York WR300, WR240 User Manual

0 (0)

®

TECHNICAL GUIDE

SUNLINE MagnaDRY™

GAS/ELECTRIC SINGLE PACKAGE AIR CONDITIONERS

WR 180, 240 & 300

15 thru 25 NOMINAL TONS

11.9 EER (15 TONS), 11.0 EER (20 TONS),

10.0 EER (25 TONS)

262292-YTG-B-0107

DESCRIPTION

YORK Sunline MagnaDRY™ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.

All units include:

Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards

Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats

Scroll compressors

Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic

Permanently lubricated motors

Bottom or side air discharge configuration capability (field convertible)

Belt Drive Blower Motor with high static drive option

Constant supply air volume (CV) with optional variable air volume (VAV)

Manufactured under the quality standards of ISO9001

Simplicity® Control Board

Zero-25% fixed air damper with hood

Copper tube/aluminum fin coils

Hinged filter access and toolless latched doors

Rigging holes in base rails for lifting

Single point power connection

Complete factory package - tested, charged and wired

CSA agency approvals on all units

WARRANTY

One-year parts warranty

A Five-year parts warranty on the compressors and electric heat elements

Ten-year parts warranty on the gas-fired heat exchangers

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

262292-YTG-B-0107

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . .3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . .8 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . .9

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . .53

LIST OF FIGURES

Fig. #

Pg. #

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 REHEAT CONTROL BOARD . . . . . . . . . . . . . . . . . . . . . 6 3 REHEAT CONTROLS - PART 1. . . . . . . . . . . . . . . . . . . 7 4 REHEAT CONTROLS - PART 2. . . . . . . . . . . . . . . . . . . 7 5 WR180 MOISTURE REMOVAL - ALT. MODE. . . . . . 21 6 WR180 MOISTURE REMOVAL - NORMAL MODE. . 21 7 WR240 MOISTURE REMOVAL - ALT. MODE. . . . . . 22 8 WR240 MOISTURE REMOVAL - NORMAL MODE. . 22 9 WR300 MOISTURE REMOVAL - ALT. MODE. . . . . . 23

10 WR300 MOISTURE REMOVAL - NORMAL MODE. . 23

11 ALTITUDE/TEMPERATURE CONVERSION

FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

12 UNIT DIMENSIONS WR180, 240 & 300

(FRONT VIEW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 13 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . . 47

14 UNIT DIMENSIONS WR180, 240 & 300

(RAINHOOD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 15 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 49 16 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . . 49 17 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 50 18 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . 51 19 ROOF CURB DUCT OPENINGS DIMENSION . . . . . 51 20 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . . 51 21 TYPICAL FIELD WIRING . . . . . . . . . . . . . . . . . . . . . . 52

LIST OF TABLES

Tbl. #

Pg. #

1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . 11 2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . 11 3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 11 4 COOLING CAPACITIES FOR WR180 . . . . . . . . . . . . 12 5 COOLING CAPACITIES FOR WR240 . . . . . . . . . . . . 14 6 COOLING CAPACITIES FOR WR300 . . . . . . . . . . . . 16

7 COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8 COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Tbl. #

Pg. #

9 COOLING CAPACITIES FOR WR300 (ALTERNATE REHEAT MODE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

10 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . . 24

11 WR180 BLOWER PERFORMANCE - 15 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 26

12 WR180 BLOWER PERFORMANCE - 15 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 27

13 WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 28

14 WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 29

15 WR240 BLOWER PERFORMANCE - 20 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 30

16 WR240 BLOWER PERFORMANCE - 20 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 31

17 WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 32

18 WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 33

19 WR300 BLOWER PERFORMANCE - 25 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 34

20 WR300 BLOWER PERFORMANCE - 25 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 35

21 WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 36

22 WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 37

23 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 38 24 STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . . . . . . 38 25 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . . 38

26 WR ELECTRICAL DATA - STANDARD DRIVE

MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 39

27 WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 40

28 WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 41

29 WR ELECTRICAL DATA - STANDARD DRIVE

MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 42

30 WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 43

31 WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 44

32 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 33 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . . 45 34 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 46 35 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 48 36 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . . 50

2

Unitary Products Group

262292-YTG-B-0107

PRODUCT NOMENCLATURE

15-25 Ton Sunline MagnaDRY™ Model Number Nomenclature

W R 180 N24 A 2 A AA 1 0 1 2 4 A

Product Category

W = A/C, Single Pkg.,

R-22 w/6-Row Evap.

Product Identifier

R = 90.1 w/Reheat

Nominal Cooling Capacity

180 = 15 Ton

240 = 20 Ton

300 = 25 Ton

Heat Type and Nominal Heat Capacity

C00 = Cooling Only. No field installed electric heat

Gas Heat Options

N24 = 240 MBH Output Aluminized Steel

N32 = 320 MBH Output Aluminized Steel

S24 = 240 MBH Output Stainless Steel

S32 = 320 MBH Output Stainless Steel

Electric Heat Options

E18 = 18 KW

E36 = 36 KW

E54 = 54 KW

E72 = 72 KW

Airflow

A = Std. Drive

B = Std. Drive/Single Input Econo.

C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only)

D = Std. Drive/Motorized Damper N = Hi Static Drive

P = Hi Static Drive/Single Input Econo.

Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only)

R = Hi Static Drive/Motorized Damper 2 = Low Static Drive

3 = Low Static Drive/Single Input Econo.

4 = Low Static Drive/Single Input Econo./Power Exhaust (Downflow Only)

5 = Low Static Drive/Motorized Damper

Voltage

2 = 208/230-3-60

4 = 460-3-60

5 = 575-3-60

Product Style

A = Style A

Configuration Options (not required for all units)

These four digits will not be assigned until a quote is requested, or an order placed.

