Installation and
Quick Configuration
Environmental Manager
Main Module
AP9340
This manual is available in English on the enclosed CD.
Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.
Este manual está disponible en español en el CD-ROM adjunto. Ce manuel est disponible en français sur le CD-ROM ci-inclus. Questo manuale è disponibile in italiano nel CD-ROM allegato.
CD-ROM
Instrukcja Obsługi w jezyku polskim jest dostepna na CD.
Данное руководство на русском языке имеется на прилагаемом компакт-диске.
O manual em Português está disponível no CD-ROM em anexo.
Bu kullanim kilavuzunun Türkçe'sä, äläxäkte gönderälen CD äçeräsände mevcuttur.
CD
Contents
Installation ............................................ |
1 |
Preliminary Information. . . . . . . . . . . . . . . . . . .1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Additional options . . . . . . . . . . . . . . . . . . . . . 2 Additional documentation . . . . . . . . . . . . . . . 2 Please recycle . . . . . . . . . . . . . . . . . . . . . . . . 2 Receiving inspection . . . . . . . . . . . . . . . . . . . 2 InfraStruXure-certified . . . . . . . . . . . . . . . . . . 2
Front and Rear Panel Components . . . . . . . . .3
Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation—Main Module. . . . . . . . . . . . . . . . .5
Toolless peg-mount installation . . . . . . . . . . 5 Rack-mount installation . . . . . . . . . . . . . . . . 5
Installation—TH Module . . . . . . . . . . . . . . . . . .6
Connecting TH Modules . . . . . . . . . . . . . . . . 6 Adding power supplies . . . . . . . . . . . . . . . . . 8 How to wire Modbus . . . . . . . . . . . . . . . . . . . 9
Installation—Accessories . . . . . . . . . . . . . . . . .9
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Alarm beacon (optional) . . . . . . . . . . . . . . . 13 User inputs (optional) . . . . . . . . . . . . . . . . . 13
Quick Configuration........................... |
15 |
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
TCP/IP Configuration Methods . . . . . . . . . . . .15
APC Device IP Configuration Wizard . . . . . 16
.ini file utility . . . . . . . . . . . . . . . . . . . . . . . . . 16 BOOTP & DHCP configuration . . . . . . . . . . 16 Local access to the control console . . . . . 18 Remote access to the control console . . . 18 Control console . . . . . . . . . . . . . . . . . . . . . . 19
Environmental Manager: Main Module |
i |
Accessing a Configured Main Module . . . . . 20
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Web interface . . . . . . . . . . . . . . . . . . . . . . . . .20 Telnet and SSH . . . . . . . . . . . . . . . . . . . . . . .21 Simple Network Management Protocol (SNMP) 21 FTP and SCP . . . . . . . . . . . . . . . . . . . . . . . . .22 Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Recovering from a Lost Password . . . . . . . . 23
Specifications ..................................... |
24 |
Environmental Manager Main Module . . . . . |
24 |
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
25 |
Product Information ........................... |
27 |
Two-Year Factory Warranty. . . . . . . . . . . . . . 27
Terms of warranty . . . . . . . . . . . . . . . . . . . . .27 Non-transferable warranty . . . . . . . . . . . . . .27 Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Warranty claims . . . . . . . . . . . . . . . . . . . . . . .28
Life-Support Policy. . . . . . . . . . . . . . . . . . . . . 28
General policy . . . . . . . . . . . . . . . . . . . . . . . .28 Examples of life-support devices . . . . . . . .29
ii |
Environmental Manager: Main Module |
Use the Environmental Manager Main Module to monitor and control the environment through peripheral devices, including temperature and humidity sensors and environmental control devices. You can increase the number of monitored racks by adding Temperature/Humidity Modules (TH Modules) to your configuration.
