Specifications

Cooling Capacity, BTUH (Nominal)

36,000

Compressor

 

R.L. Amps

14.40

L.R. Amps

82.00

Condenser Fan Motor

 

Horsepower

1/12

R.L. Amps

0.60

L.R. Amps

1.20

Liquid Line, Inches O.D.

3/8

Suction Line, Inches O.D.

7/8*

Refrigerant Charge (oz)

114

Power Supply

208/230-60-1

Min.Circuit Ampacity

18.6

Max. Overcurrent Device (Amps)

30

Electric Conduit Size

 

Power Supply

1/2" or 3/4"

Low Voltage

1/2"

Approximate Shipping Weight (lbs)

198

* A 3/4 inch O.D. suction line can be used with a corresponding 1-1/2 percent reduction in cooling capacity and efficiency.

NOTE: It is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

If installed with orifice expansion coil, orifice size 0.068 must be used (Amana part number 11076306 or B1443808).

Standard Features

Liquid Line Dryer (Shipped for field installation)

Automatic Reset High Pressure Switch

Automatic Reset Low Pressure Switch

Front Seating Valves

Crankcase Heater

Low RPM (825) 8 Pole Motor

Hard Start Capacitor and Relay

Accessories

Low Ambient Kit (LAC02A)

Sound Blanket Kit (CSB04A)

Liquid Line Solenoid (LSK01A)

Freeze Protection Kit (FSK01A) (For Indoor Coil)

Effective: February 1996

Amana Refrigeration, Inc.

11070134

Fayetteville, TN 37334