PowerFlex 520-Series Adjustable Frequency AC Drive
PowerFlex 523 Catalog Number 25A, Series B
PowerFlex 525 Catalog Number 25B
Original Instructions
Page 2
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, Rockwell Software, PowerFlex, Connected Components Workbench, Studio 5000, Studio 5000 Logix Designer, DriveTools SP, AppView, CustomView, QuickView, MainsFree
Programming, PointStop, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
6Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 7
This manual contains new and updated information.
Summary of Changes
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
Added footnote to indicate that circuit breaker selection is not available for certain drive
ratings.
Added PowerFlex 523 series B to Control I/O Wiring Block Diagram.38
Added PowerFlex 523 series B to Control I/O Terminal Designations.40
Added PowerFlex 523 series B I/O wiring examples for analog input and analog output.45
Added note to PowerFlex 525 I/O wiring example for pulse train input.46
Added footnote to enum “4” for P053 [Reset to Defalts] under Smart Start-Up with Basic
Program Group Parameters.
Added new sub topic for 32-bit parameters.72
Added footnotes to parameters that are available in PowerFlex 523 FRN 3.xxx and later.Chapter 3
Updated descriptions for parameters that are available in PowerFlex 523 FRN 3.xxx and later.
Added formula for calculating scaled process value to parameter b010 [Process Display].79
Added recommendation to perform rotate tune when using VVC mode to parameter P040
[Autotune].
Added footnote to indicate which settings are PowerFlex 525 only for parameter d394 [Dig
Out Status].
Updated descriptions for parameters A465 [PID 1 Deadband] and A477 [PID 2 Deadband].123
Added corrective action to fault F114 (uC Failure).162
Added analog output to PowerFlex 523 drives.171
Added new topic “Determine Encoder Pulse Per Revolution (PPR) Specification Based on
Speed Resolution” to Appendix E.
Updated information to verify operation of the safety inputs in Appendix G.240
General maintenance updates.Throughout manual
24
67
85
114
217
...27
Rockwell Automation Publication 520-UM001I-EN-E - July 20167
Page 8
Summary of Changes
Notes:
8Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 9
Preface
Overview
The purpose of this manual is to provide you with the basic information needed
to install, start-up and troubleshoot the PowerFlex® 520-Series Adjustable
Frequency AC Drive.
For information on…See page…
Who Should Use this Manual9
Recommended Documentation9
Manual Conventions10
Drive Frame Sizes11
General Precautions12
Catalog Number Explanation13
Who Should Use this Manual
Recommended
Documentation
This manual is intended for qualified personnel. You must be able to program
and operate Adjustable Frequency AC Drive devices. In addition, you must have
an understanding of the parameter settings and functions.
All the recommended documentation listed in this section is available online at
http://www.rockwellautomation.com/literature/
.
The following publications provide general drive information:
TitlePublication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC DrivesDRIVES-IN001
Preventive Maintenance of Industrial Control and Drive System EquipmentDRIVES-TD001
Safety Guidelines for the Application, Instal lation and Maintenance of Solid State ControlSGI-1.1
A Global Reference Guide for Reading Schematic Diagrams100-2.10
Guarding Against Electrostatic Damage8000-4.5.2
The following publications provide specific PowerFlex 520-Series information on
drive installation, features, specifications, and service:
TitlePublication
PowerFlex 520-Series AC Drive Specifications520-TD001
PowerFlex Dynamic Braking Resistor CalculatorPFLEX-AT001
PowerFlex AC Drives in Common Bus ConfigurationsDRIVES-AT002
Rockwell Automation Publication 520-UM001I-EN-E - July 20169
Page 10
Preface Overview
The following publications provide specific Network Communications
information:
• In this manual we refer to PowerFlex 520-Series Adjustable Frequency AC
Drive as; drive, PowerFlex 520-series, PowerFlex 520-series drive or
PowerFlex 520-series AC drive.
• Specific drives within the PowerFlex 520-series may be referred to as:
– PowerFlex 523, PowerFlex 523 drive or PowerFlex 523 AC drive.
– PowerFlex 525, PowerFlex 525 drive or PowerFlex 525 AC drive.
• Parameter numbers and names are shown in this format:
P 031 [Motor NP Volts]
Name
Number
Group
b
= Basic Display
P
= Basic Program
t
= Terminal Blocks
C
= Communications
L
= Logic
d
= Advanced Display
A
= Advanced Program
N
= Network
M
= Modified
f
= Fault and Diagnostic
G
= AppView and CustomView
• The following words are used throughout the manual to describe an
action:
WordsMeaning
CanPossible, able to do something
CannotNot possible, not able to do something
MayPermitted, allowed
MustUnavoidable, you must do this
ShallRequired and necessary
ShouldRecommended
Should NotNot Recommended
10Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 11
Overview Preface
• The Studio 5000® Engineering and Design Environment combines
engineering and design elements into a common environment. The first
element in the Studio 5000 environment is the Logix Designer
application. The Studio 5000 Logix Designer™ application is the
rebranding of RSLogix™ 5000 software and will continue to be the product
to program Logix 5000 controllers for discrete, process, batch, motion,
safety, and drive-based solutions. The Studio 5000 environment is the
foundation for the future of Rockwell Automation engineering design
tools and capabilities. It is the one place for design engineers to develop all
the elements of their control system.
Drive Frame Sizes
Similar PowerFlex 520-series drive sizes are grouped into frame sizes to simplify
spare parts ordering, dimensioning, etc. A cross reference of drive catalog
numbers and their respective frame sizes is provided in Appendix B
.
Rockwell Automation Publication 520-UM001I-EN-E - July 201611
Page 12
Preface Overview
General Precautions
ATT EN TI ON : The drive contains high voltage capacitors which take time to
discharge after removal of mains supply. After power has been removed from
the drive, wait three minutes to make sure DC bus capacitors are discharged.
After three minutes, verify AC voltage L1, L2, L3 (Line to Line and Line to
Ground) to ensure mains power has been disconnected. Measure DC voltage
across DC- and DC+ bus terminals to verify DC Bus has discharged to zero volts.
Measure DC voltage from L1, L2, L3, T1, T2, T3 DC – and DC+ terminals to
ground and keep the meter on the terminals until the voltage discharges to zero
volts. The discharge process may take several minutes to reach zero volts.
Darkened display LEDs is not an indication that capacitors have discharged to
safe voltage levels.
ATT EN TI ON : Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATT EN TI ON : This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed drive can result in component
damage or a reduction in product life. Wiring or application errors, such as
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATT EN TI ON : The bus regulator function is extremely useful for preventing
nuisance overvoltage faults resulting from aggressive decelerations,
overhauling loads, and eccentric loads. However, it can also cause either of the
following two conditions to occur.
1. Fast positive changes in input voltage or imbalanced input voltages can cause
uncommanded positive speed changes;
2. Actual deceleration times can be longer than commanded deceleration times
However, a “Stall Fault” is generated if the drive remains in this state for 1
minute. If this condition is unacceptable, the bus regulator must be disabled
(see parameter A550 [Bus Reg Enable]). In addition, installing a properly sized
dynamic brake resistor will provide proper stopping requirements based on
braking resistor sizing.
ATT EN TI ON : Risk of injury or equipment damage exists. Drive does not contain
user-serviceable components. Do not disassemble drive chassis.
12Rockwell Automation Publication 520-UM001I-EN-E - July 2016
(1) This rating is only available for PowerFlex 523 drives.
(2) Normal and Heavy Duty ratings are available for this drive.
Overview Preface
Rockwell Automation Publication 520-UM001I-EN-E - July 201613
Page 14
Preface Overview
Notes:
14Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 15
Chapter 1
Installation/Wiring
This chapter provides information on mounting and wiring the PowerFlex 520series drives.
For information on...See page...
Mounting Considerations
AC Supply Source Considerations19
General Grounding Requirements20
Fuses and Circuit Breakers23
Power and Control Module28
Control Module Cover31
Power Module Terminal Guard31
Power Wiring32
Power Terminal Block35
Common Bus/Precharge Notes36
I/O Wiring36
Control I/O Termin al Block37
Start and Speed Reference Control49
CE Conformity52
15
Mounting Considerations
Most start-up difficulties are the result of incorrect wiring. Every precaution must
be taken to assure that the wiring is done as instructed. All items must be read and
understood before the actual installation begins.
ATT EN TI ON : The following information is merely a guide for proper
installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise for
the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during
installation.
• Mount the drive upright on a flat, vertical and level surface.
• Protect the cooling fan by avoiding dust or metallic particles.
Rockwell Automation Publication 520-UM001I-EN-E - July 201615
Page 16
Chapter 1Installation/Wiring
25 mm
(1.0 in.)
25 mm
(1.0 in.)
(2)
(2)
25 mm
(1.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
Esc
Sel
Esc
Sel
Esc
Sel
Esc
Sel
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
E
s
c
S
e
l
E
s
c
S
e
l
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
(1)
Esc
S
el
Esc
Se
l
Esc
Sel
Esc
Sel
Esc
Sel
Esc
Sel
Vert ical, Z ero Stacki ng
No clearance between drives.
Horizontal, Zero Stacking with
Control Module Fan Kit
No clearance between drives.
Vert icalVert ical, Zero Stacking wi th
Control Module Fan Kit
No clearance between drives.
Vertical with Control Module Fan Kit
Horizontal with Control Module Fan Kit
• Do not expose to a corrosive atmosphere.
• Protect from moisture and direct sunlight.
Minimum Mounting Clearances
See Appendix B for mounting dimensions.
(2) For Frame E with Control Module Fan Kit only, clearance of 12 mm (0.5 in.) is required.
(1) For Frame E with Control Module Fan Kit only, clearance of 95 mm (3.7 in.) is required.
16Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 17
Installation/WiringChapter 1
Ambient Temperature (°C)
40
100
90
110
120
80
70
60
50
45403530
60 65 70 75 80
5550
Percentage of Rated Current (%)
IP 30/NEMA 1
with Control
Module Fan Kit
IP 20/Open Type
Ambient Temperature (°C)
40
100
90
110
120
80
70
60
50
45403530
60 65 70 75 80
5550
Percentage of Rated Current (%)
IP 30/NEMA 1
with Control
Module Fan Kit
IP 20/Open Type
Single DriveZero Stacking
Ambient Temperature (°C)
40
100
90
120
110
80
70
60
50
30 35
70 75 80
60 6550 5540 45
Percentage of Rated Current (%)
with Control
Module Fan Kit
IP 20/Open Type
Single DriveZero Stacking
Ambient Operating Temperatures
See Appendix B for option kits.
MountingEnclosure Rating
VerticalIP 20/Open Type
IP 30/NEMA 1/UL Type 145 °C (113 °F)55 °C (131 °F)–
Vertical, Zero StackingIP 20/Open Type45 °C (113 °F)55 °C (131 °F)65 °C (149 °F)
IP 30/NEMA 1/UL Type 140 °C (104 °F)50 °C (122 °F)–
Horizontal with
Control Module Fan Kit
Horizontal, Zero Stacking
with Control Module Fan Kit
(1) IP 30/NEMA 1/UL Type 1 rating requires installation of the PowerFlex 520-Series IP 30/NEMA 1/UL Type 1 option kit, catalog number 25-JBAx.
(2) For catalogs 25x-D1P4N104 and 25x-E0P9N104, the temperature listed under the Maximum (Derate) column is reduced by 5 °C (9 °F) for all mounting methods.
(3) For catalogs 25x-D1P4N104 and 25x-E0P9N104, the temperature listed under the Maximum with Control Module Fan Kit (Derate) column is reduced by 10 °C (18 °F) for vertical and vertical with zero
stacking mounting methods only.
(4) Catalogs 25x-D1P4N104 and 25x-E0P9N104 cannot be mounted using either of the horizontal mounting methods.
(5) Requires installation of the PowerFlex 520-Series Control Module Fan Kit, catalog number 25-FANx-70C.
(4)(5)
(4)(5)
IP 20/Open Type50 °C (122 °F)–70 °C (158 °F)
IP 20/Open Type
(1)
Ambient Temperature
MinimumMaximum (No Derate) Maximum (Derate)
50 °C (122 °F)60 °C (140 °F)70 °C (158 °F)
-20 °C (-4 °F)
45 °C (113 °F)–
(2)
Maximum with
Control Module Fan Kit (Derate)
65 °C (149 °F)
(3)(5)
Current Derating Curves
Vertical Mounting
Horizontal/Floor Mounting
120
110
100
90
80
70
60
50
40
Percentage of Rated Current (%)
30 35
Ambient Temperature (°C)
Rockwell Automation Publication 520-UM001I-EN-E - July 201617
IP 20/Open Type
60 6550 5540 45
with Control
Module Fan Kit
70 75 80
Page 18
Chapter 1Installation/Wiring
Altitude (m)
Percentage of Rated Current (%)
40
90
100
110
120
80
70
60
50
0
4000
300020001000
Altitude (m)
Ambient Temperature (°C)
20
50
60
40
30
0
4000
300020001000
Derating Guidelines for High Altitude
The drive can be used without derating at a maximum altitude of
1000 m (3300 ft). If the drive is used above 1000 m (3300 ft):
• Derate the maximum ambient temperature by 5 °C (9 °F) for every
additional 1000 m (3300 ft), subject to limits listed in the Altitude Limit
(Based on Voltage) table below.
Or
• Derate the output current by 10% for every additional 1000 m (3300 ft),
up to 3000 m (9900 ft), subject to limits listed in the Altitude Limit
18Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Take precautions to prevent debris from falling through the vents of the drive
housing during installation.
Storage
• Store within an ambient temperature range of -40...85°C
• Store within a relative humidity range of 0...95%, noncondensing.
• Do not expose to a corrosive atmosphere.
(1) The maximum ambient temperature for storing a Frame E drive is 70 °C.
(1)
.
Page 19
Installation/WiringChapter 1
IMPORTANT
Power Mod ule
AC Supply Source
Considerations
Ungrounded Distribution Systems
ATT EN TI ON : PowerFlex 520-series drives contain protective MOVs that are
referenced to ground. These devices must be disconnected if the drive is
installed on an ungrounded or resistive grounded distribution system.
ATT EN TI ON : Removing MOVs in drives with an embedded filter will also
disconnect the filter capacitor from earth ground.
Disconnecting MOVs
To prevent drive damage, the MOVs connected to ground shall be disconnected
if the drive is installed on an ungrounded distribution system (IT mains) where
the line-to-ground voltages on any phase could exceed 125% of the nominal lineto-line voltage. To disconnect these devices, remove the jumper shown in the
diagrams below.
1. Turn the screw counterclockwise to loosen.
2. Pull the jumper completely out of the drive chassis.
3. Tighten the screw to keep it in place.
Jumper Location (Typical)
Tighten screw after jumper removal.
Phase to Ground MOV Removal
AC Input
R/L1
S/L2
T/L3
Jumper
1234
Three-Phase
Rockwell Automation Publication 520-UM001I-EN-E - July 201619
Page 20
Chapter 1Installation/Wiring
IMPORTANT
SHLD
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Esc
Sel
Input Power Conditioning
The drive is suitable for direct connection to input power within the rated
voltage of the drive (see page 169
below are certain input power conditions which may cause component damage or
reduction in product life. If any of these conditions exist, install one of the devices
listed under the heading Corrective Action on the line side of the drive.
Only one device per branch circuit is required. It should be mounted closest to
the branch and sized to handle the total current of the branch circuit.
Input Power Conditions
). Listed in the Input Power Conditions table
General Grounding
Requirements
Input Power ConditionCorrective Action
Low Line Impedance (less than 1% line reactance)• Install Line Reactor
Greater than 120 kVA supply transformer
Line has power factor correction capacitors• Install Line Reactor
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line to line voltage• Remove MOV jumper to ground.
Ungrounded distribution system
B-phase grounded distribution system
240V open delta configuration (stinger leg)
(1) For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in
the middle to the neutral or earth is referred to as the “stinger leg,” “high leg,” “red leg,” etc. This le g should be identified throughout
the system with red or orange tape on the wire at each connect ion point. The stinger leg should be connected to the center Phase B
on the reactor. See Bulletin 1321-3R Series Line Reactors
(2) See Appendix B for accessory ordering information.
(1)
on page 183 for specific line reactor part numbers.
• or Isolation Transformer
• or Isolation Transformer
• or Install Isolation Transformer with
grounded secondary if necessary.
• Install Line Reactor
(2)
(2)
(2)
The drive Safety Ground - (PE) must be connected to system ground. Ground
impedance must conform to the requirements of national and local industrial
safety regulations and/or electrical codes. The integrity of all ground connections
should be periodically checked.
Typical Grounding
20Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 21
Installation/WiringChapter 1
Ground Fault Monitoring
If a system ground fault monitor (RCD) is to be used, only Type B (adjustable)
devices should be used to avoid nuisance tripping.
Safety Ground - (PE)
This is the safety ground for the drive that is required by code. One of these
points must be connected to adjacent building steel (girder, joist), a floor ground
rod or bus bar. Grounding points must comply with national and local industrial
safety regulations and/or electrical codes.
Network Ground
Connect terminal C1 to a clean earth ground when using a network with a star
topology (EtherNet/IP) or daisy-chain (RS485). It is acceptable to ground both
C1 and C2 terminals.
Connect terminal CS1 or CS2 to a clean ground when using a network with a
ring topology (EtherNet/IP).
For more information on EtherNet/IP networks, see Ground Connections for
EtherNet/IP Networks on page 248.
For more information on RS485 networks, see Network Wiring
on page 201.
Motor Ground
The motor ground must be connected to one of the ground terminals on the
drive.
Shield Termination - SHLD
Either of the safety ground terminals located on the power terminal block
provides a grounding point for the motor cable shield. The motor cable shield
connected to one of these terminals (drive end) should also be connected to the
motor frame (motor end). Use a shield terminating or EMI clamp to connect the
shield to the safety ground terminal. The earthing plate or conduit box option
may be used with a cable clamp for a grounding point for the cable shield.
When shielded cable is used for control and signal wiring, the shield should be
grounded at the source end only, not at the drive end.
Rockwell Automation Publication 520-UM001I-EN-E - July 201621
Page 22
Chapter 1Installation/Wiring
RFI Filter Grounding
Using a drive with filter may result in relatively high ground leakage currents.
Therefore, the filter must only be used in installations with grounded AC supply systems and be permanently installed and solidly grounded (bonded)
to the building power distribution ground. Ensure that the incoming supply
neutral is solidly connected (bonded) to the same building power distribution
ground. Grounding must not rely on flexible cables and should not include any
form of plug or socket that would permit inadvertent disconnection. Some local
codes may require redundant ground connections. The integrity of all
connections should be periodically checked.
22Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 23
Installation/WiringChapter 1
Fuses and Circuit Breakers
The PowerFlex 520-series drive does not provide branch short circuit protection.
This product should be installed with either input fuses or an input circuit
breaker. National and local industrial safety regulations and/or electrical codes
may determine additional requirements for these installations.
