Altronix ACM8CB Installation Instructions

0 (0)
Altronix ACM8CB Installation Instructions

ACM8 Series

UL Listed Sub-Assembly

Access Power Controllers

Installation Guide

Models Include:

ACM8

- Eight (8) Fuse Protected Outputs

ACM8CB

- Eight (8) PTC Protected Outputs

SECURITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rev. 042811

 

 

More than just power.TM

Overview:

These units are UL Listed Sub-Assembly multi-output Access Power Controllers which converts one (1) 12 to 24 volt DC input into eight (8) independently controlled fused or PTC protected outputs. These power outputs can be converted to dry form “C” contacts (fused models only). Outputs are activated by an open collector sink or normally open [NO] dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. Units are designed to be powered by one common power source which will provide power for both the board operation and locking devices, or two (2) totally independent power sources, one

(1) providing power for board operation and the other for lock / accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.

ACM8 & ACM8CB Series Configuration Reference Chart:

Altronix

Number

Fuse

PTC

Output

Class 2 Rated

 

Agency

UL Listings and

Model

of

Protected

Protected

Power

 

Number

Outputs

Outputs

Outputs

Ratings

Limited

 

Listings

File Numbers

 

 

 

 

 

 

 

 

 

 

 

 

ACM8

8

x

-

2.5 amp

*

SECURITY

 

 

UL File # BP6714

 

 

 

 

 

 

UL Listed for Access Control

 

 

 

 

 

 

 

 

 

 

 

System Units (UL 294).

 

 

 

 

 

 

 

 

 

 

 

ACM8CB

8

-

x

2 amp

x

 

 

 

 

 

“Signal Equipment” Evaluated to CSA

 

 

 

 

 

 

Sub-Assembly

 

 

 

 

 

 

 

 

 

 

 

Standard C22.2 No.205-M1983

Specifications:

12 to 24 volt DC operation (setting not required).

(0.5 amp @ 12volt, 0.3 amp @ 24volt current consumption with all relays energized).

Power supply input options:

a)One (1) common power input (board and lock power).

b)Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).

Eight (8) Access Control System trigger inputs:

a)Eight (8) normally open (NO) inputs.

b)Eight (8) open collector sink inputs.

c)Any combination of the above.

Eight (8) independently controlled outputs:

a)Eight (8) Fail-Safe and/or Fail-Secure power outputs.

b)Eight (8) dry form “C” 5 amp rated relay outputs.

c)Any combination of the above.

Eight (8) auxiliary power outputs (unswitched).

Output ratings:

- Fuses are rated 3.5 amp each. - PTCs are rated 2 amp each.

Main fuse is rated at 10 amp.

Note: Total output current is determined by the power supply, not to exceed a maximum of 10 amp total.

Red LEDs indicate outputs are triggered (relays energized).

Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs. Fire Alarm disconnect input options:

a)Normally open [NO] or normally closed [NC] dry contact input.

b)Polarity reversal input from FACP signaling circuit.

FACP output relay (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).

Green LED indicates when FACP disconnect is triggered.

Removable terminal blocks facilitate ease of installation.

Board Dimensions (approximate): 8”L x 4.5”W x 1.25”H

- 2 -

ACM8/CB Sub-Assembly

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed

by qualified personnel.

1.Refer to Sub Assembly Installation Instruction for mounting Rev. MS042511.

Carefully review:

Typical Application Diagram

(pg. 4)

Terminal Identification Table

(pg. 5)

LED Diagnostics

(pg. 5)

Hook-up Diagrams

(pg. 6)

2.Power supply input:

The units can be powered with one (1) power supply which will provide power for both board operation and the locking devices or two (2) separate power supplies, one (1) to provide power for the board operation and the other to provide power for the locking devices and/or access control hardware.

Note: The input power can be 12 to 24 volts DC (.5 amp @ 12 volt, .3 amp @ 24 volt current consumption

with all relays energized).

(a) Single power supply input:

If the unit and the locking devices are to be powered using a single power supply, connect the output (12 to 24 volts DC) to the terminals marked [- Control +].

(b) Dual power supply inputs (Fig. 1, pg. 4):

When the use of two power supplies is desired, jumpers J1 and J2 (located to the left of the power/control terminals) must be cut. Connect power for the unit to the terminals marked [- Control +] and connect power for the locking devices to the terminals marked [- Power +].

Note: When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed.

Note: For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories.

3.Output options (Fig. 1, pg. 4):

The ACM8 will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or

any combination of of both switched power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.

The ACM8CB will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.

(a) Switched Power outputs:

Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].

(b) Form “C” outputs:

When form “C” outputs are desired the corresponding output fuse (1-8) must be removed. Connect negative (-) of the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal marked [C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked NC]. For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].

(c) Auxiliary Power outputs (unswitched):

Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.

4.Input trigger options (Fig. 1, pg. 4):

(a) Normally Open [NO] input trigger:

Inputs 1-8 are activated by normally open or open collector sink inputs.

Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].

(b) Open Collector Sink inputs:

Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND].

5.Fire Alarm Interface options (Figs. 3 through 7, pg. 6):

A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will

trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8]. To disable FACP disconnect for an output close the corresponding switch [SW1-SW8].

(a) Normally Open [NO] input:

For non-latching hook-up (Fig. 4, pg. 6). For latching hook-up (Fig. 5, pg. 6).

(b) Normally Closed [NC] input:

For non-latching hook-up (Fig. 6, pg. 6). For latching hook-up (Fig. 7, pg. 6).

ACM8/CB Sub-Assembly

- 3 -