SS Drain Pan

CPC Controller, DFS, APS

Johnson Controller, DFS, APS

Honeywell Controller, DFS, APS

Novar Controller, DFS, APS

Simplicity IntelliComfort Controller

Simplicity IntelliComfort Controller w/ModLinc

Hot Gas Bypass (Standard on VAV, Optional on CV)

Variable Air Volume (VFD) - Not Available with Factory Installed BAS Options

Variable Air Volume (VFD With Manual Bypass) - Not Available with Factory Installed BAS Options Variable Air Volume (VFD-Ready for Customer Installed Drive)

2" Pleated filters 4" Pleated filters

BAS Ready Unit with Belimo Economizer

Double Wall Construction

Heat Reclaim Coil Options (2 or 3 Row, 1-5/8" or 2-1/8" Stub Out) (WJ and WR models only)

Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned

 

 

Product Generation

 

 

 

 

 

 

 

 

 

 

1 = First Generation

 

 

 

 

2 = Second Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional Options

 

 

 

 

 

 

Standard Cabinet

Hinged Filter Door & Toolless Access Cabinet

 

 

 

 

AA = None

BA = Hinged Filter Door & Toolless Access Panels

 

AB = Phase Monitor

BB = Phase Monitor, Hinged Filter Door & Toolless

 

AC = Coil Guard

Access Panels

 

AD = Dirty Filter Switch

BC = Coil Guard, Hinged Filter Door & Toolless

 

AE = Phase Monitor & Coil Guard

Access Panels

 

AF = Phase Monitor & Dirty Filter Switch

BD = Dirty Filter Switch, Hinged Filter Door &

 

AG = Coil Guard & Dirty Filter Switch

Toolless Access Panels

 

AH = Phase Monitor, Coil Guard & Dirty Filter Switch

BE = Phase Monitor & Coil Guard, Hinged Filter

 

RC = Coil Guard & American Flag

Door & Toolless Access Panels

 

TA = Technicoat Condenser Coil

BF = Phase Monitor & Dirty Filter Switch, Hinged

 

TJ = Technicoat Evaporator Coil

Filter Door & Toolless Access Panels

 

TS = Technicoat Evaporator & Condenser Coils

BG = Coil Guard & Dirty Filter Switch, Hinged Filter

 

 

 

 

 

Door & Toolless Access Panels

 

 

 

 

 

BH = Phase Monitor, Coil Guard & Dirty Filter Switch,

 

 

 

 

 

Hinged Filter Door & Toolless Access Panels

 

 

 

 

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be

 

 

located in digits 15-18.

 

 

 

 

 

 

 

 

 

 

Installation Options

 

 

 

 

 

 

 

A = No Options Installed

 

 

 

B = Option 1

 

 

C = Option 2

 

 

D = Options 1 & 2

 

 

E = Option 3

 

 

F = Option 4

 

 

G = Options 1 & 3

 

 

H = Options 1 & 4

 

 

J = Options 1, 2 & 3

 

 

K = Options 1, 2, & 4

 

 

L = Options 1,3 & 4

 

 

M = Options 1, 2, 3, & 4

 

 

N = Options 2 & 3

 

 

P = Options 2 & 4

 

 

Q = Options 2, 3, & 4

 

 

R = Options 3 & 4

 

 

S = Option 5

 

 

T = Options 1 & 5

 

 

U = Options 1, 3, & 5

 

 

V = Options 1, 4, & 5

 

 

W = Options 1, 3, 4, & 5

 

 

X = Options 3 & 5

 

 

Y = Options 4 & 5

 

 

Z = Options 3, 4 & 5

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

1 = Disconnect

 

 

 

2 = Non-Pwr'd Conv. Outlet

 

 

3 = Smoke Detector S.A.

 

 

4 = Smoke Detector R.A.

 

 

5 = Pwr'd Conv. Outlet

 

 

 

 

 

 

 

 

Unitary Products Group

3

262292-YTG-B-0107

FEATURES

All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.

All models are available with these “factory mounted” outdoor air damper options:

Single enthalpy economizer

Single enthalpy economizer with power exhaust

Motorized outdoor air damper

A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/ or static pressure requirement. A variable air volume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.

All compressors include scroll compressors and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.

Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0°F

outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.

Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA approved.

Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

4

Unitary Products Group

262292-YTG-B-0107

FIGURE 1: UNIT CUTAWAY

Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.

BAS Controls - York’s Magnum series units offer factory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.

REHEAT MODE SEQUENCE OF OPERATION

The reheat control board allows the user to select two different modes of operation via a jumper connection on the board. (See Figure 2.) Each mode is described below. Refer to Figures 2 - 4 when reading this section.

LOCATION OF VFD (Optional)

LOCATION OF VFD BYPASS (Optional)

“NORMAL” MODE

When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for cooling, it energizes the hot gas relay (HGR), which energizes the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and de-energizes the reheat coil bleed valve (SOL 1). The Y1 signal is passed to the unit control board (UCB), which engages circuit # 1, resulting in circuit #1 reheat mode operation.

When the room thermostat calls for first stage cooling, with or without a call for dehumidification, the RCB senses a signal through "Y1", de-energizing the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1, engaging circuit # 1, resulting in circuit #1 cooling mode operation.

When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit #1 and circuit #2 in the cooling mode.

Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.

Unitary Products Group

5

262292-YTG-B-0107

Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehumidification at "HUM".

The unit will not operate in the reheat mode if there is any call for heating.

On units with economizers, the unit will not operate in the reheat mode if there is a call for cooling and the economizer is operating as first stage of cooling.

All safety devices function as previously described.

"ALTERNATE” MODE

When the RCB detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2, and there is not a call for cooling, it energizes the HGR, which energizes the SOL 3, SOL 2, and de-energizes SOL 1. The unit then operates with circuit #1 in reheat mode and circuit #2 in cooling mode.

When the room thermostat calls for first stage cooling while there is still a call for dehumidification, no operational change is made. The call for cooling is ignored and the unit continues to operate with circuit #1 in reheat mode and circuit #2 in cooling mode.

When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and de-energizes the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1. Both circuits operate in the cooling mode.

Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.

Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is still a call for dehumidification at "HUM".

The unit will not operate in the reheat mode if there is any call for heating.

All safety devices function as previously described.

