APC ACRC501, ACRP500, ACRP101, ACRP100, ACRP501 User Manual

...
0 (0)
APC ACRC501, ACRP500, ACRP101, ACRP100, ACRP501 User Manual

User’s Guide

InRow RC/RD/RP

(600mm)

ACRC500

ACRC501

ACRD500

ACRD501

ACRP100

ACRP101

ACRP500

ACRP501

Contents

Introduction .....................................................................

1

Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Features of the InRow RC/RD/RP (600 mm) . . . . . . . . . . . . . . . . . . . 1

Initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Internal Management Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Log on control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Types of user accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

How to Recover from a Lost Password . . . . . . . . . . . . . . . . . . . . . . . 4 Display Interface LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Check log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Warning alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Critical alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Watchdog Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Network interface watchdog mechanism . . . . . . . . . . . . . . . . . . . . .

5

Resetting the network timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Control Console .............................................................

6

How to Log On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Remote access to the control console . . . . . . . . . . . . . . . . . . . . . . . 6

Local access to the control console . . . . . . . . . . . . . . . . . . . . . . . . . 7

Main Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Example main screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Information and status fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Control Console Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Device Manager option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Network option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

System option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

InRow RC/RD/RP (600 mm) User’s Guide

i

Web Interface ................................................................

13

How to Log On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Supported Web browsers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

URL address formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Common browser error messages at login . . . . . . . . . . . . . . . . . . . 14

Summary Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Navigation tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Quick status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Select a tab to perform a task . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

InRow RC/RD/RP (600 mm) Operation.........................

18

Home . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Alarm status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Detailed status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Compressor drive status (ACRD500 series and ACRP100 series) 21

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Service intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Logs ...............................................................................

23

Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Reverse lookup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

ii

InRow RC/RD/RP (600 mm) User’s Guide

Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Graphing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Syslog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

Servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

How to use FTP or SCP to retrieve the log files . . . . . . . . . . . . . . . 28

Queries (Modbus requests and SNMP GETs) . . . . . . . . . . . . . . . . . 29

Administration: Security ..............................................

30

Local Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

Permission levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Setting user access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Remote Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

RADIUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Configuring the RADIUS Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Summary of the configuration procedure . . . . . . . . . . . . . . . . . . . . 32

Configuring a RADIUS server on UNIX®, with shadow passwords 33

Supported RADIUS servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Inactivity Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

Administration: Network...............................................

34

TCP/IP and communication settings . . . . . . . . . . . . . . . . . . . . . . . . .34

TCP/IP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

DHCP response options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Port speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

DNS (Adminstration>Network>DNS>servers) . . . . . . . . . . . . . . . . . 38

Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

FTP server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Related Topics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45

InRow RC/RD/RP (600 mm) User’s Guide

iii

Administration: Notification ........................................

46

Event Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Types of notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Configuring event actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Active, Automatic, Direct Notification . . . . . . . . . . . . . . . . . . . . . . . 49

E-mail notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

SNMP traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Administration: General Options.................................

52

Information about the Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . 52

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Date & time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

User configuration file (ini) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Unit preference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Reset the interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Serial Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Quick links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

APC Device IP Configuration Wizard...........................

55

Capabilities, Requirements, and Installation . . . . . . . . . . . . . . . . . . 55

Use the Wizard to configure basic TCP/IP settings . . . . . . . . . . . . 55

System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Use the Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Launch the Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Configure the basic TCP/IP settings remotely . . . . . . . . . . . . . . . . 56

Configure or reconfigure the TCP/IP settings locally . . . . . . . . . . 57

How to Export Configuration Settings ........................

58

Retrieving and Exporting the .ini File . . . . . . . . . . . . . . . . . . . . . . . . 58

Summary of the procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Contents of the .ini file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Detailed procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

The Upload Event and Error Messages . . . . . . . . . . . . . . . . . . . . . . 61

The event and its error messages . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Errors generated by overridden values . . . . . . . . . . . . . . . . . . . . . . 61

iv

InRow RC/RD/RP (600 mm) User’s Guide

Related Topics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

File Transfers .................................................................

62

How to Upgrade Firmware . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . .62

Benefits of upgrading firmware . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 62

Firmware files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 62

Obtain the latest firmware version . . . . . . . . . . . . . . . . . . . . .

