321 Studios FLR085D36E, FLF110D60E, FH085D36E, FC085D36E, FLR140D60E User Manual

...
0 (0)

OIL FURNACE

INSTALLATION INSTRUCTIONS

 

MODELS

 

FH085D36E

FH110D48E

FH110D60E

FLF085D36E

FLF110D48E

FLF110D60E

FLR085D36E

FLR110D48E

FLR110D60E

FLR140D60E

FC085D36E

 

WARNING

READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION.

THIS INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION.

IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS.

FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH.

FOR YOUR SAFETY

DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.

IMPORTANT NOTICE

THIS FURNACE IS NOT INTENDED FOR USE AS A CONSTRUCTION HEATER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING PHASES OF A STRUCTURE IS CONSIDERED AS "OPERATION IN A CORROSIVE ATMOSPHERE" AND "UNUSUAL, NEGLIGENT OR IMPROPER USE" AND AS SUCH ARE CONSIDERED EXCLUSIONS BY THE BARD MANUFACTURING COMPANY LIMITED WARRANTY.

Bard Manufacturing Company

Manual:

2100-422B

Bryan, Ohio 43506

Supersedes:

2100-422A

Since 1914...Moving ahead just as planned.

File:

VOL. I, TAB 3

Date:

09-23-03

 

Copyright 2003

CONTENTS

Getting Other Information and Publications

......... 1

Installation and Operating Instructions

 

Equipment Selection ...............................................

2

Locating the Furnace ..............................................

2

Installing the Furnace .............................................

6

Duct Work ...............................................................

6

Installing a Cooling Unit ..........................................

6

Wiring ...............................................................

7

Oil Line Piping ......................................................

10

Beckett AFG Oil Burner ........................................

10

Beckett “CleanCut” Oil Pump ...............................

11

Beckett Solid State Igniter ....................................

11

Beckett R7184B Primary Control ..........................

11

Beckett R7184B Primary Operational Guide ........

12

Burner Set up and Adjustments ...........................

14

Short Form Adjustment Procedure .......................

16

Combustion Air Requirements ..............................

20

Louvers and Grilles ...............................................

25

Venting Options ....................................................

25

Thermostat ...........................................................

25

Filters

 

Upflow & Counterflow Filter Information .............

237

Lo-Boy Models – Filter Locations .......................

28

Maintenance

 

Lubrication ............................................................

29

Inspect Air Filter ....................................................

29

Final Inspection and Test ......................................

29

Service Hints ........................................................

29

Combination Combustion Chamber/Burner

 

Mounting System ..................................................

30

To Remove Burner Only .......................................

31

To Remove Entire Combustion Chamber

 

Mounting System ..................................................

31

Common Causes of Trouble .................................

32

Care of Finish .......................................................

32

Cleaning of the Heat Exchanger ...........................

32

Blower System Resistance Charts .................

33-34

Wiring Diagrams .............................................

35-37

TABLES

 

 

FIGURES

 

 

Table 1

Minimum Clearances .............................

2

Figure 1

FL/R Models Dimensions ...................

3

Table 2

Dimensions FLF/R Models ....................

3

Figure 2

FH Models Dimensions ......................

4

Table 3

Electrical Data ........................................

7

Figure 3

FC Models Dimensions ......................

5

Table 4

Furnace Data .......................................

14

Figure 4

Typical Unit Setup - FLF ....................

8

Table 5

Correlation of % of CO2, O2 and

19

Figure 5

Typical Flue Installation

9

 

Reserve Air ..........................................

 

Requirements - FLF ...........................

Table 6

No. 2 Fuel Oil Efficiency Chart .............

19

Figure 6

Typical Single Inside

 

Table 7

Recommended Start-Up Settings ........

19

 

Tank Installation ...............................

10

Table 8

Sq.Ft. Required as

 

Figure 7

Electronic Blower Control ................

13

Table 9

Unconfined Space ................................

22

Figure 8

Typical Smoke-CO2 Characteristic ...

17

Minimum Ventilation Openings .............

