heating Flow

B.Domestic Hot Water Outlet

C.Gas Inlet

D.Domestic Cold Water Inlet

E.Central Heating Return

F.Safety Relief Valve

Minimum clearances

In order to allow easy access to the boiler for maintenance operations, The boiler must be installed in accordance with the clearances stated below.

00

5

 

3

5

5

 

450

 

 

 

 

300

8

product description

Technical Data

NOTE

Model: CLAS HE EVO

 

 

24

30

38

 

 

 

 

 

 

CE Certification (pin)

 

 

 

0085CL0440

 

GENERAL

 

 

 

 

 

 

 

 

 

 

Boiler type

 

 

C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)

 

 

 

 

 

 

C83(X)-C93(X)-B23-B23P-B33

 

 

 

 

 

Max/min nominal calorific flow rate (Pci)

Qn

KW

22.0/5.5

28.0/6.5

31.0/7.5

 

 

 

 

 

 

 

 

Max/min nominal calorific flow rate (Pcs)

Qn

KW

24.4/6.1

31.1/7.2

34.4/8.3

 

 

 

 

 

 

 

 

Domestic hot water max/min nominal calorific flow rate (Pci)

Qn

KW

26.0/5.5

30.0/6.5

38.0/7.5

 

Domestic hot water max/min nominal calorific flow rate (Pcs)

Qn

KW

28.9/6.1

33.3/7.2

42.2/8.3

 

Max/min power output (80°C-60°C)

Pn

KW

21.5/5.4

27.3/6.3

30.2/7.3

 

 

 

 

 

 

 

SPECIFICATIONS

Max/min power output (50°C-30°C)

Pn

KW

23.3/5.7

29.7/6.8

33.0/7.9

 

 

 

 

 

 

Domestic hot water max/min power output

Pn

KW

26.0/5.5

29.3/6.3

38.0/7.5

 

 

 

 

 

 

 

 

 

Combustion efficiency (of flue gas)

 

%

97.8

97.8

97.9

 

 

 

 

 

 

 

 

Nominal calorific flow rate efficiency (60/80°C) Hi/Hs

 

%

97.5/87.8

97.6/87.8

97.6/87.9

 

 

 

 

 

 

 

POWER

Nominal calorific flow rate efficiency (30/50°C) Hi/Hs

 

%

105.8/95.3

106.0/95.5

106.4/95.8

 

 

 

 

 

 

Efficiency at 30% at 30°C Hi/Hs

 

%

107.7/97.0

107.7/97.0

107.7/97.0

 

 

 

Efficiency at 30% at 47°C Hi/Hs

 

%

97.7/88.0

97.6/87.9

97.6/87.9

 

 

 

 

 

 

 

 

Minimum calorific flow rate efficiency (60/80°C) Hi/Hs

 

%

97.6/87.9

97.5/87.8

97.5/87.8

 

 

 

 

 

 

 

 

Efficiency rating (dir. 92/42/EEC)

 

stars

****

****

****

 

Sedbuk class

 

class

A/90

A/90

A/90.1

 

 

 

 

 

 

 

 

Loss when stopped (ΔT = 50°C)

 

%

 

 

 

 

 

 

 

 

 

 

 

Loss of burner gas when operating

 

%

2.2

2.2

2.2

 

 

 

 

 

 

 

 

Available air pressure

 

Pa

100

100

100

 

 

 

 

 

 

 

 

NoX class

 

class

5

5

5

EMISSIONS

Flue gas temperature (G20) (80°C-60°C)

 

°C

64

64

64

CO2 content (G20) (80°C-60°C)

 

%

9.0

9.0

9.0

 

 

 

 

 

 

 

 

 

 

CO content (0%O2) (80°C-60°C)

 

ppm

119

101

98

 

 

 

 

 

 

 

 

O2 content (G20) (80°C-60°C)

 

%

4.5

4.5

4.5

 

 

 

 

 

 

 

 

Maximum flue gas flow (G20) (80°C-60°C)

 

Kg/h

42.8

49.4

62.6

 

 

 

 

 

 

 

 

Excess air (80°C-60°C)

 

%

27

27

27

 

 

 

 

 

 

 

CIRCUIT

Expansion chamber inflation pressure

 

bar

1

1

1

 

 

 

 

 

 