R

Y1

P4

Y2

K1

G

W1

K2

W2

OCC

K4

C

K3

COM

`

P6

 

 

P5

P3

 

 

 

 

 

 

 

 

HGRR

 

HGR

 

HUM

 

MODE

 

 

 

DEHUMIDISTAT

SELECTION

 

 

 

HARNESS

 

JUMPER

 

 

 

CONNECTION

FIGURE 2: REHEAT CONTROL BOARD

6

Unitary Products Group

York WR300, WR240 User Manual

262292-YTG-B-0107

UCB

RHB

UNIT CONTROL

REHEAT CONTROL

BOARD

BOARD

HUM

HUMIDIFY

TERMINAL

RHR

REHEAT

RELAY

RHTB

REHEAT

TERMINAL

BLOCK

FIGURE 3: REHEAT CONTROLS - PART 1

REHEAT

SOLENOID 1

REHEAT

 

REHEAT

SOLENOID 3

 

 

SOLENOID 2

 

 

UCB

UNIT CONTROL

BOARD

RHB

REHEAT

CONTROL

BOARD

FIGURE 4: REHEAT CONTROLS - PART 2

Unitary Products Group

7

 

262292-YTG-B-0107

 

 

FACTORY-INSTALLED OPTIONS

A ‘VFD-ready’ option provides the provisions for a cus-

SINGLE INPUT ELECTRONIC ENTHALPY

tomer-installed drive. The unit comes with a mounting

bracket installed in the Blower Access compartment which

ECONOMIZERS - Includes a slide-in / plug-in damper

may accommodate other vendor’s drives depending on

assembly with fully modulating spring-return motor

their size. In order to utilize the unit’s mounting bracket,

actuator capable of introducing up to 100% outdoor air

the maximum recommended drive dimensions are as fol-

with nominal 1% leakage type dampers.

lows:

The enthalpy system contains one sensor that monitors

For 5-hp motor applications ........................13” H x 6” W x 7” D

the outdoor air and determines when the air is cool

For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D

enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must

If the customer-installed drive will not fit in the allotted

be field-assembled before installing.

space, then it will have to be mounted within a NEMA-4

POWER EXHAUST - Our single economizer options are

enclosure for outside installation or inside the building on

a perpendicular wall not subjected to excessive tempera-

available with power exhaust. Whenever the outdoor air

ture, vibration, humidity, dust, corrosive gas, explosive

intake dampers are opened for free cooling, the exhaust

gas, etc.

fan will be energized to prevent the conditioned space

 

from being over-pressurized during economizer operation.

A terminal block located in the control box is provided for

The exhaust fan, motor and controls are installed and

field connection of the VFD controls.

wired at the factory. The rain hood must be assembled

HOT GAS BYPASS - To allow for low cooling load opera-

and installed in the field.

tion, a direct-acting pressure-modulating bypass control

MOTORIZED OUTDOOR AIR INTAKE DAMPER -

valve installed on the system #1 discharge line is used to

Includes a slide-in / plug-in damper assembly with a 2-

divert high temperature, high pressure refrigerant around

position, spring return motor actuator which opens to a

the TXV in order to maintain a desired minimum evaporator

pre-set position whenever the supply air blower is

pressure. HGBP is standard on all units with VAV and

operating and will drive fully closed when the blower unit

optional with CV units.

shuts down.

FILTER OPTIONS - Standard units are shipped with 2”

The rain hood is painted to match the basic unit and must

throw-away filters installed. 2” pleated and 4” pleated

be field assembled before installing.

filters are offered as a factory installed option.

PHENOLIC COATED EVAPORATOR, REHEAT, AND

CONVENIENCE OUTLET - This 110 volt outlet can be

CONDENSER COILS - Special coating process that

“powered” by the unit with a stepdown transformer or you

utilizes Technicoat 10-1" processes. Coating is applied by

may order the unit with a “non-powered” convenience

total immersion of the complete coil for maximum

outlet that can be wired in the field.

protection.

DISCONNECT SWITCH - For gas heat units and cooling

ELECTRIC HEATERS wired for single point power

units with electric heat, a HACR breaker sized to the unit

supply. These nickel chromium heater elements are

is provided. For cooling only units, a switch sized to the

provided with limit and automatic reset capability to

largest electric heat available for the particular unit is

prevent operation at excessive temperatures.

provided. Factory installed option only.

VARIABLE AIR VOLUME (VAV) - A factory-installed

DOUBLE WALL CONSTRUCTION - Optional double wall

variable frequency drive (VFD), mounted in the Blower

construction is available to provide smooth inner surfaces

Access compartment, is used to control the speed of the

for easy and effective cleaning to reduce risk of dirt and

indoor blower motor in order to maintain a constant static

bacterial accumulation. Fiberglass insulation is

pressure in the supply duct. A pressure transducer and

sandwiched between heavy gauge steel sheets to form a

VAV control board are mounted inside the control box.

durable, rigid casing to withstand higher working

The drive comes completely wired and pre-programmed

pressures and impact forces. The heavy-duty construction

from the factory.

provides excellent acoustic and thermal insulation and

An optional, factory-installed manual bypass switch avail-

eliminates erosion of insulation material and

able with factory-installed VFD can be found in the Blower

contamination of the air stream.

Motor Access compartment. The switch can be used to

• BAS - Building Automation System Controls

either route power to the VFD for modulating control of the

(available on two-system cooling product only).

blower motor, to bypass the drive and operate the motor

Simplicity® INTELLI-Comfort™ CONTROL - The York®

at full speed, or to power the drive (and not the motor) for

diagnostic purposes.

Simplicity® INTELLI-Comfort™ control is factory installed.

It includes a supply air sensor, a return air sensor, and an

Due to space limitations, VAV is not available with any of

outside air sensor. There are provisions for a field installed

the factory-installed BAS options described below, but is

dirty filter indicator switch, an air-proving switch, an Out-

available with ‘BAS-ready’ models. Terminal blocks are

side Air Humidity sensor, a Return Air Humidity sensor, an

provided in the control box for field wiring of the customer-

Inside IAQ sensor, and an Outside Air IAQ sensor. Con-

installed BAS.

 

8

Unitary Products Group

262292-YTG-B-0107

struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLIComfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

Simplicity® INTELLI-Comfort™ with ModLINC CONTROL - The York® Simplicity® INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.

Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

HIGH SPEED DRIVE - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.

DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

HINGED FILTER DOOR/”TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE: Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for toolless operation.

LOW SPEED DRIVE - Includes a motor change when high airflow is not required. (WR300 & WR240 only)

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field-assembled before installing.