Quantity |
Item |
|
|
1 |
Main Module (AP9340) |
|
|
1 |
RS-232 configuration cable |
|
|
2 |
Brackets for a standard 19-in rack |
|
|
4 |
8-32 x 1/4-in Phillips-head screws |
|
|
2 |
Toolless mounting pegs |
|
(pre-installed) |
|
|
1 |
Temperature sensor (AP9335T) |
|
|
1 |
Temperature/humidity sensor |
|
(AP9335TH) |
|
|
1 |
1.8-m (6-ft) IEC 320-C13 to IEC |
|
320-C14 power cord |
|
|
1 |
1.8-m (6-ft) NEMA 5-15P to |
|
IEC-C13 power cord |
|
|
2 |
A-Link terminators |
|
|
10 |
Tie wraps |
|
|
4 |
Adhesive cable mounts |
|
|
1 |
Adhesive temperature sensor mount |
|
|
1 |
Adhesive temperature/humidity |
|
sensor mount |
|
|
2 |
Wall anchors |
|
|
2 |
Flat-head screws |
|
|
Environmental Manager: Main Module |
1 |
The following options are available for the Main Module:
•TH Module (AP9341)
•Temperature Sensor (AP9335T)
•Temperature/Humidity Sensor (AP9335TH)
•Temperature Sensor with Digital Display (A-Link) (AP9520T)
•Temperature/Humidity Sensor with Digital Display (A-Link) (AP9520TH)
•Alarm Beacon (AP9324)
•Door Switch Kit (AP9513)
•Power Supply (AP9505i)
For additional information about management interfaces, user accounts, customizing setup, configuration utilities, file transfers, and the Device IP Configuration Wizard, see the Environmental Manager: Main Module User’s Guide, available on the supplied Utility CD or on the APC Web site: www.apc.com.
For additional security information, see the Security Handbook, available on the Utility CD or on the APC Web site: www.apc.com.
The Modbus register map is available on the APC Web site: www.apc.com.
The shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.
Inspect the package and its contents for shipping damage and ensure that the parts included in the shipment match all of the parts listed in the inventory table on page 1. Immediately report any shipping damage to the shipping agent. Report missing contents, damage, or other problems to APC or your APC reseller.
This product is certified for use in APC InfraStruXure systems. If you have InfraStruXure Manager as part of your system, the Quick Configuration instructions in this document do not apply. See the documentation included with your InfraStruXure Manager for more information.
2 |
Environmental Manager: Main Module |
Front and Rear Panel
Components
Use the toolless mounting pegs on the front panel of the Main Module to install it in an APC rack or enclosure without using any U-spaces.
+ G NC N |
|
2412+ |
N OO C |
D M
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
|
|
|
|
|
|
|
|
–+ |
–+ |
–+ |
–+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GD D N0 1 D
Environmental
Manager
aem0048a
|
Item |
Description |
|
|
|
|
AC Line Inlet |
Provides power to the Main |
|
|
Module; see “Specifications” on |
|
|
page 24 for voltage information. |
|
|
|
|
Switched |
Provides power to a device at a |
|
Outlet |
total maximum amperage of 10 A. |
|
|
Activate a connected device when |
|
|
configured events are activated |
|
|
(e.g., turn on a fan when |
|
|
temperature rises above 23.9°C |
|
|
[75°F]). |
|
|
|
|
Voltage |
Provides 12 Vdc or 24 Vdc |
|
Output |
(75 mA) to a connected device. |
|
|
|
|
Relay Output |
Connects to relay-controlled |
|
|
external devices. |
|
|
|
|
Peripheral port |
Connects to an optional device. |
|
|
|
|
Sensor ports |
Connect six temperature or |
|
|
temperature/humidity sensors |
|
|
(AP9335T or AP9335TH). |
|
|
|
|
User Inputs |
Connect four sensor devices. |
|
|
Supports the following: |
|
|
• Dry contacts |
|
|
• 0-5 V digital signals |
|
|
• 0-5 Vdc analog voltage |
|
|
• 4-20 mA current-loop sensors. |
|
|
See the Environmental Manager: |
|
|
Main Module User’s Guide, |
|
|
available on the included Utility |
|
|
CD or on the APC Web site |
|
|
(www.apc.com), for configuration |
|
|
information. |
|
|
|
|
Modbus |
Connect the Main Module to a |
|
RS-485 port |
building management system using |
|
|
the Modbus protocol. |
|
|
|
Environmental Manager: Main Module |
3 |
|
Item |
Description |
|
|
|
|
10/100 Base-T |
Connect the Main Module to the |
|
Network Port |
network; Status and Link LEDs |