The tables found on pages 24
...27 provide recommended AC line input fuse and
circuit breaker information. See Fusing and Circuit Breakers below for UL and
IEC requirements. Sizes listed are the recommended sizes based on 40 °C
(104 °F) and the U.S. N.E.C. Other country, state or local codes may require
different ratings.
Fusing
The recommended fuse types are listed in the tables found on pages 24...27. If
available current ratings do not match those listed in the tables provided, choose
the next higher fuse rating.
(1)
• IEC – BS88 (British Standard) Parts 1 & 2
type GG or equivalent should be used.
• UL – UL Class CC, T, RK1, or J should be used.
, EN60269-1, Parts 1 & 2,
Circuit Breakers
The “non-fuse” listings in the tables found on pages 24...27 include inverse time
circuit breakers, instantaneous trip circuit breakers (motor circuit protectors)
and 140M self-protected combination motor controllers. If one of these is chosen
as the desired protection method, the following requirements apply:
• IEC – Both types of circuit breakers and 140M self-protected
combination motor controllers are acceptable for IEC installations.
• UL – Only inverse time circuit breakers and the specified 140M selfprotected combination motor controllers are acceptable for UL
installations.
When using Bulletin 140M or UL489 rated circuit breakers, the guidelines listed
below must be followed in order to meet the NEC requirements for branch
circuit protection.
• Bulletin 140M can be used in single motor applications.
• Bulletin 140M can be used up stream from the drive without the need for
fuses.
(1) Typical designations include, but may not be limited to the following;
25A-A8P0N104 25B-A8P0N104 2.0 1.5 2.0 1.5 8.0 4.8 18.0B 100-C23 2540140U-D6D2-C25 140M-F8E-C25CLASS CC, J, or T / 40140U-D6D2-C25 140M-F8E-C25–
25A-A8P0N114 25B-A8P0N114 2.0 1.5 2.0 1.5 8.0 4.8 18.0B 100-C23 2540140U-D6D2-C25 140M-F8E-C25CLASS CC, J, or T / 40140U-D6D2-C25 140M-F8E-C25–
25A-A011N104 25B-A011N104 3.0 2.2 3.0 2.2 11.0 6.0 22.9B 100-C37 3250140G-G6C3-C35 140M-F8E-C25CLASS CC, J, or T / 50–
25A-A011N114 25B-A011N114 3.0 2.2 3.0 2.2 11.0 6.0 22.9B 100-C37 3250140G-G6C3-C35 140M-F8E-C25CLASS CC, J, or T / 50–
(4) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y /277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(1) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(2) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
(5) Circuit breaker selection is not available for this drive rating.
(3) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
24Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 25
)
3
Enclosure
Vol. (in.
(3)(4)(5)
Installation/WiringChapter 1
(6)
–
140M-F8E-C32–
(7)
(7)
140M-F8E-C45–
140M-F8E-C451416.0
–
(7)
(7)
(7)
CLASS CC, J, or T / 125–
Fuses and Circuit Breakers for PowerFlex 520-Series Drives (continued)
(1) Normal Duty (ND) and Heavy Dut y (HD) ratings are available for this drive.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y /277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
(4) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Circuit breaker selection is not available for this drive rating.
(6) When using a Manual Self-Protected (Type E) Combination Motor Controller with this drive power rating, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
Rockwell Automation Publication 520-UM001I-EN-E - July 201625
Page 26
Chapter 1Installation/Wiring
Enclosure
(3)(4)(5)
)
3
(6)
(6)
(6)
(6)
Vol. (in.
140M-C2E-B25–
140M-C2E-B25–
140M-C2E-B40–
140M-C2E-B40–
140M-C2E-B63–
140M-C2E-B63–
140M-C2E-C10–
140M-C2E-C10–
140M-C2E-C16–
140M-C2E-C16–
140M-D8E-C20–
140M-D8E-C20–
140M-D8E-C20–
140M-D8E-C20–
140M-F8E-C32656.7
140M-F8E-C32656.7
140M-F8E-C45656.7
140M-F8E-C45656.7
140M-F8E-C45–
140M-F8E-C45–
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
Fuses and Circuit Breakers for PowerFlex 520-Series Drives (continued)
HP kW HP kWMin.Max.140U/140G140MClass / Catalog No.140U/140G140M
(1)
Catalog No.
PF 523PF 525NDHD
25A-D1P4N104 25B-D1P4N104 0.5 0.4 0.5 0.4 1.4 1.7 1.9A 100-C09 36140U-D6D3-B30 140M-C2E-B25CLASS RK5, CC, J, or T / DLS-R-6 –
25A-D1P4N114 25B-D1P4N114 0.5 0.4 0.5 0.4 1.4 1.7 1.9A 100-C09 36140U-D6D3-B30 140M-C2E-B25CLASS RK5, CC, J, or T / DLS-R-6 –
25A-D2P3N104 25B-D2P3N104 1.0 0.75 1.0 0.75 2.3 2.9 3.2A 100-C09 610140U-D6D3-B60 140M-C2E-B40CLASS RK5, CC, J, or T / DLS-R-10 –
25A-D2P3N114 25B-D2P3N114 1.0 0.75 1.0 0.75 2.3 2.9 3.2A 100-C09 610140U-D6D3-B60 140M-C2E-B40CLASS RK5, CC, J, or T / DLS-R-10 –
25A-D4P0N104 25B-D4P0N104 2.0 1.5 2.0 1.5 4.0 5.2 5.7A 100-C09 1016140U-D6D3-B60 140M-C2E-B63CLASS RK5, CC, J, or T / DLS-R-15 –
25A-D4P0N114 25B-D4P0N114 2.0 1.5 2.0 1.5 4.0 5.2 5.7A 100-C09 1016140U-D6D3-B60 140M-C2E-B63CLASS RK5, CC, J, or T / DLS-R-15 –
25A-D6P0N104 25B-D6P0N104 3.0 2.2 3.0 2.2 6.0 6.9 7.5A 100-C09 1016140U-D6D3-C10 140M-C2E-C10CLASS RK5, CC, J, or T / DLS-R-15 –
25A-D6P0N114 25B-D6P0N114 3.0 2.2 3.0 2.2 6.0 6.9 7.5A 100-C09 1016140U-D6D3-C10 140M-C2E-C10CLASS RK5, CC, J, or T / DLS-R-15 –
25A-D010N104 25B-D010N104 5.0 4.0 5.0 4.0 10.5 12.6 13.8B 100-C23 2032140U-D6D3-C15 140M-C2E-C16CLASS RK5, CC, J, or T / DLS-R-30 –
25A-D010N114 25B-D010N114 5.0 4.0 5.0 4.0 10.5 12.6 13.8B 100-C23 2032140U-D6D3-C15 140M-C2E-C16CLASS RK5, CC, J, or T / DLS-R-30 –
25A-D013N104 25B-D013N104 7.5 5.5 7.5 5.5 13.0 14.1 15.4C 100-C23 2035140U-D6D3-C25 140M-D8E-C20CLASS CC, J, or T / 35–
25A-D013N114 25B-D013N114 7.5 5.5 7.5 5.5 13.0 14.1 15.4C 100-C23 2035140U-D6D3-C25 140M-D8E-C20CLASS CC, J, or T / 35–
25A-D017N104 25B-D017N104 10.0 7.5 10.0 7.5 17.0 16.8 18.4C 100-C23 2540140U-D6D3-C25 140M-D8E-C20CLASS CC, J, or T / 40–
25A-D017N114 25B-D017N114 10.0 7.5 10.0 7.5 17.0 16.8 18.4C 100-C23 2540140U-D6D3-C25 140M-D8E-C20CLASS CC, J, or T / 40–
25A-D024N104 25B-D024N104 15.0 11.0 15.0 11.0 24.0 24.1 26.4D 100-C37 3563140G-G6C3-C40 140M-F8E-C32CLASS CC, J, or T / 60–
25A-D024N114 25B-D024N114 15.0 11.0 15.0 11.0 24.0 24.1 26.4D 100-C37 3563140G-G6C3-C40 140M-F8E-C32CLASS CC, J, or T / 60–
25A-D030N104 25B-D030N104 20.0 15.0 15.0 11.0 30.0 30.2 33.0D 100-C43 4570140G-G6C3-C50 140M-F8E-C45CLASS CC, J, or T / 70–
25A-D030N114 25B-D030N114 20.0 15.0 15.0 11.0 30.0 30.2 33.0D 100-C43 4570140G-G6C3-C50 140M-F8E-C45CLASS CC, J, or T / 70–
26Rockwell Automation Publication 520-UM001I-EN-E - July 2016
considerations may require a larger enclosure.
25A-D037N114 25B-D037N114 25.0 18.5 20.0 15.0 37.0 30.8 33.7E 100-C43 4570140G-G6C3-C50 140M-F8E-C45CLASS CC, J, or T / 70–
25A-D043N114 25B-D043N114 30.0 22.0 25.0 18.5 43.0 35.6 38.9E 100-C60 5080140G-G6C3-C60 140M-F8E-C45CLASS CC, J, or T / 80–
(1) Normal Duty (ND) and Heavy Dut y (HD) ratings are available for this drive.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
(4) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Circuit breaker selection is not available for this drive rating.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y /277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(6) When using a Manual Self-Protected (Type E) Combination Motor Controller with this drive power rating, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
Page 27
)
3
Enclosure
Vol. (in.
(3)(4)(5)
140M-C2E-B25–
(8)
Installation/WiringChapter 1
(7)
(7)
(7)
(7)
–
(6)
140M-C2E-B25–
140M-C2E-B40–
140M-D8E-B63–
140M-D8E-C10–
140M-D8E-C16
140M-D8E-C16–
140M-F8E-C25656.7
140M-F8E-C32656.7
140M-F8E-C321416.0
140M-F8E-C321416.0
(8)
(8)
(8)
(8)
(8)
(8)
(8)
(8)
(8)
(8)
Fuses and Circuit Breakers for PowerFlex 520-Series Drives (continued)
HP kW HP kWMin.Max.140U/140G140MClass / Catalog No.140U/140G140M
(1)
considerations may require a larger enclosure.
Catalog No.
PF 523PF 525NDHD
25A-E0P9N104 25B-E0P9N104 0.5 0.4 0.5 0.4 0.9 1.4 1.2A 100-C09 36140U-D6D3-B20 140M-C2E-B25CLASS RK5, CC, J, or T / DLS-R-6 –
25A-E1P7N104 25B-E1P7N104 1.0 0.75 1.0 0.75 1.7 2.6 2.3A 100-C09 36140U-D6D3-B30 140M-C2E-B25CLASS RK5, CC, J, or T / DLS-R-6 –
25A-E3P0N104 25B-E3P0N104 2.0 1.5 2.0 1.5 3.0 4.3 3.8A 100-C09 610140U-D6D3-B50 140M-C2E-B40CLASS RK5, CC, J, or T / DLS-R-10 –
25A-E4P2N104 25B-E4P2N104 3.0 2.2 3.0 2.2 4.2 6.1 5.3A 100-C09 1016140U-D6D3-B80 140M-C2E-B63CLASS RK5, CC, J, or T / DLS-R-15 –
25A-E6P6N104 25B-E6P6N104 5.0 4.0 5.0 4.0 6.6 9.1 8.0B 100-C09 1020140U-D6D3-C10 140M-C2E-C10CLASS RK5, CC, J, or T / DLS-R-20 –
25A-E9P9N104 25B-E9P9N104 7.5 5.5 7.5 5.5 9.9 12.8 11.2C 100-C16 1625140U-D6D3-C15 140M-C2E-C16CLASS RK5, CC, J, or T / DLS-R-25 –
25A-E012N104 25B-E012N104 10.0 7.5 10.0 7.5 12.0 15.4 13.5C 100-C23 2032140U-D6D3-C20 140M-C2E-C16CLASS RK5, CC, J, or T / DLS-R-30 –
25A-E019N104 25B-E019N104 15.0 11.0 15.0 11.0 19.0 27.4 24.0D 100-C30 3250140G-G6C3-C30 140M-F8E-C25CLASS CC, J, or T / 50–
25A-E022N104 25B-E022N104 20.0 15.0 15.0 11.0 22.0 31.2 27.3D 100-C30 3563140G-G6C3-C35 140M-F8E-C32CLASS CC, J, or T / 60–
25A-E027N104 25B-E027N104 25.0 18.5 20.0 15.0 27.0 28.2 24.7E 100-C30 3550140G-G6C3-C35 140M-F8E-C32CLASS CC, J, or T / 50–
25A-E032N104 25B-E032N104 30.0 22.0 25.0 18.5 32.0 33.4 29.2E 100-C37 4063140G-G6C3-C50 140M-F8E-C32CLASS CC, J, or T / 60–
(1) Normal Duty (ND) and Heavy Dut y (HD) ratings are available for this drive.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y /277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
(4) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(8) Circuit breaker selection is not available for this drive rating.
(7) When using a Manual Self-Protected (Type E) Combination Motor Controller with this drive power rating, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
(6) When used with the 140M circuit breaker, the 25A-E9P9104 must be installed in a ventil ated or non-ventilated enclosure with the minimum size of 457.2 x 457.2 x 269.8 mm (18 x 18 x 10.62 in.).
Rockwell Automation Publication 520-UM001I-EN-E - July 201627
Page 28
Chapter 1Installation/Wiring
1
2
Power and Control Module
PowerFlex 520-series drives consist of a Power Module and Control Module.
Separating the Power and Control Module
ATT EN TI ON : Perform this action only when drive is NOT powered.
1. Press and hold down the catch on both sides of the frame cover, then pull
out and swing upwards to remove (Frames B...E only).
2. Press down and slide out the top cover of the Control Module to unlock it
from the Power Module.
28Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 29
Installation/WiringChapter 1
3. Hold the sides and top of the Control Module firmly, then pull out to
separate it from the Power Module.
Connecting the Power and Control Module
1. Align the connectors on the Power Module and Control Module, then
push the Control Module firmly onto the Power Module.
Rockwell Automation Publication 520-UM001I-EN-E - July 201629
Page 30
Chapter 1Installation/Wiring
2. Push the top cover of the Control Module towards the Power Module to
lock it.
3. Insert the catch at the top of the frame cover into the Power Module, then
swing the frame cover to snap the side catches onto the Power Module
(Frames B...E only).
30Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 31
Installation/WiringChapter 1
1
2
Control Module Cover
To access the control terminals, DSI port, and Ethernet port, the front cover must
be removed. To remove:
1. Press and hold down the arrow on the front of the cover.
2. Slide the front cover down to remove from the Control Module.
Power Module Terminal
Guard
Re-attach the front cover when wiring is complete.
To access the power terminals, the terminal guard must be removed. To remove:
1. Press and hold down the catch on both sides of the frame cover, then pull
out and swing upwards to remove (Frames B...E only).
Rockwell Automation Publication 520-UM001I-EN-E - July 201631
Page 32
Chapter 1Installation/Wiring
2. Press and hold down the locking tab on the terminal guard.
3. Slide the terminal guard down to remove from the Power Module.
Re-attach the terminal guard when wiring is complete.
Power Wiring
To access the power terminals for Frame A, you need to separate the Power and
Control Modules. See Separating the Power and Control Module
instructions.
ATT EN TI ON : National Codes and standards (NEC, VDE, BSI, etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection and disconnect devices. Failure to do so may result in personal injury
and/or equipment damage.
ATT EN TI ON : To avoid a possible shock hazard caused by induced voltages,
unused wires in the conduit must be grounded at both ends. For the same
reason, if a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled. This will help minimize the possible shock
hazard from “cross coupled” power leads.
on page 28 for
Motor Cable Types Acceptable for 100...600 Volt Installations
A variety of cable types are acceptable for drive installations. For many
installations, unshielded cable is adequate, provided it can be separated from
sensitive circuits. As an approximate guide, allow a spacing of 0.3 m (1 ft) for
every 10 m (32.8 ft) of length. In all cases, long parallel runs must be avoided. Do
not use cable with an insulation thickness less than 15 mils (0.4 mm/0.015 in.).
Do not route more than three sets of motor leads in a single conduit to minimize
“cross talk”. If more than three drive/motor connections per conduit are required,
shielded cable must be used.
32Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 33
Installation/WiringChapter 1
UL installations above 50 °C ambient must use 600V, 90 °C wire.
UL installations in 50 °C ambient must use 600V, 75 °C or 90 °C wire.
UL installations in 40 °C ambient should use 600V, 75 °C or 90 °C wire.
Use copper wire only. Wire gauge requirements and recommendations are based
on 75 °C. Do not reduce wire gauge when using higher temperature wire.
WARNING: The distance between the drive and motor must not exceed the
maximum cable length stated in the Motor Cable Length Restrictions Tables in
“Wiring and Grounding Guide, (PWM) AC Drives,” publication DRIVES-IN001
.
Unshielded
THHN, THWN or similar wire is acceptable for drive installation in dry
environments provided adequate free air space and/or conduit fill rates limits are
provided. Any wire chosen must have a minimum insulation thickness of 15 mils
and should not have large variations in insulation concentricity.
ATT EN TI ON : Do not use THHN or similarly coated wire in wet areas.
Shielded/Armored Cable
Shielded cable contains all of the general benefits of multi-conductor cable with
the added benefit of a copper braided shield that can contain much of the noise
generated by a typical AC Drive. Strong consideration for shielded cable should
be given in installations with sensitive equipment such as weigh scales, capacitive
proximity switches and other devices that may be affected by electrical noise in
the distribution system. Applications with large numbers of drives in a similar
location, imposed EMC regulations or a high degree of communications /
networking are also good candidates for shielded cable.
Shielded cable may also help reduce shaft voltage and induced bearing currents
for some applications. In addition, the increased impedance of shielded cable may
help extend the distance that the motor can be located from the drive without the
addition of motor protective devices such as terminator networks. Refer to
Reflected Wave in “Wiring and Grounding Guide, (PWM) AC Drives,”
publication DRIVES-IN001
Consideration should be given to all of the general specifications dictated by the
environment of the installation, including temperature, flexibility, moisture
characteristics and chemical resistance. In addition, a braided shield should be
included and be specified by the cable manufacturer as having coverage of at
least 75%. An additional foil shield can greatly improve noise containment.
.
A good example of recommended cable is Belden® 295xx (xx determines gauge).
This cable has four (4) XLPE insulated conductors with a 100% coverage foil and
an 85% coverage copper braided shield (with drain wire) surrounded by a
PVC jacket.
Rockwell Automation Publication 520-UM001I-EN-E - July 201633
Page 34
Chapter 1Installation/Wiring
Other types of shielded cable are available, but the selection of these types may
limit the allowable cable length. Particularly, some of the newer cables twist 4
conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and reduce
the overall drive performance. Unless specified in the individual distance tables as
tested with the drive, these cables are not recommended and their performance
against the lead length limits supplied is not known.
Recommended Shielded Wire
LocationRating/TypeDescription
Standard (Option 1) 600V, 90 °C (194 °F) XHHW2/RHW-2
Standard (Option 2) Tray rated 600V, 90 °C (194 °F)
Class I & II;
Division I & II
Anixter B209500-B209507, Belden
29501-29507, or equivalent
RHH/RHW-2 Anixter OLF-7xxxxx or
equivalent
Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter 7V-7xxxx-3G or
equivalent
• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and
tinned copper drain wire.