. . . . . 62

Firmware file transfer methods . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 63

Use FTP or SCP to upgrade one cooling unit . . . . . . . . . . .

. . . . . 64

Upgrade multiple InRow RC/RD/RP (600 mm) cooling units

. . . . . 65

Use XMODEM to upgrade one InRow RC/RD/RP (600 mm)

. . . . . 65

Verifying Upgrades and Updates. . . . . . . . . . . . . . . .

. . . . . . . . . . . .66

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 66

Last transfer result codes . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 66

InRow RC/RD/RP (600 mm) User’s Guide

v

Introduction

Product Description

Features of the InRow RC/RD/RP (600 mm) cooling unit

The American Power Conversion (APC®) InRow RC/RD/RP (600 mm) cooling unit is a modular air conditioning unit that is available in either a direct expansion (DX) model (ACRD500 series or ACRP100 series) or a chilled water (CW) model (ACRC500 series or ACRP500 series). It is the width of a standard enclosure (600 mm), and can be placed in a data-center row. It provides full management capabilities over a network using HyperText Transfer Protocol (HTTP), Telnet, HTTP over Secure Sockets Layer (HTTPS), Secure Shell (SSH), Simple Network Management Protocol (SNMP), File Transfer Protocol, (FTP), Secure CoPy (SCP), and Modbus. The cooling unit provides the following features:

Group control

Temperature monitoring

Remote shutdown

Output contact monitoring

Event log accessible by Telnet, FTP, SSH, SCP, serial connection, the display interface, or a Web browser

SNMP traps and e-mail notifications sent in response to events

Syslog events sent to configured Syslog servers

Security protocols for authentication and encryption

Initial setup

You must define the following three TCP/IP settings for the cooling unit before it can operate on the network:

IP address of the cooling unit

Subnet mask

IP address of the default gateway

Note: Never use the loopback address (127.0.0.1) as the default gateway address for the cooling unit. Doing so will disable the unit and will require you to reset TCP/IP settings to their defaults using a local serial login.

To use a DHCP server to configure the TCP/IP settings for a cooling unit, see “TCP/ IP settings” on page 37.

To configure the TCP/IP settings, see the Installation Manual for your cooling unit, provided in printed form and in PDF on either the Utility CD or on the APC Web site, www.apc.com.

InRow RC/RD/RP (600 mm) User’s Guide

1

Internal Management Features

Overview

You can manage the cooling unit through the Web interface, display interface, control console, Modbus, or SNMP. SNMP requires the PowerNet® MIB, available on the Utility CD or from the APC Web site, www.apc.com.

For more information about the menu-driven interfaces of the cooling unit, see “Web Interface” on page 13 and “Control Console” on page 6.

For more information about the display interface, see the Operation and Maintenance manual for your cooling unit, available on the Utility CD or on the APC Web site, www.apc.com.

To download the latest version of the Modbus register map, go to the APC Web site, www.apc.com, search by part number, and click the link to the register map in the list of documentation. Check the publication date at the start of the file.

For more information about Modbus, see the Modbus Standard Library at www.modbus.org.

To use the PowerNet MIB with an SNMP browser, see the PowerNet SNMP Management Information Base (MIB) Reference Guide, provided on the Utility CD.

Access priority for logging on

Only one user at a time can log on to the cooling unit to use its internal user interface features. The priority for access is as follows:

Local access to the control console from a computer with a direct serial connection to the cooling unit always has the highest priority.

Telnet or Secure SHell (SSH) access to the control console from a remote computer has the next highest priority.

Web access, either directly or through the InfraStruXure Central, has the lowest priority.

For information on how to control SNMP access to the cooling unit, see “SNMP” on page 46.

2

InRow RC/RD/RP (600 mm) User’s Guide

Types of user accounts

The cooling unit has three levels of access (Administrator, Device User, and Read-Only User), all of which are protected by user name and password requirements.

An Administrator can use all of the management menus available in the control console and the Web interface. The Administrator’s default user name and password are both apc.

A Device User (Device Manager in the control console) can access only the Log option in the Events menu and use the Group, Unit, and Alarms menus. The Device User’s default user name is device, and the default password is apc.

A Read-Only User has the following restricted access:

Access through the Web interface only.