Unitary Products Group

9

262292-YTG-B-0107

Power exhaust is not available as a field installed option.

ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air

pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

WOOD SKID - Allows unit to be handled with 90” forks.

CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

10

Unitary Products Group

262292-YTG-B-0107

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

RPM

BHP

63

125

 

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

 

10Ft.2

 

 

 

 

 

WR180

6,000

1.00

1,080

4.60

99

99

 

89

82

84

77

 

72

67

89

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WR240

8,000

1.00

1,120

6.65

102

102

 

92

85

87

80

 

75

70

92

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WR300

10,000

1.30

1160

12.5

108

108

 

98

91

93

86

 

81

76

98

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1

MODEL

MBH

EER2

IPLV3

COOLING ONLY

 

 

 

WR180C/E00

180

11.9

12.7

WR240C/E00

240

11.0

11.3

WR300C/E00

300

10.0

10.6

COOLING WITH GAS HEAT

 

 

 

WR180N/S

180

11.9

12.7

WR240N/S

240

11.0

11.3

WR300N/S

300

10.0

10.6

COOLING WITH ELECTRIC HEAT

 

 

WR180E18

180

11.9

12.7

WR180E36

180

11.9

12.7

WR180E54

178

11.7

12.5

WR180E72

178

11.7

12.5

WR240E18

240

11.0

11.3

WR240E36

240

11.0

11.3

WR240E54

238

10.8

11.1

WR240E72

238

10.8

11.1

WR300E18

300

10.0

10.6

WR300E36

300

10.0

10.6

WR300E54

298

9.8

10.4

WR300E72

298

9.8

10.4

1.Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/ 360.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.IPLV = Integrated Part Load Value.

TABLE 3: GAS HEAT RATINGS

MODEL

MBH INPUT

MBH OUTPUT

WR180N/S24

300

240

 

 

 

WR180N/S32

400

320

WR240N/S24

300

240

 

 

 

WR240N/S32

400

320

WR300N/S24

300

240

 

 

 

WR300N/S32

400

320

NOTE:All gas units are two-stage heating. First stage is 50% of total.

S.S.E. = Steady State Efficiency (80%) - output divided by input.

For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across electric heating elements or gas heat exchanger tubes.

Unitary Products Group

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

262292-YTG-B-0107

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 4: COOLING CAPACITIES FOR WR180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on Evaporator Coil

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

75°F

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

90

85

 

80

75

70

65

90

85

 

80

 

75

70

65

 

 

 

 

 

 

77

217

10.8

74

71

 

59

45

30

16

210

11.8

80

73

 

58

 

43

28

14

3750

72

200

10.5

115

100

 

86

72

57

43

193

11.6

114

99

 

85

 

70

55

40

67

184

10.2

156

128

 

113

99

84

70

177

11.3

148

126

 

111

 

96

82

67

 

 

 

 

 

62

165

9.9

163

153

 

132

117

103

88

160

11.0

159

152

 

130

 

116

101

86

 

77

227

11.0

100

83

 

66

48

31

14

219

11.9

99

81

 

64

 

47

29

12

4500

72

210

10.6

130

113

 

96

78

61

44

202

11.7

128

111

 

93

 

76

59

41

67

192

10.3

161

143

 

126

108

91

74

185

11.4

158

140

 

123

 

106

88

71

 

62

172

10.0

171

164

 

147

129

112

95

167

11.1

166

162

 

144

 

127

109

92

 

57

171

10.0

171

171

 

152

135

118

100

166

11.1

166

166

 

150

 

132

115

97

 

77

237

11.1

127

95

 

72

52

32

11

228

12.1

117

90

 

70

 

50

30

10

5250

72

219

10.8

146

126

 

105

85

65

45

210

11.8

143

123

 

102

 

82

62

42

67

201

10.4

165

159

 

139

118

98

78

192

11.5

168

155

 

135

 

115

94

74

 

62

180

10.1

178

175

 

161

141

121

101

174

11.3

173

171

 

158

 

138

118

98

 

57

178

10.1

178

178

 

168

148

127

107

173

11.2

173

173

 

164

 

144

124

104

 

77

247

11.2

153

107

 

79

56

32

9

237

12.2

136

99

 

76

 

53

31

8

6000

72

228

10.9

161

138

 

115

92

69

45

219

11.9

157

134

 

111

 

88

66

43

67

209

10.5

170

170

 

151

128

105

82

200

11.6

178

169

 

146

 

124

101

78

 

62

187

10.2

186

186

 

176

153

130

107

181

11.4

180

180

 

172

 

149

126

103

 

57

186

10.2

186

186

 

183

160

137

114

180

11.3

180

180

 

178

 

155

133

110

 

72

236

10.9

176

150

 

125

99

73

47

226

11.9

171

145

 

120

 

95

70

44

6750

67

217

10.6

184

187

 

164

138

112

86

207

11.7

185

181

 

158

 

133

108

82

62

194

10.3

193

193

 

188

162

136

110

187

11.4

186

186

 

182

 

157

131

106

 

 

 

 

 

57

193

10.2

193

193

 

191

166

140

114

186

11.3

186

186

 

185

 

160

135

109

 

72

245

10.9

191

163

 

134

106

77

49

233

12.0

184

157

 

129

 

101

74

46

7500

67

224

10.6

199

199

 

177

148

120

91

213

11.7

192

192

 

170

 

142

114

87

62

201

10.3

199

199

 

199

171

142

114

193

11.4

192

192

 

192

 

164

137

109

 

 

 

 

 

57

200

10.3

200

200

 

200

171

143

114

192

11.4

192

192

 

192

 

165

137

109

 

 

 

 

 

95°F

 

 

 

 

 

 

 

105°F

 

 

 

 

 

77

203

12.8

87

72

 

57

42

27

12

195

14.3

77

69

 

53

 

38

22

6

3750

72

186

12.6

113

98

 

83

68

53

38

179

14.1

111

96

 

80

 

64

49

33

67

170

12.4

139

124

 

109

94

79

64

164

13.9

144

122

 

107

 

91

75

60

 

 

 

 

 

62

155

12.1

155

152

 

129

114

99

84

151

13.7

148

149

 

125

 

109

94

78

 

77

211

12.9

97

80

 

