Operation Manual
Smart-UPS® X
Uninterruptible Power Supply
Low Voltage (100-127 V)
SMX2000RMLV2U
SMX2200RMLV2U
SMX3000RMLV2U
SMX3000RMLV2UNC
SMX3000RMJ2U
High Voltage (200-240 V)
SMX2200RMHV2U
SMX3000RMHV2U
SMX3000RMHV2UNC
Overview
About the UPS
The APC® by Schneider Electric Smart-UPS® X is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.
The Smart-UPS X has both high and low voltage models
Low Voltage (100-127 V) |
High Voltage (200-240 V) |
SMX2000RMLV2U |
SMX2200RMHV2U |
SMX2200RMLV2U |
SMX3000RMHV2U |
SMX3000RMLV2U |
SMX3000RMHV2UNC |
SMX3000RMLV2UNC |
|
SMX3000RMJ2U |
|
Safety
Read the Safety Guide included in the package before installing the UPS.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
Recycle the packaging.
Heavy: The external battery packs (XLBPs) are heavy. Always install the XLBPs at the bottom of the rack. Install the UPS above the installed XLBPs.
Product Overview
Front panel
Battery
Battery connectorDisplay interfaceBezel
su0498a
Smart-UPS X 2000/2200/3000 VA |
1 |
Rear panel
SmartSlot |
Controllable Outlet Group 3 |
|
UPS input |
External battery pack connector |
|
Ground screw |
EPO connector |
|
Controllable Outlet Group 1 |
Serial port |
|
Controllable Outlet Group 2 |
USB port |
|
2200 VA Low Voltage |
2000 VA Low Voltage |
|
|
su0494a |
su0492a |
3000 VA Low Voltage |
2200/3000 VA High Voltage |
|
su0495a |
su0493a |
Specifications
Operating Conditions
This unit is intended for indoor use only. Select a location sturdy enough to support the weight of the UPS and XLBP.
Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits.
This unit has front and rear air vents. Allow adequate space for proper ventilation.
Environmental Specifications
Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.
For additional specifications, see the APC Web site at www.apc.com.
Operating 0° to 40° C (32° to 104° F) Temperature Storage -15° to 45° C (5° to 113° F)
charge UPS battery every six months
Maximum |
Operating |
3,000 m (10,000 ft) |
Elevation |
|
|
Storage |
15,000 m (50,000 ft) |
|
Humidity |
0% to 95% relative humidity, non-condensing |
2 |
Smart-UPS X 2000/2200/3000 VA |
Installation
UPS
For UPS installation information, see the Smart-UPS X 2000-3000 VA Quick-Start that is included with the UPS. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.
Network Management Card
For installation information, see the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC Web site at www.apc.com.
External Battery Pack
For installation information, see the Smart-UPS X 2000-3000 VA External Battery Pack Installation guide that is included with the external battery pack. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.
Smart-UPS X 2000/2200/3000 VA |
3 |
Operation
Connect Equipment to the UPS
Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.
1.Connect equipment to the outlets on the rear panel of the UPS.
2.Connect the UPS to the building utility power. Connect the UPS to a two-pole, three-wire, grounded source only.
3.Press the ON/OFF button on the front panel of the UPS to power the unit and all connected equipment.
4.To use the UPS as a master on/off switch, turn on all the equipment that is connected to the UPS.
See “Switched Outlet Groups” on page 11 for information on how to use the Switched Outlet Groups.
su0475a
Basic Connections
Serial port: Connect to a computer to use power management software, use the serial cable included with the unit.
USB port: Connect to a computer to use power management software.
Note: Serial and USB communication can only be used individually, they cannot communicate at the same time.
External Battery Pack connector: Connect XLBPs to provide extended runtime during power outages. The UPS can support up to 10 external battery packs.
Ground Screw: The UPS features a ground screw for connecting the ground leads on transient voltage devices. Prior to connecting a ground lead, disconnect the UPS from utility power.
4 |
Smart-UPS X 2000/2200/3000 VA |