• PVC jacket.
• Three tinned copper conductors with XLPE insulation.
• 5 mil single helical copper tape (25% overlap min.)
with thre e bare copper g rounds in conta ct with shiel d.
• PVC jacket.
• Three bare copper conductors with XLPE insulation
and impervious co rrugated continuously welded
aluminum armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations with
long motor cables may require the addition of external devices to limit voltage
reflections at the motor (reflected wave phenomena). Refer to Reflected Wave in
“Wiring and Grounding Guide, (PWM) AC Drives,” publication DRIVES-
IN001.
The reflected wave data applies to all carrier frequencies 2...16 kHz.
For 240V ratings and lower, reflected wave effects do not need to be considered.
Output Disconnect
The drive is intended to be commanded by control input signals that will start
and stop the motor. A device that routinely disconnects then reapplies output
power to the motor for the purpose of starting and stopping the motor should
not be used. If it is necessary to disconnect power to the motor with the drive
outputting power, an auxiliary contact should be used to simultaneously disable
drive (Aux Fault or Coast to Stop).
34Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 35
Installation/WiringChapter 1
IMPORTANT
V/T2T/L3S/L2R/L1U/T1W/T3
V/T2T/L3S/L2R/L1U/T1W/T3
BR+
BR-
DC-DC+
BR+
BR-
DC-
DC+
Frame A, B, C & DFrame E
Power Terminal Block
Power Terminal Block
TerminalDescription
R/L1, S/L21-Phase Input Line Voltage Connection
R/L1, S/L2, T/L33-Phase Input Line Voltage Connection
U/T1, V/T2, W/T3 Motor P hase Connection =Switch any two moto r leads to change
forward direction.
DC+, DC-DC Bus Connection (except for 110V 1-Phase)
BR+, BR-Dynamic Brake Resistor Connection
Safety Ground - PE
Terminal screws may become loose during shipment. Ensure that all terminal
screws are tightened to the recommended torque before applying power to the
drive.
Power Terminal Block Wire Specifications
FrameMaximum Wire Size
A5.3 mm
B8.4 mm
C8.4 mm
D13.3 mm
E26.7 mm
(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.
Rockwell Automation Publication 520-UM001I-EN-E - July 201635
Page 36
Chapter 1Installation/Wiring
IMPORTANT
Common Bus/Precharge
Notes
I/O Wiring
If drives are used with a disconnect switch to the common DC bus, then an
auxiliary contact on the disconnect must be connected to a digital input of the
drive. The corresponding input (parameter t062
TermBlk xx]) must be set to 30, “Precharge En” This provides the proper
precharge interlock, guarding against possible damage to the drive when
connected to a common DC bus. For more information, see Drives in Common
Bus Configurations, publication DRIVES-AT002
, t063, t065...t068 [DigIn
.
Motor Start/Stop Precautions
ATT EN TI ON : A contactor or other device that routinely disconnects and
reapplies the AC line to the drive to start and stop the motor can cause drive
hardware damage. The drive is designed to use control input signals that will
start and stop the motor. If used, the input device must not exceed one
operation per minute or drive damage can occur.
ATT EN TI ON : The drive start/stop control circuitry includes solid-state
components. If hazards due to accidental contact with moving machinery or
unintentional flow of liquid, gas or solids exist, an additional hardwired stop
circuit may be required to remove the AC line to the drive. When the AC line is
removed, there will be a loss of any inherent regenerative braking effect that
might be present - the motor will coast to a stop. An auxiliary braking method
may be required. Alternatively, use the drive’s safety input function.
Important points to remember about I/O wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at least
0.3 m (1 ft).
I/O terminals labeled “Common” are not referenced to the safety ground (PE)
terminal and are designed to greatly reduce common mode interference.
ATT EN TI ON : Driving the 4-20 mA analog input from a voltage source could
cause component damage. Verify proper configuration prior to applying input
signals.
Signal and Control Wire Types
Recommendations are for 50 °C ambient temperature.
75 °C wire must be used for 60 °C ambient temperature.
90 °C wire must be used for 70 °C ambient temperature.
36Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 37
Installation/WiringChapter 1
Recommended Signal Wire
Signal Type/
Where Used
Analog I/O & PTC 8760/94600.750 mm2 (18 AWG), twisted pair,
Remote Pot87700.750 mm
Encoder/Pulse I/O 9728/97300.196 mm
(1) Stranded or solid wire.
(2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessar y,
but is always recommended.
Belden Wire Type(s)
(or equivale nt)
(1)
DescriptionMin. Insulation
100% shield with drain
2
(18 AWG), 3 conductor, shielded
2
(24 AWG), individually shielded pairs
(2)
Rating
300V,
60 °C (140 °F)
Recommended Control Wire for Digital I/O
Control I/O Terminal Block
TypeWire Typ e(s)DescriptionMin. Insulatio n
UnshieldedPer US NEC or applicable
national or local code
ShieldedMulti-conductor shielded
cable such as Belden 8770
(or equivalent)
–300V,
2
0.750 mm
(18 AWG), 3 conductor, shielded.
Rating
60 °C (140 °F)
Maximum Control Wire Recommendations
Do not exceed control wiring length of 30 m (100 ft). Control signal cable length
is highly dependent on electrical environment and installation practices. To
improve noise immunity, the I/O terminal block Common may be connected to
ground terminal/protective earth.
Control I/O Terminal Block Wire Specifications
FrameMaximum Wire Size
A...E1.3 mm
(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.
• 3 = per P045 [Stop Mode]
49 “3-Wire Start”Per P045 [Stop Mode]
50 “2-Wire REV”t064 [2-Wire Mode] is set to:
• 0, 1, or 2 = Coast
• 3 = per P045 [Stop Mode]
51 “3-Wire Dir”Per P045 [Stop Mode]
The drive is shipped with a jumper installed between I/O Terminals 01 and 11.
Remove this jumper when using I/O Terminal 01 as a stop or enable input.
(2) Two wire co ntrol shown. For three wire con trol use a mom entary input on I/O Terminal 02 to command a start. Use a
maintained input for I/O Terminal 03 to change direction.
(3) Analog output (terminal 15) is only available on PowerFlex 523 series B drive, and requires firmware 3.001 and later to configure the
analog output parameters (t088, t089, and t090).
(4) Potentiometer connection is only applicable when the 0-10V setting (default) is selected for jumper J4.
(5) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an
undetermined frequency reference will result.
Control I/O Terminal Designations
No. SignalDefaultDescriptionParameter
R1 Relay N.O.FaultNormally open contact for output relay.
R2 Relay CommonFaultCommon for output relay.
R3 Relay N.C.Motor Running Normally closed contact for output relay.t081
01 Stop CoastThree wire stop. However, it func tions as a stop under all input
modes and cannot be disabled.
02 DigIn TermBlk 02/
Start/Run FWD
Run FWDUsed to initiate motion and also can be used as a programmable
digital input. It can be programmed with t062 [DigIn TermBlk
02] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.
03 DigIn TermBlk 03/
Dir/Run REV
Run REVUsed to initiate motion and also ca n be used as a programma ble
digital input. It can be programmed with t063 [DigIn TermBlk
03] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.
04 Digital Common –Return for digital I/O. Electrically isolated (along with the digital
I/O) from the rest of the drive.
05 DigIn TermBlk 05/
Pulse In
Preset FreqProgram with t065 [DigIn TermBlk 05].
Also functions as a Pulse Train input for reference or speed
feedback. Requires an NPN pulse input. The maximum
frequency is 100 kHz. Current consumption is 6 mA.
49 “3-Wire Start”Per P045 [Stop Mode]
50 “2-Wire REV”t064 [2-Wire Mode] is set to:
• 0, 1, or 2 = Coast
• 3 = per P045 [Stop Mode]
51 “3-Wire Dir”Per P045 [Stop Mode]
Per P045
[Stop Mode]
The drive is shipped with a jumper installed between I/O Terminals 01 and 11.
Remove this jumper when using I/O Terminal 01 as a stop or enable input.
(2) Two wire co ntrol shown. For three wire con trol use a mom entary input on I/O Terminal 02 to command a start. Use a
maintained input for I/O Terminal 03 to change direction.
(3) When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as shown, to prevent
damage to the output.
Control I/O Terminal Designations
No. SignalDefaultDescriptionParameter
R1 Relay 1 N.O.FaultNormally open contact for output relay.
R2 Relay 1 Common FaultCommon for output relay.
R5 Relay 2 Common Motor Running Common for output relay.
R6 Relay 2 N.C.Motor Running Normally closed contact for output relay.
01 Stop CoastThree wire stop. However, it func tions as a stop under all input
02 DigIn TermBlk 02/
Start/Run FWD
03 DigIn TermBlk 03/
Dir/Run REV
04 Digital Common –Return for digital I/O. Electrically isolated (along with the digital
08 DigIn TermBlk 08 Jog ForwardProgram with t068 [DigIn TermBlk 08].
C1 C1–This terminal is tied to the RJ-45 port shield. Tie this terminal to
C2 C2–This is the signal common for the communication signals.–
S1 Safety 1–Safety input 1. Current consumption is 6 mA.–
S2 Safety 2–Safety input 2. Current consumption is 6 mA.–
S+ Safety +24V–+24V supply for safety circuit. Internally tied to the +24V DC
11 +24V DC–Referenced to Digital Common.
Run FWDUsed to initiate motion and also can be used as a programmable
Run REVUsed to initiate motion and also ca n be used as a programma ble
Start Sou rce 2
+ Speed
Reference2
modes and cannot be disabled.
digital input. It can be programmed with t062 [DigIn TermBlk
02] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.
digital input. It can be programmed with t063 [DigIn TermBlk
03] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.
I/O) from the rest of the drive.
Current consumption is 6 mA.
Current consumption is 6 mA.
Program with t067 [DigIn TermBlk 07].
Also functions as a Pulse Train input for reference or speed
feedback. Requires an NPN pulse input. Maximum frequency is
100 kHz. Current consumption is 6 mA.
Current consumption is 6 mA.
a clean ground in order to improve noise immunity when using
external communication peripherals.
source (Pin 11).
Drive supplied power for digital inputs.
Maximum output current is 100 mA.
t076
t081
(1)
P045
P045, P046,
P048, P050,
A544, t062
t063
–
t065
t066
t067
t068
–
–
–
Rockwell Automation Publication 520-UM001I-EN-E - July 201643
Page 44
Chapter 1Installation/Wiring
Control I/O Terminal Designations
No. SignalDefaultDescriptionParameter
12 +10V DC–Referenced to Analog Common.
Drive supplied power for 0...10V external potentiometer.
Maximum output current is 15 mA.
13 ±10V In Not ActiveFor external 0-10V (unipolar) or ±10V (bipolar) input supply or
potentiometer wiper.
Input impedance:
Voltage source = 100 kΩ
Allowable potentiometer resistance range = 1...10 kΩ
14 Analog Common –Return for the analog I/O. Electrically isolated (along with the
analog I/O) from the rest of the drive.
15 4-20mA InNot ActiveFor external 4-20 mA input supply.
Input impedance = 250 Ω
16 Analog OutputOutFreq 0-10 The default analog output is 0-10V. To convert a current value,
change the Analog Output jumper to 0-20 mA. Program with
t088 [Analog Out Sel]. Maximum analog value can be scaled
with t089 [Analog Out High].
Maximum Load: 4-20 mA = 525 Ω (10.5V)
0-10V = 1 kΩ (10 mA)
17 Opto Output 1Motor Running Program with t069 [Opto Out1 Sel].
Each Opto-Output is rated 30V DC 50 mA (Non-inductive).
18 Opto Output 2At Frequency Program with t072 [Opto Out1 Sel].
Each Opto-Output is rated 30V DC 50 mA (Non-inductive).
19 Opto Common–The emitters of the Optocoupler Outputs (1 and 2) are tied
together at Optocoupler Common. Electrically isolated from the
rest of the drive.
(1) See Footnote (1) on page 39.
P047
, P049
P047, P049,
t062, t063,
t065
, t066,
t093, A459,
A471
–
, P049,
P047
t062, t063,
t065, t066,
A459, A471
t088, t089
t069, t070,
t075
t072, t073,
t075
–
44Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 45
I/O Wiring Examples
13
14
+
Common
I/OConnection Example
Potentiometer
1...10k Ω Pot.
Recommended
(2 W minimum)
[Speed Reference1] = 5 “0-10V Input”
P047
Installation/WiringChapter 1
12
13
14
Analog Input
0-10V, 100k Ω impedance
4-20 mA, 250 Ω
impedance
Analog Input, PTC
For Drive Fault
Bipolar
P047 [Speed Reference1] = 5 “0-10V Input”
Unipolar (Voltage)
P047 [Speed Reference1] = 5 “0-10V Input”
and t093 [10V Bipolar Enbl] = 1 “Bi-Polar In”
13
±10V
Common
14
Unipolar (Current)
[Speed Reference1] = 6 “4-20mA Input”
P047
Common
PowerFlex 523 Series BPowerFlex 523 Series A,
13
+
14
4-20 mA
Analog In
0-10V
PowerFlex 525
Common
+
14
15
Wire the PTC and External Resistor (typically matched to the PTC Hot Resistance) to I/O
Terminals 12, 13, 14.
When using Opto-Output
with an inductive load
such as a relay, install a
recovery diode parallel to
the relay as shown, to
prevent damage to the
output.
Internal Supply (SRC)External Supply (SRC)
Stop
Start
Direction
+24VCommon
Each digital input draws 6 mA.
Internal Supply (SNK)
Stop
Start
Direction
01
02
03
04
Opto-Output 1
17
CR
19
Common+24V
Each Opto-Output is rated 30V DC 50 mA (Non-inductive).
01
02
03
04
Rockwell Automation Publication 520-UM001I-EN-E - July 201647
Page 48
Chapter 1Installation/Wiring
ATTENTION: I/O Common terminals should not be tied
together when using SNK (Internal Supply) mode. In
SNK mode, if power is removed from one drive,
inadvertent operation of other drives that share the
same I/O Common connection may occur.
I/OConnection Example
Analog Output
t088 [Analog Out Sel]
determines analog output
type and drive conditions.
0-10V,
(2)
[Analog Out Sel] = 0 through 23
t088
The Analog Output Select jumper must be set to match the analog output signal mode set in
[Analog Out Sel].
t088
PowerFlex 523 Series BPowerFlex 525
1k Ω minimum
0-20 mA/4-20 mA,
525 Ω maximum
(1) Feature is specific to PowerFlex 525 drives only
(2) Feature is not applicable to PowerFlex 523 series A drives.
Common
14
15
+
Common
+
Typical Multiple Drive Connection Examples
Input/OutputConnection Example
Multiple Digital Input
Connections
Customer Inputs can be
wired per External Supply
(SRC).
14
16
040204020402
Multiple Analog
Connections
Customer InputsOptional Ground Connection
When connecting a single input such as Run, Stop, Reverse or Preset Speeds to multiple
drives, it is important to connect I/O Terminal 04 common together for al l drives. If they are to
be tied into another common (such as earth ground or separate apparatus ground) only one
point of the daisy chain of I/O Terminal 04 should be connec ted.
1213 1413 1413 14
Remote PotentiometerOptional Ground Connection
When connecting a single potentiometer to multiple drives it is important to connect I/O
Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13
(potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up
for the analog signal to be read correctly.
48Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 49
Installation/WiringChapter 1
Purge Input Enabled
AND Active
Jog Input Enabled
AND Active
Preset Inputs Active
[Speed Referencex]
= 11 or 12 (PIDx Output)
AND
[PID x Ref Sel]
= 7 (Preset Freq)
[Speed Reference3]
select
(1)
[Start Source 3]
select
(1)
[Start Source 2]
select
(1)
[Speed Reference2]
select
(1)
Drive stopped
(NOT running)
Drive will start and
run at Purge Speed.
Direction is always
FORWARD.
Drive will start and run at
Jog Speed.
Direction is from Terminal
Block REV terminal (03),
Comms,
OR
FWD/REV determined by
Jog FWD/Jog REV command.
Run as specied by
[PIDx Output].
Start and Direction
commands come from
[Start Source x].
Run as specied by
[Preset Freq x].
Start and Direction
commands come from
[Start Source x].
Run as specied by
[Speed Reference3].
Run as specied by
[Speed Reference2].
Run as specied by
[Speed Reference1].
Start and Direction
command from
[Start Source 1].
Start and Direction
command from
[Start Source 3].
(2)
No
No
No
No
No
NoNo
No
No
Yes
YesYe s
YesYes
Yes
Yes
Yes
Start and Direction
command from
[Start Source 2].
(2)
Yes
Start and Speed Reference
Control
Start Source and Speed Reference Selection
The start and drive speed command can be obtained from a number of different
sources. By default, start source is determined by P046
speed source is determined by P047
[Speed Reference1]. However, various inputs
can override this selection, See below for the override priority.
[Start Source 1] and drive
(1) [Start Source 2/3] and [Speed Reference2/3] can be selected by the control terminal block or communication commands.
(2) See Digital Input Selection for Start Source
Rockwell Automation Publication 520-UM001I-EN-E - July 201649
on page 50 for information on selecting the correct digital input.
Page 50
Chapter 1Installation/Wiring
Digital Input Selection for Start Source
If P046, P048 or P050 [Start Source x] has been set to 2, “DigIn TermBlk”, then
t062
and t063 [DigIn TermBlk xx] must be configured for 2-Wire or 3-Wire
control for the drive to function properly.
[Start Source x]
[Start Source x]
= 2 (DigIn TrmBlk)
NoNo
Start and Direction
command from
[Start Source x].
[DigIn TermBlk
YesYe s
02/03] = 48/49/50/51
(2-Wire or
3-Wire)
Drive will not start.
Start and Direction
command from
Terminal Block.
50Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 51
Purge Input Enabled
AND Active
Terminal Block Jog
Input Enabled AND
Active
Input(s) is
programmed as
Acc/Dec
(2/3/4)
Is speed controlled
by [Preset Freq x]
Active
[Speed Referencex]
= Comms
and
[Start Source x]
= 3 “Serial/DSI” or
4 “Network Opt” or
5 “EtherNet/IP”
Active
[Speed Referencex]
= 13 (Step Logic)
(1)
Drive stopped
(NOT running)
Accel/Decel always
Accel/Decel 1.
Accel/Decel from
[Jog Acc/Dec].
Accel/Decel 2 is active
when input is selected
by Accel and Decel in put.
Drive uses Accel 1
and Decel 1.
No
No
No
No
No
No
No
Yes
YesYes
Yes
Yes
Yes
Yes
Accel/Decel 1/2/3/4 is
selected by the default
[Preset Freq x] setting.
Accel/Decel 1 or 2 is
selected according
to Comms.