|
|
indicate network traffic. |
|
|
• Status LED—blinks orange and |
|
|
green at start-up; indicates the |
|
|
status of the network connection |
|
|
(solid green—IP address |
|
|
established; blinking green— |
|
|
attempting to obtain an IP |
|
|
address). |
|
|
• Link LED—blinks to indicate |
|
|
network traffic (green—operating |
|
|
at 10 mbps; orange—operating at |
|
|
100 mbps). |
|
|
|
|
RS-232 |
Serial port used to configure initial |
|
Console Port |
network settings using the provided |
|
|
RS-232 configuration cable. |
|
|
|
|
Reset switch |
Resets the Main Module. |
|
|
|
|
Power LED |
Indicates whether the unit is |
|
|
receiving power (green–receiving |
|
|
power; dark–not receiving power). |
|
|
|
|
A-Link ports |
Expansion bus for adding APC TH |
|
|
Modules (AP9341), temperature |
|
|
sensors (AP9520T), and |
|
|
temperature/humidity sensors |
|
|
(AP9520TH). The bus provides |
|
|
communications and power to the |
|
|
TH Modules using standard CAT5 |
|
|
cabling with straight-through |
|
|
wiring. |
|
|
|
|
Alarm beacon |
Connect an alarm beacon |
|
port |
(AP9324). |
|
|
|
4 |
Environmental Manager: Main Module |
You can install the Main Module in the front or the rear of the rack or enclosure, using either the rack-mount option, which uses 1 U of rack space, or the toolless peg-mount option, which does not use any U-spaces. (The toolless peg-mount option is available only with APC NetShelter® VX and SX racks and enclosures).
1. Slide both mounting pegs into the holes located in the cable channel in the rear panel of the rack.
2. Snap the Main Module into place by pushing it downward until it locks into position.
aem0049a
1. Remove the toolless mounting pegs located at the front of the unit.
2. Attach the brackets (provided) to each end of the Main Module, using two screws for each bracket.
3. Choose a location in the rack for the Main Module.
Note: The Main Module occupies one U-space. A notched hole (or a number, on newer racks) on the rack’s vertical rail denotes the middle of a U-space.
Environmental Manager: Main Module |
5 |
7
1 U 6
5
ns0014a
4. Insert cage nuts (provided with the rack) on the vertical mounting rails above a number at the top of a U-space in your rack and below the same number at the bottom of the U-space.
5. Align the mounting holes of the brackets with the installed cage nuts, and insert four mounting screws (provided with the rack) to secure the brackets to the rack.
pdu0080a
Add TH Modules to the Main Module to monitor additional racks. The Main Module can support a maximum of 32 TH Modules (with additional power supplies).
To connect the TH Module to the Main Module:
1. Connect the first TH Module to either port marked A-Link on the rear of the Main Module, using a standard CAT5 (or equivalent) Ethernet patch cable. Do not use a crossover cable for connection.
6 |
Environmental Manager: Main Module |
Note: A-Link is an APC proprietary CAN (Controller Area Network) bus. Devices compatible with A-Link are not Ethernet devices and cannot coexist on an Ethernet bus with other networking devices, such as hubs and switches.
2. Connect the cable from the Main Module to the top A-Link connector labeled (indicating “input”) on the TH Module. Connect the bottom A-Link connector labeled (indicating “output”) to the next TH Module.
3. Plug an APC terminator into the unused A-Link port at each end of the string.
The Main Module does not have to be at the beginning of the chain of cascaded modules. You can cascade TH Modules from both A-Link ports of the Main Module. Always connect the Main Module to the input connector on the TH Module, as described in step 2.
Note: The maximum combined length of all A-Link cables is 1000 m (3,280 ft).
Note: You cannot cascade Main Modules. Install only one Main Module per system.
Main Module |
(AP9340) |
TH Module
(AP9341)
TH Module
(AP9341)
A-Link port used to plug in an APC terminator.
Main Module monitoring connected devices.
CAT5 (or equivalent) cable connecting to the TH Module.
TH Module to be monitored by the Main Module.
Environmental Manager: Main Module |
7 |