APC SMX2200RMLV2U, 100-127 V, SMX3000RMJ2U, SMX2000RMLV2U, SMX3000RMLV2UNC User Manual

...
0 (0)
APC SMX2200RMLV2U, 100-127 V, SMX3000RMJ2U, SMX2000RMLV2U, SMX3000RMLV2UNC User Manual

Operation Manual

Smart-UPS® X

Uninterruptible Power Supply

Low Voltage (100-127 V)

SMX2000RMLV2U

SMX2200RMLV2U

SMX3000RMLV2U

SMX3000RMLV2UNC

SMX3000RMJ2U

High Voltage (200-240 V)

SMX2200RMHV2U

SMX3000RMHV2U

SMX3000RMHV2UNC

Overview

About the UPS

The APC® by Schneider Electric Smart-UPS® X is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.

The Smart-UPS X has both high and low voltage models

Low Voltage (100-127 V)

High Voltage (200-240 V)

SMX2000RMLV2U

SMX2200RMHV2U

SMX2200RMLV2U

SMX3000RMHV2U

SMX3000RMLV2U

SMX3000RMHV2UNC

SMX3000RMLV2UNC

 

SMX3000RMJ2U

 

Safety

Read the Safety Guide included in the package before installing the UPS.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.

Recycle the packaging.

Heavy: The external battery packs (XLBPs) are heavy. Always install the XLBPs at the bottom of the rack. Install the UPS above the installed XLBPs.

Product Overview

Front panel

Battery

Battery connectorDisplay interfaceBezel

su0498a

Smart-UPS X 2000/2200/3000 VA

1

Rear panel

SmartSlot

Controllable Outlet Group 3

 

UPS input

External battery pack connector

 

Ground screw

EPO connector

 

Controllable Outlet Group 1

Serial port

 

Controllable Outlet Group 2

USB port

 

2200 VA Low Voltage

2000 VA Low Voltage

 

 

su0494a

su0492a

3000 VA Low Voltage

2200/3000 VA High Voltage

 

su0495a

su0493a

Specifications

Operating Conditions

This unit is intended for indoor use only. Select a location sturdy enough to support the weight of the UPS and XLBP.

Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits.

This unit has front and rear air vents. Allow adequate space for proper ventilation.

Environmental Specifications

Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.

For additional specifications, see the APC Web site at www.apc.com.

Operating 0° to 40° C (32° to 104° F) Temperature Storage -15° to 45° C (5° to 113° F)

charge UPS battery every six months

Maximum

Operating

3,000 m (10,000 ft)

Elevation

 

 

Storage

15,000 m (50,000 ft)

Humidity

0% to 95% relative humidity, non-condensing

2

Smart-UPS X 2000/2200/3000 VA

Installation

UPS

For UPS installation information, see the Smart-UPS X 2000-3000 VA Quick-Start that is included with the UPS. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Network Management Card

For installation information, see the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC Web site at www.apc.com.

External Battery Pack

For installation information, see the Smart-UPS X 2000-3000 VA External Battery Pack Installation guide that is included with the external battery pack. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Smart-UPS X 2000/2200/3000 VA

3

Operation

Connect Equipment to the UPS

Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.

1.Connect equipment to the outlets on the rear panel of the UPS.

2.Connect the UPS to the building utility power. Connect the UPS to a two-pole, three-wire, grounded source only.

3.Press the ON/OFF button on the front panel of the UPS to power the unit and all connected equipment.

4.To use the UPS as a master on/off switch, turn on all the equipment that is connected to the UPS.

See “Switched Outlet Groups” on page 11 for information on how to use the Switched Outlet Groups.

su0475a

Basic Connections

Serial port: Connect to a computer to use power management software, use the serial cable included with the unit.

USB port: Connect to a computer to use power management software.

Note: Serial and USB communication can only be used individually, they cannot communicate at the same time.

External Battery Pack connector: Connect XLBPs to provide extended runtime during power outages. The UPS can support up to 10 external battery packs.

Ground Screw: The UPS features a ground screw for connecting the ground leads on transient voltage devices. Prior to connecting a ground lead, disconnect the UPS from utility power.