62

45

27

10

202

14.4

95

77

 

59

 

41

23

5

4500

72

194

12.7

126

109

 

91

74

56

39

186

14.2

124

106

 

88

 

70

52

34

67

177

12.5

155

137

 

120

103

85

68

170

14.0

153

135

 

117

 

99

81

63

 

62

161

12.3

161

159

 

142

124

107

89

157

13.8

155

155

 

137

 

119

101

83

 

57

161

12.2

161

161

 

147

129

112

95

156

13.7

156

156

 

141

 

123

105

87

 

77

219

13.0

108

88

 

68

48

28

8

209

14.5

113

84

 

64

 

44

23

3

5250

72

202

12.8

139

119

 

99

79

59

39

192

14.3

136

116

 

96

 

75

55

35

67

184

12.6

171

151

 

131

111

91

71

175

14.1

162

148

 

127

 

107

87

66

 

62

168

12.4

168

167

 

155

135

115

95

162

13.8

162

161

 

149

 

129

109

88

 

57

168

12.3

168

168

 

160

140

120

100

162

13.8

162

162

 

154

 

134

113

93

 

77

228

13.2

119

96

 

74

51

29

6

216

14.6

131

92

 

69

 

47

24

1

6000

72

209

13.0

153

130

 

108

85

63

40

199

14.4

149

126

 

104

 

81

58

35

67

191

12.7

186

164

 

141

119

96

74

181

14.2

167

161

 

138

 

115

92

70

 

62

174

12.5

174

174

 

167

145

122

100

168

13.9

167

167

 

162

 

139

116

94

 

57

174

12.4

174

174

 

173

151

128

106

167

13.9

167

167

 

166

 

144

121

98

 

72

216

13.0

165

140

 

116

91

66

42

204

14.4

160

136

 

111

 

86

62

37

6750

67

197

12.8

186

174

 

152

127

103

78

187

14.2

172

169

 

148

 

123

99

74

62

179

12.5

179

179

 

176

151

127

102

172

13.9

172

172

 

169

 

145

120

95

 

 

 

 

 

57

179

12.5

179

179

 

179

154

130

105

172

13.9

172

172

 

172

 

147

122

98

 

72

222

13.0

177

151

 

124

97

70

43

210

14.4

172

145

 

119

 

92

65

39

7500

67

203

12.8

185

185

 

163

136

109

82

192

14.2

177

177

 

158

 

131

105

78

62

185

12.5

185

185

 

185

158

131

104

177

13.9

177

177

 

177

 

150

124

97

 

 

 

 

 

57

185

12.5

185

185

 

185

158

131

104

177

13.9

177

177

 

177

 

150

123

97

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity

12

Unitary Products Group

262292-YTG-B-0107

TABLE 4: COOLING CAPACITIES FOR WR180 (CONTINUED)

Air on Evaporator Coil

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

77

187

15.8

73

66

50

34

17

-

179

17.3

74

60

47

30

13

-

3750

72

172

15.6

110

93

77

61

44

28

165

17.1

108

91

74

57

40

23

67

157

15.4

146

120

104

88

71

55

151

16.9

142

118

101

84

67

50

 

 

62

147

15.2

147

147

121

104

88

72

143

16.7

145

143

117

100

83

66

 

77

193

15.9

92

74

55

36

18

-

184

17.3

92

70

51

32

13

-

4500

72

177

15.7

122

103

84

66

47

29

169

17.1

119

100

81

62

43

24

67

162

15.5

151

133

114

95

77

58

155

16.9

146

130

111

92

73

54

 

62

152

15.2

151

151

133

114

96

77

147

16.7

147

146

128

109

90

71

 

57

151

15.2

151

151

136

117

99

80

146

16.6

146

146

130

111

92

73

 

77

198

15.9

111

81

60

39

18

-

188

17.4

111

80

56

35

14

-

5250

72

183

15.7

133

113

92

71

51

30

173

17.2

130

109

88

67

46

25

67

167

15.5

156

145

124

103

83

62

159

17.0

150

142

121

100

79

58

 

62

156

15.3

156

156

144

124

103

82

151

16.8

149

149

139

118

97

76

 

57

156

15.2

156

156

148

127

106

86

150

16.7

150

150

141

120

99

78

 

77

204

16.0

130

88

65

42

19

-

193

17.4

130

90

60

37

14

-

6000

72

188

15.8

145

122

99

77

54

31

177

17.2

142

118

95

72

49

26

67

172

15.6

160

157

134

111

88

66

162

17.0

153

147

131

108

84

61

 

62

161

15.4

160

160

156

133

110

87

154

16.8

153

153

151

127

104

81

 

57

160

15.3

160

160

160

137

114

91

154

16.7

154

154

153

130

107

84

 

72

193

15.8

156

131

106

82

57

32

182

17.2

151

127

102

77

52

28

6750

67

176

15.6

165

163

144

119

94

69

166

17.0

157

154

139

115

90

65

62

165

15.4

165

165

163

138

113

89

158

16.8

157

157

156

131

107

82

 

 

57

165

15.3

165

165

164

140

115

90

157

16.7

157

157

157

133

107

83

 

72

198

15.8

167

140

113

87

60

34

186

17.1

161

135

108

82

55

29

7500

67

181

15.6

169

169

153

126

100

73

170

16.9

161

161

148

122

95

69

62

169

15.3

169

169

169

143

116

90

162

16.7

161

161

161

135

109

82

 

 

57

169

15.2

169

169

169

143

116

89

161

16.6

161

161

161

136

108

82

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity

Unitary Products Group

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

262292-YTG-B-0107

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 5: COOLING CAPACITIES FOR WR240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on Evaporator Coil

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

75°F

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

90

85

 

80

75

70

65

90

85

 

80

 

75

70

65

 

 

 

 

 

 

77

287

15.1

117

99

 

80

62

43

25

278

16.4

112

96

 

77

 

58

39

20

5000

72

263

14.6

152

134

 

115

96

78

59

254

16.0

150

131

 

112

 

93

74

55

67

238

14.2

187

168

 

150

131

113

94

230

15.6

187

165

 

146

 

127

108

89

 

 

 

 

 

62

219

13.8

215

198

 

176

157

139

120

212

15.3

210

198

 