23

Figure 9

Pressure Gauge Connection to

 

Table 10

Temperature Rise Ranges, Limit

 

 

Pressure Gauge Port .......................

18

 

Control Settings, and

 

Figure 10

Electrode Adjustments .....................

20

 

Heating Blower Speeds ........................

26

Figure 11

Combination Air Boot Assembly ......

21

Table 11 Filter Sizes for Gas Furnaces ...............

27

Figure 12

All Air From Inside Building..............

22

 

 

 

Figure 13

All Air From Outdoors ......................

23

 

 

 

Figure 14

All Air From Outdoors Through

 

CHARTS

 

 

 

Ventilated Attic .................................

24

 

 

Figure 15

All Air From Outdoors - Inlet Air

 

Chart 1

FH085D36E Data

33

 

 

From Ventilated Crawl Space and

 

Chart 2

FH110D48E Data

33

 

 

 

Outlet Air to Ventilated Attic

24

Chart 3

FH110D60E Data

33

 

Figure 16

Typical Installation of 16x25x1

 

Chart 4

FLF/FLR085D36E Data

33

 

 

Filter Rack

27

Chart 5

FLF/FLR110D48E Data

33

 

Figure 17

Typical Installation of 20x25x1

 

Chart 6

FLF/FLR110D60E Data

33

 

 

Filter Rack ........................................

27

Chart 7

FLR140D60E Data ...............................

34

Figure 18

Filter Installation - Lo-Boy Models ...

28

Chart 8

FC085D36E Data .................................

34

Figure 19

Removal of Burner Only ..................

30

 

 

 

Figure 20

Removal of Entire Combustion

 

 

 

 

 

Chamber Mounting System .............

31

i

GETTING OTHER INFORMATION and PUBLICATIONS

These publications can help you install the furnace. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

National Fuel Gas Code ...........

ANSI Z223.1/NFPA54

National Electrical Code ......................

ANSI/NFPA 70

Standard for the Installation ..............

ANSI/NFPA 90A

of Air Conditioning and Ventilating Systems

Standard for Warm Air ......................

ANSI/NFPA 90B

Heating and Air Conditioning Systems

Standard for Chimneys, Fireplaces, Vents ... NFPA 211 and Solid Fuel Burning Appliances

Load Calculation for ..........................

ACCA Manual J

Residential Winter and Summer Air Conditioning

Duct Design for Residential ..............

ACCA Manual D

Winter and Summer Air Conditioning

and Equipment Selection

FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:

ACCA

Air Conditioning Contractors of America

 

1712 New Hampshire Ave. N.W.

 

Washington, DC 20009

 

Telephone: (202) 483-9370

 

Fax: (202) 234-4721

ANSI

American National Standards Institute

 

11 West Street, 13th Floor

 

New York, NY 10036

 

Telephone: (212) 642-4900

 

Fax: (212) 302-1286

ASHRAE American Society of Heating Refrigerating,

and Air Conditioning Engineers, Inc.

1791 Tullie Circle, N.E.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA

National Fire Protection Association

 

Batterymarch Park

 

P.O. Box 9101

 

Quincy, MA 02269-9901

 

Telephone: (800) 344-3555

 

Fax: (617) 984-7057

Manual 2100-422

Page 1

INSTALLATION and OPERATING INSTRUCTIONS

EQUIPMENT SELECTION

An accurate heating load calculation must be conducted using American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) or Air Conditioning Contractors of America (ACCA) manuals. Do not add a large safety factor above the calculated value. If the calculated heating load requirement exceeds the heating capacity rating of a given model, use only the next larger size available. Never increase by any more than absolutely necessary based upon available equipment heating capacities. Always select based upon heat capacity (output), never use input capacities.

NOTE: It is the personal responsibility and obligation of the purchaser to contract a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.

LOCATING THE FURNACE

When installing the furnace be sure to provide adequate space for easy service and maintenance. Locate the furnace as close to the chimney as practical, giving consideration to the accessibility of the oil burner, controls, and blower for service. Allow a minimum of 24 inches at front of furnace for servicing oil burner. Allow adequate room for filter and blower maintenance. Clearance from combustible material as stated on the furnace and repeated in Table 1 must be maintained. For damp basement installations, a raised concrete pad is recommended. This will help keep the bottom of the furnace dry and reduce the risk of rusting.

