A.O. Smith DSE-5A, DSE-10A, DSE-20A, DSE-30A, DSE-40A User Manual

...
4.5 (2)
A.O. Smith DSE-5A, DSE-10A, DSE-20A, DSE-30A, DSE-40A User Manual

COMMERCIAL

ELECTRIC WATER HEATERS

CUSTOM XiSERIES

HEAVY DUTY COMMERCIAL ELECTRIC WATER HEATERS

ADVANCED ELECTRONIC CONTROL

A. O. Smith’s new proprietary electronic water heater control provides precise + or – 1° temperature control that is ideal for industrial and food service applications where exact temperatures are needed.

The Operating Set Point is adjustable from 90°F/42°C to 190°F/88°C. The factory setting is 120°F/49°C.

Approved for 180°F/82°C sanitizing applications.

PLAIN ENGLISH TEXT

Animated icons display detailed operational and diagnostic information. Fault or Alert messages appear if an operational issue occurs.

ELEMENT SENSING

Each element is constantly monitored and current on/off state is displayed, any element failure is reported and its exact location is shown, eliminates a need for field testing of elements.

LOW WATER CUT OFF

Factory standard on board low water cutoff uses a remote electric immersion type probe to prevent energizing of the elements in the event of low water condition and eliminates accidental dry firing.

SEQUENCING

Units with multiple element contactors are sequenced on with one-second delay

between stages. Prevents high amp electrical loads from hitting the electric system all at once and provides a smoother operating unit. Adjustable modulating mode is optional see options.

NIGHT SETBACK OPERATION

Control system automatically lowers the operating set point by a user defined value during setback periods. Seven-day clock may be programmed for night set back and or weekend shutdown to reduce operating cost and save energy.

BUILDING MANAGEMENT SYSTEM

BACnet or Modbus compatible with optional ICC Gateway.

Call 1.888.WATER02 for more information.

POWERED ANODE

The DSE models use a unique combination of a conventional sacrificial anode and an adaptive powered anode. The powered anode is self-adjusting to water conditions, does not require maintenance and provides longer-lasting tank protection in hard to reach areas. This multi-anode system provides superior anodic protection to hidden surfaces of the tank not protected in conventional commercial electric water heaters.

INCOLOY IMMERSION HEATERS

Heavy-duty elements provide excellent protection against oxidation and scaling. Input ranges from 3kW to 90kW available (see accompanying chart). Rugged, industrial grade, elements.

FOAM INSULATED

All models meet or exceed the thermal efficiency and/or standby loss requirements of the U. S. Department of Energy and current edition ASHRAE/IES 90.1.

GLASSLINED TANK

A. O. Smith’s PermaGlas® coating provides truly superior protection against corrosion and is permanently bonded to all inner tank surfaces at 1600°F.

ASME TANK CONSTRUCTION

• 160 psi working pressure

THREE YEAR LIMITED WARRANTY

For complete warranty information consult written warranty.

Features and benefits continued on the following page.

Attention: Changes have been made to some models. Please note that this spec sheet refers specifically to models manufactured in McBee, SC

DSE-5A thru DSE-120A (DSE-100A Shown)

© August 2018 | A. O. Smith Corporation. All rights reserved.

Page 1 of 4

www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015

AOSCE15100

FEATURES AND BENEFITS (CONTINUED)

STANDARD VOLTAGES

208, 240 and 480 volt single and three phase. All 208 and 240 volt at 24kW and below are supplied phase convertible (single to three and vice versa). 277 volt single phase also available. Consult factory for 120 volt power circuit availability.

TERMINAL BLOCK

To accept copper or aluminum leads (on units with more than one contactor).

120 VOLT CONTROL CIRCUIT

Powered by fused transformer.

MAGNETIC CONTACTORS

Heavy-duty UL rated for 100,000 cycles.

ROUGH-IN DIMENSIONS

COMMERCIAL

ELECTRIC WATER HEATERS

POWER CIRCUIT FUSING (120 AMP CURRENT DRAW AND ABOVE)

Meets National Electric Code and UL requirements that water heaters must have internal fusing when current draw exceeds 120 amps.

SIMPLIFIED CIRCUITRY, COLOR-CODED FOR EASE OF SERVICE HINGED CONTROL COMPARTMENT DOOR

CSA CERTIFIED AND ASME RATED T&P RELIEF VALVE

Model Number

Tank Capacity

Maximum kW

 

Dimensions in Inches (mm)

 

Approx. Shipping Weight

 

 

 

 

 

 

 

 

Gallons

Litres

Input

A

B

C

D

lbs.

Kg.

 

 

 

 

 

 

 

 

 

 

 

 

 

DSE-5A

5

19

3

22 in

16 in

24 in

4.25 in

82

37.2

DSE-10A

10

38

6

28.13 in

18 in

26 in

5.25 in

116

48.1

DSE-20A

20

76

18

31.75 in

22 in

28 in

5.75 in

145

65.7

DSE-30A

30

114

24

43.25 in

22 in

28 in

5.75 in

218

98.9

DSE-40A

40

151

36 *

54.75 in

22 in

28 in

5.75 in

245

111.1

DSE-50A

50

189

90

66.19 in

22 in

28 in

5.75 in

291

132.0

DSE-65A

65

246

90

57.25 in

26.5 in

32.5 in

11.38 in

344

156.0

DSE-80A

80

303

90

58.13 in

28 in

35 in

12.5 in

406

184.2

DSE-100A

100

379

90

70.25 in

28 in

35 in

12.5 in

419

190.1

DSE-120A

120

450

90

70.25 in

30.13 in

37 in

12.5 in

453

205.5

* Not available in 208 volt