172

 

153

134

115

 

77

304

15.2

133

111

 

89

67

45

23

294

16.5

130

108

 

85

 

63

41

19

6000

72

278

14.8

171

150

 

128

106

84

62

269

16.1

169

146

 

124

 

102

79

57

67

252

14.3

210

188

 

166

144

122

100

243

15.7

207

185

 

162

 

140

118

95

 

62

232

14.0

228

217

 

195

173

151

129

224

15.4

222

214

 

191

 

169

147

124

 

57

229

13.8

229

227

 

205

183

161

139

222

15.2

222

221

 

199

 

177

154

132

 

77

320

15.4

149

123

 

98

73

47

22

310

16.7

148

120

 

94

 

68

43

17

7000

72

293

14.9

190

165

 

140

115

90

64

283

16.3

187

162

 

136

 

111

85

59

67

265

14.4

233

207

 

182

157

132

107

256

15.9

226

204

 

179

 

153

127

102

 

62

244

14.1

241

235

 

214

189

164

138

236

15.5

234

230

 

210

 

185

159

134

 

57

241

13.9

241

240

 

225

200

175

149

234

15.3

234

234

 

219

 

193

167

142

 

77

337

15.5

165

135

 

107

78

50

21

325

16.8

167

131

 

102

 

74

45

16

8000

72

308

15.1

210

181

 

153

124

96

67

297

16.4

206

178

 

149

 

120

91

62

67

279

14.6

254

227

 

199

170

142

113

269

16.0

246

224

 

195

 

166

137

108

 

62

257

14.2

254

254

 

233

205

176

148

248

15.7

246

246

 

230

 

201

172

143

 

57

254

14.1

254

254

 

245

217

188

160

246

15.5

246

246

 

239

 

210

181

152

 

72

302

15.0

213

184

 

155

126

97

69

291

16.4

209

180

 

151

 

122

93

64

8500

67

274

14.5

249

230

 

202

173

144

115

264

16.0

241

227

 

198

 

169

140

110

62

252

14.2

249

249

 

239

210

181

152

243

15.6

241

241

 

233

 

204

174

145

 

 

 

 

 

57

249

14.0

249

249

 

245

216

187

158

241

15.4

241

241

 

237

 

208

179

150

 

72

296

14.9

216

187

 

157

128

99

70

285

16.3

212

183

 

153

 

124

95

65

9000

67

268

14.4

244

224

 

205

176

147

118

258

15.9

236

231

 

201

 

172

142

113

62

247

14.1

244

244

 

244

215

186

157

238

15.6

236

236

 

236

 

207

177

148

 

 

 

 

 

57

244

13.9

244

244

 

244

215

186

157

236

15.3

236

236

 

236

 

207

177

148

 

 

 

 

 

95°F

 

 

 

 

 

 

 

105°F

 

 

 

 

 

77

270

17.6

105

93

 

73

54

35

15

255

19.4

103

89

 

70

 

50

31

11

5000

72

246

17.3

147

127

 

108

89

69

50

234

19.1

143

124

 

104

 

85

65

46

67

222

17.0

188

162

 

143

123

104

84

212

18.8

183

158

 

139

 

119

100

80

 

 

 

 

 

62

206

16.7

205

197

 

169

149

130

111

195

18.5

192

190

 

164

 

144

125

105

 

77

285

17.8

127

104

 

82

59

36

14

269

19.6

127

101

 

78

 

55

32

9

6000

72

259

17.5

166

143

 

120

97

75

52

246

19.3

162

139

 

116

 

93

70

48

67

234

17.2

204

181

 

159

136

113

91

224

19.0

197

177

 

155

 

132

109

86

 

62

217

16.8

216

210

 

188

165

142

120

206

18.7

204

202

 

183

 

160

137

114

 

57

216

16.6

216

216

 

193

170

147

125

205

18.1

205

205

 

185

 

162

139

117

 

77

299

17.9

149

116

 

90

64

38

12

283

19.8

150

112

 

86

 

59

33

7

7000

72

273

17.6

184

158

 

132

106

80

54

259

19.5

180

154

 

128

 

102

76

49

67

247

17.3

220

201

 

175

149

123

97

236

19.2

211

197

 

170

 

144

118

92

 

62

228

17.0

227

224

 

207

181

155

129

217

18.8

216

214

 

201

 

175

149

123

 

57

227

16.7

227

227

 

212

186

160

134

216

18.3

216

216

 

204

 

178

152

125

 

77

314

18.1

171

128

 

98

69

40

10

297

19.9

173

123

 

94

 

64

34

5

8000

72

286

17.8

203

174

 

145

115

86

56

272

19.6

199

169

 

140

 

110

81

51

67

259

17.5

236

220

 

191

162

132

103

248

19.3

225

216

 

186

 

157

127

97

 

62

239

17.1

238

238

 

226

196

167

138

228

19.0

226

226

 

220

 

190

161

131

 

57

238

16.9

238

238

 

232

203

173

144

226

18.4

226

226

 

223

 

193

164

134

 

72

280

17.7

206

177

 

147

117

88

58

266

19.6

202

172

 

143

 

113

83

53

8500

67

253

17.4

232

224

 

194

165

135

105

242

19.3

220

212

 

190

 

160

130

100

62

234

17.1

233

233

 

227

197

168

138

223

18.9

222

222

 

218

 

188

159

129

 

 

 

 

 

57

233

16.8

233

233

 

230

200

171

141

222

18.4

222

222

 

220

 

190

160

130

 

72

274

17.7

209

179

 

150

120

90

60

261

19.5

206

175

 

145

 

115

85

55

9000

67

248

17.4

227

227

 

197

168

138

108

237

19.2

216

209

 

193

 

163

133

103

62

229

17.1

228

228

 

228

198

168

139

218

18.9

217

217

 

217

 

186

156

126

 

 

 

 

 

57

228

16.8

228

228

 

228

198

169

139

217

18.3

217

217

 

217

 

187

157

126

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity

14

Unitary Products Group

262292-YTG-B-0107

TABLE 5: COOLING CAPACITIES FOR WR240 (CONTINUED)