An oil burner must have a generous supply of combustion air to operate properly. The flow of combustion and ventilating air must not be obstructed from reaching the furnace. See “Combustion Air Requirements” section.

The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.

This unit is not designed for mobile home or trailer installations. Always install furnace in a level position.

TABLE 1

MINIMUM CLEARANCES

 

 

 

Minimum Installation Clearnaces — Inches

 

Minimum Service

 

 

 

Furnace

 

Plenum

1

Flue

 

Clearances

 

 

 

 

 

 

 

 

 

 

 

 

Model

Front

Back

 

Sides

Top

Sides

Duct

Pipe

Floor

Front

Back

Sides

 

 

 

 

 

 

 

 

 

 

 

 

 

FH085D36E

4

1

 

2

2

2

2

9

C

24

FH110D48E

4

1

 

2

2

2

2

9

C

24

FH110D60E

4

1

 

2

2

2

2

9

C

24

FLF085D36E

6

0

 

2

2

2

2

9

NC

24

24

18 *

FLR085D36E

6

18

 

2

2

2

2

9

NC

24

24

18 *

FLF110D48E

6

0

 

2

2

2

2

9

NC

24

24

18 *

FLF110D60E

6

0

 

2

2

2

2

9

NC

24

24

18 *

 

 

 

 

 

 

 

 

 

 

 

 

 

FLR110D48E

6

18

 

2

2

2

2

9

NC

24

24

18 *

FLR110D60E

6

18

 

2

2

2

2

9

NC

24

24

18 *

FLR140D60E

6

18

 

2

2

2

2

9

NC

24

24

18 *

FC085D36E

6

1

 

2

2

2

2

9

NC **

24

 

 

 

 

 

 

 

 

 

 

 

 

j For the first three (3) feet from plenum. After three (3) feet, no clearance required.

 

 

C

Combustible flooring

 

 

 

 

 

 

 

 

 

NC

Noncombustible floor

 

 

 

 

 

 

 

 

 

*Maintained on one side or the other to achieve filter access and/or blower service.

**Floor must be noncombustible. For furnace only installation can be installed on combustible flooring only when installed on special base part no. CFB7 available from factory. When air conditioning coil cabinet DCB23-22 is used then use special base part no. CFB23.

Manual 2100-422

Page 2

Page

Manual

3

422-2100

 

FLF/FLR 085, 110 AND 140 SPECIFICATION SHEET

 

TOP VIEW

J

RETURN

SUPPLY

 

DUCT

 

DUCT

D

G

 

F

E

 

"FLF" FLUE

REAR FLUE

KNOCKOUT

 

ON "FLR" MODELS

OPTIONAL

 

HIGH VOLTAGE

 

ENTRANCE

OPTIONAL

LOW VOLTAGE

ENTRANCE

H

OIL

ENTRANCE

OPTIONAL

FILTER OIL

DOOR ENTRANCE

FRESH AIR

KNOCKOUT

LEFT SIDE VIEW

FIGURE 1

FLF/R MODELS DIMENSIONS

TABLE 2

FLF/R MODELS DIMENSIONS (INCHES)

 

 

Cabinet

 

Plenum

Flue Conection

 

Air Filters

 

 

 

 

Openings

 

1

Model

A

B

 

C

D x E

D x F

Location

G

H

J

Size

 

No.

Number

Width

Depth

 

Height

Supply

Return

Dia.

