American Power Conversion LVD400, LVD300, LVD500, LVD600, LVD1000 User Manual

0 (0)
EQUIPMENT HANDBOOK FOR
LOW VOLTAGE DISCONNECTORS
LVD300 (15000248),
LVD400 (15000408) &
LVD600 (15000218),
LVD1000 (15000264),
American Power Conversion,
132 Fairgrounds Road,
West Kingston,
RI 02892 USA
Tel: 1-800-788-2208
Web: www.apc.com
American Power Conversion UK Ltd.,
Raynham Road,
Bishops Stortford,
Herts, CM23 5PF UK.
Tel: +44 (0) 1279 655155
Fax: +44 (0) 1279 655322
TEXT ARTWORK NO. 990-9030. (Formerly 524809)
Handbook 990-9033 (Formerly 524810)
Page 2 of 20 Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series
CONTENTS
Section Description Page
1 Safety instructions 4
2 Specification 5
3 Circuit description 6
4 Controls and indicators 7
5 Installation and commissioning 8
6 Routine maintenance 11
7 Fault diagnosis and repair 12
8 Manual handling 16
Appendix
A Service log 17
B System drawings: 19
Test certificate 00524484 (A524484) Attached
Outline drawing 0S-9023 (B524821) Attached
Circuit diagram 0S-9018 (B524682) Attached
Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series Page 3 of 20
ISSUE RECORD
SERIAL NO. _________
Issue Description Date
1 New Document 17-10-95
2 Addition of 1000 A varia n t 20-12-95
3 Removal of external busbars 11-7-97
4 Master file converted in Word for Windows format 09-08-99
Delete all references to Advance Power Systems and replace
Advance Power in accordance with change form 12823
Amended section 2 part 9
Amended section 6, Commissioning, inserted a new paragraph
9.1 and renumbered following paragraphs accordingly.
5 Add 400A and 500A variants. 25-08-99
6 Change Brand Na me t o APC. 05-10- 00
7 Changed the Part No. to the APC system. 27-03-01
Change the part numbers quoted in the text to APC system.
American Power Conversion UK Ltd. Confidential Proprietary
The drawing on this print and information therein are proprietary to APC, and shall not be used or
discussed without the prior consent of APC in writing.
(c) Copyright, APC. This notice does not imply publication.
NOTE
This handbook covers five variants of Low Voltage Disconnector (product codes 15000248
15000408,15000409 15000218 and 15000264). The only differences between the five are the
following:
(1) The rating of fuse FS1 (300A for 15000248, 400A for 15000408, 500A for 15000409, 600A for
15000218 and 1000A for 15000264).
(2) 15000264 has external b usbars fitted .
Page 4 of 20 Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series
SECTION 1: SAFETY INSTRUCTIONS
1 Before using the units, carry out the following:
1.1 READ AND FOLLOW THE SAFETY INSTRUCTIONS.
1.2 IF A FAULT IS FOUND WHEN IN USE, DO NOT PROCEED FURTHER WITHOUT CLEARING
THE FAULT.
1.3 CHECK THE UNIT VOLTAGE AND POLARITY AGAINST THE VALUE GIVEN IN THE
INSTALLATION INSTRUCTIONS, SECTION 5.
1.4 BECOME FAMILIAR WITH THE HAZARDS ASSOCIATE D WITH THE UNITS .
WARNING
THESE UNITS CONTAIN THE FOLLOWING HAZARDS:
ELECTRICAL VOLTAGE
ENERGY
WEIGHT
ONLY COMPETENT PERSONS MAY WORK ON THESE UNITS.
IT IS IMPERATIVE THAT ONLY SKILLED SERVICE PERSONNEL BE
ALLOWED TO INSTALL AND/OR REMOVE THE PROTECTIVE COVERS FOR
SERVICING OR OTHER PURPOSES.
THE UNITS CONTAIN POTENTIALLY LETHAL VOLTAGES AND SOURCES
OF HIGH ENERGY.
REFER TO MANUAL HANDLING, SECTION 8, BEFORE ATTEMPTING TO
LIFT OR MOVE THE UNITS.
REFER TO THE FOLLOWING DOCUMENTS BEFORE COMMENCING WORK.
ALL WORK MUST BE CARRIED OUT IN ACCORDANCE WITH THE
INSTRUCTIONS THEREIN:
- MANUFACTURER'S INSTRUCTIONS
- HEALTH AND SAFETY AT WORK ACT, 1974
- ELECTRICITY AT WORK ACT, 1989
- CONTROL OF SUBSTANCES HAZARDOUS TO
HEALTH (COSHH) REGULATIONS
- MANUAL HANDLING REGULATIONS.
Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series Page 5 of 20
SECTION 2: SPECIFICATION
INPUT
1 The input voltage is -54.5 V dc nominal from an external power system.
OUTPUT
2 The output voltage is -54.5 V dc nominal.
MECHANICAL
3 The units are housed in grey plastic boxes of dimensions 366mm wide x 193 mm deep x 470mm
high. External busbars for input and output connections are provided on 15000264.
WEIGHT
4 The weight of the units are 15 kg.
OPERATIONAL TEMPERATURE
5 The operationa l t e mperature is -5 °C to +50 °C.
OPERATIONAL HUMIDITY
6 The operational relative humidity is 5% to 95% non-condensing.
SAFETY STANDARDS
7 The units are for use in conjunction with telecommunications apparatus and are designed to meet the
standard BS EN 60950 specification for safety of information technology equipment, including
electrical business equipment.
ALARMS
8 One set of vo lt free cha nge over con tacts are provide d on a t erminal bl ock (TB1) t o indica te the state
of the contactor.
9 The input and output sides of the fuse can be monitored via a 27k resistor on TB2
Page 6 of 20 Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series
SECTION 3: CIRCUIT DESCRIPTION
GENERAL
1 With reference to the circuit diagram in Appendix B, the units consist of a contactor and control
circuitry to connect and disconnect the input voltage to and from the output. The units are typically
used in line with a positive earth power system, between for example a power cubicle (input) and a
battery (output).
DC CONNECTIONS
2 The input voltage on the negative input terminal is fed via fuse FS1 to the contactor BC1, which is
normally closed, directly to the output at the negative output terminal. The positive common output
cable from the external power system is not connected to the units (only an auxiliary input, capable of
carrying a light current to power the LVD PCA is required).
LOW VOLTAGE DISCONNECTION
3 If the input voltage decreases to 42.5 V the contactor is de-energised and the contacts opened via a
signal from the LVD PCA, which disconnects the output. The contactor is energised and the contacts
closed, reconnecting the output when the input voltage increases to 51.5 V.
4 The remote contacts change over when the contactor is de-energised with the N/C and C terminals
(terminals 4 and 5) on TB1 being opened and the N/O and C terminals (terminals 5 and 6) being
closed.
MANUAL OVERRIDE
5 The keyswitch provides a manual override to de-energise the contactor irrespective of the input
voltage, when set to the OPEN position.
REMOTE LOOP CONTACTS
6 The REMOTE LOOP c o ntacts on TB1 termin a l s 1 a n d 2 are normally linked and if t h e lin k is broken the
contactor is de-energised and disconnects the unit from the external equipment. When installed, this
link can be replaced by a link to a remote location which is broken when an emergency occurs.