Access to the same menus as a Device User, but without the capability to change configurations, control devices, or delete data. Links to configuration options may be visible but are disabled, and the event log displays no Clear Log button.

The Read-Only User’s default user name is readonly, and the default password is apc.

To set User Name and Password values for the Administrator, Device User, and

Read-Only User accounts, see “Setting user access” on page 32. You must use the

Web interface to configure values for the Read-Only User.

InRow RC/RD/RP (600 mm) User’s Guide

3

How to Recover from a Lost Password

Use a local computer, a computer that connects to the cooling unit through the serial port, to access the control console.

1.Select a serial port at the local computer and disable any service that uses that port.

2.Connect the configuration cable (APC part number 940-0103 and extension, if required, 9401000A) to the selected port on the computer and to the serial port at the cooling unit (use the DB- 9 connector on the front of the electrical panel).

Note: Do not touch components on the electrical panel, other than the service port.

3.Run a terminal program (such as HyperTerminal) and configure the selected port as follows:

9600 bps

8 data bits

no parity

1 stop bit

no flow control

4.Press ENTER on the computer, repeatedly if necessary, to display the User Name prompt.

5.If you are unable to display the User Name prompt, verify the following:

The serial port is not in use by another application.

The terminal settings are correct as specified in step 3.

The correct cable is being used as specified in step 2.

6.Switch the main breaker to OFF. Wait one second. Switch the main breaker to ON.

Note: If you wait too long to return power to the cooling unit, you must repeat step 5.

7.Press ENTER as many times as necessary to redisplay the User Name prompt, then use the default, apc, for the user name and password. (If you take longer than 30 seconds to log on after the User Name prompt is redisplayed, you must repeat step 5 and log on again.)

8.From the Control Console menu, select System, then User Manager.

9.Select Administrator, and change the User Name and Password settings, both of which are now defined as apc. Select Accept Changes to store the new user name and password values.

10.Press CTRL+C, log off, reconnect any serial cable you disconnected, restart any service you disabled.

4

InRow RC/RD/RP (600 mm) User’s Guide

Display Interface LEDs

Status

This LED indicates the status of the cooling unit.

Condition

Description

 

 

Off

The cooling unit has no power.

 

 

Solid Green

The cooling unit is receiving power.

 

 

Flashing Green

The cooling unit is receiving a firmware upgrade.

 

 

Check log

When yellow, this LED indicates that at least one new critical alarm, warning alarm, or event has occurred since the last time the event log was viewed from the display interface.

Warning alarm

When yellow, this LED indicates that a warning alarm condition exists and may require your attention to prevent it from deteriorating into a critical state. A new alarm will cause a beep every 30 seconds until you silence the alarm by pressing any function key.

Critical alarm

When red, this LED indicates that a critical alarm condition exists and requires your immediate attention. An audible alarm beeps every 30 seconds. Press any function key to silence the audible alarm.

Watchdog Features

Overview

To detect internal problems and recover from unanticipated inputs, the cooling unit uses internal, systemwide watchdog mechanisms. When it reboots to recover from an internal problem, a System: Warmstart event is recorded in the event log.

Network interface watchdog mechanism

The cooling unit implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the cooling unit does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts.

Resetting the network timer

To ensure that the cooling unit does not restart if the network is quiet for 9.5 minutes, the cooling unit attempts to contact the Default Gateway every 4.5 minutes. If the gateway is present, it responds to the cooling unit, and that response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network most of the time and is on the same subnet. The network traffic of that computer will reset the 9.5-minute timer frequently enough to prevent the cooling unit from restarting.

InRow RC/RD/RP (600 mm) User’s Guide

5

Control Console

How to Log On

Overview

You can use either a local (serial) connection, or a remote (Telnet or SSH) connection to access the control console.

Use case-sensitive user name and password entries to log on (by default, apc and apc for an Administrator, or device and apc for a Device User). A Read-Only User cannot access the control console.

If you cannot remember your user name or password, see “How to Recover from a Lost Password” on page 4.

Remote access to the control console

You can access the control console through Telnet or Secure SHell (SSH), depending on which is enabled. (An Administrator can enable these access methods through the Telnet/SSH option of the Network menu.) By default, Telnet is enabled. Enabling SSH automatically disables Telnet.