 

Used

FLF085D36E

23

48.125

 

36.625

22x20

22x14

Front

6

31.625

5.125

16 x 20 x 1

 

1

FLR085D36E

23

48.125

 

36.625

22x20

22x14

Rear

6

31.625

5.125

16 x 20 x 1

 

1

FLF110D48E

23

48.125

 

40.625

22x20

22x14

Front

6

35.625

5.125

20 x 20 x 1

 

1

FLF110D60E

23

48.125

 

40.625

22x20

22x14

Front

6

35.625

5.125

20 x 20 x 1

 

1

FLR110D48E

23

48.125

 

40.625

22x20

22x14

Rear

6

35.625

5.125

20 x 20 x 1

 

1

FLR110D60E

23

48.125

 

40.625

22x20

22x14

Rear

6

35.625

5.125

20 x 20 x 1

 

1

FLR140D60E

26

50.250

 

47.625

25x20

25x16

Rear

6

42.125

- - -

20 x 25 x 1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

j Washable type filter 1” nom. thickness

"FLF" FLUE KNOCKOUT

A

B

 

 

"FLF" FLUE

 

KNOCKOUT

 

LOW VOLTAGE

 

ENTRANCE

C

HIGH VOLTAGE

 

ENTRANCE

 

OPTIONAL

 

OIL ENTRANCE

FRONT VIEW

RIGHT SIDE VIEW

MIS-1815 A

Page

Manual

4

422-2100

 

19 1/4"

 

RETURN

16"

OPENING

(CUT OUT)

 

LEFT SIDE VIEW

FIGURE 2

FH MODELS DIMENSIONS

TOP VIEW

 

 

21 7/8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19 7/8"

FLUE

KNOCKOUT

23"

FLUE

KNOCKOUT

OPTIONAL

HIGH VOLTAGE

ENTRANCE

OPTIONAL

LOW VOLTAGE

ENTRANCE

OPTIONAL

OIL

ENTRANCE

OIL

ENTRANCE

FRESH AIR

KNOCKOUT

VESTIBULE

DOOR

FH085 AND FH110

SUPPLY SPECIFICATION SHEET

OPENING

30 1/2"

FLUE

KNOCKOUT

REAR CLEANOUT

DOOR

HIGH

VOLTAGE

ENTRANCE

53" (FH085) 59" (FH110)

LOW VOLTAGE

ENTRANCE

OPTIONAL

OIL

ENTRANCE RETURN OPENING (CUT OUT)

FRONT VIEW

RIGHT SIDE VIEW

MIS-1814 A

 

 

FIGURE 3

FC085 MODEL DIMENSIONS

21 7/8"

FC085

 

 

 

 

19 7/8"

 

SPECIFICATION

 

 

 

 

SHEET

 

 

 

 

FLUE

KNOCKOUT

OPTIONAL

HIGH VOLTAGE

ENTRANCE

OPTIONAL

LOW VOLTAGE

ENTRANCE

OIL ENTRANCE

OPTIONAL

OIL ENTRANCE

FRESH AIR

KNOCKOUT

LEFT SIDE VIEW

RETURN

OPENING

SUPPLY

OPENING

30 1/2"

TOP VIEW

FLUE

23" KNOCKOUT

 

FLUE

 

KNOCKOUT

54 1/4"

REAR

 

CLEANOUT

 

DOOR

 

LOW VOLTAGE

 

ENTRANCE

 

HIGH VOLTAGE

 

ENTRANCE

FRONT VIEW

OPTIONAL

OIL ENTRANCE

 

RIGHT SIDE VIEW

18 1/8"

BOTTOM VIEW

 

19 1/8"

MIS-1826

 

Manual 2100-422

Page 5

INSTALLING THE FURNACE

INSTRUMENTS REQUIRED FOR PROPER SETUP OF THE FURNACE

It is important that a set of instruments capable of the following requirements be used for the setup of this furnace to ensure proper and safe operation:

1.Oil pump pressure gauge that measures up to 150 PSI.

2.Smoke gun to pull smoke samples from flue.

3.Draft gauge that will measure -.02” water column (W.C.)

4.Duct static pressure gauge 0-1.0” W.C. range.

5.Temperature gauge that can read from 50° F up to 700° F.

6.A gauge to measure CO2 or O2.

INSTALLATION

A typical installation is shown in Figures 4 and 5. All parts of the furnace installation (furnace, oil tank and piping systems, combustion and ventilation air, venting, etc.) must comply with NFPA31, Installation of Oil Burning Equipment -- latest edition. This drawing shows the typical connecting parts needed to correctly install this furnace. Make sure that all parts of the heating system comply with the local codes.