Accel/Decel 1/2/3/4 is
selected according to
Step Logic
Active [DigIn TermBlk xx]
= 32 (Sync Enable)
[Sync Time] is used
for Accel/Decel rate
No
Yes
Traverse active if
[Max Traverse] > 0 Hz
Traverse Inc/Dec
is used for
Accel/Decel rate
No
Yes
Installation/WiringChapter 1
Accel/Decel Selection
The Accel/Decel rate can be obtained by a variety of methods. The default rate is
determined by P041
Accel/Decel rates can be made through digital inputs, communications and/or
parameters. See below for the override priority.
[Accel Time 1] and P042 [Decel Time 1]. Alternative
(1) Setting is specific to PowerFlex 525 drives only.
Rockwell Automation Publication 520-UM001I-EN-E - July 201651
Page 52
Chapter 1Installation/Wiring
CE Conformity
Compliance with the Low Voltage Directive and Electromagnetic Compatibility
Directive has been demonstrated using harmonized European Norm (EN)
standards published in the Official Journal of the European Communities.
PowerFlex 520-series drives comply with the EN standards listed below when
installed according to the installation instructions in this manual.
CE Declarations of Conformity are available online at:
• EN 61800-5-1 Adjustable speed electrical power drive systems – Part 5-1:
Safety requirements – Electrical, thermal and energy.
Pollution Degree Ratings According to EN 61800-5-1
Pollution
Degree
1No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
2Normally, only non-conductive pollution occurs. Occasionally, however, a temporary
Description
conductivity caused by condensation is to be expected, when the drive is out of operation.
EMC Directive (2004/108/EC and 2014/30/EU)
• EN 61800-3 – Adjustable speed electrical power drive systems - Part 3:
EMC requirements and specific test methods
Machinery Directive (2006/42/EC)
• EN ISO 13849-1 – Safety of machinery – Safety related parts of control
systems -Part 1: General principles for design
• EN 62061 – Safety of machinery – Functional safety of safety-related
electrical, electronic and programmable electronic control systems
• EN 60204-1 – Safety of machinery – Electrical equipment of machines Part 1: General requirements
• EN 61800-5-2 – Adjustable speed electrical power drive systems - Part 5-2:
Safety requirement – Functional
Refer to Appendix G
Directive.
for installation consideration related to Machinery
ATEX Directive (94/9/EC and 2014/34/EU)
• EN 50495 – Safety devices required for the safe functioning of equipment
with respect to explosion risks.
52Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 53
Installation/WiringChapter 1
General Considerations
• For CE compliance, drives must satisfy installation requirements related to
both EN 61800-5-1 and EN 61800-3 provided in this document.
• PowerFlex 520-series drives must be installed in a pollution degree 1 or 2
environment to be compliant with the CE LV Directive. See Pollution
Degree Ratings According to EN 61800-5-1 on page 52 for descriptions of
each pollution degree rating.
• PowerFlex 520-series drives comply with the EMC requirements of EN
61800-3 when installed according to good EMC practices and the
instructions provided in this document. However, many factors can
influence the EMC compliance of an entire machine or installation, and
compliance of the drive itself does not ensure compliance of all
applications.
• PowerFlex 520-series drives are not intended to be used on public lowvoltage networks which supply domestic premises. Without additional
mitigation, radio frequency interference is expected if used on such a
network. The installer is responsible for taking measures such as a
supplementary line filter and enclosure (see Connections and Grounding
on page 55) to prevent interference, in addition to the installation
requirements of this document.
ATTENTION: NEMA/UL Open Type drives must either be installed in a
supplementary enclosure or equipped with a “NEMA Type 1 Kit” to be
CE compliant with respect to protection against electrical shock.
• PowerFlex 520-series drives generate harmonic current emissions on the
AC supply system. When operated on a public low-voltage network it is
the responsibility of the installer or user to ensure that applicable
requirements of the distribution network operator have been met.
Consultation with the network operator and Rockwell Automation may
be necessary.
• If the optional NEMA 1 kit is not installed, the drive must be installed in
an enclosure with side openings less than 12.5 mm (0.5 in.) and top
openings less than 1.0 mm (0.04 in.) to maintain compliance with the LV
Directive.
• The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.
• Use of line filters in ungrounded systems is not recommended.
• In CE installations, input power must be a Balanced Wye with Center
Ground configuration for EMC compliance.
Installation Requirements Related to EN 61800-5-1 and the Low Voltage Directive
• 600V PowerFlex 520-series drives can only be used on a “center grounded”
supply system for altitudes up to and including 2000 m (6562 ft).
Rockwell Automation Publication 520-UM001I-EN-E - July 201653
Page 54
Chapter 1Installation/Wiring
• When used at altitudes above 2000 m (6562 ft) up to a maximum of
4800 m (15,748 ft), PowerFlex 520-series drives of voltage classes up to
480V may not be powered from a “corner-earthed” supply system in order
to maintain compliance with the CE LV Directive. See Derating
Guidelines for High Altitude on page 18.
• PowerFlex 520-series drives produce leakage current in the protective
earthing conductor which exceeds 3.5 mA AC and/or 10 mA DC. The
minimum size of the protective earthing (grounding) conductor used in
the application must comply with local safety regulations for high
protective earthing conductor current equipment.
ATTENTION: PowerFlex 520-series drives produce DC current in the
protective earthing conductor which may reduce the ability of RCD’s
(residual current-operated protective devices) or RCM’s (residual
current-operated monitoring devices) of type A or AC to provide
protection for other equipment in the installation. Where an RCD or
RCM is used for protection in case of direct or indirect contact, only an
RCD or RCM of Type B is allowed on the supply side of this product.
Installation Requirements Related to EN 61800-3 and the EMC Directive
• The drive must be earthed (grounded) as described in Connections and
Grounding on page 55. See General Grounding Requirements on page 20
for additional grounding recommendations.
• Output power wiring to the motor must employ cables with a braided
shield providing 75% or greater coverage, or the cables must be housed in
metal conduit, or equivalent shield must be provided. Continuous
shielding must be provided from the drive enclosure to the motor
enclosure. Both ends of the motor cable shield (or conduit) must terminate
with a low-impedance connection to earth.
Drive Frames A...E: At the drive end of the motor, either
a. The cable shield must be clamped to a properly installed “EMC Plate”
for the drive. Kit number 25-EMC1-Fx.
or
b. The cable shield or conduit must terminate in a shielded connector
installed in an EMC plate, conduit box, or similar.
• At the motor end, the motor cable shield or conduit must terminate in a
shielded connector which must be properly installed in an earthed motor
wiring box attached to the motor. The motor wiring box cover must be
installed and earthed.
• All control (I/O) and signal wiring to the drive must use cable with a
braided shield providing 75% or greater coverage, or the cables must be
housed in metal conduit, or equivalent shielding must be provided. When
shielded cable is used, the cable shield should be terminated with a low
impedance connection to earth at only one end of the cable, preferably the
end where the receiver is located. When the cable shield is terminated at
the drive end, it may be terminated either by using a shielded connector in
conjunction with a conduit plate or conduit box, or the shield may be
clamped to an “EMC plate.”
54Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 55
Installation/WiringChapter 1
IMPORTANT
IMPORTANT
Esc
Sel
• Motor cabling must be separated from control and signal wiring wherever
possible.
• Maximum motor cable length must not exceed the maximum length
indicated in PowerFlex 520-Series RF Emission Compliance and
Installation Requirements on page 55 for compliance with radio frequency
emission limits for the specific standard and installation environment.
Connections and Grounding
Shielded enclosure
EMI lter
L1
L2
L3
Enclosure ground connection
Building structure steel
(1) Some installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the
EMI filter.
(1)
IP 30/NEMA 1/UL Type 1
option kit or EMC kit
EMI ttings and metal conduit
R/L1
L1'
S/L2
L2'
T/L3
L3'
Shielded motor cable
U/T1
V/T2
W/T3
PowerFlex 520-Series RF Emission Compliance and Installation Requirements
Filter TypeStandard/Limits
EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B
Internal–10 m (33 ft)20 m (66 ft)
(1)
External
(1) See Appendix B for more information on optional external filters.
30 m (16 ft)100 m (328 ft)100 m (328 ft)
EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power ≤ 20 kVA)
EN61800-3 Category C3
(I ≤ 100 A)
CISPR11 Group 1 Class A
(Input power > 20 kVA)
Additional Installation Requirements
This section provides information on additional requirements for category C1
and C2 installation, such as enclosures and EMC cores.
EMC cores are included with:
• drives that have an internal EMC filter (25x-xxxxN114)
Rockwell Automation Publication 520-UM001I-EN-E - July 201655
• external EMC filter accessory kit (25-RFxxx)
An enclosure, shielded input cable, and EMC cores are not required to meet
category C3 requirements.
Page 56
Chapter 1Installation/Wiring
Additional Installation Requirements
Frame
Category C1Category C2
Size
EnclosureConduit or Shielded
Cable @ Input
100...120V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...120V 1-Phase Output
ANoNo NoNoNo No
BNoNo NoNoNo No
200...240V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...230V 3-Phase Output
(1) An (*) indicates that EMC requirements are not met.
EMC Cores Required
(Included with product)
EnclosureConduit or Shielded
Cable @ Input
(1)
(1)
EMC Cores Required
(Included with product)
56Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 57
Recommended Placement of EMC Cores
CORE-x x-A-1
CORE-xx-A -2
CORE-x x-B-1
CORE-xx-B-2
CORE-xx-C-1
CORE-x x-C-2
CORE-xx-D-1
CORE-x x-D-2
CORE-E-1
CORE-E-2
CORE-E-3
CORE-E-4
Ground
cable
CORE-xx-x-1CORE-xx-x-2
CORE-E-1
CORE-E-2
CORE-E-3
CORE-E-4
Ground
cable
Shows contact to
shielded layer
Secure EMC core by
using cable/zip ties
Output cable from drive (Shielded)
Input cable to drive (Shielded or Unshielded)
IMPORTANT
Input coreOutput core
Incoming power
EMC FilterDriveMotor
All Frame sizes
Frame AFrame BFrame CFrame DFrame E
With optional EMC plate (25-EMC-Fx)
Without EMC plate
Installation/WiringChapter 1
The ground cable/shield for both input and output must pass through the EMC core(s), except for the following:
• Frame E drives with internal filters where the grounded input cable must not pass through EMC CORE-E-1.
• 600V drives with external filters where the grounded output cable must not pass through the EMC core(s).
Recommended Placement of EMC Cores Relative to External Filter
Rockwell Automation Publication 520-UM001I-EN-E - July 201657
Page 58
Chapter 1Installation/Wiring
Notes:
58Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 59
Chapter 2
IMPORTANT
Start Up
This chapter describes how to start up the PowerFlex 520-series drive. To simplify
drive setup, the most commonly programmed parameters are organized in a
single Basic Program Group.
For information on...See page...
Prepare for Drive Start-Up59
Display and Control Keys62
Viewing and Editing Parameters63
Drive Programming Tools64
Smart Start-Up with Basic Program Group Parameters65
LCD Display with QuickView Technology67
Using the USB Port67
Read the General Precautions section before proceeding.
Prepare for Drive Start-Up
ATT EN TI ON : Power must be applied to the drive to perform the following
start-up procedures. Some of the voltages present are at incoming line
potential. To avoid electric shock hazard or damage to equipment, only
qualified service personnel should perform the following procedure.
Thoroughly read and understand the procedure before beginning. If an event
does not occur while performing this procedure, Do Not Proceed. Remove A ll Power including user supplied control voltages. User supplied voltages may
exist even when main AC power is not applied to the drive. Correct the
malfunction before continuing.
Drive Startup Task List
1. Disconnect and lock out power to the machine.
2. Verify that AC line power at the disconnect device is within the rated value
of the drive.
3. If replacing a drive, verify the current drive’s catalog number. Verify all
options installed on the drive.
4. Verify that any digital control power is 24 volts.
5. Inspect grounding, wiring, connections, and environmental compatibility.
Rockwell Automation Publication 520-UM001I-EN-E - July 201659
Page 60
Chapter 2Start Up
IMPORTANT
6. Verify that the Sink (SNK)/Source (SRC) jumper is set to match your
control wiring scheme. See the PowerFlex 523 Control I/O Wiring Block
Diagram on page 38 and PowerFlex 525 Control I/O Wiring Block
Diagram on page 42 for location.
The default control scheme is Source (SRC). The Stop terminal is jumpered to
allow starting from the keypad or comms. If the control scheme is changed to
Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and
installed between I/O Terminals 01 and 04.
7. Wire I/O as required for the application.
8. Wire the power input and output terminals.
9. Confirm that all inputs are connected to the correct terminals and are
secure.
10. Collect and record motor nameplate and encoder or feedback device
information. Verify motor connections.
• Is the motor uncoupled?
• What direction will the motor need to turn for the application?
11. Verify the input voltage to the drive. Verify if the drive is on a grounded
system. Ensure the MOV jumpers are in the correct position. See AC
Supply Source Considerations on page 19 for more information.
12. Apply power and reset the drive and communication adapters to factory
default settings. To reset the drive, see parameter P053
[Reset to Defalts].
To reset the communication adapters, see the user manual of the adapter
for more information.
13. Configure the basic program parameters related to the motor. See Smart
Start-Up with Basic Program Group Parameters on page 65.
14. Complete the autotune procedure for the drive. See parameter P040
[Autotune] for more information.
15. If you are replacing a drive and have a backup of the parameter settings
obtained using the USB utility application, use the USB utility application
to apply the backup to the new drive. See Using the USB Port
on page 67
for more information.
Otherwise, set the necessary parameters for your application using the
LCD keypad interface, Connected Components Workbench, or RSLogix
or Logix Designer if using an Add-on Profile through EtherNet/IP.
• Configure the communication parameters needed for the application
(node number, IP address, Datalinks in and out, communication rate,
speed reference, start source, and so on). Record these settings for your
reference.
• Configure the other drive parameters needed for the drive analog and
digital I/O to work correctly. Verify the operation. Record these
settings for your reference.
60Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 61
Start UpChapter 2
IMPORTANT
IMPORTANT
16. Verify the drive and motor perform as specified.
• Verify that the Stop input is present or the drive will not start.
If I/O Terminal 01 is used as a stop input, the jumper between I/O
Terminals 01 and 11 must be removed.
• Verify the drive is receiving the speed reference from the correct place
and that the reference is scaled correctly.
• Verify the drive is receiving start and stop commands correctly.
• Verify input currents are balanced.
• Verify motor currents are balanced.
17. Save a backup of the drive settings using the USB utility application. See
Using the USB Port
on page 67 for more information.
Start, Stop, Direction and Speed Control
Factory default parameter values allow the drive to be controlled from the
keypad. No programming is required to start, stop, change direction and control
speed directly from the keypad.
To disable reverse operation, see A544 [Reverse Disable].
If a fault appears on power up, see Fault Descriptions on page 159
explanation of the fault code.
for an
Variable Torque Fan/Pump Applications
For improved motor and drive performance, tune the motor in SVC mode using
parameter P040 [Autotune]. If V/Hz mode is selected, use parameter A530
[Boost Select] to adjust the boost.
Rockwell Automation Publication 520-UM001I-EN-E - July 201661
Page 62
Chapter 2Start Up
Esc
Sel
FWD
Esc
Sel
FWD
ENET LINK
EtherNet/IP
Menu Parameter Group and Description
Basic Display
Commonly viewed drive operating conditions.
Basic Program
Commonly used programmable functions.
Ter mina l Bl ocks
Programmable terminal functions.
Communications
Programmable communication functions.
Logic (PowerFlex 525 only)
Programmable logic functions.
Advanced Display
Advanced drive operating conditions.
Advanced Program
Remaining programmable functions.
Network
Network functions that are shown only when a comm
card is used.
Modified
Functions from the other groups with values changed
from default.
Fault and Diagnostic
Consists of list of codes for specific fault conditions.
AppView and CustomView
Functions from the other groups organized for specific
applications.
PowerFlex 523
PowerFlex 525
Esc
Sel
Display and Control Keys
Control and Navigation Keys
DisplayDisplay State Descr iption
ENET (PowerFlex 525 only)OffAdapter is not connected to the network.
SteadyAdapter is connected to the network and drive is controlled
FlashingAdapter is conne cted to the network but drive is not controlled
62Rockwell Automation Publication 520-UM001I-EN-E - July 2016
LINK (PowerFlex 525 only)OffAdapter is not connected to the network.
SteadyAdapter is connected to the network but n ot transmitting data.
FlashingAdapter is connected to the network and transmitting data.
LEDLED StateDescription
FAULTFlashing RedIndicates drive is faulted.
KeyNameDescription
Up Arrow
Down Arrow
EscapeBack one step in programming menu.
SelectAdvance one step in programming menu.
EnterAdvance one step in programming menu.
through Ethernet.
through Ethernet.
Scroll through user-selectable display parameters or groups.
Increment values.
Cancel a change to a parameter value and exit Program Mode.
Select a digit when viewing parameter value.
Save a change to a parameter value.
Page 63
KeyNameDescription
HERT
Z
FWD
Esc
FWD
Esc
FWD
or
FWD
Sel
or
FWDorFWD
VOLTS
FWD
Sel
or
PROGRAM
VOLTS
FWD
or
PROGRAM
VOLTS
FWD
ReverseUsed to reverse direction of the drive. Default is active.
Controlled by parameters P046, P048 and P050 [Start Source x]
and A544 [Reverse Disable].
StartUsed to start the drive. Default is active.
Controlled by parameters P046, P048 and P050 [Start Source x].
StopUsed to stop the drive or clear a fault.
This key is always active.
Controlled by parameter P045 [Stop Mode].
Potentiometer Used to control speed of drive. Default is ac tive.
Controlled by parameters P047, P049 and P051
[Speed Referencex].
Start UpChapter 2
Viewing and Editing
Parameters
The following is an example of basic integral keypad and display functions. This
example provides basic navigation instructions and illustrates how to program
a parameter.
StepKey(s)Example Display
1. When power is applied, the last user-selected
Basic Display Group parameter number is briefly
displayed with flashing characters. The display
then defaults to that parameter’s current value.
(Example shows the value of b001 [Output
Freq] with the drive stopped.)
2. Press Esc to display the Basic Display Group
parameter number shown on power-up. The
parameter number will flash.
3. Press Esc to enter the parameter group list. The
parameter group letter will flash.
4. Press the Up Ar row or Down Arrow to scroll
through the group list (b, P, t, C, L, d, A, f and
Gx).
5. Press Enter or Sel to enter a group. The right
digit of the last viewed parameter in that group
will flash.
6. Press the Up Ar row or Down Arrow to scroll
through the parameter list.
7. Press Enter to view the value of the parameter.
Or
Press Esc to return to the parameter list.
8. Press Enter or Sel to enter Program Mode and
edit the value. The right digit will flash and the
word Program on the LCD display will light up.
9. Press the Up Arrow or Down Arrow to change
the parameter value.
Rockwell Automation Publication 520-UM001I-EN-E - July 201663
Page 64
Chapter 2Start Up
Sel
PROGRAM
VOLTS
FWD
Esc
or
VOLTS
FWD
VOLTS
FWD
or
Esc
FWD
StepKey(s)Example Display
10. If desired, press Sel to move from digit to digit
or bit to bit. The digit or bit that you can change
will flash.
11. Press Esc to cancel a change and exit Program
Mode.
Or
Press Enter to save a change and exit Program
Mode.
The digit will stop flashing and the word
Program on the LCD display will turn off.
12. Press Esc to return to the parameter list.
Continue to press Esc to back out of the
programming menu.
If pressing Esc does not change the display, then
b001 [Output Freq] is displayed. Press Enter or
Sel to enter the group list again.
Drive Programming Tools
Some features in the PowerFlex 520-series drive are not supported by older
configuration software tools. It is strongly recommended that customers using
such tools migrate to RSLogix 5000 (version 17.0 or greater) or Logix Designer
(version 21.0 or greater) with Add-On-Profile (AOP), or Connected
Components Workbench (version 5.0 or greater) to enjoy a richer, full-featured
configuration experience. For Automatic Device Configuration (ADC) support,
RSLogix 5000 version 20.0 or greater is required.
DescriptionCatalog Number/Release Version
Connected Components Workbench
Logix DesignerVersion 21.0 or greater
RSLogix 5000Version 17.0 or greater
Built-in USB software tool–
Serial Converter Module
USB Converter Module
(1) Available as a free download at http://ab.rockwellautomation.com/programmable-controllers/connected-components-
workbench-software.
(2) Does not support the new dynamic parameter groups (AppView, CustomView), and CopyCat functionality is limite d to the linear
parameter list.
(1)
Version 5.0 or greater
22-SCM-232
1203-USB
(2)
(2)
22-HIM-C2S
22-HIM-A3
Language Support
LanguageKeypad/LCD DisplayRSLogix 5000/
EnglishYYY
FrenchYYY
SpanishYYY
ItalianYYY
GermanYYY
Japanese–Y–
Port ugues eYY–
Chinese Simplified–YY
Korean–Y–
64Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Logix Designer
Connected Components
Work bench
Page 65
Start UpChapter 2
PF 525
PF 525
Smart Start-Up with Basic
Program Group Parameters
LanguageKeypad/LCD DisplayRSLogix 5000/
(1)
Poli sh
(1)
Tur ki sh
(1)
Czech
(1) Due to a limitation of the LCD Display, some of the characters for Polish, Turkish, and Czech will be modified.
Y––
Y––
Y––
Logix Designer
Connected Components
Work bench
The PowerFlex 520-series drive is designed so that start up is simple and efficient.
The Basic Program Group contains the most commonly used parameters. See
Programming and Parameters on page 71
for detailed descriptions of the
parameters listed here, as well as the full list of available parameters.
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No.ParameterMin/MaxDisplay/OptionsDefault
P030 [Language]1/151 = English
Selects the language displayed.
Important: The setting takes effect after the drive
P037 [Motor NP Power]0.00/Drive Rated Power0.01 kWDrive Rated Power
Sets the motor nameplate power. Used in PM
regulato r.
P038 [Voltage Class]2/32 = “480V”
Sets the voltage class of 600V drives. Only applicable
to 600V drives.
2= Français
3= Español
4 = Italiano
5= Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reser ved
11 = Reser ved
12 = Polish
13 = Reser ved
14 = Turkish
15 = Czech
1VBased on Drive Rating
3 = “600V”
1
3
Rockwell Automation Publication 520-UM001I-EN-E - July 201665
Page 66
Chapter 2Start Up
PF 525
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No.ParameterMin/MaxDisplay/OptionsDefault
P039 [Torque Perf Mode] 0/40 = “V/Hz”
Selects the motor control mode.
(1) Setting is specific to PowerFlex 525 drives only.
(2) Setting is available in PowerFlex 525 FRN 5.xxx and
later.
(3) When P039 [Torque Perf Mode] is set to 4 and
A535
[Motor Fdbk Type] is set to 0, 1, 2 or 3, the drive
is in open loop PM motor control mode.
When P039 [Torque Perf Mode] is set to 4 and
A535
[Motor Fdbk Type] is set to 4 or 5, the drive is in
closed loop PM motor control mode.
1 = “SVC”
2 = “Economize”
3 = “Vector”
(1)
4 = “PM Control”
P040 [Autotune]0/20 = “Ready/Idle”
Enables a static (not spinning) or dynamic (motor
spinning) autotune.
1 = “Static Tune”
2 = “Rotate Tune”
(1)(2)(3)
1
0
P041 [Accel Time 1]0.00/600.00 s0.01 s10.00 s
Sets the time for the drive to accel from 0 Hz to
[Maximum Freq].
P042 [Decel Time 1]0.00/600.00 s0.01 s10.00 s
Sets the time for the drive to decel from [Maximum
Freq] to 0 Hz.
P043 [Minimum Freq]0.00/500.00 Hz0.01 Hz0.00 Hz
Sets the lowest frequency the drive outputs.
P044 [Maximum Freq]0.00/500.00 Hz0.01 Hz60.00 Hz
Sets the highest frequency the drive outputs.
P045 [Stop Mode]0/110 = “Ramp, CF”
Stop command for normal stop.
Important: I/O Terminal 01 is always a stop input.
The stopping mode is determined by the drive
setting.
Important: The drive is shipped with a jumper
installed between I/O Terminals 01 and 11. Remove
this jumper when using I/O Terminal 01 as a stop or
enable input.
(1) Stop input also clears active fault.
P046,
[Start Source 1]1/51 = “Keypad”
P048,
Sets the default control scheme used to start the
P050
drive unless overriden by P048 [Start Source 2] or
P050 [Start Source 3].
(1) When active, the Reverse key is also active unless
disabled by A544 [Reverse Disable].
(2) If “DigIn TrmBlk” is selected, ensure that the digital
inputs are properly configured.
(3) Setting is specific to PowerFlex 525 drives only.
QuickView™ technology enables text to scroll across the LCD display of the
PowerFlex 520-series drive. This allows you to easily configure parameters,
troubleshoot faults and view diagnostic items without using a separate device.
Use parameter A556
the display. Select 0 “Off ” to turn off text scrolling. See Language Support
[Text Scroll] to set the speed at which the text scrolls across
on
page 64 for the languages supported by the PowerFlex 520-series drive.
The PowerFlex 520-series drive has a USB port that connects to a PC for the
purpose of upgrading drive firmware or uploading/downloading a parameter
configuration.
To use the USB feature of the PowerFlex 520-series drive, Microsoft .Net
Framework 2.0 and Windows XP or later is required.
MainsFree Programming
The MainsFree™ programming feature allows you to quickly configure your
PowerFlex 520-series drive without having to power up the control module or
install additional software. Simply connect the control module to your PC with a
USB Type B cable and you can download a parameter configuration to your
drive. You can also easily upgrade your drive with the latest firmware.
Rockwell Automation Publication 520-UM001I-EN-E - July 201667
Page 68
Chapter 2Start Up
IMPORTANT
USB port
Control Module
USB Type B cable
Connec t to Control ModuleConnect to PC
Connecting a PowerFlex 520-series drive to a PC
When connected, the drive appears on the PC and contains two files:
• GUIDE.PDF
This file contains links to relevant product documentation and software
downloads.
• PF52XUSB.EXE
This file is an application to flash upgrade firmware or upload/download a
parameter configuration.
It is not possible to delete these files or add more to the drive.
Double-click on the PF52XUSB.EXE file to launch the USB utility application.
The main menu is displayed. Follow the program instructions to upgrade the
firmware or upload/download configuration data.
Make sure your PC is powered by an AC power outlet or has a fully charged
battery before starting any operation. This prevents the operation from
terminating before completion due to insufficient power.
68Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 69
Start UpChapter 2
Limitation in Downloading .pf5 Configuration Files with the USB
Utility Application
Before downloading a .pf5 configuration file using the USB utility application,
parameter C169 [MultiDrv Sel] in the destination drive must match the
incoming configuration file. If it does not, set the parameter manually to match
and then cycle drive power. Also, the drive type of the .pf5 file must match the
drive.
This means you cannot apply a multi-drive configuration using the USB utility
application to a drive in single mode (parameter C169 [MultiDrv Sel] set to 0
“Disabled”), or apply a single mode configuration to a drive in multi-drive mode.
Rockwell Automation Publication 520-UM001I-EN-E - July 201669
Page 70
Chapter 2Start Up
Notes:
70Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 71
Chapter 3
Programming and Parameters
This chapter provides a complete listing and description of the PowerFlex 520series drive parameters. Parameters are programmed (viewed/edited) using either
the drive’s built-in keypad, RSLogix 5000 version 17.0 or greater, Logix Designer
version 21.0 or greater, o r Connected Components Workbench version 5.0 or
greater software. The Connected Components Workbench software can be used
offline (through USB) to upload parameter configurations to the drive or online
(through Ethernet connection).
Limited functionality is also available when using the Connected Components
Workbench software online (through DSI and serial converter module), a legacy
external HIM, or legacy software online (DriveTools SP™). When using these
methods, the parameter list can only be displayed linearly, and there is no access
to communications option card programming.
About Parameters
For information on...See page...
About Parameters71
Paramete r Groups73
Basic Display Group78
Basic Program Group83
Terminal Block Group89
Communications Group101
Logic G roup107
Advanced Display Group110
Advanced Program Group115
Network Parameter Group141
Modified Parameter Group142
Fault and Diagnostic Group142
AppView Parameter Groups150
CustomView Parameter Group151
Parameter Cross Reference by Name152
To configure a drive to operate in a specific way, drive parameters may have to be
set. Three types of parameters exist:
•ENUM
ENUM parameters allow a selection from 2 or more items. Each item is
represented by a number.
•Numeric Parameters
These parameters have a single numerical value (0.1V).
Rockwell Automation Publication 520-UM001I-EN-E - July 201671
Bit parameters have five individual digits associated with features or
conditions. If the digit is 0, the feature is off or the condition is false. If the
digit is 1, the feature is on or the condition is true.
Some parameters are marked as follows.
= Stop drive before changing this parameter.
= 32 bit parameter.
= Parameter is specific to PowerFlex 525 drives only.
32-bit Parameters
Parameters marked 32-bit will have two parameter numbers when using RS485
communications and programming software. For example, parameters b010
[Process Display] and b011 [Process Fract] are scaled and displayed as follows.
• P043 [Minimum Freq] = 0 Hz
• P044 [Maximum Freq] = 60 Hz
• A481 [Process Display Lo] = 0
• A482 [Process Display Hi] = 10
Using the forumla,
when the drive is running at 10 Hz, the Process Value will be 1.66.
On the drive LCD display, only parameter b010 [Process Display] is shown.
In Connected Components Workbench software, parameter b010 [Process
Display] and b011 [Process Fract] are shown separately.
72Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Comm Wri te ModeC1 21
Cmd Stat Select
RS485 Data RateC123
RS485 Node AddrC124
Comm Loss ActionC125
Comm Loss TimeC126
RS485 FormatC127
Logic
Stp Logic 0L180
Stp Logic 1L181
Advanced Display
Analog In 0-10Vd360
Analog In 4-20mAd361
Elapsed Time-hrd362
(1)
(1)
C122
For an alphabetical listing of parameters, see Parameter Cross Reference by Name
on page 152.
Output Voltageb004
DC Bus Voltageb005
Drive Statusb006
Fault 1 Codeb007
Fault 2 Codeb008
Fault 3 Codeb009
Process Displayb010
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
Motor NP RPMP036
Motor NP Power
DigIn TermBlk 07
DigIn TermBlk 08
Opto Out1 Sel
Opto Out1 Level
Opto Out2 Sel
Opto Out2 Level
Opto Out Logic
Relay Out1 Selt076
Relay Out1 Levelt077
EN Addr Sel
EN IP Addr Cfg 1
EN IP Addr Cfg 2
EN IP Addr Cfg 3
EN IP Addr Cfg 4
EN Subnet Cfg 1
EN Subnet Cfg 2
EN Subnet Cfg 3
EN Subnet Cfg 4
EN Gateway Cfg 1
EN Gateway Cfg 2
Control Sourceb0 12
Contrl In Statusb013
Dig In Statusb014
Output RPMb015
Output Speedb016
Output Powerb017
Power Savedb 018
Volt age C lassP 038
Torque Perf ModeP039
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Relay 1 On Timet079
Relay 1 Off Timet080
Relay Out2 Sel
Relay Out2 Level
Relay 2 On Time
Relay 2 Off Time
(1)
(1)
(1)
(1)
t081
t082
t084
t085
EM Brk Off Delayt086
EM Brk On Delayt087
Analog Out Sel
EN Gateway Cfg 3
EN Gateway Cfg 4
EN Rate Cfg
EN Comm Flt Actn
EN Idle Flt Actn
EN Flt Cfg Logic
EN Flt Cfg Ref
EN Flt Cfg DL 1
EN Flt Cfg DL 2
EN Flt Cfg DL 3
EN Flt Cfg DL 4
(2)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
t088
C139
C140
C141
(1)
C143
C144
C145
C146
C147
C148
C149
C150
Stp Logic Time 0L190
Stp Logic Time 1L191
Stp Logic Time 2L192
Stp Logic Time 3L193
Stp Logic Time 4L194
Stp Logic Time 5L195
Speed Feedbackd376
Encoder Speed
(2)
d378
DC Bus Rippled380
Output Powr Fctrd381
Tor que Cur ren td38 2
PID1 Fdbk Displd383
PID1 Setpnt Dispd384
Elapsed Run Timeb019
Average Powerb020
Elapsed kWhb021
Elapsed MWhb022
Energy Savedb023
Accum kWh Savb024
Accum Cost Savb025
t090
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
10V Bipolar Enbl
(1)
t093
Anlg In V Losst094
Anlg In4-20mA Lot095
Anlg In4-20mA Hit096
Anlg In mA Losst097
EN Data In 1
EN Data In 2
EN Data In 3
EN Data In 4
EN Data Out 1
EN Data Out 2
EN Data Out 3
EN Data Out 4
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
C153
C154
C155
C156
C157
C158
C159
C160
Opt Data In 1C161
Opt Data In 2C162
Opt Data In 3C163
Stp Logic Time 6L196
Stp Logic Time 7L197
Step Units 0L200
Step Units 1L202
Step Units 2L204
Step Units 3L206
PID2 Fdbk Displ
PID2 Setpnt Disp
Position Status
Units Traveled H
Units Traveled L
Fiber Statusd390
Stp Logic Status
(1)
(1)
(1)
(1)
(1)
(1)
d385
d386
d387
d388
d389
d391
Accum CO2 Savb026
Drive Tempb027
Control Tempb028
Control SW Verb029
Start Source 3P050
Speed Reference3P051
Average kWh CostP052
Reset To DefaltsP053
Anlg Loss Delayt098
Analog In Filtert099
Sleep-Wake Selt100
Sleep Levelt101
Sleep Timet102
Wake Leve lt103
Wake Timet104
Safety Open En
SafetyFlt RstCfg
(1)
(1)(3)
t105
t106
Opt Data In 4C164
Opt Data Out 1C165
Opt Data Out 2C166
Opt Data Out 3C167
Opt Data Out 4C168
MultiDrv SelC169
Drv 1 AddrC171
Drv 2 AddrC172
Drv 3 AddrC173
Drv 4 AddrC174
DSI I/O CfgC175
Step Units 4L208
Step Units 5L210
Step Units 6L212
Step Units 7L214
RdyBit Mode Act
Drive Status 2
(2)(3)
Dig Out Status
(2)(4)
(2)(3)
d392
d393
d394
Rockwell Automation Publication 520-UM001I-EN-E - July 201673
A425
Keypad FreqA426
MOP FreqA427
MOP Reset SelA428
MOP PreloadA429
MOP TimeA430
Jog FrequencyA431
Jog Accel/DecelA432
Purge FrequencyA433
DC Brake TimeA434
DC Brake LevelA435
DC Brk Time@StrtA436
DB Resistor SelA437
DB ThresholdA438
S Curve %A439
PWM FrequencyA440
Droop Hertz@ FLA
(1)
A441
Network
Accel Time 2A442
Decel Time 2A443
Accel Time 3A444
Decel Time 3A445
Accel Time 4A446
Decel Time 4A447
Skip Frequency 1A448
Skip Freq Band 1A449
Skip Frequency 2A450
Skip Freq Band 2A451
Skip Frequency 3
Skip Freq Band 3
Skip Frequency 4
Skip Freq Band 4
(1)
(1)
(1)
(1)
A452
A453
A454
A455
PID 1 Trim HiA456
PID 1 Trim LoA457
PID 1 Trim SelA458
PID 1 Ref SelA459
PID 1 Fdback SelA460
PID 1 Prop GainA461
PID 1 Integ TimeA462
PID 1 Diff RateA463
PID 1 SetpointA464
PID 1 DeadbandA465
PID 1 PreloadA466
PID 1 Invert ErrA467
PID 2 Trim Hi
PID 2 Trim Lo
PID 2 Trim Sel
PID 2 Ref Sel
PID 2 Fdback Sel
PID 2 Prop Gain
PID 2 Integ Time
PID 2 Diff Rate
PID 2 Setpoint
PID 2 Deadband
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
A468
A469
A470
A471
A472
A473
A474
A475
A476
A477
PID 2 Preload
PID 2 Invert Err
(1)
(1)
A478
A479
Process Disp LoA481
Process Disp HiA482
Testpoint SelA483
Current Limit 1A484
Current Limit 2
(1)
A485
Shear Pin1 LevelA486
Shear Pin 1 TimeA487
Shear Pin2 Level
Shear Pin 2 Time
Load Loss Level
Load Loss Time
(1)
(1)
(1)
(1)
A488
A489
A490
A491
Stall Fault TimeA492
Motor OL SelectA493
Motor OL RetA494
Drive OL ModeA495
IR Voltage DropA496
Flux Current RefA497
(1)
Motor Rr
(1)
Motor Lm
(1)
Motor Lx
PM IR Voltage
(1)(3)
PM IXd Voltage
PM IXq Voltage
PM BEMF Voltage
Speed Reg Sel
Freq 1
Freq 1 BW
Freq 2
Freq 2 BW
Freq 3
Freq 3 BW
PM Initial Sel
PM DC Inject Cur
PM Align Time
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)(3)
(1)(3)
(1)(3)
(1)(3)
(1)(3)
(1)(3)
A498
A499
A500
A501
A502
A503
A504
A509
A510
A511
A512
A513
A514
A515
A516
A517
A518
PM HIFI NS Cur
PM Bus Reg Kd
Freq 1 Kp
Freq 1 Ki
Freq 2 Kp
Freq 2 Ki
Freq 3 Kp
Freq 3 Ki
PM FWKn 1 Kp
PM FWKn 2 Kp
PM Control Cfg
Boost SelectA530
Start BoostA531
Break VoltageA532
Break FrequencyA533
Maximum VoltageA534
Motor Fdbk Type
Encoder PPR
Pulse In ScaleA537
Ki Speed Loop
Kp Speed Loop
Var PWM DisableA540
Auto Rstrt TriesA541
Auto Rstrt DelayA542
Start At PowerUpA543
Reverse DisableA544
Flying Start EnA545
FlyStrt CurLimitA546
CompensationA547
Power Loss ModeA548
Half Bus EnableA549
Bus Reg EnableA550
Fault ClearA 551
Program LockA552
Program Lock ModA553
Drv Ambient SelA554
(1)(3)
(1)(3)
(1)
(1)
(1)
(1)
(1)
(1)
(1)(3)
(1)(3)
(1)(3)
(2)
(1)
(2)
(2)
This group contains parameters for the network option card that is installed.
See the network option card’s user manual for more information on the available parameters.
A519
Reset MetersA555
A520
Tex t S cro llA55 6
A521
Out Phas Loss EnA557
A522
A523
A524
A525
A526
A527
A528
A529
This group contains parameters that have their values changed from the factory default.
When a parameter has its default value changed, it is automatically added to this group. When a parameter has its value changed back to the
factory default, it is automatically removed from this group.
74Rockwell Automation Publication 520-UM001I-EN-E - July 2016
(1) Parameter is specific to PowerFlex 525 drives only.
(2) Parameter is also available in PowerFlex 523 FRN 3.xxx and later.
(3) Parameter is available in PowerFlex 525 FRN 5.xxx and later.
(4) Parameter is available in PowerFlex 525 FRN 3.xxx and later.
(5) Parameter is available in PowerFlex 525 FRN 2.xxx and later.
Fault 5 Time-minF625
Fault 6 Ti me-m in
Fault 7 Ti me-m in
Fault 8 Ti me-m in
Fault 9 Ti me-m in
Fault10 Time-min
Fault 1 FreqF631
Fault 2 FreqF632
Fault 3 FreqF633
Fault 4 FreqF634
Fault 5 FreqF635
Fault 6 Freq
Fault 7 Freq
Fault 8 Freq
Fault 9 Freq
Fault10 Freq
F616
Fault 1 CurrentF641
F617
Fault 2 CurrentF642
F618
Fault 3 CurrentF643
F619
Fault 4 CurrentF644
F620
Fault 5 CurrentF645
Fault 6 Cu rrent
Fault 7 Cu rrent
Fault 8 Cu rrent
Fault 9 Cu rrent
HW Addr 4
HW Addr 5
HW Addr 6
EN IP Addr Act 1
EN IP Addr Act 2
EN IP Addr Act 3
EN IP Addr Act 4
EN Subnet Act 1
EN Subnet Act 2
EN Subnet Act 3
(1)
(1)
(1)
(1)
(1)
EN Subnet Act 4
F666
EN Gateway Act 1
F667
EN Gateway Act 2
F668
EN Gateway Act 3
F669
EN Gateway Act 4
F670
Drv 0 Logic CmdF705
Drv 0 ReferenceF706
(1)
Drv 0 Logic StsF707
F683
Drv 0 FeedbackF708
F684
Drv 1 Logic CmdF709
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
F685
Drv 1 ReferenceF710
Drv 1 Logic StsF711
F687
Drv 1 FeedbackF712
F688
Drv 2 Logic CmdF713
F689
Drv 2 ReferenceF714
F690
Drv 2 Logic StsF715
F691
Drv 2 FeedbackF716
F692
Drv 3 Logic CmdF717
F693
Drv 3 ReferenceF718
F694
Drv 3 Logic StsF719
F695
Drv 3 FeedbackF720
F696
Drv 4 Logic CmdF721
F697
Drv 4 ReferenceF722
F698
Drv 4 Logic StsF723
F699
Drv 4 FeedbackF724
F700
EN Rx Overruns
F701
EN Rx Packets
F702
EN Rx Errors
F703
EN Tx Packets
F704
EN Tx Errors
(1)
(1)
(1)
(1)
(1)
EN Missed IO Pkt
F725
F726
F727
F728
(1)
F729
F730
DSI ErrorsF731
Rockwell Automation Publication 520-UM001I-EN-E - July 201675
Page 76
Chapter 3Programming and Parameters
AppView Parameter Groups
PowerFlex 520-series drives include various AppView™ parameter groups that
groups certain parameters together for quick and easy access based on different
types of applications. See AppView Parameter Groups
information.
on page 150 for more
Conveyor
LanguageP030
Output Freqb001
Commanded Freqb002
Mixer
LanguageP030
Output Freqb001
Compressor
LanguageP030
Output Freqb001
Commanded Freqb002
Motor NP VoltsP031
Centrifugal Pump
LanguageP030
Output Freqb001
Commanded Freqb002
Motor NP VoltsP031
Motor NP HertzP032
Blower/Fan
LanguageP030
Output Freqb001
Commanded Freqb002
Motor NP VoltsP031
Motor NP HertzP032
Motor NP VoltsP031
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Commanded Freqb002
Output Currentb003
Motor NP VoltsP031
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Stop ModeP045
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Stop ModeP045
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Stop ModeP045
Start Source 1P046
Speed Reference1P047
DigIn TermBlk 02t062
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Maximum FreqP044
Stop ModeP045
Start Source 1P046
Speed Reference1P047
Relay Out1 Selt076
Analog Out Selt088
Analog Out Hight089
Anlg Out Setptt090
Start Source 1P046
Speed Reference1P047
Relay Out1 Selt076
Analog Out Selt088
Analog Out Hight089
Anlg Out Setptt090
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Anlg In4-20mA Lot095
Start Source 1P046
Speed Reference1P047
Relay Out1 Selt076
Analog Out Selt088
Analog Out Hight089
Anlg Out Setptt090
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Anlg In4-20mA Lot095
Stop ModeP045
Start Source 1P046
Speed Reference1P047
Relay Out1 Selt076
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Anlg In4-20mA Lot095
Anlg In4-20mA Hit096
Anlg In mA Losst097
Preset Freq 0A410
Auto Rstrt TriesA541
Auto Rstrt DelayA542
Anlg In4-20mA Hit096
Anlg In mA Losst097
Preset Freq 0A410
PID 1 Trim HiA456
PID 1 Trim LoA457
PID 1 Ref SelA459
PID 1 Fdback SelA460
PID 1 Prop GainA461
PID 1 Integ TimeA462
Anlg In4-20mA Hit096
Anlg In mA Losst097
Preset Freq 0A410
PID 1 Trim HiA456
PID 1 Trim LoA457
PID 1 Ref SelA459
PID 1 Fdback SelA460
PID 1 Prop GainA461
PID 1 Integ TimeA462
Anlg In mA Losst097
Slip Hz Meterd375
Preset Freq 0A410
Jog FrequencyA431
Jog Accel/DecelA432
S Curve %A439
Reverse DisableA544
Anlg In4-20mA Lot095
Anlg In4-20mA Hit096
Anlg In mA Losst097
Preset Freq 0A410
Stall Fault TimeA492
Start At PowerUpA543
Reverse DisableA544
Power Loss ModeA548
Half Bus EnableA549
PID 1 Diff RateA463
PID 1 SetpointA464
PID 1 DeadbandA465
PID 1 PreloadA466
Auto Rstrt TriesA541
Auto Rstrt DelayA542
Start At PowerUpA543
Reverse DisableA544
PID 1 Diff RateA463
PID 1 SetpointA464
PID 1 DeadbandA465
PID 1 PreloadA466
Auto Rstrt TriesA541
Auto Rstrt DelayA542
Start At PowerUpA543
Reverse DisableA544
Flying Start EnA545
76Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 77
Programming and ParametersChapter 3
Extruder
LanguageP030
Output Freqb001
Commanded Freqb002
Output Currentb003
Motor NP VoltsP031
Posit ionin g
LanguageP030
Output Freqb001
Commanded Freqb002
Motor NP VoltsP031
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Tex til e/ Fib er
LanguageP030
Output Freqb001
Commanded Freqb002
Motor NP VoltsP031
Motor NP HertzP032
Motor OL CurrentP033
(1) This AppView parameter group is specific to PowerFlex 525 drives only.
(1)
Motor NP HertzP032
Motor OL CurrentP033
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Motor NP FLAP034
Motor NP PolesP035
AutotuneP040
Accel Time 1P041
Decel Time 1P042
Minimum FreqP043
Maximum FreqP044
Stop ModeP045
Start Source 1P046
Speed Reference1P047
Stop ModeP045
Start Source 1P046
Speed Reference1P047
Relay Out1 Selt076
Analog Out Selt088
Analog Out Hight089
Anlg Out Setptt090
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Stp Logic 5L185
Stp Logic 6L186
Stp Logic 7L187
Stp Logic Time 0L190
Stp Logic Time 1L191
Stp Logic Time 2L192
Stp Logic Time 3L193
Stp Logic Time 4L194
Stp Logic Time 5L195
Stp Logic Time 6L196
Stp Logic Time 7L197
Step Units 0L200
Step Units 1L202
Step Units 2L204
Step Units 3L206
Step Units 4L208
Step Units 5L210
DigIn TermBlk 02t062
DigIn TermBlk 03t063
Opto Out1 Selt069
Opto Out2 Selt072
Relay Out1 Selt076
Anlg In 0-10V Lot091
Anlg In 0-10V Hit092
Anlg In4-20mA Lot095
Anlg In4-20mA Hit096
Anlg In mA Losst097
Anlg In4-20mA Lot095
Anlg In4-20mA Hit096
Anlg In mA Losst097
Slip Hz Meterd375
Speed Feedbackd376
Encoder Speedd378
Preset Freq 0A410
Stall Fault TimeA492
Motor Fdbk TypeA535
Step Units 6L212
Step Units 7L214
Slip Hz Meterd375
Speed Feedbackd376
Encoder Speedd378
Units Traveled Hd388
Units Traveled Ld389
Preset Freq 0A410
Preset Freq 1A411
Preset Freq 2A412
Preset Freq 3A413
Preset Freq 4A414
Preset Freq 5A415
Preset Freq 6A416
Preset Freq 7A417
Preset Freq 8A418
Jog FrequencyA431
Slip Hz Meterd375
Fiber Statusd390
Preset Freq 0A410
Jog FrequencyA431
Jog Accel/DecelA432
S Curve %A439
Reverse DisableA544
Power Loss ModeA548
Half Bus EnableA549
Bus Reg EnableA550
Encoder PPRA536
Pulse In ScaleA537
Ki Speed LoopA538
Kp Speed LoopA539
Power Loss ModeA548
Half Bus EnableA549
Jog Accel/DecelA432
DB ThresholdA438
S Curve %A439
Motor Fdbk TypeA535
Encoder PPRA536
Pulse In ScaleA537
Ki Speed LoopA538
Kp Speed LoopA539
Bus Reg EnableA550
Positioning ModeA558
Counts Per UnitA559
Enh Control WordA560
Find Home FreqA562
Find Home DirA563
Encoder Pos TolA564
Pos Reg FilterA565
Pos Reg GainA566
Max TraverseA567
Tra ver se I ncA5 68
Tra ver se D ecA 569
P JumpA570
Sync TimeA 571
Speed RatioA572
Custom Group
CustomView Parameter Group
PowerFlex 520-series drives include a CustomView™ parameter group for you to
store frequently used parameters for your application. See CustomView
Parameter Group on page 151 for more information.
This group can store up to 100 parameters.
Rockwell Automation Publication 520-UM001I-EN-E - July 201677
Page 78
Chapter 3Programming and Parameters
IMPORTANT
The frequency command can come from a number of sources. See Start and Speed Reference Control on page 49 for more information.
Output frequency present at T1, T2 & T3 (U, V & W). Does not include slip frequency.
ValuesDefault:Read Only
Min/Max:0.00/[Maximum Freq]
Display:0.01 Hz
b002 [Commanded Freq]Related Parameter(s): b001, b013, P043, P044, P048, P050, P052
Value of the active frequency command even if the drive is not running.
ValuesDefault:Read Only
Min/Max:0.00/[Maximum Freq]
Display:0.01 Hz
b003 [Output Current]
Output current present at T1, T2 & T3 (U, V & W).
ValuesDefault:Read Only
Min/Max:0.00/(Drive Rated Amps x 2)
Display:0.01 A
b004 [Output Voltage]Related Parameter(s): P031, A530, A534
Output voltage present at T1, T2 & T3 (U, V & W).
ValuesDefault:Read Only
Min/Max:0.0/Drive Rated Volts
Display:0.1V
b005 [DC Bus Voltage]
Filtered DC bus voltage level of the drive.
ValuesDefault:Read Only
Min/Max:0/1200VDC
Display:1VDC
b006 [Drive Status]Related Parameter(s): A544
Present operating condition of the drive.
ValuesDefault:Read Only
Min/Max:00000/11111
78Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Frequency Command SourceDigit 4
0 = Other (Digit 2 & 3 are used. Digit 4 is not shown.)
1 = Jog
2 = Purge
Not Used
Display reads... Description
2004Start source comes from Network Opt and Frequency source is Purge.
113Start source comes from Serial/DSI and Frequency source comes from PID1 Output.
155Start source and Frequency source comes from EtherNet/IP.
052Start source comes from DigIn TrmBlk and Frequency source from 0-10V Input.
011Start source comes from Keypad and Frequency source comes from Drive Pot.
A code that represents a drive fault. Codes appear in these parameters in the order they occur (b007
See Fault and Diagnostic Group for more information.
Active source of the Start Command and Frequency Command. Normally defined by the settings of P046, P048, P050 [Start Source x] and P047, P049, P051 [Speed Referencex].
See Start and Speed Reference Control
on page 49 for more information.
[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.
t062
, t063, t065-t068, L180-L187, A410-A425
ValuesDefault:Read Only
Min/Max:0000/2165
Display:0000
Rockwell Automation Publication 520-UM001I-EN-E - July 201679
Page 80
Chapter 3Programming and Parameters
IMPORTANT
Actual control commands may come from a source other than the control terminal block.
1 = Closed State, 0 = Open State
DigIn TBlk 1Digit 1
DigIn TBlk 2Digit 2
DigIn TBlk 3Digit 3
DB Trans On
(1)
Digit 4
(1) The DB Transistor “on” indication must have a 0.5 s hysteresis. It will turn on and stay
on for at least 0.5 s every time the DB transistor is turned on.
Not Used
1 = Closed State, 0 = Open State
DigIn TBlk 5Digit 1
DigIn TBlk 6Digit 2
DigIn TBlk 7
(1)
Digit 3
(1) Setting is specific to PowerFlex 525 drives only.
DigIn TBlk 8
(1)
Digit 4
Not Used
Basic Display Group (continued)
b013 [Contrl In Status]Related Parameter(s): b002, P044, P045
State of the digital terminal blocks 1...3 and DB transistor.
ValuesDefault:Read Only
Min/Max:0000/1111
Display:0000
b014 [Dig In Status]Related Parameter(s): t065-t068
State of the programmable digital inputs.
ValuesDefault:Read Only
Min/Max:0000/1111
Display:0000
b015 [Output RPM]Related Parameter(s): P035
Current output frequency in rpm. Scale is based on P035 [Motor NP Poles].
ValuesDefault:Read Only
Min/Max:0/24000 rpm
Display:1 rpm
b016 [Output Speed]Related Parameter(s): P044
Current output frequency in %. Scale is 0% at 0.00 Hz to 100% at P044 [Maximum Freq].
ValuesDefault:Read Only
Min/Max:0.0/100.0%
Display:0.1%
b017 [Output Power]Related Parameter(s): b018
Output power present at T1, T2 & T3 (U, V & W).
ValuesDefault:Read Only
Min/Max:0.00/(Drive Rated Power x 2)
Display:0.01 kW
80Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 81
Programming and ParametersChapter 3
Basic Display Group (continued)
b018 [Power Saved]Related Parameter(s): b017
Instantaneous power savings of using this drive compared to an across the line starter.
ValuesDefault:Read Only
Min/Max:0.00/655.35 kW
Display:0.01 kW
b019 [Elapsed Run time]Related Parameter(s): A555
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
ValuesDefault:Read Only
Min/Max:0/65535 x 10 hr
Display:1 = 10 hr
b020 [Average Power]Related Parameter(s): A555
Average power used by the motor since the last reset of the meters.
ValuesDefault:Read Only
Min/Max:0.00/(Drive Rated Power x 2)
Display:0.01 kW
b021 [Elapsed kWh]Related Parameter(s): b022
Accumulated output energy of the drive. When the maximum value of this parameter is reached, it resets to zero and b022 [Elapsed MWh] is incremented.
ValuesDefault:Read Only
Min/Max:0.0/100.0 kWh
Display:0.1 kWh
b022 [Elapsed MWh]Related Parameter(s): b021
Accumulated output energy of the drive.
ValuesDefault:Read Only
Min/Max:0.0/6553.5 MWh
Display:0.1 MWh
b023 [Energy Saved]Related Parameter(s): A555
Total energy savings of using this drive compared to an across the line starter since the last reset of the meters.
ValuesDefault:Read Only
Min/Max:0.0/6553.5 kWh
Display:0.1 kWh
b024 [Accum kWh Sav]Related Parameter(s): b025
Total approximate accumulated energy savings of the drive compared to using an across the line starter.
ValuesDefault:Read Only
Min/Max:0.0/6553.5 kWh
Display:0.1 = 10 kWh
Rockwell Automation Publication 520-UM001I-EN-E - July 201681
Total approximate accumulated cost savings of the drive compared to using an across the line starter.
[Accum Cost Sav] = [Average kWh cost] x [Accum kWh S av]
ValuesDefault:Read Only
Min/Max:0.0/6553.5
Display:0.1
b026 [Accum CO2 Sav]Related Parameter(s): A555
Total approximate accumulated CO2 savings of the drive compared to using an across the line starter.
ValuesDefault:Read Only
Min/Max:0.0/6553.5 kg
Display:0.1 kg
b027 [Drive Temp]
Present operating temperature of the drive heatsink (inside module).
ValuesDefault:Read Only
Min/Max:0/120 °C
Display:1 °C
b028 [Control Temp]
Present operating temperature of the drive control.
ValuesDefault:Read Only
Min/Max:0/120 °C
Display:1 °C
b029 [Control SW Ver]
Current drive firmware version.
ValuesDefault:Read Only
Min/Max:0.000/65.535
Display:0.001
82Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 83
Programming and ParametersChapter 3
IMPORTANT
The drive will fault on an F007 “Motor Overload” if the value of this parameter is exceeded based on class 10 motor overload protection according to NEC article
430 and motor over-temperature protection according to NEC article 430.126 (A) (2). UL 508C File 29572
Basic Program Group
P030 [Language]Language Support
Selects the language displayed. A reset or power cycle is required after selection is made.Keypad/
Sets the motor nameplate rated frequency.
ValuesDefault:60 Hz
Min/Max:15/500 Hz
Display:1 Hz
P033 [Motor OL Current]Related Parameter(s): t069, t072, t076, t081, A484, A485, A493
Sets the motor nameplate overload current. Used to determine motor overload conditions and can be set from 0.1 A to 200% of drive rated current.
ValuesDefault:Drive Rated Amps
Min/Max:0.0/(Drive Rated Amps x 2)
Display:0.1 A
Rockwell Automation Publication 520-UM001I-EN-E - July 201683
Page 84
Chapter 3Programming and Parameters
PF 525
Basic Program Group (continued)
P034 [Motor NP FLA]Related Parameter(s): P040
Sets the motor nameplate FLA. Used to assist the Autotune routine and motor control.
ValuesDefault:Based on Drive Rating
Min/Max:0.1/(Drive Rated Amps x 2)
Display:0.1 A
P035 [Motor NP Poles]Related Parameter(s): b015
Sets the number of poles in the motor.
ValuesDefault:4
Min/Max:2/40
Display:1
P036 [Motor NP RPM]
Stop drive before changing this parameter.
Sets the rated nameplate rpm of the motor. Used to calculate the rated slip of the motor. To reduce the slip frequency, set this parame ter closer to the motor syn chronous speed.
ValuesDefault:1750 rpm
Min/Max:0/24000 rpm
Display:1 rpm
P037 [Motor NP Power]
PowerFlex 525 only.
Sets the motor nameplate power. Used in PM regulator.
ValuesDefault:Drive Rated Power
Min/Max:0.00/Drive Rated Power
Display:0.01 kW
P038 [Voltage Class]
Stop drive before changing this parameter.
Sets the voltage class of 600V drives. Only applicable to 600V drives.
Options2 “480V”
When P039 [Torque Perf Mode] is set to 4 and A535 [Motor Fdbk Type] is set to 0, 1, 2 or 3, the drive is in open loop PM motor
control mode.
When P039 [Torque Perf Mode] is set to 4 and A535
[Motor Fdbk Type] is set to 4 or 5, the drive is in closed loop PM motor control
mode.
(1) Setting is specific to PowerFlex 525 drives only.
(2) Setting is available in PowerFlex 525 FRN 5.xxx and later.
84Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 85
Programming and ParametersChapter 3
IMPORTANT
All motor parameters in the Basic Program group must be set before running the routine. If a start command is not given (or a stop command is given) within
30 s, the parameter automati cally returns to a zero and an Autotune Fault occurs.
ATT EN TI ON : Rotation of the motor in an undesired direction can occur during this procedure. To guard against possible injury and/or equipment damage, it is
recommended that the motor be disconnected from the load before proceeding.
Enables a static (not spinning) or dynamic (motor spinning) autotune to automatically set the motor parameters. Set the parameter value to a one or two, then issue a valid “Start”
command to begin the routine. After the routine is complete the parameter resets to a zero. A failure (such as if a motor is not connected) results in an Autotune Fault.
It is recommended to perform a full rotate tune when using VVC mode.
Options0 “Ready/Idle” (Default)
1 “Static Tune”A temporar y command that initiates a non-rotational motor stator resistance test for the best possible automatic setting of A496
[IR Voltage Drop]. A start command is required following initiation of this setting. The parameter returns to 0 “Ready/Idle”
following the test, at which time another start transition is required operate the drive in normal mode. Used when motor cannot
be uncoupled from the load.
2 “Rotate Tune”A temporary command that initiates a “Static Tune” followed by a rotational test for the best possible automatic setting of A497
[Flux Current Ref]. A start command is required following initiation of this setting. The parameter returns to 0 “Ready/Idle”
following the test, at which time another start transition is required to operate the drive in normal mode. Important: Used when
motor is uncoupled from the load. Results may not be valid if a load is coupled to the motor during this procedure.
P041 [Accel Time 1]Related Parameter(s): P044, A439
Sets the time for the drive to accelerate from 0 Hz to P044 [Maximum Freq].
Accel Rate = [Maximum Freq] / [Accel Time x]
ValuesDefault:10.00 s
Min/Max:0.00/600.00 s
Display:0.01 s
P042 [Decel Time 1]Related Parameter(s): P044, A439
Sets the time for the drive to decelerate from P044 [Maximum Freq] to 0 Hz.
Decel Rate = [Maximum Freq] / Decel Time x]
ValuesDefault:10.00 s
Min/Max:0.00/600.00 s
Display:0.01 s
Rockwell Automation Publication 520-UM001I-EN-E - July 201685
Page 86
Chapter 3Programming and Parameters
IMPORTANT
This value must be greater than the value set in P043 [Minimum Freq].
P045 [Stop Mode]Related Parameter(s): t086, t087, A434, A435, A550
Determines the stopping mode used by the drive when a stop is initiated.
Options0 “Ramp, CF” (Default)Ramp to Stop. Stop command clears active fault.
1 “Coast, CF”Coast to Stop. Stop command clears active fault.
2 “DC Brake, CF”DC Injection Braking Stop. Stop command clears active fault.
3 “DC BrkAuto,CF”DC Injection Braking Stop with Auto Shutoff.
4“Ramp”Ramp to Stop.
5 “Coast”Coast to Stop.
6 “DC Brake”DC Injection Braking Stop.
7 “DC BrakeAuto”DC Injection Braking Stop with Auto Shutoff.
8 “Ramp+EM B,CF”Ramp to Stop with EM Brake Control. Stop command clears active fault.
9 “Ramp+EM Brk”Ramp to Stop with EM Brake Control.
10 “PointStp,CF”PointStop. Stop command clears
11 “PointStop”PointStop.
• Standard DC Injection Braking for value set in A434
[DC Brake Time].
OR
• Drive shuts off if the drive detects that the motor is stopped.
Stop command clears active fault.
• Standard DC Injection Braking for value set in A434
[DC Brake Time].
OR
• Drive shuts off if the drive detects that the motor is stopped.
Provides a method to stop at a constant distance instead of a fixed rate.
active fault.
When a Stop command is given, the distance required for the machine to travel to
standstill based on the programmed maximum speed and deceleration time is calculated.
If the drive is running slower than the maximum speed, the function will apply a calculated
deceleration time that allows the machine to travel to standstill in the same distance based
on the current speed.
It is recommended to use braking resistors or set A550
better performance.
[Bus Reg Enable] to 0 “Disabled” for
86Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 87
Programming and ParametersChapter 3
IMPORTANT
For all settings except when t064 [2-Wire Mode] is set to 1 “Level Sense”, the drive must receive a leading edge from the start input for the drive to start after a
stop input, loss of power, or fault condition.
Configures the start source of the drive. Changes to these inputs take effect as soon as they are entered. P046 [Start Source 1] is the factory default start source unless overridden.
See Start and Speed Reference Control
(1) Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or 25-COMM-P adapters as the star t source.
(2) Setting is specific to PowerFlex 525 drives only.
Selects the source of speed command for the drive. Changes to these inputs take effect as soon as they are entered. P047 [Speed Reference1] is the factory default speed reference
unless overridden.
See Start and Speed Reference ControlOptions1 “Drive Pot”[Speed Reference1] default
(1) Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or 25-COMM-P adapters as the speed reference.
(2) Setting is specific to PowerFlex 525 drives only.
on page 49 for more information.
(1)
(2)
on page 49 for more information.
(1)
(2)
(2)
(2)
(2)
(2)
[Start Source 3] default for PowerFlex 525
[Speed Reference3] default for PowerFlex 525
Referencing from A558 [Positioning Mode]
P052 [Average kWh Cost]Related Parameter(s): b025
Sets the average cost per kWh.
ValuesDefault:0.00
Min/Max:0.00/655.35
Display:0.01
Rockwell Automation Publication 520-UM001I-EN-E - July 201687
P030 [Language]C138 [EN Gateway Cfg 2]C159 [EN Data Out 3]
C121 [Comm Write Mode]C139 [EN Gateway Cfg 3]C160 [EN Data Out 4]
C122 [Cmd Stat Select]C140 [EN Gateway Cfg 4]C161 [Opt Data In 1]
C123 [RS485 Data Rate]C141 [EN Rate Cfg]C162 [Opt Data In 2]
C124 [RS485 Node Addr]C143 [EN Comm Flt Actn]C163 [Opt Data In 3]
C124 [Comm Loss Action]C144 [EN Idle Flt Actn]C164 [Opt Data In 4]
C126 [Comm Loss Time]C145 [EN Flt Cfg Logic]C165 [Opt Data Out 1]
C127 [RS485 Format]C146 [EN Flt Cfg Ref]C166 [Opt Data Out 2]
C128 [EN Addr Sel]C147 [EN Flt Cfg DL 1]C167 [Opt Data Out 3]
C129 [EN IP Addr Cfg 1]C148 [EN Flt Cfg DL 2]C168 [Opt Data Out 4]
C130 [EN IP Addr Cfg 2]C149 [EN Flt Cfg DL 3]C169 [MultiDrv Sel]
C131 [EN IP Addr Cfg 3]C150 [EN Flt Cfg DL 4]C171 [Drv 1 Addr]
C132 [EN IP Addr Cfg 4]C153 [EN Data In 1]C172 [Drv 2 Addr]
C133 [EN Subnet Cfg 1]C154 [EN Data In 2]C173 [Drv 3 Addr]
C134 [EN Subnet Cfg 2]C155 [EN Data In 3]C174 [Drv 4 Addr]
C135 [EN Subnet Cfg 3]C156 [EN Data In 4]C175 [DSI I/O Cfg]
C136 [EN Subnet Cfg 4]C157 [EN Data Out 1]GC [Parameters in Custom Group]
C137 [EN Gateway Cfg 1]C158 [EN Data Out 2]
Basic Program Group (continued)
P053 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameters to their factory de fault values. After a Reset command, the value of this parameter returns to zero.
Options0 “Ready/Idle” (Default)
1 “Param Reset”Does not reset custom groups, parameter P030 [Language], and communication parameters.
2 “Factory Rset”Restore drive to factory condition.
3 “Power Reset”Resets only power parameters. Can be used when swapping power modules.
4 “Module Reset”
(1) Setting is available in PowerFlex 525 FRN 5.xxx and later.
(2) Setting is available in PowerFlex 523 FRN 3.xxx and later.
(1) (2)
Power cycle of the drive, NO parameters are reset.
88Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 89
Terminal Block Group
PF 525
IMPORTANT
Digital Inputs have priority for frequency control when programmed as Preset Speed and are active.
See Start Source and Speed Reference Selection on page 49 for more information.
Programmable digital input. Changes to these inputs takes effect as soon as they are entered. If a digital input is set for a selection that is only usable on one input, no other input can
be set for the same selection.
Options0 “Not Used”Terminal has no function but can be read over network communications with b013
[Start Source 2] as control source to start the drive.
[Start Source 3] as control source to start the drive.
5 “Spd + Strt 2”[DigIn TermBlk 07] default.
Selects combination of P049 [Speed Reference2] and P048 [Start Source 2] as spe ed command with control source to start
the drive.
6 “Spd + Strt 3”Selects combination of P051
[Speed Reference3] and P050 [Start S ource 3] as speed command with control source to start
the drive.
7 “Preset Freq”
[DigIn TermBlk 05] and [DigIn TermBlk 06] default.
• Selects a preset frequency in Velocity mode (P047, P049, P051 [Speed Referencex] = 1...15). S ee A410...A425 [Preset Freq x].
(PF523: only for DigIn TermBlk 03, 05,
and 06)
• Selects a preset frequency and position in Positioning mode (P047, P049, P051 [Speed Referencex] = 16).
See L200...L214 [Step Units x] (only for PowerFlex 525 drives).
(PF525: only for DigIn TermBlk 05...08)
8“Jog”• When input is present, drive accelerates according to the value set in A432
A431 [Jog Frequency].
• When input is removed, drive ramps to a stop according to the value set in A432 [Jog Accel/Decel].
• A valid Start command will override this input.
9 “Jog Forward”[DigIn TermBlk 08] default.
Drive accelerates to A431 [Jog Frequency] according to A432 [Jog Accel/Decel] and ramps to a stop when input becomes
inactive. A valid Start command will override this input.
10 “Jog Reverse”Drive accelerates to A431
[Jog Frequency] according to A432 [Jog Accel/Decel] and ramps to a stop when input becomes
inactive. A valid Start command will override this input.
11 “Acc/Dec Sel2”
(1)
If active, determines which Accel/Decel time will be used for all ramp rates except jog.
Can be used with option 29 “Acc/Dec Sel3” for additional Accel/Decel times. See A442 [Accel Time 2] for more information.
12 “Aux Fault”When enabled, an F002
“Auxiliary Input” fault will occur when the input is removed.
13 “Clear Fault”When active, clears an active fault.
14 “RampStop,CF”Causes drive to immediately ramp to a stop regardless of how P045
15 “CoastStop,CF”Causes drive to immediately coast to a stop regardless of how P045
[Stop Mode] is set.
[Stop Mode] is set.
16 “DCInjStop,CF”Causes drive to immediately begin a DC Injection stop regardless of how P045
17 “MOP Up”Increases the value of A427
18 “MOP Down”Decreases the value of A427
19 “Timer Start”
20 “Counter In”
(1)
(1)
Clears and starts the timer function. May be used to control the relay or opto outputs.
Starts the counter function. May be used to control the relay or opto outputs.
21 “Reset Timer”Resets the internal active timer, d365
22 “Reset Countr”Resets the count in the accumulated internal active counter, d364
[MOP Freq] at the rate set in A430 [MOP Time].
[MOP Freq] at the rate set in A430 [MOP Time].
[Timer Status]. For more information, see Timer Function on page 211.
[Counter Status]. For more information, see Counter Func tion
on page 212.
23 “Rset Tim&Cnt”Resets both the internal active timer and accumulated internal active counter.
24 “Logic In 1”
(1)(2)
Logic function input number 1. May be used to control the relay or opto outputs (t076, t081 [Relay Outx Sel] and
t069, t072 [Opto Outx Sel], options 11...14). May be used in conjunction with StepLogic parameters L180...L187 [Stp Logic x].
25 “Logic In 2”
(1)(2)
Logic function input number 2. May be used to control the relay or opto outputs (t076, t081 [Relay Outx Sel] and
t069, t072 [Opto Outx Sel], options 11...14). May be used in conjunction with StepLogic parameters L180...L187 [Stp Logic x].
[Jog Accel/Decel] and ramps to the value set in
[Stop Mode] is set.
Rockwell Automation Publication 520-UM001I-EN-E - July 201689
Page 90
Chapter 3Programming and Parameters
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliar y
mechanical braking device must be used.
OptionDescription
29 11
00Acc/Dec 1
01Acc/Dec 2
10Acc/Dec 3
11Acc/Dec 4
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliar y
mechanical braking device must be used.
Options26 “Current Lmt2”
27 “Anlg Invert”Inverts the scaling of the analog input levels set in
28 “EM Brk Rlse”If EM brake function is enabled, this input releases the brake. See t086
29 “Acc/Dec Sel3”
30 “Precharge En”Forces drive into precharge state. Typically controlled by auxiliary contact on the disconnec t at the DC input to the drive. If this
31 “Inertia Dcel”Forces drive into Inertia Ride -Through state. The drive attempts to regulate the DC bus at the current level.
32 “Sync Enable”Must be used in order to hold the existing frequency when Sync Time is set to enable speed synchronization. When this input is
33 “Traverse Dis”When an input is programmed the traverse function is disabled while this input is ac tive. See A567
34 “Home Limit”
35 “Find Home”
36 “Hold Step”
(2)
37 “Pos Redefine”
38 “Force DC”If the drive is not running, causes the drive to apply a DC Holding current (A435
39 “Damper Input”When active, drive is allowed to run normally.
40 “Purge”
(1)
(2)
When active, A485 [Current Limit 2] determines the drive current limit level.
t091
[Anlg In 0-10V Lo] and t092 [Anlg In 0-10V Hi] or
t095 [Anlg In4-20mA Lo] and t096 [Anlg In4-20mA Hi].
[EM Brk Off Delay] for more information.
(1)
If active, determines which Accel/Decel time is used for all ramp rates except jog.
Used with option 11 “Acc/Dec Sel2” for the Accel/Decel times listed in this table.
input is assigned, it must be energized for the pre-charge relay to close and for the drive to run. If it is de-energized, the pre-
charge relay opens and the drive coasts to a stop.
released the drive accelerates to the commanded frequency in A571
[Sync Time].
[Max Traverse].
(2)
(2)
In Positioning mode, indicates the drive is at the home position. See Appendix E for more information on Positioning.
In Positioning mode, causes the drive to return to the Home position when a Start command is issued.
[Find Home Freq] and A563 [Find Home Dir] until the “Home Limit” input is activated. If it passes this point, it then
Uses A562
runs in the reverse direction at 1/10th the frequency of [Find Home Freq] until the “Home Limit” is activated again. As long as
this input is active, any start command causes the drive to enter the homing routine. Only functions if in Positioning mode. Once
the Find Home routine has finished, the drive stops. See Appendix E for more information on Positioning.
In Positioning mode, overrides other inputs and causes the drive to remain at its current step (running at zero speed once it
reaches its position) until released.
While in “Hold”, the drive ignores any input command which would normally result in a move to a new step. Timers continue to
run. Therefore, when the Hold is removed, the drive must see any required digital inputs transition (even if they already
transitioned during the hold), but it does not reset any timer. See Appendix E for more information on Positioning.
(2)
In Positioning mode, resets the home position to the current position of the machine. See Appendix E for more information on
Posi tionin g.
[DC Brake Level], ignoring A434 [DC Brake Time])
while the input is applied.
When inactive, drive is forced into sleep mode and is prevented from accelerating to command speed.
Starts the drive at A433 [Purge Frequency] regardless of the selected control source. Supersedes the keypad Control function as
well as any other control command to take control of the drive. Purge can occur, and is operational, at any time whether the
drive is running or stopped regardless of the selected logic source selection. If a valid stop (other than from comms or SW
enable) is present, the drive will not start on the purge input transition.
90Rockwell Automation Publication 520-UM001I-EN-E - July 2016
41 “Freeze-Fire”When inactive, will cause an immediate F094
“Function Loss” fault. Use to safely bypass the drive with an external switching
device.
42 “SW Enable”Works like an interlock that has to be active for the drive to run.
43 “SherPin1 Dis”Disables shear pin 1 but leaves shear pin 2 active. If A488
[Shear Pin 2 Level] is greater than 0.0 A, shear pin 2 is enabled.
44 Reserved
45 Reserved
46 Reserved
47 Reserved
Page 91
Programming and ParametersChapter 3
Drive Start Condition
Matrix for t062 and t063
t062 Setting
t063
Setting
3-Wire
Start
2-Wire
FWD
2-Wire
REV
Drive will
not start
OK
3-Wire
Dir
OKDrive will
not start
ATT EN TI ON : Hazard of injury exists due to unintended operation. When t064 [2-Wire Mode] is set to
option 1, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input for
the drive to run again. A Stop function is provided only when the Stop input is active (open).
ATT EN TI ON : When operating in 2-Wire Level Sense (Run Level), the PowerFlex 523 and PowerFlex 525
drive should only be controlled from the Digital Input Terminal Blocks. This should NOT be used with any
other DSI or Network device.
IMPORTANT
There is greater potential voltage on the output terminals when using this option.
Options48 “2-Wire FWD”
(only for DigIn TermBlk 02)
[DigIn TermBlk 02] default. Select 2-Wire FWD for this input.
Select this option and set P046
, P048 or P050 [Start Source x] to 2 “DigIn TrmBlk” to
configure [Start Source x] to a 2-wire run for ward mode. Also see t064 [2-Wire Mode] for
level trigger settings.
49 “3-Wire Start”
(only for DigIn TermBlk 02)
Select 3-Wire Start for this input.
Select this option and set P046, P048 or P050 [Start Source x] to 2 “DigIn TrmBlk” to
configure [Start Source x] to a 3-wire start mode.
50 “2-Wire REV”
(only for DigIn TermBlk 03)
[DigIn TermBlk 03] default. Select 2-Wire REV for this input.
Select this option and set P046, P048 or P050 [Start Source x] to 2 “DigIn TrmBlk” to
config ure [Star t Source x] to a 2-wire run reverse mode. Also see t064 [2-Wire Mode] for level
trigger settings.
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to
7 “Preset Freq”.
51 “3-Wire Dir”
(only for DigIn TermBlk 03)
Select 3-Wire Dir for this input.
Select this option and set P046, P048 or P050 [Start Source x] to 2 “DigIn TrmBlk” to change
the direction of [Start Source x].
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to
7 “Preset Freq”.
52 “Pulse Train”
(PF523: only for DigIn TermBlk 05)
(PF525: only for DigIn TermBlk 07)
(1) This function may be tied to one input only.
(2) Setting is specific to PowerFlex 525 drives only.
Select pulse train for this input.
Use P047, P049 and P051 [Speed Referencex] to select pulse input.
Jumper for DigIn TermBlk 05 or 07 Sel must be moved to Pulse In.
Programs the mode of trigger only for t062 [DigIn TermBlk 02] and t063 [DigIn TermBlk 03] when 2-wire option is being selected as P046, P048 or P050 [Start Source x].
Options0 “Edge Trigger” (Default)Standard 2-Wire operation.
1 “Level Sense”• I/O Terminal 01 “Stop” = Coast to stop. Drive will restart after a Stop command when:
– Stop is removed
and
– Start is held active
• I/O Terminal 03 “Run REV”
2 “Hi-Spd Edge”
• Outputs are kept in a ready-to-run state. The drive will respond to a Start command within 10 ms.
• I/O Terminal 01 “Stop” = Coast to stop.
• I/O Terminal 03 “Run REV”
3“Momentary”• Drive will start after a momentary input from either the Run FWD input (I/O Terminal 02) or the Run REV input (I/O Terminal
03).
• I/O Terminal 01 “Stop” = Stop according to the value set in P045
[Stop Mode].
Rockwell Automation Publication 520-UM001I-EN-E - July 201691
Page 92
Chapter 3Programming and Parameters
PF 525
OptionsSetting Output Changes State When...Hysteresis
0 “Ready/Fault”Opto outputs are active when power is applied. Indicates that the drive is ready for operation. Opto outputs are
inactive when power is removed or a fault occurs.
None
1 “At Frequency”Drive reaches commanded frequency.0.5 Hz above; 1.0 Hz below
2 “MotorRunning”Motor is receiving power from the drive.None
3 “Reverse”Drive is commanded to run in reverse direction.None
4 “Motor Overld”Motor overload condition exists.100 ms time delay on or off
5 “Ramp Reg”Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from
occurring.
100 ms time delay on or off
6 “Above Freq”Drive exceeds the frequency (Hz) value set in t070
or t073 [Opto Outx Level].100 ms time delay on or off
7 “Above Cur”Drive exceeds the current (% Amps) value set in t070
or t073 [Opto Outx Level].100 ms time delay on or off
8 “Above DCVolt”Drive exceeds the DC bus voltage value set in t070
or t073 [Opto Outx Level].100 ms time delay on or off
9 “Retries Exst”Value set in A541
[Auto Rstrt Tries] is exceeded.None
10 “Above Anlg V”Analog input voltage (0-10V input) exceeds the value set in t070
or t073 [Opto Outx Level].100 ms time delay on or off
11 “Above PF Ang”Power Factor angle exceeds the value set in t070 or t073 [Opto Outx Level].100 ms time delay on or off
12 “Anlg In Loss”Analog input loss has occurred. Program t094
[Anlg In V Loss] or t097 [Anlg In mA Loss] for desired action when
input loss occurs.
On, 2 mA / ±1V
Off, 3 mA / ±1.5V
13 “ParamCo ntrol”Output is directly controlle d by the state of the t070
or t073 [Opto Outx Level]. A value of 0 causes the output to
turn off. A value of 1 or greater in this parameter causes the output to turn on.
None
14 “NonRec Fault”• Va lue set i n A541
[Auto Rstrt Tries] is exceeded or
• A541 [Auto Rstrt Tries] is not enabled or
• A non-resettable fault has occurred.
None
15 “EM Brk Cntrl”EM Brake is energized. Program t087
[EM Brk On Delay] and t086 [EM Brk Off Delay] for desired ac tion.None
16 “Thermal OL”Relay energizes when thermal Motor overload counter is above the value set in t077
or t082 [Relay Outx Level]. It
also energizes if the drive is within 5 °C of the drive overheat trip point.
None
17 “Amb OverTemp”Relay energizes when control module over temperature occurs.None
18 “Local Active”Active when drive P046
, P048 or P050 [Start Source x] is in local keypad control.None
19 “Comm Loss”Active when communication is lost from any comm source with reference or control. None
20 “Logic In 1”An input is programmed as “Logic Input 1” and is active.None
21 “Logic In 2”An input is programmed as “Logic Input 2” and is active.None
22 “Logic 1 & 2”Both Logic inputs are programmed and active.None
23 “Logic 1 or 2”One or both Logic inputs are programmed and one or both is active.None
24 “StpLogic Out”Drive enters StepLogic step with Command Word set to enable Logic output.None
25 “Timer Out”Timer has reached the value set in t070
or t073 [Opto Outx Level] or not timing.None
26 “Counter Out”Counter has reached the value set in t070
or t073 [Opto Outx Level] or not counting.None
27 “At Position”Drive is in Positioning mode and has reached the commanded position. Tolerance is adjusted with A564
[Encoder
Pos Tol] .
–
28 “At Home”Drive is in Positioning mode and has reached the home position. Tolerance is adjusted with A564
Determines the on/off point for the digital outputs when t069 or t072 [Opto Outx Sel] is set to the values shown below.
ValuesDefault:0.0
Min/Max:0.0/9999.0
Display:0.1
t075 [Opto Out Logic]
PowerFlex 525 only.
Determines the logic (Normally Open/NO or Normally Closed/NC) of the digital outputs only.
ValuesDefault:0
Min/Max:0/3
Display:1
Rockwell Automation Publication 520-UM001I-EN-E - July 201693
Page 94
Chapter 3Programming and Parameters
PF 525
OptionsOutput Relay Changes State When...Hysteresis
0 “Ready/Fault”Relay changes state when power is applied. Indicates that the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.
None
1 “At Frequency”Drive reaches commanded frequency.0.5 Hz above; 1.0 Hz below
2 “MotorRunning”Motor is receiving power from the drive.None
3 “Reverse”Drive is commanded to run in reverse direction.None
4 “Motor Overld”Motor overload condition exists.100 ms time delay on or off
5 “Ramp Reg”Ramp regulator is modifying the programmed accel/ decel times to avoid an overcurrent or overvoltage fault from
occurring.
100 ms time delay on or off
6 “Above Freq”Drive exceeds the frequency (Hz) value set in t077
or t082 [Relay Outx Level].100 ms time delay on or off
7 “Above Cur”Drive exceeds the current (% Amps) value set in t077
or t082 [Relay Outx Level].100 ms time delay on or off
8 “Above DCVolt”Drive exceeds the DC bus voltage value set in t077
or t082 [Relay Outx Level].100 ms time delay on or off
9 “Retries Exst”Value set in A541
[Auto Rstrt Tries] is exceeded.None
10 “Above Anlg V”Analog input voltage (0-10V input) exceeds the value set in t077
or t082 [Relay Outx Level].100 ms time delay on or off
11 “Above PF Ang”Power Factor angle exceeds the value set in t077 or t082 [Relay Outx Level].100 ms time delay on or off
12 “Anlg In Loss”Analog input loss has occurred. Program t094
[Anlg In V Loss] or t097 [Anlg In mA Loss] for desired action when
input loss occurs.
On, 2 mA / ±1V
Off, 3 mA / ±1.5V
13 “ParamControl”Output will be directl y controlled by the state of the t077
or t082 [Relay Outx Level]. A value of 0 causes the output
to turn off. A value of 1 or greater in this parameter causes the output to turn on.
None
14 “NonRec Fault”• Va lue set i n A541
[Auto Rstrt Tries] is exceeded or
• A541 [Auto Rstrt Tries] is not enabled or
• A non-resettable fault has occurred.
None
15 “EM Brk Cntrl”EM Brake is energized. Program t087
[EM Brk On Delay] and t086 [EM Brk Off Delay] for desired ac tion.None
16 “Thermal OL”Relay energizes when thermal Motor overload counter is above the value set in t077
or t082 [Relay Outx Level]. It
also energizes if the drive is within 5°C of the drive overheat trip point.
None
17 “Amb OverTemp”Relay energizes when control module over temperature occurs.None
18 “Local ActiveActive when drive P046
, P048 or P050 [Start Source x] is in local keypad control.None
19 “Comm Loss”Active when communication is lost from any comm source with reference or control. None
20 “Logic In 1”
(1)
An input is programmed as “Logic Input 1” and is active.None
21 “Logic In 2”
(1)
An input is programmed as “Logic Input 2” and is active.None
22 “Logic 1 & 2”
(1)
Both Logic inputs are programmed and active.None
23 “Logic 1 or 2”
(1)
One or both Logic inputs are programmed and one or both is active.None
24 “StpLogic Out”
(1)
Drive enters StepLogic step with Command Word set to enable Logic output.None
25 “Timer Out”Timer has reached the value set in t077
or t082 [Relay Outx Level] or not timing.None
26 “Counter Out”Counter has reached the value set in t077
or t082 [Relay Outx Level] or not counti ng.None
27 “At Position”
(1)
Drive is in Positioning mode and has reached the commanded position. Tolerance is adjusted with A564 [Encoder
Pos Tol] .
–
28 “At Home”
(1)
Drive is in Positioning mode and has reached the home position. Tolerance is adjusted with A564 [Encoder Pos Tol]. –
29 “Safe-Off”
(1)
Both safe-off inputs are active.–
30 “SafeTqPermit”
(1)(2)
Both safe-off inputs are inactive (closed).–
31 “AutoRst Ctdn”
(1)(2)
Drive is counting down to an automatic restart.–
IMPORTANT
Value for t077 or t082 [Relay Outx Level] must be entered in percent of drive rated output
current.
IMPORTANT
Do not use if t093 [10V Bipolar Enbl] is set to 1 “Bi-Polar In”.
Determines the on/off point for the output relay when t076 or t081 [Relay Outx Sel] is set to the values shown below.
ValuesDefault:0.0
Min/Max:0.0/9999.0
Display:0.1
t079 [Relay 1 On Time]
t084 [Relay 2 On Time]
PowerFlex 525 only.
Sets the delay time before Relay energizes after required condition is met.
ValuesDefault:0.0 s
Min/Max:0.0/600.0 s
Display:0.1 s
t080 [Relay 1 Off Time]
t085 [Relay 2 Off Time]
PowerFlex 525 only.
Sets the delay time before Relay de-energizes after required condition ceases.
ValuesDefault:0.0 s
Min/Max:0.0/600.0 s
Display:0.1 s
t086 [EM Brk Off Delay]Related Parameter(s): P045
Sets the time the drive remains at minimum frequency before ramping up to the commanded frequency (and engaging the brake coil relay) if Electromechanical (EM) Brake Control
Mode is enabled with P045 [Stop Mode].
ValuesDefault:2.00 s
Min/Max:0.00/10.00 s
Display:0.01 s
Rockwell Automation Publication 520-UM001I-EN-E - July 201695
Page 96
Chapter 3Programming and Parameters
Frequency
Time
[Minimum Freq]
[EM Brk O Delay]
[EM Brk On Delay]
Stop
commanded
Start
commanded
EM Brk
de-energized (On)
Drive stopsEM Brk
energized (O)
Ramp accel
Ramp decel
OptionsOutput RangeMinimum Output ValueMaximum Output Value =
t089 [Analog Out High]
Filter
(1)
(1) Filter A is a single pole digital filter with a 162 ms time constant. Given a 0...100% step input from a steady state, the output of Filter A takes 500 ms to get to 95% of maximum, 810 ms to get to 99%,
Sets the time the drive remains at minimum frequency (after releasing the brake coil relay) before stopping if EM Brake Control Mode is enabled with P045 [Stop Mode].
ValuesDefault:2.00 s
Min/Max:0.00/10.00 s
Display:0.01 s
t088 [Analog Out Sel]Related Parameter(s): t090
The 0-10V, 0-20 mA or 4-2 0 mA analog output can be used to provide a signal proportional to several drive conditions. This parameter also selects which analog calibration parameters
(1)
to use.
ValuesDefault:0
Min/Max:0/23
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
Display:1
96Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 97
Programming and ParametersChapter 3
PF 525
Terminal Block Group (continued)
t089 [Analog Out High]
Scales the maximum output value (V or mA) when the source setting is at maximum.
ValuesDefault:100%
Min/Max:0/800%
Display:1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
t090 [Anlg Out Setpt]Related Parameter(s): t088
Sets the percentage of output desired when t088 [Analog Out Sel] is set to 6, 14 or 22 “Analog Setpoint”.
ValuesDefault:0.0%
Min/Max:0.0/100.0%
Display:0.1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
t091 [Anlg In 0-10V Lo]Re lated Parameter(s): P043, t092, t093
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent P043 [Minimum Freq].
Analog inversion can be accomplished by setting this value larger than t092 [Anlg In 0-10V Hi].
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, this parameter is ignored.
If t093ValuesDefault:0.0%
Min/Max:0.0/200.0%
Display:0.1%
(1)
(1)
t092 [Anlg In 0-10V Hi]Related Parameter(s): P044, t091, t093
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent P044 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than t091 [Anlg In 0-10V Lo].
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, the same value applies to positive and negative voltage.
Enables/disables bi-polar control. In bi-polar mode direction is commanded by the polarity of the voltage.
If bi-polar control is enabled, P043
[Minimum Freq] and t091 [Anlg In 0-10V Lo] are ignored.
Options0 “Uni-Polar In” (Default)0-10V only
1 “Bi-Polar In”±10V
Rockwell Automation Publication 520-UM001I-EN-E - July 201697
Page 98
Chapter 3Programming and Parameters
Terminal Block Group (continued)
t094 [Anlg In V Loss]Related Parameter(s): P043, P044, A426, A427
Sets the response to a loss of input. When t he 0-10V input (or –10 to +10V) is used for any reference, any input less than 1V is reported as a signal loss. Input must exceed 1.5V for the
signal loss condition to end.
If enabled, this function affects any input that is being used as a speed reference, PID reference or PID setpoint in the drive.
Options0 “Disabled” (Default)
Sets the percentage (based on 4-20 mA) of input current applied to the 4-20 mA analog input used to represent P043 [Minimum Freq].
Analog inversion can be accomplished by setting this value larger than t096 [Anlg In4-20mA Hi].
Sets the percentage (based on 4-20 mA) of input current applied to the 4-20 mA analog input used to represent P044 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than t095
ValuesDefault:100.0%
Min/Max:0.0/200.0%
Display:0.1%
t097 [Anlg In mA Loss]Related Parameter(s): P043, P044, A426, A427
Sets the response to a loss of input. When the 4-20mA input is used for any reference, any input less than 2 mA is reported as a signal loss. Input must exceed 3 mA for the signal loss
condition to end.
If enabled, this function affects any input that is being used as a speed reference or PID reference or PID setpoint in the drive.
98Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Page 99
Programming and ParametersChapter 3
ATT EN TI ON : Enabling the Sleep-Wake function can cause unexpected machine operation during the Wake mode. Equipment damage and/or personal injury
can result if this parameter is used in an inappropriate application. In addition, all applicable local, national and international codes, standards, regulations or
industry guidelines must be considered.
Terminal Block Group (continued)
t098 [Anlg Loss Delay]Related Parameter(s): t094, t097
Sets the length of time after power-up during which the drive detects no analog signal loss.
Response to an analog signal loss is set in t094 or t097 [Analog In x Loss].
ValuesDefault:0.0 s
Min/Max:0.0 /20.0 s
Display:0.1 s
t099 [Analog In Filter]
Sets the level of additional filtering of the analog input signals. A higher number increases filtering and decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2
= 4x filter, and so on).
ValuesDefault:0
Min/Max:0/14
Display:1
t100 [Sleep -Wake Sel]Related Parameter(s): t101, t102, t103
Drive “sleeps” if the appropriate analog input drops below the set t101 [Sleep Level] for the time set in t102 [Sleep Time] and the drive is running. When entering sleep mode the drive
ramps to zero and the run indicator on the keypad display flashes to indicate the drive is in “sleep” mode.
When the appropriate analog input rises above the set [Wake Level], the drive “wakes” and ramps to the commanded frequency.
Inversion can be accomplished by setting [Sleep Level] to a higher setting than t103
[Wake Level].
Options0 “Disabled” (Default)
1 “0-10V Input”Sleep enabled from 0-10V Analog Input 1
2 “4-20mA Input”Sleep enabled from 4-20 mA Analog Input 2
3 “Command Freq”Sleep enabled based on drive commanded frequency
t101 [Sleep Level]
Sets the analog input level the drive must reach to enter sleep mode.
ValuesDefault:10.0%
Min/Max:0.0/100.0%
Display:0.1%
t102 [Sleep Time]
Sets the analog input time the drive must stay below to enter sleep mode.
ValuesDefault:0.0 s
Min/Max:0.0/600.0 s
Display:0.1 s
t103 [Wake Level]
Sets the analog input level the drive must reach to wake from sleep mode.
ValuesDefault:15.0%
Min/Max:0.0/100.0%
Display:0.1%
Rockwell Automation Publication 520-UM001I-EN-E - July 201699
Page 100
Chapter 3Programming and Parameters
PF 525
PF 525
Terminal Block Group (continued)
t104 [Wake Time]
Sets the analog input time the drive must stay above to wake from sleep mode.
ValuesDefault:0.0 s
Min/Max:0.0/600.0 s
Display:0.1 s
t105 [Safety Open En]
PowerFlex 525 only.
Sets the action when both safety inputs (Safety 1 and Safety 2) are disabled (de-energized – no power is applied).
Options0“FaultEnable” (Default)
1 “FaultDisable”
t106 [SafetyFlt RstCfg]
PowerFlex 525 only.
(With FRN 5.xxx and later.)
Sets the method of resetting fault F111 “Safety Hardware” either by means of a power cycle or fault clear operation.
Options0 “PwrCycleRset” (Default)Reset fault F111 using power cycle.
1 “FltClr Reset”Reset fault F111 using fault clear mechanism without power cycle.
100Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.