Maximum heating pressure

 

bar

2,5

2,5

2,5

 

 

 

 

 

 

 

 

 

HEATING

Expansion chamber capacity

 

L

6.5

6.5

6.5

 

 

 

 

 

 

Min/max heating temperature (high temperature range)

 

°C

35 / 82

35 / 82

35 / 82

 

 

 

Min/max heating temperature (low temperature range)

 

°C

20 / 45

20 / 45

20 / 45

CIRCUIT

Specific flow rate of domestic hot water (ΔT=30°C)

 

l/mn

12.2

14.1

18.4

 

Domestic hot water max/min temperature

 

°C

36 / 60

36 / 60

36 / 60

WATER

 

 

 

 

 

 

Quantity of hot water ΔT=25°C

 

l/mn

14.5

16.8

21.3

 

 

 

 

 

 

 

 

 

HOT

Quantity of hot water ΔT=35°C

 

l/mn

10.4

12.0

15.2

 

 

 

 

 

 

Hot water comfort rating (EN13203)

 

stars

***

***

***

DOMESTIC

 

 

 

 

 

 

 

Domestic hot water max/min pressure

 

bar

7 / 0.3

7 / 0.3

7 / 0.3

 

Hot water minimum flow rate

 

l/mn

<2

<2

<2

 

 

 

 

 

 

 

 

Power supply frequency/voltage

 

V/Hz

230/50

230/50

230/50

ELECTRICAL

 

 

 

 

 

 

Protection level for the electrical appliance

 

PI

X5D

X5D

X5D

 

Total electrical power absorbed

 

W

110

113

116

 

Minimum ambient temperature for use

 

°C

+5

+5

+5

 

 

 

 

 

 

 

 

Weight

 

kg

32

35

36

 

 

 

 

 

 

 

9

product description

GENERAL NOTE

POWER SPECIFICATIONS

EMISSIONS

ELECTRICAL DOMESTIC HOT WATER CIRCUIT HEATING CIRCUIT

Model: CLAS HE EVO SYSTEM

 

 

18

24

30

 

 

 

 

 

 

CE Certification (pin)

 

 

 

0085CL0440

 

 

 

 

 

Boiler type

 

 

C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)

 

 

C83(X)-C93(X)-B23-B23P-B33

 

 

 

Max/min nominal calorific flow rate (Pci)

Qn

kW

18.0/4.5

22.0/5.5

28.5/6.5

Max/min nominal calorific flow rate (Pcs)

Qn

kW

20.0/5.0

24.4/6.1

31.1/7.2

 

 

 

 

 

 

Max/min power output (80°C-60°C)

Pn

kW

17.6/4.4

21.5/5.4

27.3/6.3

 

 

 

 

 

 

Max/min power output (50°C-30°C)

Pn

kW

19.1/4.7

23.3/5.7

29.7/6.8

 

 

 

 

 

 

Combustion efficiency (of flue gas)

 

%

98.0

97.8

97.8

 

 

 

 

 

 

Nominal calorific flow rate efficiency (60/80°C) Hi/Hs

 

%

97.6/87.9

97.5/87.8

97.6/87.8

 

 

 

 

 

 

Nominal calorific flow rate efficiency (30/50°C) Hi/Hs

 

%

106,1/95.5

105.8/95.3

106.0/95.5

 

 

 

 

 

 

Efficiency at 30% at 30°C Hi/Hs

 

%

107.7/97.0

107.7/97.0

107.7/97.0

 

 

 

 

 

 

Efficiency at 30% at 47°C Hi/Hs

 

%

97.7/88.0

97.7/88.0

97.6/87.9

 

 

 

 

 

 

Minimum calorific flow rate efficiency (60/80°C) Hi/Hs

 

%

97.6/87.9

97.6/87.9

97.5/87.8

Efficiency rating (dir. 92/42/EEC)

 

stars

****

****

****

Sedbuk Band / Rating

 

Band / %

A/90.1

A/90.0

A/90.0

 

 

 

 

 

 

Loss when stopped (ΔT = 50°C)

 

%

 

 

 

 

 

 

 

 

 

Loss of burner gas when operating

 

%

2.0

2.2

2.2

Available air pressure

 

Pa

100

100

100

 

 

 

 

 

 

NoX class (5 = less than 70mg/kWh

 

class

5

5

5

 

 

 

 