Check the furnace and your load calculation to verify that the unit is properly sized. (Refer to Equipment Selection” section on Page 2.)

The correct size of unit needed may be substantially smaller than the unit being replaced due to home improvements and technology advancements since the initial installation.

INADEQUATE SUPPLY AIR and/or RETURN AIR DUCT SYSTEMS

Short cycling because of limit control operation can be created by incorrectly designed or installed supply and/ or return air duct systems.

The duct systems must be designed using ASHRAE or ACCA design manuals and the equipment CFM and external static pressure ratings to insure proper air delivery capabilities.

On replacement installations, particularly if equipment is oversized, the duct systems can easily be undersized. Modifications may be required to assure that the equipment is operating within the approved temperature rise range when under full rated input conditions, and that no short cycling on limit controls is occurring.

DUCT WORK

The air distribution system should be designed and installed in conformance with manuals published by Air Conditioning Contractors of America (ACCA) as set forth in Manual D, or ASHRAE publications.

IMPORTANT

When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace This is to prevent drawing possible hazardous combustion products into the circulated air.

INSTALLING A COOLING UNIT

When the furnace is used in connection with a cooling unit*, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit, unless the damper is in the full heat or cool position.

*A cooling unit is an air conditioning coil, heat pump coil or chilled water coil.

When installing a cooling unit above an FH or FL (below on an FC) series furnace, the coil must be spaced far enough from the furnace outlet to assure proper operation of the furnace. Bard supplied coils, when used with Bard supplied coil cabinets, are automatically positioned.

For top discharge FH and FL models, when coils are installed without using Bard coil cabinets or coils of another brand are used, the coil drain pan should be located a minimum of two (2) inches above the top of the furnace cabinet. If a greater clearance is specified by the coil manufacturer then it would apply.

NOTE: IF DRAIN PAN IS ANYTHING OTHER THAN A STEEL PAN PARTICULAR ATTENTION MUST BE GIVEN TO THE INSTALLATION INSTRUCTIONS FOR THE COIL TO MAKE SURE IT IS ACCEPTABLE FOR USE WITH THESE OIL FURNACES HAVING MAXIMUM OUTLET AIR TEMPERATURE OF 200° F.

See CFM versus static pressure curves on pages 33-36 for additional information.

Manual 2100-422

Page 6

WIRING

FACTORY WIRING

All units are fully factory wired. Multispeed blowers are factory wired on high speed for cooling/manual fan operation. Heating speeds are wired for the largest input and may need lower speed for field installed low input nozzle. If replacement wire is necessary, use 105 degrees C minimum. See electrical data, Table 3.

FIELD WIRING

All wiring must conform to the National Electrical Code and all local codes. A separate fuse or breaker should be used for the furnace.

TABLE 3

ELECTRICAL DATA

 

 

 

Blower Motor

Burner Motor

 

Max. Time

 

 

 

Minimum

Delay Fuse

 

 

Total

HP

FLA

HP

FLA

Circuit

or HACR

Model

Volts-HZ-PH

Amps

Ampacity

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

FH085D36E

115-60-1

9.2

1/3

7.5

1/7

1.7

15

15

FH110D48E

115-60-1

12.2

1/2

10.5

1/7

1.7

16

20

 

 

 

 

 

 

 

 

 

FH110D60E

115-60-1

14.2

3/4

12.5

1/7

1.7

19

20

FLF085D36E

115-60-1

17.3

1/3

5.6

1/7

1.7

15

15

 

 

 

 

 

 

 

 

 

FLR085D36E

115-60-1

17.3

1/3

5.6

1/7

1.7

15

15

FLF110D48E

115-60-1

12.2

1/2

10.5

1/7

1.7

16

20

 

 

 

 

 

 

 

 

 

FLR110D48E

115-60-1

12.2

1/2

10.5

1/7

1.7

16

20

FLF100D60E

115-60-1

14.2

3/4

12.5

1/7

1.7

19

20

 