Telnet for basic access. Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption. To use Telnet to access the control console from any computer on the same subnet:

1.At a command prompt, type telnet and the System IP address for the cooling unit (when the cooling unit uses the default Telnet port of 23), and press ENTER. For example:

telnet 139.225.6.133

Note: If the cooling unit uses a non-default port number (between 5000 and 32767), you need to include a colon or a space (depending on your Telnet client) between the IP address and the port number.

2.Enter the user name and password (by default, apc and apc for an Administrator, or device and apc for a Device User).

SSH for high-security access. If you use the high security of SSL for the Web interface, use Secure SHell (SSH) for access to the control console. SSH encrypts user names, passwords, and transmitted data.

The interface, user accounts, and user access rights are the same whether you access the control console through SSH or Telnet, but to use SSH, you must first configure SSH and have a SSH client program installed on your computer.

6

InRow RC/RD/RP (600 mm) User’s Guide

Local access to the control console

You can use a local computer that connects to the cooling unit through the serial port.

Note: To access the serial port, remove the front panel and lower air filter of the cooling unit.

1.Select a serial port at the local computer and disable any service that uses that port.

2.Use the configuration cable (APC part number 940-0103 and extension, if required, 940-1000A) to connect the selected port of the local computer to the serial port at the cooling unit (use the DB-9 connector on the front of the electrical panel).

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.

4.Enter the user name and password for the access desired (Administrator or Device User).

InRow RC/RD/RP (600 mm) User’s Guide

7

Main Screen

Example main screen

The following is an example of the screen that appears when you log on to the control console at the cooling unit.

User Name

: apc

 

 

 

 

 

 

Password

: ***

 

 

 

 

 

 

American Power

Conversion

 

Network

Management Card AOS

vx.x.x

Copyright

2005

All Rights

Reserved

InRow

RC

APP

vx.x.x

-------------------------------------------------------------------------------

Name:

InRow RC

 

Date : 04/29/2009

Contact:

Bill Cooper

Time : 10:16:58

Location:

Testing Lab

User : Administrator

Up Time:

0

Days 0

Hours 43 Minutes

Stat : P+ N+ A+

Cooling Group

Status

: None

 

Cooling Unit

 

Status

: None

 

------- Control Console -------------------------------------------------------

1- Device Manager

2- Network

3- System

4- Logout

<ESC>- Main Menu, <ENTER>- Refresh, <CTRL-L>- Event Log

8

InRow RC/RD/RP (600 mm) User’s Guide

Information and status fields

Main screen information fields.

Two fields identify the APC operating system (AOS) and application (APP) firmware versions. The application firmware name identifies the type of device that connects to the network. On the example main screen, the application firmware for the cooling unit is displayed.

Network Management Card AOS

vx.x.x

InRow RC APP

vx.x.x

• Three fields identify the system Name, Contact, and Location values.

Name:

InRow RC

Contact: Bill Cooper

Location: Testing Lab

To set the Name, Contact, and Location values, see “Identification” on page 21.

An Up Time field reports how long the management interface has been running since it was last reset or since power was applied.

Up Time: 0 Days 0 Hours 43 Minutes

Two fields identify the date and time at which the screen most recently refreshed.

Date: 03/29/2009 Time: 10:16:58

A User field identifies whether you logged on as Administrator or Device User.

User: Administrator

or

User: Device Manager

InRow RC/RD/RP (600 mm) User’s Guide

9

Main screen status fields.

A Stat field reports the cooling unit status.

Stat: P+ N+ A+

P+

The APC operating system (AOS) is functioning properly.

 

 

 

 

N+

The network is functioning properly.

 

 

 

 

N?

A BOOTP or DHCP request cycle is in progress.

 

 

 

 

N–

The cooling unit failed to connect to the network.

 

 

 

 

N!

Another device is using the IP address of the cooling unit.

 

 

 

 

A+

The application is functioning properly.

 

 

 

 

A–

The application has a bad checksum.

 

 

 

 

A?

The application is initializing.

 

 

 

 

A!

The application is not compatible with the AOS.

 

 

 

 

 

Note: If the AOS status is not P+, contact “APC Worldwide Customer Support” at the web

 

address on the back cover, even if you can still access the cooling unit.