 

 

Flue gas temperature (G20) (80°C-60°C)

 

°C

61

64

64

 

 

 

 

 

 

CO2 content (G20) (80°C-60°C)

 

%

9.0

9.0

9.0

 

 

 

 

 

 

CO content (0%O2) (80°C-60°C)

 

ppm

93

119

101

 

 

 

 

 

 

O2 content (G20) (80°C-60°C)

 

%

4.5

4.5

4.5

Maximum flue gas flow (G20) (80°C-60°C)

 

Kg/h

29.7

36.3

46.1

 

 

 

 

 

 

Excess air (80°C-60°C)

 

%

27

27

27

Expansion chamber inflation pressure

 

bar

1

1

1

 

 

 

 

 

 

Maximum heating pressure

 

bar

2,5

2,5

2,5

 

 

 

 

 

 

Expansion chamber capacity

 

L

6.5

6.5

6.5

 

 

 

 

 

 

Min/max heating temperature (high temperature range)

 

°C

35 / 82

35 / 82

35 / 82

 

 

 

 

 

 

Min/max heating temperature (low temperature range)

 

°C

20 / 45

20 / 45

20 / 45

Power supply frequency/voltage

V/Hz

230/50

230/50

230/50

Total electrical power absorbed

W

106

113

116

 

 

 

 

 

Minimum ambient temperature for use

°C

+5

+5

+5

 

 

 

 

 

Protection level for the electrical appliance

PI

X5D

X5D

X5D

 

 

 

 

 

Weight

kg

32

32

35

10

installation

Reference Standards

In the United Kingdom, the installation and initial start-up of the boiler must be by a Gas Safe registered installer in accordance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e. Gas Safe.

In the Republic of Ireland the installation and initial start-up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations” and the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.

The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the by-laws of the local authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635, “Electricity at Work Regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813 and the Local Building Regulations (IE).

C.O.S.H.H.

Materials used in the manufacture of this appliance are nonhazardous and no special precautions are required when servicing.

Codes of Practive

Installation should also comply with the following British Standards Code of Practice:

BS 7593:

Treatment of water in domestic hot water

 

central heating systems

BS 5546:

Installation of hot water supplies for

 

domestic purposes

BS 5440-1:

Flues

BS 5440-2:

Air supply

BS 5449:

Forced circulation hot water systems

BS 6798:

Installation of gas fired hot water boilers

 

of rated input not exceeding 70kW

BS 6891:

Installation of low pressure gas pipes up to

 

28mm

BS 7671:

IEE Wiring Regulations

BS 4814:

Specification for expansion vessels

BS 5482:

Installation of L.P.G.

and in the Republic of Ireland in accordancce with the following codes of practice:

I.S. 813

Domestic Gas Installations

Avoid installing the boiler where the air inlet can be polluted by chemical products such as chlorine (swimming pool area), or ammonia (hair dresser), or alkalin products (launderette).

Flue

Detailed information on flue assembly can be found in the “Connecting the Flue” section.

The boiler must be installed so that the flue terminal is exposed to the free passage of external air at all times and must not be installed in a place likely to cause nuisance. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to.

Condensing boilers have a tendency to form a plume of water vapour from the flue terminal due to the low temperature of the flue gasses. The terminal should therefore be located with due regard for the damage or discolouration that may occur to building within the vicinity and consideration must also be given to adjacent boundaries, openable windows should also be taken into consideration when siting the flue.

The minimum acceptable clearances are shown below:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- A Directly below an opening, window, etc

 

300 mm

 

 

 

 

- B Horizontally to an opening, window, etc

 

300 mm

- C Below gutters, soils pipes or drain pipes

 

75 mm

- D Below eaves

 

200 mm

- E From vertical drain pipe or soil pipe

 

75 mm

- F From internal or external corner

 

300 mm

- G Above ground, roof or balcony level

 

300 mm

- H From a surface facing the terminal

 

600 mm

- I From a terminal facing a terminal

 

1200 mm

- J Vertically from a terminal on the same wall

 

1500 mm

- K Horizontally from an terminal on the same wall

 

300 mm

- L Fixed by vertical flue terminal

 

 

 

NOTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY TO CAUSE A NUISANCE AND POSITIONED TO ENSURE THAT PRODUCTS OF COMBUSTION DO NOT DISCHARGE ACROSS A BOUNDARY

It may be necessary to protect the terminal with a guard, if this is the case it will be necessary to purchase a stainless steel terminal guard. Reference should be made to the Building Regulations for guidance.

Ventilation

The room in which the boiler is installed does not require specific ventilation. If the boiler is installed in a cupboard or compartment ventilation is not required for cooling purposes.

11

installation

Gas Supply

The gas installation and tightness testing must be in accordance with the requirements of BS6891. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply.

Electrical Supply

The appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. regulations. It must also be possible to be able to completely isolate the appliance electrically. Connection should be via a 3 amp double pole fused isolating switch with contact separation of at least 3mm on both poles. Alternatively, a fused 3 amp, 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower, it. It should only supply the appliance.

Water Supply

The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 6 bar. All fittings and pipework for the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 6 bar, particularly at night, then a suitable pressure limiting valve must be fitted.

The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the boiler has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.

Showers

Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.

Flushing and Water Treatment

The boiler is equipped with a stainless steel heat exchanger.

The detailed recommendations for water treatment are given in BS 7593:2006 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance.

If the boiler is installed on an existing system, any unsuitable additives must be removed.

Under no circumstances should the boiler be fired before the system has been thoroughly flushed; the flushing procedure must be in line with BS 7593:2006.

We highly recommend the use of a flushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox BetzDearbon, whose function is to disolve any foreign matter that may be in the system.

In hard water areas or where large quantities of water are in the system the treatment of water to prevent premature scaling of the main exchanger is necessary.

The formation of scale heat compromises the efficiency of the thermic exchanger because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.

Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.

Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all metals used in the circuit.

The use of a corrosion inhibitor in the sysem such as Fernox MB-1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;

If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.

ARISTON suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place.

Periodically check the pH balance of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer (7 < pH < 8).

DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE

In under-floor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler etc), through the formation of oxides and bacterial agents.

To prevent this problem it is necessary to use pipes with an“oxygen proof barrier”, in accordance with standards DIN 4726/4729. If pipes of this kind are not used, keep the system separate by installing heat exchangers of those with a specific system water treatment.

IMPORTANT

Failure to carry out the water treatment procedure will invalidate the appliance guarantee.

System Controls

The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be beneficial to the efficient operation of the system. The boiler connections for external controls are 12V DC and so only controls of 12V DC that have voltage free contacts should be used. (page 25).

ARISTON supply a range of wired and wireless system controls. Contact your supplier for more details.

Location

The boiler can be installed on any suitable internal wall (suitable sound proofing may be required when installing onto a stud partition wall). Provision must be made to allow for the correct routing of the flue and siting of the terminal to allow the safe and efficient removal of the flue products. A compartment or cupboard may be used provided that it has been built or modified for this purpose. It is not necessary to provide permanent ventilation for cooling purposes. Detailed recommendations are given in BS 5440 Part 2. If it is proposed that it is to be installed in a timber framed building then reference should be made to IGEM Document, IGE/UP/7 or advice sought from Gas Safe.

Where a room sealed appliance is installed in a room containing a bath or shower, the appliance and any electrical switch or appliance control, utilising mains electricity should be situated specifically in accordance with current IEE Wiring Regulations.

For unusual locations, special procedures may be necessary. BS 6798 gives detailed guidance on this aspect.

12

installation

Codensate Discharge

The condensate discharge hose from the boiler must have a continuous fall of 2.5o and must be inserted by at least 50mm into a suitable acid resistant pipe - e.g. plastic waste or overflow pipe. The condensate discharge pipe must have a minimum diameter of 22mm, must have a continuous fall and preferably be installed and terminated to prevent freezing. The discharge pipe must be terminated in a suitable position:

i)Connecting into an internal soil stack (at least 450mm above the invert of the stack). A trap giving a water seal of at least 75mm must be incorporated into the pipe run, there also must be an air beak upstream of the trap.

ii)Connecting into the waste system of the building such as a washing maching or sink trap. The connection must be upstream of the washing machine/sink. If the connection is downstream of the waste trap then an additional trap giving a minimum water seal of 75mm and an air break must be incorporated in the pipe run, as above.

iii)Terminating into a gully, below the grid level but above the water level

iv)Into a soakaway

Note: If any condensate pipework is to be installed externally then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall. The total length of external pipe used should not exceed 3 metres.

Some examples of the type of condensate terminations can be found below.

1. Internal termination of condensate drainage pipe to internal stack.

Tundish

2. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste) and condensate siphon.

Tundish

trap

3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste - proprietary fitting).

Tundish

trap

4. External termination of condensate drainage pipe via condensate siphon

 

External pipe length

Tundish

max. 3 metres

 

(must be insulated)

Condensate Discharge

Push fit the flexible condensate pipe into the outlet spigot on the appliance. Cut to length and locate outlet into a tundish

13

installation

Installing the Boiler

Please check that you are familiar with the installation requirement before commencing work (pages 11 - 15).

The installation accessories described in the following list are included in the boiler packaging:

-Hanging bracket

-A paper template (showing the dimensions of the boiler with 5 mm side clearances)

-Connection valves (compression)

-Screws and washers

-Filling loop

-Installation, Servicing and User manual

Method of positioning the boiler on the wall

The paper template can be used to ensure the correct positioning of kitchen cabinets etc.

The paper template has to be fixed to the wall and used to locate the position of the hanging bracket and the centre for the flue hole.

Drill and plug the wall and secure the hanging bracket using the screws provided ensure the hanging bracket is level. Remove the boiler from its packaging and remove the front casing panel.

Place the boiler on the hanging bracket.

NOTE: THE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE WALL SURFACE.

Connecting the boiler to the system

-Remove the boiler casing as described on page 15

-Remove the caps and connect the valves to the boiler using the washers provided

-5 x fibre washers for the CH flow and return, cold water inlet, gas and hot water outlet connections

Safety Valve Discharge

The pressure relief valve pipe is made of copper. It should terminate below the boiler safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.

Warning !

Do not apply heat to the copper safety valve outlet pipe whilst it is connected to the 3 bar safety relief valve.

Fill the central heating and DHW system and bleed air from the system as described in the Commissioning instructions (page 31).

The system should be carefully checked for leaks, as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the trap should be connected to a drain as described in the relevant regulations.

Pay special attention not to bend the condensate silicone drain pipe is such a way as to interrupt the flow. Please only use drain pipe material compatible with condensate products (refer to BS 6798:2009).

The condensate flow can reach 2 litres/hour because of the acidity of the condensate products (Ph close to 2), take care before operation.

See page 13 for condensate discharge options.

CLAS HE EVO

CLAS HE EVO SYSTEM

Note: Connections viewed from behind boiler

Note.

Note: Connections viewed from behind boiler

Connections viewed from behind boiler.

A

A

-remove the 2 screws A from the transport bar

-dispose of the transport bar and reassemble the fixing screws.

14

installation

Gas connection

Make sure, using the labels on the packaging and the data plate on the appliance itself, that the boiler is in the correct country and that the gas category for which the boiler was designed corresponds to one of the categories available in the country where it will be used.

The gas supply piping must be created and measured out in compliance with specific legal requirements and in accordance with the maximum power of the boiler.

Check that the supplied gas corresponds to the type of gas for which the boiler was designed (see the data plate located on the appliance itself).

It is also important to check that the pressure of the gas (methane or LPG) you will be using to feed the boiler is suitable, because if it is insufficient the power may be reduced, causing inconvenience for the user.

Water connection

The illustration below shows the connections for the water and gas attachments of the boiler. See valves configuration on page 14.

Check that the maximum water mains pressure does not exceed 6 bar; if it does, a pressure reducing valve must be installed.

For the measuring of the pipes and of the heating bodies in the heating system, the residual head value should be calculated as a function of the requested flow rate, in accordance with the values shown in the circulation pump graph.

Instructions for opening the casing and performing an internal inspection

Before performing any work on the boiler, first disconnect it from the electrical power supply using the external bipolar switch removing the fuse and shutting off the gas valve.

To access the inside of the boiler, the following is necessary:

1.Remove the casing by unhooking it from the control panel (a)

2.Loosen the two screws on the front casing (b), pull it forwards and unhook it from the upper pins (c)

3.Lower the control panel (d)

4.Unhook the two clips on the combustion chamber panel and lift off (e).

(a)

(b)

(c)

 

CLAS HE EVO

 

 

 

(d)

 

E

 

 

D

 

F

C

 

 

 

B

H

 

A

 

 

I

 

 

 

CLAS HE EVO SYSTEM

 

 

E

(e)

 

D

F

C

 

 

 

A

H

 

 

 

I

 

 

A. Central heating Flow

 

 

B. Domestic Hot Water Outlet

 

 

C. Gas Inlet

 

 

D. Domestic Cold Water Inlet

 

 

E. Central Heating Return

 

 

F. Safety Valve Discharge

 

 

H. Drain Valve

 

 

I. Drain condensate

 

 

15

installation

To calculate the size of the heating installation, refer to the "Available pressure" graph below.

Graph representing the available circulation pump pressure T20oC

CLAS HE EVO

38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

5

 

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[mCE]

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

100

200

300

400

500

600

700

800

900

1000

1100

 

 

 

 

 

 

[l\h]

 

 

 

 

 

CLAS HE EVO SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18/24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[mCA]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

100

200

300

 

400

500

600

700

800

900

1000

Before the equipment is used, for the first time the trap must be filled with water. To do this, add approximately 1/4 litre of water via the flue outlet before fitting the flue system, or unscrew the cap on the trap positioned underneath the boiler, fill it with water and refit it

Warning! Insufficient water in the trap can temporarily cause the flue gas to be expelled into the surrounding ambient air

Underfloor heating

For appliances with underfloor heating, it is possible but not necessary to fit a safety thermostat onto the underfloor heating outlet. For the electrical connection of the thermostat see the section on “Electrical connections - page 25”.

If the outlet temperature is too high, the boiler will stop both domestic hot water and the heating production and the error code 1 16 “floor thermostat contact open” will appear on the display. The boiler will restart when the thermostat is closed during automatic resetting.

If the thermostat cannot be installed, the underfloor heating equipment must be protected by a thermostatic valve, or by a bypass to prevent the floor from reaching too high a temperature.

I

16

installation

Water circuit diagram

1

 

 

 

 

1

 

 

3

 

 

 

22

3

 

22

 

 

 

 

 

 

4

 

 

 

21

4

 

21

 

 

 

 

 

 

 

 

 

 

20

5

 

 

5

 

 

 

 

 

20

 

 

 

 

 

 

 

6

 

 

 

 

6

 

 

 

 

 

 

19

 

 

19

7

 

 

 

18

 

 

18

8

 

 

 

17

8

 

17

 

 

 

 

 

10

 

 

 

16

10

 

 

 

 

 

 

 

 

11

 

 

 

15

11

 

 

 

 

 

 

12

 

14

12

 

 

 

14

 

 

 

 

 

13

 

 

 

 

A

B

C

D E

A

C

E

 

 

 

 

1.

Manual air vent

 

 

 

 

 

3.

Burner

 

 

 

 

 

 

4.

Detection electrode

 

 

 

 

 

5.

C.H. flow temperature probe

 

 

 

 

6.

C.H. return temperature probe

 

 

 

 

7.

Secondary heat exchanger

 

 

 

 

8.

C.H. pressure relief valve

 

 

 

 

10.

By-pass

 

 

 

 

 

 

11.

Drain valve

 

 

 

 

 

12.

Condensate trap

 

 

 

 

 

13.

Filling loop

 

 

 

 

 

14.

C.H. circuit filter

 

 

 

 

 

15.

D.H.W. Flow switch

 

 

 

 

 

16.

diverter valve

 

 

 

 

 

17.

water pressure sensor

 

 

 

 

18.

circulation Pump

 

 

 

 

 

19.

expansion vessel

 

 

 

 

 

20.

modulating Fan

 

 

 

 

 

21.

ignition electrodes

 

 

 

 

 

22.

thermal fuse

 

 

 

 

 

 

 

 

 

 

 

 

17

installation

Connecting the Flue

Flue System

The provision for satisfactory flue termination must be made as described in BS 5440-1.

The appliance must be installed so that the flue terminal is exposed to outdoor air.

The terminal must not discharge into another room or space such as an outhouse or lean-to.

It is important that the position of the terminal allows a free passage of air across it at all times.

The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity, it must also be located in a place not likely to cause nuisance.

In cold or humid weather water vapour may condense on leaving the flue terminal.

The effect of such “steaming” must be considered.

If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable stainless steel terminal guard must be fitted.

The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in Fig. 1.

Fig. 1

- A Directly below an opening, window, etc

300 mm

- B Horizontally to an opening, window, etc

300 mm

- C Below gutters, soils pipes or drain pipes

75 mm

- D Below eaves

200 mm

- E From vertical drain pipe or soil pipe

75 mm

- F From internal or external corner

300 mm

- G Above ground, roof or balcony level

300 mm

- H From a surface facing the terminal

600 mm

- I From a terminal facing a terminal

1200 mm

- J Vertically from a terminal on the same wall

1500 mm

- K Horizontally from an terminal on the same wall

300 mm

- L Fixed by vertical flue terminal

 

Minimum Length = 500 mm

150 mm

180 mm

118 mm

Fig. 2

18

 

installation

Warning

Important

The exhaust gas ducts must not be in contact with or close

to inflammable material and must not pass through building

Ensure that the flue is not blocked.

structures or walls made of inflammable material.

Ensure that the flue is supported and assembled in accordance

When replacing an old appliance, the flue system must be

with these instructions.

changed.

 

 

Installation without extension

Level

 

 

118

 

 

 

 

150 mm

Installation with extension

 

Level

 

 

 

*slopepente

 

 

 

150 mm

 

* Min slope: 1˚

 

 

1˚= 17.5mm per metre

 

 

Fig. 3

Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)

Contents:

1x Silicone O-Ring (60mm)

1x Elbow (90°)

2x Wall Seals (Internal & External)

1x Flue Pipe including Terminal (1 metre - 60/100)

2x Flue Clamps

4x Screws

2x Seals

Once the boiler has been positioned on the wall, fit the rubber flue seal into the internal flue turret (see diagram opposite),

Insert the elbow into the socket and rotate to the required position. note: It is possible to rotate the elbow 360° on its vertical axis.

Using the flue clamp, seals and screws supplied (Fig 4) secure the elbow to the boiler.

The 1 metre horizontal flue kit (3318073) supplied is suitable for an exact X dimension of 753mm.

Measure the distance from the face of the external wall to the face of the flue elbow (X - Fig 2), this figure must now be subtracted from 753mm, you now have the total amount to be cut from the plain end of the flue.

Note: A Plume management kit is available for 60/100 horizontal termination. Instructions for installation are supplied with the Plume management kit.

Draw a circle around the outer flue and cut the flue to the required length taking care not to cut the inner flue, next cut the inner flue ensuring that the length between the inner and outer flue is maintained. (Fig 4).

e.g.

X = 555mm

753-555 = 198mm (Length to be cut from the plain end of the flue).

Once cut to the required length, ensure that the flue is free from burrs and reassemble the flue. If fitting the flue from inside of the building attach the outer wall seal to the flue terminal and push the flue through the hole, once the wall seal has passed through the hole, pull the flue back until the seal is flush with the wall. Alternatively, the flue can be installed from outside of the building, the outer seal being fitted last.

Should the flue require extending, the flue connections are push fit, however, one flue bracket should be used to secure each metre of flue.

Note: See table for maximum and minimum flue runs.

19

installation

Clamp

Screws

Seal

Fig. 4

Fitting the 5” Flue

(Ø 80 / 125 Horizontal/vertical)

Total length

Useable length

of Vertical flue

of Vertical Kit

575 mm*

1240 mm

 

5" Adaptor

180 mm

Part no: 3318095

 

* This length will vary according to the type

Fig. 5of flashing installed

Once the boiler has been positioned on the wall, it is necessary to insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical flue runs into the boiler flue socket (not supplied with flue kit - Part No 3318095).

Push the adaptor onto the boilers flue connection, grease the seals then add extensions or elbows as required, secure the adaptor, using the clamp and screws provided.

To fit extensions or elbows it is first necessary to ensure that the lip seal is fitted correctly into the inner flue, once verified, it is simply necessary to push them together, no clamps are necessary to secure the flue components.

Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, for each additional 90° elbow 1 metre must be subtracted from the total flue length, and for each 45° 0.5 metres must be subtracted from the total flue length (the height of the vertical adaptor and a 45° bend can be seen in Fig.6 and a 90° bend in Fig. 7).

Note: DO NOT cut the vertical flue kit.

Fig. 6

Fig. 7

20

installation

Fitting the Coaxial Flue

(Ø 60 / 100 Vertical)

Total length

of Vertical Kit

1355 mm

Vert Adaptor

(supplied with flue kit)

Useable length

of Vertical flue

690 mm*

180 mm

Vertical Starter

Part No: 3318079

*This length will vary according to the type of flashing installed

Fig. 7

Fig. 8

Note: See table for maximum and minimum flue runs.

Contents:

1x Conical Adaptor (60/100mm)

1x Vertical Flue Kit (80/125mm)

The vertical flue kit is supplied with a specially designed weather proof terminal fitted, it can be used either with a flat roof or a pitched roof.

The Vertical flue kits useable lengths with the pitched roof flashings are indicated in Fig. 7.

Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, for each additional 90° elbow 1 metre must be subtracted from the total flue length, and for each 45° 0.5 metres must be subtracted from the total flue length (the height of the vertical adaptor and a 45° bend can be seen in Fig. 8).

Mark the position of the flue hole in the ceiling and/or roof (see Fig. 7 for distance from wall to the centre of the flue).

Cut a 130mm diameter hole through the ceiling and/or roof and fit the flashing plate to the roof.

DO NOT cut the vertical flue kit.

To connect the vertical flue kit directly to the boiler, place the vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold and secure with the clamp, fit the vertical adaptor onto the vertical starter kit (note: there is no need to use a clamp to secure this as it is a push fit connection), the vertical flue kit must then be inserted through the roof flashing, this will ensure that the correct clearance above the roof is provided as the terminal is a fixed height.

Should extensions be required, they are available in 1 metre (Part No. 3318077), 500mm (Part No. 3318078) and they must be connected directly to the vertical starter kit before connecting the adaptor to allow the vertical flue kit to be fitted. In the event that extension pieces need to be shortened, they must only be cut at the male end and it must be ensured that the inner and outer flue remain flush.

When utilising the vertical flue system, action must be taken to ensure that the flue is supported adequately to prevent the weight being transferred to the appliance flue connection by using 1 flue bracket per extension.

When the flue passes through a ceiling or wooden floor, there must be an air gap of 25mm between any part of the flue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the flue passes from one room to another a fire stop must be fitted to prevent the passage of smoke or fire, irrespective of the structural material through which the flue passes.

21

installation

Fitting the Twin Pipe (Ø80 / 80)

Note: See table for maximum and minimum flue runs.

Where it is not possible to terminate the flue within the distance permitted for coaxial flues, the twin flue pipe can be used by fitting a special adaptor to the flue connector and using the aperture for the air intake located on top of the combustion chamber.

Always ensure that the flue is adequately supported, using one flue bracket per extension and avoiding low points. (ARISTON supply suitable clamps as Part No. 705778).

To utilise the air intake it is necessary to:

1)Take the air intake cover off the top of the appliance

2)Assemble the flange on the header supplied with the boiler

3)Insert the header on the tube or the elbow up until the lower stop (you do not have to use the washer).

4)Insert the elbow/header in the boiler air intake hole and fasten it with screws.

The twin flue pipes can be fitted with or without additional elbows and need no clamps, simply ensure that the lip seal is inserted in the female end of the flue pipe and push the extension piece fully into the previous section of flue pipe or elbow, check that the lip seal is not dislodged when assembling the flue (greasing the seal will aid assembly).

Twin pipe can also be converted back to Coaxial flue to enable vertical termination with a coaxial kit by using the pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089). When running the twin flue pipe vertically.

It is not possible to terminate concentrically horizontally. Termination is only possible with separate air and exhaust terminals.

When siting the twin flue pipe, the air intake and exhaust terminals must terminate on the same wall, the centres of the terminals must be a minimum of 280 mm apart and the air intake must not be sited above the exhaust terminal (refer to Fig. 10). The air intake pipe can be run horizontally, however, the terminal and the final 1 metre of flue must be installed either horizontally or with a slight fall away from the boiler to avoid rain ingress.

It is also strongly recommended that the air intake pipe run be constructed of insulated pipe to prevent condense forming on the outside of the tube.

Ensure the exhaust tube has a minimum fall back to the boiler of 1˚ / metre (1˚ = 17.5mm/metre)

The maximum permissible flue length for twin flue is dependent on the type of run used (see table on page 24).

For further information relating to flue runs not illustrated, please contact the Technical Department on 0870 241 8180.

22