Safety
Read the following information before installing or operating your APC by Schneider
Electric Rack Power Distribution Unit (PDU).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The Rack PDU is intended to be installed and operated by a skilled person in a
controlled location.
• Do not operate the Rack PDU with the covers removed.
• This Rack PDU is intended for indoor use only.
• Do not install this Rack PDU where excessive moisture or heat is present.
• Never install any wiring, equipment, or Rack PDUs during a lightning storm.
• Plug this Rack PDU into a grounded power outlet only. The power outlet must be
connected to appropriate branch circuit/mains protection (fuse or circuit breaker).
Connection to any other type of power outlet may result in a shock hazard.
• Do not use extension cords or adapters with this Rack PDU.
• If a socket-outlet is not accessible to the equipment, a socket-outlet shall be
installed.
• Do not work alone under hazardous conditions.
• Check that the power cord, plug, and socket are in good condition.
• Disconnect the Rack PDU from the power outlet before you install or connect
equipment to reduce the risk of electric shock when you cannot verify grounding.
Reconnect the Rack PDU to the power outlet only after you make all connections.
• Do not handle any kind of metallic connector before the power has been removed.
• Use one hand, whenever possible, to connect or disconnect signal cables to avoid a
possible shock from touching two surfaces with different grounds.
• This unit does not have any user-serviceable parts. Repairs are to be performed only
by factory-trained service personnel.
• High leakage current from attached loads is possible. If total leakage current will
exceed 3.5mA, attach a ground wire from the Rack PDU supplementary ground (M5
thread) to a reliable ground in your facility before energizing the Rack PDU.
Failure to follow these instructions will result in death or serious injury.
Installation
Mount the Rack PDU vertically in an Easy rack or any standard EIA-310 rack.
Option 1 - Vertical Installation with Brackets
1. Install the two (2) brackets to the Rack PDU with the
screws provided.
2. Install the PDU to the rack
with the provided four (4)
M5 x10 mm self tapping
screws.
Overview
This sheet provides installation information for your Easy PDU. Read the instructions
carefully.
Receiving
Inspect the package and contents for shipping damage. Make sure all parts were sent.
Immediately report any shipping damage to the shipping agent. Report missing
contents, product damage, or other problems with the product to APC by Schneider
Electric or your APC by Schneider Electric reseller.
Material recycling
The shipping materials are recyclable. Please save them for later use, or dispose of
them appropriately.
WARNING
FIRE HAZARD
• This equipment should be connected to a single-outlet dedicated circuit protected by
a circuit breaker or fuse with the same current rating as the Rack PDU.
• The plug or inlet serves as the disconnect for the Rack PDU. Make sure the utility
power outlet for the Rack PDU will be close to the Rack PDU and readily accessible.
Failure to follow these instructions can result in death or serious injury.
Option 2 - Toolless Mounting Pegs
The mounting pegs of the Rack PDU are
installed at the factory. Slide both mounting
pegs into the holes located in the channel in
the rear panel of the rack. Snap the Rack PDU
into place by pushing it downward until it locks
into position.
NOTE: When installing the Rack PDU, ensure
that the power cord plug is accessible and that
it is connected to a grounded outlet.

Item Function Description
LCD Display View functional data
Run Indicator LED Indicates the status when the power is on
Up Button Scroll up for function status, Alarm shutoff.
Scroll down for function status, Alarm shutoff/reset
Down Button
(Press and hold for 10 seconds to reset to the default
settings)
Temp/Humidity
Port
Temp/Humidity Sensor connection port
Network Port Connect the Rack PDU to your network
Use the scroll button to view the total current, voltage, and power. Press the scroll button
to move through the displayed information.
To configure the network settings and access the Rack PDU
Connect the network cable to the network port and apply power to the unit. When you
hear a “Beep” sound and the status LED for the network connection is flashing green,
press the Up function button until the IP address appears.
To access the Rack PDU software interface, enter the IP address in your browser
address field. You will be prompted for a user name and password. Enter the default
“apc” for each. See the User Guide for this device online at www.apc.com for more
detailed information.
Specifications
EPDU1216M EPDU1232M
Electrical
Nominal Input Voltage 200/346V - 240/415V
Maximum Input Current (Phase) 16A 32A
Input Frequency 50/60Hz
Input Connection IEC309 16A IEC309 32A
Output Voltage 200 - 240 VAC
L1 Bank 1:
Three (3) C13
One (1) C19
L1 Bank 2:
Three (3) C13
One (1) C19
L1: Seven (7) C13,
One (1) C19
Output Connections
L2: Seven (7) C13,
One (1) C19
L3: Seven (7) C13,
One (1) C19
Circuit Breakers None
Physical
Dimensions (H x W x D)
1175 x 62 x 44.4 mm
(46.25 x 2.44 x 1.74 in)
Input power cord length 2 m (6 ft) 2 m (6 ft)
Shipping dimensions (H x W x D)
Weight/Shipping weight
1320 x 160 x 110 mm
(52.0 x 6.30 x 4.33 in)
2.74 kg (6.04 lb)/
3.26 kg (7.18 lb)
Environmental
Maximum elevation (above MSL)
Operating/Storage
Temperature: Operating/Storage
0–3000 m (0–10,000 ft) /
0–15000 m (0–50,000 ft)
–5 to 45°C (23 to 113°F)/
–25 to 65°C (–13 to 149°F)
Humidity: Operating/Storage 5–95% RH, non-condensing
Compliance
EMC verification CE EN55035, EN55032, EN55024
Safety verification CE, TUV, EAC, UKCA, EN/IEC62368-1
CE EU Contact Address
Schneider Electric, 35 rue Joseph Monier
92500 Rueil Malmaison, France
Environmental RoHS & Reach
L2 Bank 3:
Three (3) C13
One (1) C19
L2 Bank 4:
Three (3) C13
One (1) C19
L3 Bank 5:
Three (3) C13
One (1) C19
L3 Bank 6:
Three (3) C13
One (1) C19
Six (6) 16A 1-pole
hydraulic-magnetic
circuit breakers
1506 x 62 x 44.4 mm
(59.29 x 2.44 x 1.74 in)
1660 x 160 x 110 mm
(65.35 x 6.30 x 4.33 in)
4.64 kg (10.23 lb)/
5.48 kg (12.08 lb)
Life Support Policy
General policy
APC by Schneider Electric does not recommend the use of any of its products in the following
situations:
• In life-support applications where failure or malfunction of the APC by Schneider Electric
product can be reasonably expected to cause failure of the life-support device or to affect
significantly its safety or effectiveness.
• In direct patient care.
APC by Schneider Electric will not knowingly sell its products for use in such applications unless it
receives in writing assurances satisfactory to APC by Schneider Electric that (a) the risks of injury or
damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of APC by
Schneider Electric is adequately protected under the circumstances.
Examples of life-support devices
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve
stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices,
blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems,
peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants),
anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S.
FDA.
Hospital-grade wiring devices and leakage current protection may be ordered as options on many
APC by Schneider Electric UPS systems. APC by Schneider Electric does not claim that units with
these modifications are certified or listed as hospital-grade APC by Schneider Electric or any other
organization. Therefore these units do not meet the requirements for use in direct patient care.
Radio frequency interference
Changes or modifications to this unit not expressly approved by the party responsible for compliance
could void the user's authority to operate this equipment.
Factory Warranty
This warranty applies only to the products you purchase for your use in accordance with this manual.
Terms of warranty
APC by Schneider Electric warrants its products to be free from defects in materials and
workmanship for a period of one year from the date of purchase. APC by Schneider Electric will repair
or replace defective products covered by this warranty. This warranty does not apply to equipment
that has been damaged by accident, negligence or misapplication or has been altered or modified in
any way. Repair or replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly registered the product.
The product may be registered at the APC by Schneider Electric website,
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused by end user’s or any third
person’s misuse, negligence, improper installation or testing. Further, APC by Schneider Electric shall
not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate
electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC by
Schneider Electric recommendations or specifications or in any event if the APC by Schneider
Electric serial number has been altered, defaced, or removed, or any other cause beyond the range
of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT
OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR
PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE
ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL
ARISE OUT OF, APC BY SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES
AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC BY SCHNEIDER
ELECTRIC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH
OF SUCH WARRANTIES. WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL,
CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR
INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR
TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC BY
SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS,
SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF
EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY
THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS AUTHORIZED
TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE
MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY SCHNEIDER ELECTRIC
OFFICER AND LEGAL DEPARTMENT.
Warranty claims
Customers with warranty claims issues may access the APC by Schneider Electric customer support
network through the Support page of the APC by Schneider Electric website,
Select your country from the country selection pull-down menu at the top of the Web page. Select the
Support tab to obtain contact information for customer support in your region.
www.apc.com.
www.apc.com/support.