Cooling unit status field. The Status field displays the status of the cooling units. Under normal operation this field will read:

Cooling Group Status: None

Cooling Unit Status: None

None will be replaced with Warning or Critical if an alarm condition exists.

10

InRow RC/RD/RP (600 mm) User’s Guide

Control Console Menus

Menu structure

The menus in the control console list options by number and name. To use an option, type the option’s number and press ENTER, then follow any on-screen instructions.

For menus that allow you to change a setting you must use the Accept Changes option to save the changes you made. Some changes may only take effect after you log off.

While in a menu, you can also do the following:

Type ? and press ENTER to access a brief menu of option descriptions (if the menu has help available).

Press ENTER to refresh the menu.

Press ESC to return to the menu from which you accessed the current menu.

Press CTRL+C to return to the main (control console) menu.

Press CTRL+L to access the event log.

For more information about the event log, see “Events” on page 24.

Main menu

The main control console menu has options that provide access to the management features of the control console.

1- Device Manager (equivalent to Device User in the Web interface)

2- Network

3- System

4- Logout

Note: When you log on as Device Manager, you do not have access to the Network or

System menus.

Device Manager option

This option accesses the Device Manager menu, which displays information about the unit and the group. Select the components you want to manage. For example:

1- View Active Alarms

2- Cooling Group

3- Cooling Unit

InRow RC/RD/RP (600 mm) User’s Guide

11

Network option

Use this option to perform any of the following tasks:

Configure the cooling unit’s TCP/IP settings.

Configure the settings for the type of server (DHCP or BOOTP) used to provide the TCP/IP settings to the cooling unit.

Use the Ping utility.

Define settings that affect the FTP, Telnet/SSH, Web/SSL, SNMP, Syslog, Serial Modbus, E-mail, and DNS features of the cooling unit.

System option

Use this option to perform any of the following tasks:

Control Administrator and Device Manager access.

Define the System Name, Contact, and Location values.

Set the date and time used by the cooling unit.

Restart the cooling unit’s management interface.

Reset control console settings to their default values.

Define RADIUS access and set primary and secondary servers.

12

InRow RC/RD/RP (600 mm) User’s Guide

Web Interface

How to Log On

Overview

You can use the cooling unit’s DNS name or System IP address for the URL address of the Web interface. Use your case-sensitive User Name and Password settings to log on. The default user name differs by account type:

apc for an Administrator

device for a Device User

readonly for a Read-Only User

The default password is apc for all three account types.

Note: If you are using HTTPS as your access protocol, your login credentials are compared with information in a server certificate. If the certificate was created with the APC Security Wizard, and an IP address was specified as the common name in the certificate, you must use an IP address to log on to the cooling unit. If a DNS name was specified as the common name on the certificate, you must use a DNS name to log on.

For information about the Web page that appears when you log on to the Web interface, see “Summary Page” on page 15.

Supported Web browsers

You can use Microsoft® Internet Explorer (IE) 7.x and higher (on Windows operating systems only), Firefox, version 3.0.6, and higher by Mozilla Corporation (on all operating systems) to access the cooling unit through its Web interface. Other commonly available browsers also may work but have not been fully tested by APC.

Note: For optimal functioning of the Web interface, enable JavaScript® for your Web browser.

In addition, the cooling unit’s management interface cannot work with a proxy server. Therefore, before you can use a Web browser to access the cooling unit’s Web interface, you must do one of the following:

Configure the Web browser to disable the use of a proxy server for the cooling unit.

Configure the proxy server so that it does not proxy the specific IP address of the cooling unit.

URL address formats

Type the DNS name or IP address of the cooling unit in the Web browser’s URL address field, and press ENTER. When you specify a non-default Web server port in Internet Explorer, you must include http:// or https:// in the URL.

InRow RC/RD/RP (600 mm) User’s Guide

13

Common browser error messages at log on

Error Message

Browser

Cause of the Error

 

 

 

“You are not authorized to view this page” or

Internet Explorer,

Someone else is logged on.

“Someone is currently logged in...”

Firefox

 

 

 

 

“This page cannot be displayed.”

Internet Explorer

Web access is disabled, or the URL

 

 

was not correct

“Unable to connect.”

Firefox

 

 

 

 

For a DNS name of Web1, the entry would be one of the following:

http://Web1 if HTTP is your access mode

https://Web1 if HTTPS is your access mode

For a System IP address of 139.225.6.133, when the cooling unit uses the default port (80) at the Web server, the entry would be one of the following:

http://139.225.6.133 if HTTP is your access mode

https//139.225.6.133 if HTTPS is your access mode

For a System IP address of 139.225.6.133, when the cooling unit uses a non-default port (5000, in this example) at the Web server, the entry would be one of the following:

http://139.225.6.133:5000 if HTTP is your access mode

https://139.225.6.133:5000 if HTTPS is your access mode

14

InRow RC/RD/RP (600 mm) User’s Guide

Summary Page

When you log on to the Web interface at the cooling unit, navigation tabs are displayed at the top of the screen. Below the navigation tabs, a top menu bar lists options related to the selected tab. The status field displays information about the selected tab or top menu bar option.

Navigation tabs

Five tabs are displayed at the top of the screen:

Home—View any active alarm or warning conditions and clear active alarms; this tab is displayed when you log on for the first time.

Group—View and configure group settings.

Unit—View cooling settings, unit properties, identification information, view or reset run hours, and configure service intervals.

Logs—View and configure the event and data logs, and configure Syslog settings.

Administration—Configure security, network connection, notification, and device settings.

Quick status

The quick status tab is displayed in the upper right of every screen in the Web interface. The tab displays a warning of any alarms.

Click the green “device operating normally” icon to return to the status screen where the status of the cooling unit is displayed.

Click the “attention required” icon to return to the status screen where active warnings and alarms are displayed.

Click the “alarm detected” icon to return to the status screen where active alarms are displayed.

Status

The Active Alarms field displays the states (No alarms present, Warning, or Critical) of both the cooling group and individual cooling units. The Recent Device Events table displays the five most recent device events, and the dates and times they took place. Click More Events at the bottom of the Recent Device Events table to see the entire event log.

Help

Click Help, located in the upper right hand corner of the Web interface, to view context-sensitive information.

InRow RC/RD/RP (600 mm) User’s Guide

15

Select a tab to perform a task

To do the following, see “Home” on page 18:

• View and clear alarms.

To do the following, see “Group” on page 18:

View the status of the group.

Set the number of units in the group.

Define the configuration type used by the group.

Set the cool setpoints. For the ACRP100 series and ACRP500 series only, set the humidify, dehumidify, and reheat setpoints.

Set the fan speed preference.

Set the cool, dehumidify, and reheat PIDs, and the humidify sensitivity band (ACRP100 series and ACRP500 series only).

Set the percentage of glycol in the group (ACRC500 series and ACRP500 series).

To do the following, see “Unit” on page 20:

View the status and properties of each unit.

Set unit delays.

Change the unit identification values.

Configure and control the modes.

Assign the type of alarm that will activate the output sensor.

Set the normal state of the input and output.

Reset the unit run hours alarms.

Set alarm threshold values.

Set service intervals.

To do the following, see “Logs” on page 24:

Access the event and data logs.

Set the interval and rotation for the data log.

Create data log graphs.

Configure Syslog settings.

To do the following, see “Administration: Security” on page 32:

• Control Administrator, Device User, and Read-Only user access.

Configure RADIUS access, servers, and server secret. To do the following, see “Administration: Network” on page 37:

Configure new TCP/IP settings for the cooling unit.

Select the port speed.

Identify the Domain Name System (DNS) Server and test the network connection to that server.

Define settings for the FTP server, SNMP, Control Console/SSH, and Web/SSL.

To do the following, see “Administration: Notification” .

Configure the actions to be taken based on an event’s severity level.

Configure SNMP Trap Receiver settings for sending event-based traps.

Define who will receive e-mail notifications of events.

Test e-mail settings.

16

InRow RC/RD/RP (600 mm) User’s Guide

To do the following, see “Administration: General Options” on page 55:

Define the System name, contact, and location values.

Set the date and time used by the cooling unit.

Select the temperature scale used by the cooling unit.

Restart the user interface of the cooling unit.

Reset network interface settings to their default settings.

Upload a user configuration file.

Configure Modbus settings.

View information about the cooling unit.

Define the URL addresses of the user links in the Web interface.

InRow RC/RD/RP (600 mm) User’s Guide

17