Air on Evaporator Coil

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

77

240

21.3

101

86

66

46

27

-

225

23.1

100

81

63

43

23

-

5000

72

221

21.0

140

120

101

81

61

42

208

22.8

136

117

97

77

57

37

67

202

20.7

179

155

135

115

96

76

192

22.5

174

151

131

111

92

72

 

 

62

185

20.4

184

184

159

139

120

100

175

22.2

175

174

154

134

115

95

 

77

253

21.4

126

97

74

51

28

-

238

23.3

126

93

70

47

23

-

6000

72

233

21.1

158

135

112

89

66

43

220

23.0

154

131

108

85

62

38

67

214

20.8

190

173

150

127

104

81

203

22.7

183

169

146

123

100

77

 

62

195

20.5

194

194

177

154

131

108

185

22.3

184

184

172

149

126

103

 

57

194

19.7

194

194

177

154

131

108

184

21.2

184

184

170

147

123

100

 

77

267

21.6

151

108

81

55

29

-

250

23.4

151

105

77

50

24

-

7000

72

246

21.3

176

150

124

97

71

44

232

23.1

172

146

119

93

66

39

67

225

21.0

202

192

166

139

113

87

214

22.8

192

188

161

135

108

82

 

62

206

20.7

205

205

196

169

143

116

195

22.5

193

194

190

163

137

110

 

57

205

19.8

205

205

196

169

143

117

194

21.4

194

194

187

161

134

108

 

77

280

21.8

176

119

89

59

29

-

263

23.6

176

117

84

54

24

-

8000

72

258

21.5

195

165

135

105

76

46

244

23.3

190

160

130

100

70

41

67

236

21.1

213

211

181

152

122

92

225

23.0

204

204

177

147

117

87

 

62

216

20.8

215

215

214

184

154

124

205

22.7

204

204

205

178

148

118

 

57

215

20.0

215

215

214

184

154

125

204

21.5

204

204

204

175

145

115

 

72

252

21.4

198

168

138

108

78

48

238

23.2

194

164

134

103

73

43

8500

67

231

21.1

209

201

185

155

125

95

220

22.9

198

189

181

151

120

90

62

211

20.8

210

210

209

179

149

119

200

22.6

199

199

200

170

140

110

 

 

57

210

19.9

210

210

210

180

149

119

199

21.5

199

199

199

169

139

108

 

72

247

21.3

202

172

141

111

80

50

233

23.1

194

168

137

106

76

45

9000

67

226

21.0

205

190

190

159

129

98

215

22.8

194

171

186

155

124

94

62

206

20.7

205

205

205

175

144

114

195

22.5

194

194

194

163

132

101

 

 

57

205

19.8

205

205

205

175

144

114

194

21.4

194

194

194

163

132

102

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity

Unitary Products Group

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

262292-YTG-B-0107

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 6: COOLING CAPACITIES FOR WR300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on Evaporator Coil

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

75°F

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

90

85

 

80

75

70

65

90

85

 

80

 

75

70

65

 

 

 

 

 

 

77

331

17.7

186

162

 

137

113

88

64

322

20.0

168

144

 

119

 

95

70

46

6250

72

315

17.2

212

187

 

163

138

114

90

303

19.4

199

175

 

151

 

126

102

78

67

299

16.7

237

213

 

188

164

140

115

284

18.8

231

206

 

182

 

158

133

109

 

 

 

 

 

62

273

16.3

265

257

 

231

207

182

158

259

18.4

253

249

 

223

 

198

174

149

 

77

380

20.7

217

189

 

160

131

102

73

371

23.3

197

168

 

139

 

110

82

53

7500

72

362

20.1

247

218

 

189

161

132

103

349

22.6

234

205

 

176

 

147

118

89

67

343

19.5

277

248

 

219

190

161

133

327

21.9

271

242

 

213

 

184

155

126

 

62

313

19.0

305

299

 

269

240

211

182

298

21.4

292

289

 

260

 

231

202

173

 

57

305

18.5

305

305

 

288

259

230

201

292

20.9

292

292

 

279

 

250

221

192

 

77

378

21.0

220

190

 

161

131

102

73

370

23.4

200

170

 

141

 

111

82

52

7750

72

360

20.3

249

220

 

191

161

132

102

348

22.7

237

207

 

178

 

148

119

89

67

342

19.7

279

250

 

221

191

162

132

326

22.0

274

245

 

215

 

186

156

127

 

62

312

19.2

304

301

 

270

241

212

182

298

21.5

292

290

 

263

 

233

204

174

 

57

304

18.7

304

304

 

290

260

231

201

292

21.0

292

292

 

282

 

253

223

194

 

77

376

21.2

222

192

 

162

132

102

72

370

23.6

203

172

 

142

 

112

82

52

8000

72

358

20.6

252

222

 

192

162

132

102

348

22.9

240

210

 

180

 

150

119

89

67

340

19.9

282

252

 

222

192

162

132

326

22.1

278

248

 

217

 

187

157

127

 

62

310

19.4

303

303

 

272

242

212

182

297

21.7

292

292

 

266

 

236

205

175

 

57

303

18.9

303

303

 

291

261

231

201

292

21.1

292

292

 

285

 

255

225

195

 

72

356

20.6

259

228

 

197

166

135

104

347

23.0

248

216

 

185

 

154

123

92

8650

67

338

20.0

290

259

 

228

197

166

135

326

22.3

284

255

 

224

 

193

162

131

62

309

19.4

301

300

 

279

248

217

187

297

21.8

291

291

 

274

 

243

211

180

 

 

 

 

 

57

301

18.9

301

301

 

295

264

233

202

291

21.3

291

291

 

288

 

257

226

195

 

72

354

20.7

266

234

 

202

170

139

107

347

23.1

255

223

 

191

 

159

126

94

9300

67

336

20.1

299

265

 

234

202

170

138

325

22.4

291

263

 

230

 

198

166

134

62

307

19.5

299

299

 

286

255

223

191

296

21.9

291

291

 

282

 

250

217

185

 

 

 

 

 

57

299

19.0

299

299

 

299

267

235

203

291

21.4

291

291

 

291

 

259

227

194

 

 

 

 

 

95°F

 

 

 

 

 

 

 

105°F

 

 

 

 

 

77

313

22.2

150

125

 

101

77

53

28

297

24.4

139

117

 