 

 

 

 

 

 

 

 

FLR100D60E

115-60-1

14.2

3/4

12.5

1/7

1.7

19

20

FLR140D60E

115-60-1

14.2

3/4

12.5

1/7

1.7

19

20

 

 

 

 

 

 

 

 

 

FC085D36E

115-60-1

7.3

1/3

5.6

1/7

1.7

15

15

Manual 2100-422

Page 7

321 Studios FLR085D36E, FLF110D60E, FH085D36E, FC085D36E, FLR140D60E User Manual

WARNING

ALL WIRING MUST

CONFORM TO THE ! NATIONAL ELECTRIC

CODE AND ALL LOCAL

CODES.

Left side high voltage (unit power) entrance

Left side low voltage (thermostat) entrance

Left side oil line entrance for opt. air boot

Left side oil line entrance

Oil line (see burner

pump inst. for hookup info.)

Air Boot knockout (optional)

Control panel (junction box in FH units)

FIGURE 4

TYPICAL UNIT SETUP

FLF UNIT SHOWN

TYPICAL UNIT

SETUP

(FLF UNIT SHOWN)

Right side high voltage

(unit power)

entrance Right side oil line

entrance

Inspection door

Right side low voltage (thermostat) entrance

To thermostat and optional A/C unit

To power source

Shut off switch (if not fused, power line must include fuse or circuit breaker)

Power Wires:

Black (HOT)

White (NEUTRAL)

Green (GROUND)

MIS-1836

Manual 2100-422

Page 8

L i n e d

C h i m n e y

Clean-out Door (keep closed)

FIGURE 5

TYPICAL FLUE INSTALLATION REQUIREMENTS FRONT FLUE LOWBOY MODEL SHOWN (REPRESENTS ALL MODELS)

Thimble

INSTALLER NOTE:

 

 

Follow all appropriate

 

standards for installing

 

needed venting system.

 

Draft Regulator

 

(Be sure to follow

 

installation inst.

1/4 inch per

supplied with

regulator).

1 foot rise

 

 

90° Rotatable

 

Flue Box on front

 

flue models

 

(remove appropriate

 

cabinet knockout).

 

Mounting screws

 

located under flue

 

box cover.

 

Flue Box

 

Cover

Optional

Flue

Locations

Oil Burner

Optional Fresh

Air Boot (remove MIS-1825 rect. knockout).

Manual 2100-422

Page 9

OIL LINE PIPING

First determine whether the pipe system is to be a single line system or a two line system. All connections must be absolutely air tight or you will have a malfunction of the burner. When installing the piping, a good oil filter should be installed close to the burner. A single line system is recommended for gravity feed.

A typical single inside tank installations shown in Figure 6. For installation details for this and other tank configurations, refer to NFPA31 -- latest edition. All tank and pipe setups must comply with NFPA31.

BECKETT AFG OIL BURNER

This furnace is equipped with a high static Beckett AFG oil burner which is designed to produce adequate draft in nearly any vertically vented application. The burner employs the latest time tested controls of the highest quality. The controls consist of a high voltage Beckett solid state igniter, a Beckett “CleanCut” oil pump with an integral solenoid valve, and a Beckett R7184B primary control.

FIGURE 6

TYPICAL SINGLE INSIDE TANK INSTALLATION

Vent Cap

2" Cap

2" Fill Pipe

1-1/4"

 

 

Return Line

Vent Pipe

 

 

 

 

 

 

 

 

Guage

Oil

 

 

Bushing,

 

 

2" x 1-1/2" or

Tank

 

 

 

 

1-1/4"

 

 

 

 

 

 

Gate Valve

 

 

 

3/8" x 4"

 

6"

 

nipple

 

 

 

 

 

 

3/8" x 3/8"

 

 

 

Adapter

 

 

 

3/8" O.D. Copper

 

 

 

Fuel Tubing

Legs (either 1-1/4"x10"

Bushing

Oil Filter

MIS-1823

or 1-1/2"x10" nipples)

Manual 2100-422

Page 10

Loading...