92

 

68

44

20

6250

72

291

21.5

187

163

 

138

114

90

66

276

23.7

180

155

 

131

 

107

83

59

67

268

20.8

200

200

 

176

151

127

103

256

23.1

220

194

 

170

 

146

122

98

 

 

 

 

 

62

245

20.5

241

241

 

214

190

165

141

232

22.6

230

225

 

199

 

175

151

127

 

77

362

25.8

177

148

 

119

90

61

32

343

28.3

166

137

 

109

 

80

51

22

7500

72

336

25.0

220

192

 

163

134

105

76

319

27.6

212

183

 

154

 

125

97

68

67

310

24.2

264

235

 

206

178

149

120

295

26.8

257

229

 

200

 

171

142

113

 

62

283

23.8

279

279

 

251

222

194

165

268

26.3

266

262

 

234

 

205

177

148

 

57

279

23.2

279

279

 

270

241

213

184

266

25.8

266

266

 

256

 

227

198

170

 

77

362

25.9

180

150

 

121

91

61

32

343

28.5

171

140

 

110

 

81

51

22

7750

72

337

25.1

224

195

 

165

136

106

76

319

27.7

216

186

 

156

 

127

97

68

67

311

24.3

269

239

 

210

180

150

121

296

26.9

260

232

 

203

 

173

144

114

 

62

283

23.9

280

280

 

255

226

196

166

268

26.4

266

264

 

238

 

208

179

149

 

57

280

23.3

280

280

 

275

245

215

186

266

25.9

266

266

 

260

 

230

201

171

 

77

363

26.0

183

153

 

123

92

62

31

343

28.6

176

142

 

112

 

82

51

21

8000

72

338

25.2

229

198

 

168

137

107

77

320

27.8

219

189

 

159

 

129

98

68

67

312

24.3

274

243

 

213

183

152

122

296

27.1

263

236

 

206

 

175

145

115

 

62

284

23.9

281

281

 

259

229

198

168

269

26.6

266

266

 

241

 

211

181

150

 

57

281

23.4

281

281

 

279

248

218

188

266

26.1

266

266

 

264

 

233

203

173

 

72

339

25.3

236

205

 

173

142

111

79

321

27.9

227

196

 

165

 

133

102

71

8650

67

313

24.5

278

252

 

220

189

157

126

297

27.1

266

245

 

213

 

182

151

119

62

285

24.1

282

282

 

268

237

205

174

270

26.6

267

267

 

250

 

219

187

156

 

 

 

 

 

57

282

23.6

282

282

 

281

249

218

187

267

26.1

267

267

 

266

 

235

203

172

 

72

340

25.5

244

211

 

179

147

114

82

322

28.0

235

203

 

170

 

138

106

73

9300

67

314

24.7

283

260

 

227

195

163

130

298

27.2

268

253

 

221

 

189

156

124

62

286

24.3

283

283

 

277

244

212

180

271

26.7

268

268

 

259

 

226

194

162

 

 

 

 

 

57

283

23.8

283

283

 

283

250

218

185

268

26.2

268

268

 

268

 

236

203

171

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity

16

Unitary Products Group

262292-YTG-B-0107

TABLE 6: COOLING CAPACITIES FOR WR300 (CONTINUED)

Air on Evaporator Coil

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

Total2

 

Sensible Capacity (MBH)*

 

Total

Total2

 

Sensible Capacity (MBH)*

 

CFM

Cap.1

Input

 

Return Dry Bulb (°F)

 

Cap.1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBH)

(kW)

 

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

77

281

26.6

128

108

84

60

36

12

265

28.8

122

99

75

51

27

-

6250

72

262

26.0

172

148

124

100

76

52

248

28.2

165

141

117

93

69

45

67

243

25.3

216

188

164

140

116

92

230

27.5

207

183

159

135

111

87

 

 

62

220

24.8

218

209

185

161

137

113

208

26.9

207

193

170

146

122

98

 

77

324

30.9

155

127

98

70

41

12

305

33.5

149

116

88

59

31

-

7500

72

302

30.2

203

174

146

117

88

60

285

32.8

194

166

137

109

80

52

67

280

29.4

250

222

193

164

136

107

265

32.0

239

215

186

158

129

101

 

62

254

28.8

252

245

217

188

159

131

239

31.3

239

228

199

171

142

114

 

57

252

28.4

252

252

241

213

184

155

239

30.9

239

239

227

198

170

141

 

77

324

31.1

162

129

100

70

41

11

304

33.7

157

118

89

60

31

-

7750

72

302

30.4

207

177

148

118

89

60

284

33.0

198

168

139

110

80

51

67

280

29.6

251

225

196

166

137

108

264

32.3

238

218

189

160

130

101

 

62

254

29.0

252

249

220

190

161

132

239

31.6

238

233

202

173

143

114

 

57

252

28.5

252

252

245

215

186

157

238

31.1

238

238

230

201

171

142

 

77

323

31.3

168

131

101

71

41

11

303

34.0

164

120

90

60

30

-

8000

72

302

30.5

210

180

150

120

89

59

284

33.2

201

171

141

111

81

51

67

280

29.8

252

229

199

168

138

108

264

32.5

238

222

191

161

131

101

 

62

253

29.2

252

252

223

193

163

132

238

31.8

238

238

205

175

145

115

 

57

252

28.7

252

252

248

218

188

158

238

31.4

238

238

233

203

173

143

 

72

303

30.5

218

187

156

125

93

62

284

33.1

209

178

147

116

85

53

8650

67

281

29.8

253

238

206

175

144

113

265

32.4

239

231

200

168

137

106

62

254

29.2

253

253

232

201

169

138

239

31.7

239

239

214

182

151

120

 

 

57

253

28.7

253

253

251

220

189

157

239

31.3

239

239

236

205

174

143

 

72

304

30.5

226

194

162

129

97

65

285

33.0

218

185

153

121

89

56

9300

67

282

29.8

254

247

214

182

150

117

265

32.3

239

239

208

176

143

111

62

255

29.1

254

254

241

208

176

144

240

31.6

239

239

222

190

158

126

 

 

57

254

28.7

254

254

254

221

189

157

239

31.2

239

239

239

207

175

143

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity