TECHNICAL GUIDE
SUNLINE MagnaDRY™
GAS/ELECTRIC SINGLE PACKAGE AIR CONDITIONERS
WR 180, 240 & 300
15 thru 25 NOMINAL TONS
11.9 EER (15 TONS), 11.0 EER (20 TONS),
10.0 EER (25 TONS)
262292-YTG-B-0107
YORK Sunline MagnaDRY™ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
All units include:
•Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
•Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats
•Scroll compressors
•Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic
•Permanently lubricated motors
•Bottom or side air discharge configuration capability (field convertible)
•Belt Drive Blower Motor with high static drive option
•Constant supply air volume (CV) with optional variable air volume (VAV)
•Manufactured under the quality standards of ISO9001
•Simplicity® Control Board
•Zero-25% fixed air damper with hood
•Copper tube/aluminum fin coils
•Hinged filter access and toolless latched doors
•Rigging holes in base rails for lifting
•Single point power connection
•Complete factory package - tested, charged and wired
•CSA agency approvals on all units
WARRANTY
•One-year parts warranty
•A Five-year parts warranty on the compressors and electric heat elements
•Ten-year parts warranty on the gas-fired heat exchangers
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
262292-YTG-B-0107
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . .3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . .8 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . .9
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . .53
LIST OF FIGURES
Fig. # |
Pg. # |
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 REHEAT CONTROL BOARD . . . . . . . . . . . . . . . . . . . . . 6 3 REHEAT CONTROLS - PART 1. . . . . . . . . . . . . . . . . . . 7 4 REHEAT CONTROLS - PART 2. . . . . . . . . . . . . . . . . . . 7 5 WR180 MOISTURE REMOVAL - ALT. MODE. . . . . . 21 6 WR180 MOISTURE REMOVAL - NORMAL MODE. . 21 7 WR240 MOISTURE REMOVAL - ALT. MODE. . . . . . 22 8 WR240 MOISTURE REMOVAL - NORMAL MODE. . 22 9 WR300 MOISTURE REMOVAL - ALT. MODE. . . . . . 23
10 WR300 MOISTURE REMOVAL - NORMAL MODE. . 23
11 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
12 UNIT DIMENSIONS WR180, 240 & 300
(FRONT VIEW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 13 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . . 47
14 UNIT DIMENSIONS WR180, 240 & 300
(RAINHOOD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 15 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 49 16 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . . 49 17 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 50 18 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . 51 19 ROOF CURB DUCT OPENINGS DIMENSION . . . . . 51 20 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . . 51 21 TYPICAL FIELD WIRING . . . . . . . . . . . . . . . . . . . . . . 52
LIST OF TABLES
Tbl. # |
Pg. # |
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . 11 2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . 11 3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 11 4 COOLING CAPACITIES FOR WR180 . . . . . . . . . . . . 12 5 COOLING CAPACITIES FOR WR240 . . . . . . . . . . . . 14 6 COOLING CAPACITIES FOR WR300 . . . . . . . . . . . . 16
7 COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Tbl. # |
Pg. # |
9 COOLING CAPACITIES FOR WR300 (ALTERNATE REHEAT MODE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . . 24
11 WR180 BLOWER PERFORMANCE - 15 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 26
12 WR180 BLOWER PERFORMANCE - 15 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 27
13 WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 28
14 WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 29
15 WR240 BLOWER PERFORMANCE - 20 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 30
16 WR240 BLOWER PERFORMANCE - 20 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 31
17 WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 32
18 WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 33
19 WR300 BLOWER PERFORMANCE - 25 TON STD. DRIVE (COOLING ONLY) DOWNFLOW . . . . . . . . . . . 34
20 WR300 BLOWER PERFORMANCE - 25 TON STD. DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . . . . . . . . 35
21 WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW . . . . 36
22 WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW . . . . . . . . 37
23 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 38 24 STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . . . . . . 38 25 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . . 38
26 WR ELECTRICAL DATA - STANDARD DRIVE
MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 39
27 WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 40
28 WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONV. OUTLET . . . . . . . . . 41
29 WR ELECTRICAL DATA - STANDARD DRIVE
MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 42
30 WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 43
31 WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR WITH POWERED CONV. OUTLET . . . . . . . . 44
32 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 33 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . . 45 34 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 46 35 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 48 36 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . . 50
2 |
Unitary Products Group |
262292-YTG-B-0107
15-25 Ton Sunline MagnaDRY™ Model Number Nomenclature
W R 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category
W = A/C, Single Pkg.,
R-22 w/6-Row Evap.
Product Identifier
R = 90.1 w/Reheat
Nominal Cooling Capacity
180 = 15 Ton
240 = 20 Ton
300 = 25 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed electric heat
Gas Heat Options
N24 = 240 MBH Output Aluminized Steel
N32 = 320 MBH Output Aluminized Steel
S24 = 240 MBH Output Stainless Steel
S32 = 320 MBH Output Stainless Steel
Electric Heat Options
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW
Airflow
A = Std. Drive
B = Std. Drive/Single Input Econo.
C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only)
D = Std. Drive/Motorized Damper N = Hi Static Drive
P = Hi Static Drive/Single Input Econo.
Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only)
R = Hi Static Drive/Motorized Damper 2 = Low Static Drive
3 = Low Static Drive/Single Input Econo.
4 = Low Static Drive/Single Input Econo./Power Exhaust (Downflow Only)
5 = Low Static Drive/Motorized Damper
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Product Style
A = Style A
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume (VFD) - Not Available with Factory Installed BAS Options
Variable Air Volume (VFD With Manual Bypass) - Not Available with Factory Installed BAS Options Variable Air Volume (VFD-Ready for Customer Installed Drive)
2" Pleated filters 4" Pleated filters
BAS Ready Unit with Belimo Economizer
Double Wall Construction
Heat Reclaim Coil Options (2 or 3 Row, 1-5/8" or 2-1/8" Stub Out) (WJ and WR models only)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
|
|
Product Generation |
|
|
|
|
|
|
|
|
|
|
|
1 = First Generation |
|
|
|
|
|
2 = Second Generation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Additional Options |
|
|
|
|
|
||
|
|
Standard Cabinet |
Hinged Filter Door & Toolless Access Cabinet |
||
|
|
|
|||
|
AA = None |
BA = Hinged Filter Door & Toolless Access Panels |
|||
|
AB = Phase Monitor |
BB = Phase Monitor, Hinged Filter Door & Toolless |
|||
|
AC = Coil Guard |
Access Panels |
|||
|
AD = Dirty Filter Switch |
BC = Coil Guard, Hinged Filter Door & Toolless |
|||
|
AE = Phase Monitor & Coil Guard |
Access Panels |
|||
|
AF = Phase Monitor & Dirty Filter Switch |
BD = Dirty Filter Switch, Hinged Filter Door & |
|||
|
AG = Coil Guard & Dirty Filter Switch |
Toolless Access Panels |
|||
|
AH = Phase Monitor, Coil Guard & Dirty Filter Switch |
BE = Phase Monitor & Coil Guard, Hinged Filter |
|||
|
RC = Coil Guard & American Flag |
Door & Toolless Access Panels |
|||
|
TA = Technicoat Condenser Coil |
BF = Phase Monitor & Dirty Filter Switch, Hinged |
|||
|
TJ = Technicoat Evaporator Coil |
Filter Door & Toolless Access Panels |
|||
|
TS = Technicoat Evaporator & Condenser Coils |
BG = Coil Guard & Dirty Filter Switch, Hinged Filter |
|||
|
|
|
|
|
Door & Toolless Access Panels |
|
|
|
|
|
BH = Phase Monitor, Coil Guard & Dirty Filter Switch, |
|
|
|
|
|
Hinged Filter Door & Toolless Access Panels |
|
|
|
|||
|
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be |
||||
|
|
located in digits 15-18. |
|
||
|
|
|
|||
|
|
|
|
|
|
Installation Options |
|
|
|
||
|
|
|
|
||
A = No Options Installed |
|
|
|
||
B = Option 1 |
|
|
|||
C = Option 2 |
|
|
|||
D = Options 1 & 2 |
|
|
|||
E = Option 3 |
|
|
|||
F = Option 4 |
|
|
|||
G = Options 1 & 3 |
|
|
|||
H = Options 1 & 4 |
|
|
|||
J = Options 1, 2 & 3 |
|
|
|||
K = Options 1, 2, & 4 |
|
|
|||
L = Options 1,3 & 4 |
|
|
|||
M = Options 1, 2, 3, & 4 |
|
|
|||
N = Options 2 & 3 |
|
|
|||
P = Options 2 & 4 |
|
|
|||
Q = Options 2, 3, & 4 |
|
|
|||
R = Options 3 & 4 |
|
|
|||
S = Option 5 |
|
|
|||
T = Options 1 & 5 |
|
|
|||
U = Options 1, 3, & 5 |
|
|
|||
V = Options 1, 4, & 5 |
|
|
|||
W = Options 1, 3, 4, & 5 |
|
|
|||
X = Options 3 & 5 |
|
|
|||
Y = Options 4 & 5 |
|
|
|||
Z = Options 3, 4 & 5 |
|
|
|||
|
|
|
|
||
|
Options |
|
|
|
|
|
|
|
|
||
1 = Disconnect |
|
|
|
||
2 = Non-Pwr'd Conv. Outlet |
|
|
|||
3 = Smoke Detector S.A. |
|
|
|||
4 = Smoke Detector R.A. |
|
|
|||
5 = Pwr'd Conv. Outlet |
|
|
|||
|
|
|
|
|
|
Unitary Products Group |
3 |
262292-YTG-B-0107
All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
All models are available with these “factory mounted” outdoor air damper options:
•Single enthalpy economizer
•Single enthalpy economizer with power exhaust
•Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/ or static pressure requirement. A variable air volume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.
All compressors include scroll compressors and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.
•Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls.
•Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0°F
outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
•Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
•Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
•Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
•Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
•Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
•On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
•Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
•Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
4 |
Unitary Products Group |
262292-YTG-B-0107
FIGURE 1: UNIT CUTAWAY
•Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
•The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
•BAS Controls - York’s Magnum series units offer factory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.
REHEAT MODE SEQUENCE OF OPERATION
The reheat control board allows the user to select two different modes of operation via a jumper connection on the board. (See Figure 2.) Each mode is described below. Refer to Figures 2 - 4 when reading this section.
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)
When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for cooling, it energizes the hot gas relay (HGR), which energizes the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and de-energizes the reheat coil bleed valve (SOL 1). The Y1 signal is passed to the unit control board (UCB), which engages circuit # 1, resulting in circuit #1 reheat mode operation.
When the room thermostat calls for first stage cooling, with or without a call for dehumidification, the RCB senses a signal through "Y1", de-energizing the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1, engaging circuit # 1, resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit #1 and circuit #2 in the cooling mode.
Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.
Unitary Products Group |
5 |
262292-YTG-B-0107
Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call for heating.
On units with economizers, the unit will not operate in the reheat mode if there is a call for cooling and the economizer is operating as first stage of cooling.
All safety devices function as previously described.
When the RCB detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2, and there is not a call for cooling, it energizes the HGR, which energizes the SOL 3, SOL 2, and de-energizes SOL 1. The unit then operates with circuit #1 in reheat mode and circuit #2 in cooling mode.
When the room thermostat calls for first stage cooling while there is still a call for dehumidification, no operational change is made. The call for cooling is ignored and the unit continues to operate with circuit #1 in reheat mode and circuit #2 in cooling mode.
When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and de-energizes the HGR, which de-energizes SOL 3 and SOL 2, and energizes SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is still a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call for heating.
All safety devices function as previously described.
R
Y1
P4
Y2
K1
G
W1
K2
W2
OCC
K4
C
K3
COM
` |
P6 |
|
|
P5 |
P3 |
|
|
|
|
|
|
|
|
HGRR |
|
HGR |
|||||||
|
HUM |
|||||||
|
MODE |
|
|
|
DEHUMIDISTAT |
|||
SELECTION |
|
|
|
HARNESS |
||||
|
JUMPER |
|
|
|
CONNECTION |
FIGURE 2: REHEAT CONTROL BOARD
6 |
Unitary Products Group |
262292-YTG-B-0107
UCB |
RHB |
UNIT CONTROL |
REHEAT CONTROL |
BOARD |
BOARD |
HUM
HUMIDIFY
TERMINAL
RHR
REHEAT
RELAY
RHTB
REHEAT
TERMINAL
BLOCK
FIGURE 3: REHEAT CONTROLS - PART 1
REHEAT
SOLENOID 1
REHEAT |
|
REHEAT |
SOLENOID 3 |
|
|
|
SOLENOID 2 |
|
|
|
UCB
UNIT CONTROL
BOARD
RHB
REHEAT
CONTROL
BOARD
FIGURE 4: REHEAT CONTROLS - PART 2
Unitary Products Group |
7 |
|
262292-YTG-B-0107 |
|
|
|
|
FACTORY-INSTALLED OPTIONS |
A ‘VFD-ready’ option provides the provisions for a cus- |
|
• SINGLE INPUT ELECTRONIC ENTHALPY |
tomer-installed drive. The unit comes with a mounting |
|
bracket installed in the Blower Access compartment which |
||
ECONOMIZERS - Includes a slide-in / plug-in damper |
may accommodate other vendor’s drives depending on |
|
assembly with fully modulating spring-return motor |
their size. In order to utilize the unit’s mounting bracket, |
|
actuator capable of introducing up to 100% outdoor air |
the maximum recommended drive dimensions are as fol- |
|
with nominal 1% leakage type dampers. |
lows: |
|
The enthalpy system contains one sensor that monitors |
For 5-hp motor applications ........................13” H x 6” W x 7” D |
|
the outdoor air and determines when the air is cool |
||
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D |
||
enough and dry enough to provide free cooling. |
||
The rainhood is painted to match the basic unit and must |
If the customer-installed drive will not fit in the allotted |
|
be field-assembled before installing. |
space, then it will have to be mounted within a NEMA-4 |
|
• POWER EXHAUST - Our single economizer options are |
enclosure for outside installation or inside the building on |
|
a perpendicular wall not subjected to excessive tempera- |
||
available with power exhaust. Whenever the outdoor air |
||
ture, vibration, humidity, dust, corrosive gas, explosive |
||
intake dampers are opened for free cooling, the exhaust |
||
gas, etc. |
||
fan will be energized to prevent the conditioned space |
||
|
||
from being over-pressurized during economizer operation. |
A terminal block located in the control box is provided for |
|
The exhaust fan, motor and controls are installed and |
field connection of the VFD controls. |
|
wired at the factory. The rain hood must be assembled |
• HOT GAS BYPASS - To allow for low cooling load opera- |
|
and installed in the field. |
||
tion, a direct-acting pressure-modulating bypass control |
||
• MOTORIZED OUTDOOR AIR INTAKE DAMPER - |
||
valve installed on the system #1 discharge line is used to |
||
Includes a slide-in / plug-in damper assembly with a 2- |
||
divert high temperature, high pressure refrigerant around |
||
position, spring return motor actuator which opens to a |
||
the TXV in order to maintain a desired minimum evaporator |
||
pre-set position whenever the supply air blower is |
||
pressure. HGBP is standard on all units with VAV and |
||
operating and will drive fully closed when the blower unit |
||
optional with CV units. |
||
shuts down. |
||
• FILTER OPTIONS - Standard units are shipped with 2” |
||
The rain hood is painted to match the basic unit and must |
||
throw-away filters installed. 2” pleated and 4” pleated |
||
be field assembled before installing. |
||
filters are offered as a factory installed option. |
||
• PHENOLIC COATED EVAPORATOR, REHEAT, AND |
||
• CONVENIENCE OUTLET - This 110 volt outlet can be |
||
CONDENSER COILS - Special coating process that |
||
“powered” by the unit with a stepdown transformer or you |
||
utilizes Technicoat 10-1" processes. Coating is applied by |
||
may order the unit with a “non-powered” convenience |
||
total immersion of the complete coil for maximum |
||
outlet that can be wired in the field. |
||
protection. |
||
• DISCONNECT SWITCH - For gas heat units and cooling |
||
• ELECTRIC HEATERS wired for single point power |
||
units with electric heat, a HACR breaker sized to the unit |
||
supply. These nickel chromium heater elements are |
||
is provided. For cooling only units, a switch sized to the |
||
provided with limit and automatic reset capability to |
||
largest electric heat available for the particular unit is |
||
prevent operation at excessive temperatures. |
||
provided. Factory installed option only. |
||
• VARIABLE AIR VOLUME (VAV) - A factory-installed |
||
• DOUBLE WALL CONSTRUCTION - Optional double wall |
||
variable frequency drive (VFD), mounted in the Blower |
||
construction is available to provide smooth inner surfaces |
||
Access compartment, is used to control the speed of the |
||
for easy and effective cleaning to reduce risk of dirt and |
||
indoor blower motor in order to maintain a constant static |
||
bacterial accumulation. Fiberglass insulation is |
||
pressure in the supply duct. A pressure transducer and |
||
sandwiched between heavy gauge steel sheets to form a |
||
VAV control board are mounted inside the control box. |
||
durable, rigid casing to withstand higher working |
||
The drive comes completely wired and pre-programmed |
||
pressures and impact forces. The heavy-duty construction |
||
from the factory. |
||
provides excellent acoustic and thermal insulation and |
||
An optional, factory-installed manual bypass switch avail- |
||
eliminates erosion of insulation material and |
||
able with factory-installed VFD can be found in the Blower |
contamination of the air stream. |
|
Motor Access compartment. The switch can be used to |
• BAS - Building Automation System Controls |
|
either route power to the VFD for modulating control of the |
||
(available on two-system cooling product only). |
||
blower motor, to bypass the drive and operate the motor |
||
Simplicity® INTELLI-Comfort™ CONTROL - The York® |
||
at full speed, or to power the drive (and not the motor) for |
||
diagnostic purposes. |
Simplicity® INTELLI-Comfort™ control is factory installed. |
|
It includes a supply air sensor, a return air sensor, and an |
||
Due to space limitations, VAV is not available with any of |
||
outside air sensor. There are provisions for a field installed |
||
the factory-installed BAS options described below, but is |
dirty filter indicator switch, an air-proving switch, an Out- |
|
available with ‘BAS-ready’ models. Terminal blocks are |
side Air Humidity sensor, a Return Air Humidity sensor, an |
|
provided in the control box for field wiring of the customer- |
Inside IAQ sensor, and an Outside Air IAQ sensor. Con- |
|
installed BAS. |
|
8 |
Unitary Products Group |
262292-YTG-B-0107
struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLIComfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with ModLINC CONTROL - The York® Simplicity® INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
•COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
•SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
•STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
•STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
•PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.
•HIGH SPEED DRIVE - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.
•DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
•HINGED FILTER DOOR/”TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for toolless operation.
•LOW SPEED DRIVE - Includes a motor change when high airflow is not required. (WR300 & WR240 only)
•SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field-assembled before installing.
Unitary Products Group |
9 |
262292-YTG-B-0107
Power exhaust is not available as a field installed option.
•ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
•HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
•PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
•HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
•SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.
•BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air
pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
•ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
•BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
•FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
•WOOD SKID - Allows unit to be handled with 90” forks.
•CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.
•COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
•PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.
10 |
Unitary Products Group |
262292-YTG-B-0107
TABLE 1: SOUND POWER RATING1
|
|
ESP |
BLOWER |
|
|
|
|
SOUND POWER (db 10-12 |
Watts) |
|
|
|
||||
UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
CFM |
|
|
|
|
|
Octave Band Centerline Frequency (Hz) |
|
SWL |
dB(A) |
|||||||
SIZE |
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
@ |
||
|
|
IWG |
RPM |
BHP |
63 |
125 |
|
250 |
500 |
1,000 |
2,000 |
|
4,000 |
8,000 |
dB(A) |
|
|
|
|
|
10Ft.2 |
||||||||||||
|
|
|
|
|
||||||||||||
WR180 |
6,000 |
1.00 |
1,080 |
4.60 |
99 |
99 |
|
89 |
82 |
84 |
77 |
|
72 |
67 |
89 |
56 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WR240 |
8,000 |
1.00 |
1,120 |
6.65 |
102 |
102 |
|
92 |
85 |
87 |
80 |
|
75 |
70 |
92 |
59 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WR300 |
10,000 |
1.30 |
1160 |
12.5 |
108 |
108 |
|
98 |
91 |
93 |
86 |
|
81 |
76 |
98 |
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2.At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 360)1
MODEL |
MBH |
EER2 |
IPLV3 |
COOLING ONLY |
|
|
|
WR180C/E00 |
180 |
11.9 |
12.7 |
WR240C/E00 |
240 |
11.0 |
11.3 |
WR300C/E00 |
300 |
10.0 |
10.6 |
COOLING WITH GAS HEAT |
|
|
|
WR180N/S |
180 |
11.9 |
12.7 |
WR240N/S |
240 |
11.0 |
11.3 |
WR300N/S |
300 |
10.0 |
10.6 |
COOLING WITH ELECTRIC HEAT |
|
|
|
WR180E18 |
180 |
11.9 |
12.7 |
WR180E36 |
180 |
11.9 |
12.7 |
WR180E54 |
178 |
11.7 |
12.5 |
WR180E72 |
178 |
11.7 |
12.5 |
WR240E18 |
240 |
11.0 |
11.3 |
WR240E36 |
240 |
11.0 |
11.3 |
WR240E54 |
238 |
10.8 |
11.1 |
WR240E72 |
238 |
10.8 |
11.1 |
WR300E18 |
300 |
10.0 |
10.6 |
WR300E36 |
300 |
10.0 |
10.6 |
WR300E54 |
298 |
9.8 |
10.4 |
WR300E72 |
298 |
9.8 |
10.4 |
1.Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/ 360.
2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3.IPLV = Integrated Part Load Value.
TABLE 3: GAS HEAT RATINGS
MODEL |
MBH INPUT |
MBH OUTPUT |
WR180N/S24 |
300 |
240 |
|
|
|
WR180N/S32 |
400 |
320 |
WR240N/S24 |
300 |
240 |
|
|
|
WR240N/S32 |
400 |
320 |
WR300N/S24 |
300 |
240 |
|
|
|
WR300N/S32 |
400 |
320 |
NOTE:All gas units are two-stage heating. First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.
If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across electric heating elements or gas heat exchanger tubes.
Unitary Products Group |
11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
262292-YTG-B-0107 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TABLE 4: COOLING CAPACITIES FOR WR180 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air on Evaporator Coil |
|
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|
|
||||||
|
|
|
75°F |
|
|
|
|
|
|
|
85°F |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
|
90 |
85 |
|
80 |
75 |
70 |
65 |
90 |
85 |
|
80 |
|
75 |
70 |
65 |
|||||
|
|
|
|
|
||||||||||||||||
|
77 |
217 |
10.8 |
74 |
71 |
|
59 |
45 |
30 |
16 |
210 |
11.8 |
80 |
73 |
|
58 |
|
43 |
28 |
14 |
3750 |
72 |
200 |
10.5 |
115 |
100 |
|
86 |
72 |
57 |
43 |
193 |
11.6 |
114 |
99 |
|
85 |
|
70 |
55 |
40 |
67 |
184 |
10.2 |
156 |
128 |
|
113 |
99 |
84 |
70 |
177 |
11.3 |
148 |
126 |
|
111 |
|
96 |
82 |
67 |
|
|
|
|
|
|||||||||||||||||
|
62 |
165 |
9.9 |
163 |
153 |
|
132 |
117 |
103 |
88 |
160 |
11.0 |
159 |
152 |
|
130 |
|
116 |
101 |
86 |
|
77 |
227 |
11.0 |
100 |
83 |
|
66 |
48 |
31 |
14 |
219 |
11.9 |
99 |
81 |
|
64 |
|
47 |
29 |
12 |
4500 |
72 |
210 |
10.6 |
130 |
113 |
|
96 |
78 |
61 |
44 |
202 |
11.7 |
128 |
111 |
|
93 |
|
76 |
59 |
41 |
67 |
192 |
10.3 |
161 |
143 |
|
126 |
108 |
91 |
74 |
185 |
11.4 |
158 |
140 |
|
123 |
|
106 |
88 |
71 |
|
|
62 |
172 |
10.0 |
171 |
164 |
|
147 |
129 |
112 |
95 |
167 |
11.1 |
166 |
162 |
|
144 |
|
127 |
109 |
92 |
|
57 |
171 |
10.0 |
171 |
171 |
|
152 |
135 |
118 |
100 |
166 |
11.1 |
166 |
166 |
|
150 |
|
132 |
115 |
97 |
|
77 |
237 |
11.1 |
127 |
95 |
|
72 |
52 |
32 |
11 |
228 |
12.1 |
117 |
90 |
|
70 |
|
50 |
30 |
10 |
5250 |
72 |
219 |
10.8 |
146 |
126 |
|
105 |
85 |
65 |
45 |
210 |
11.8 |
143 |
123 |
|
102 |
|
82 |
62 |
42 |
67 |
201 |
10.4 |
165 |
159 |
|
139 |
118 |
98 |
78 |
192 |
11.5 |
168 |
155 |
|
135 |
|
115 |
94 |
74 |
|
|
62 |
180 |
10.1 |
178 |
175 |
|
161 |
141 |
121 |
101 |
174 |
11.3 |
173 |
171 |
|
158 |
|
138 |
118 |
98 |
|
57 |
178 |
10.1 |
178 |
178 |
|
168 |
148 |
127 |
107 |
173 |
11.2 |
173 |
173 |
|
164 |
|
144 |
124 |
104 |
|
77 |
247 |
11.2 |
153 |
107 |
|
79 |
56 |
32 |
9 |
237 |
12.2 |
136 |
99 |
|
76 |
|
53 |
31 |
8 |
6000 |
72 |
228 |
10.9 |
161 |
138 |
|
115 |
92 |
69 |
45 |
219 |
11.9 |
157 |
134 |
|
111 |
|
88 |
66 |
43 |
67 |
209 |
10.5 |
170 |
170 |
|
151 |
128 |
105 |
82 |
200 |
11.6 |
178 |
169 |
|
146 |
|
124 |
101 |
78 |
|
|
62 |
187 |
10.2 |
186 |
186 |
|
176 |
153 |
130 |
107 |
181 |
11.4 |
180 |
180 |
|
172 |
|
149 |
126 |
103 |
|
57 |
186 |
10.2 |
186 |
186 |
|
183 |
160 |
137 |
114 |
180 |
11.3 |
180 |
180 |
|
178 |
|
155 |
133 |
110 |
|
72 |
236 |
10.9 |
176 |
150 |
|
125 |
99 |
73 |
47 |
226 |
11.9 |
171 |
145 |
|
120 |
|
95 |
70 |
44 |
6750 |
67 |
217 |
10.6 |
184 |
187 |
|
164 |
138 |
112 |
86 |
207 |
11.7 |
185 |
181 |
|
158 |
|
133 |
108 |
82 |
62 |
194 |
10.3 |
193 |
193 |
|
188 |
162 |
136 |
110 |
187 |
11.4 |
186 |
186 |
|
182 |
|
157 |
131 |
106 |
|
|
|
|
|
|||||||||||||||||
|
57 |
193 |
10.2 |
193 |
193 |
|
191 |
166 |
140 |
114 |
186 |
11.3 |
186 |
186 |
|
185 |
|
160 |
135 |
109 |
|
72 |
245 |
10.9 |
191 |
163 |
|
134 |
106 |
77 |
49 |
233 |
12.0 |
184 |
157 |
|
129 |
|
101 |
74 |
46 |
7500 |
67 |
224 |
10.6 |
199 |
199 |
|
177 |
148 |
120 |
91 |
213 |
11.7 |
192 |
192 |
|
170 |
|
142 |
114 |
87 |
62 |
201 |
10.3 |
199 |
199 |
|
199 |
171 |
142 |
114 |
193 |
11.4 |
192 |
192 |
|
192 |
|
164 |
137 |
109 |
|
|
|
|
|
|||||||||||||||||
|
57 |
200 |
10.3 |
200 |
200 |
|
200 |
171 |
143 |
114 |
192 |
11.4 |
192 |
192 |
|
192 |
|
165 |
137 |
109 |
|
|
|
|
|
95°F |
|
|
|
|
|
|
|
105°F |
|
|
|
|
|||
|
77 |
203 |
12.8 |
87 |
72 |
|
57 |
42 |
27 |
12 |
195 |
14.3 |
77 |
69 |
|
53 |
|
38 |
22 |
6 |
3750 |
72 |
186 |
12.6 |
113 |
98 |
|
83 |
68 |
53 |
38 |
179 |
14.1 |
111 |
96 |
|
80 |
|
64 |
49 |
33 |
67 |
170 |
12.4 |
139 |
124 |
|
109 |
94 |
79 |
64 |
164 |
13.9 |
144 |
122 |
|
107 |
|
91 |
75 |
60 |
|
|
|
|
|
|||||||||||||||||
|
62 |
155 |
12.1 |
155 |
152 |
|
129 |
114 |
99 |
84 |
151 |
13.7 |
148 |
149 |
|
125 |
|
109 |
94 |
78 |
|
77 |
211 |
12.9 |
97 |
80 |
|
62 |
45 |
27 |
10 |
202 |
14.4 |
95 |
77 |
|
59 |
|
41 |
23 |
5 |
4500 |
72 |
194 |
12.7 |
126 |
109 |
|
91 |
74 |
56 |
39 |
186 |
14.2 |
124 |
106 |
|
88 |
|
70 |
52 |
34 |
67 |
177 |
12.5 |
155 |
137 |
|
120 |
103 |
85 |
68 |
170 |
14.0 |
153 |
135 |
|
117 |
|
99 |
81 |
63 |
|
|
62 |
161 |
12.3 |
161 |
159 |
|
142 |
124 |
107 |
89 |
157 |
13.8 |
155 |
155 |
|
137 |
|
119 |
101 |
83 |
|
57 |
161 |
12.2 |
161 |
161 |
|
147 |
129 |
112 |
95 |
156 |
13.7 |
156 |
156 |
|
141 |
|
123 |
105 |
87 |
|
77 |
219 |
13.0 |
108 |
88 |
|
68 |
48 |
28 |
8 |
209 |
14.5 |
113 |
84 |
|
64 |
|
44 |
23 |
3 |
5250 |
72 |
202 |
12.8 |
139 |
119 |
|
99 |
79 |
59 |
39 |
192 |
14.3 |
136 |
116 |
|
96 |
|
75 |
55 |
35 |
67 |
184 |
12.6 |
171 |
151 |
|
131 |
111 |
91 |
71 |
175 |
14.1 |
162 |
148 |
|
127 |
|
107 |
87 |
66 |
|
|
62 |
168 |
12.4 |
168 |
167 |
|
155 |
135 |
115 |
95 |
162 |
13.8 |
162 |
161 |
|
149 |
|
129 |
109 |
88 |
|
57 |
168 |
12.3 |
168 |
168 |
|
160 |
140 |
120 |
100 |
162 |
13.8 |
162 |
162 |
|
154 |
|
134 |
113 |
93 |
|
77 |
228 |
13.2 |
119 |
96 |
|
74 |
51 |
29 |
6 |
216 |
14.6 |
131 |
92 |
|
69 |
|
47 |
24 |
1 |
6000 |
72 |
209 |
13.0 |
153 |
130 |
|
108 |
85 |
63 |
40 |
199 |
14.4 |
149 |
126 |
|
104 |
|
81 |
58 |
35 |
67 |
191 |
12.7 |
186 |
164 |
|
141 |
119 |
96 |
74 |
181 |
14.2 |
167 |
161 |
|
138 |
|
115 |
92 |
70 |
|
|
62 |
174 |
12.5 |
174 |
174 |
|
167 |
145 |
122 |
100 |
168 |
13.9 |
167 |
167 |
|
162 |
|
139 |
116 |
94 |
|
57 |
174 |
12.4 |
174 |
174 |
|
173 |
151 |
128 |
106 |
167 |
13.9 |
167 |
167 |
|
166 |
|
144 |
121 |
98 |
|
72 |
216 |
13.0 |
165 |
140 |
|
116 |
91 |
66 |
42 |
204 |
14.4 |
160 |
136 |
|
111 |
|
86 |
62 |
37 |
6750 |
67 |
197 |
12.8 |
186 |
174 |
|
152 |
127 |
103 |
78 |
187 |
14.2 |
172 |
169 |
|
148 |
|
123 |
99 |
74 |
62 |
179 |
12.5 |
179 |
179 |
|
176 |
151 |
127 |
102 |
172 |
13.9 |
172 |
172 |
|
169 |
|
145 |
120 |
95 |
|
|
|
|
|
|||||||||||||||||
|
57 |
179 |
12.5 |
179 |
179 |
|
179 |
154 |
130 |
105 |
172 |
13.9 |
172 |
172 |
|
172 |
|
147 |
122 |
98 |
|
72 |
222 |
13.0 |
177 |
151 |
|
124 |
97 |
70 |
43 |
210 |
14.4 |
172 |
145 |
|
119 |
|
92 |
65 |
39 |
7500 |
67 |
203 |
12.8 |
185 |
185 |
|
163 |
136 |
109 |
82 |
192 |
14.2 |
177 |
177 |
|
158 |
|
131 |
105 |
78 |
62 |
185 |
12.5 |
185 |
185 |
|
185 |
158 |
131 |
104 |
177 |
13.9 |
177 |
177 |
|
177 |
|
150 |
124 |
97 |
|
|
|
|
|
|||||||||||||||||
|
57 |
185 |
12.5 |
185 |
185 |
|
185 |
158 |
131 |
104 |
177 |
13.9 |
177 |
177 |
|
177 |
|
150 |
123 |
97 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
12 |
Unitary Products Group |
262292-YTG-B-0107
TABLE 4: COOLING CAPACITIES FOR WR180 (CONTINUED)
Air on Evaporator Coil |
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|||||||
|
|
|
115°F |
|
|
|
|
|
|
125°F |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
90 |
85 |
80 |
75 |
70 |
65 |
90 |
85 |
80 |
75 |
70 |
65 |
||||||
|
|
|||||||||||||||||
|
77 |
187 |
15.8 |
73 |
66 |
50 |
34 |
17 |
- |
179 |
17.3 |
74 |
60 |
47 |
30 |
13 |
- |
|
3750 |
72 |
172 |
15.6 |
110 |
93 |
77 |
61 |
44 |
28 |
165 |
17.1 |
108 |
91 |
74 |
57 |
40 |
23 |
|
67 |
157 |
15.4 |
146 |
120 |
104 |
88 |
71 |
55 |
151 |
16.9 |
142 |
118 |
101 |
84 |
67 |
50 |
||
|
||||||||||||||||||
|
62 |
147 |
15.2 |
147 |
147 |
121 |
104 |
88 |
72 |
143 |
16.7 |
145 |
143 |
117 |
100 |
83 |
66 |
|
|
77 |
193 |
15.9 |
92 |
74 |
55 |
36 |
18 |
- |
184 |
17.3 |
92 |
70 |
51 |
32 |
13 |
- |
|
4500 |
72 |
177 |
15.7 |
122 |
103 |
84 |
66 |
47 |
29 |
169 |
17.1 |
119 |
100 |
81 |
62 |
43 |
24 |
|
67 |
162 |
15.5 |
151 |
133 |
114 |
95 |
77 |
58 |
155 |
16.9 |
146 |
130 |
111 |
92 |
73 |
54 |
||
|
62 |
152 |
15.2 |
151 |
151 |
133 |
114 |
96 |
77 |
147 |
16.7 |
147 |
146 |
128 |
109 |
90 |
71 |
|
|
57 |
151 |
15.2 |
151 |
151 |
136 |
117 |
99 |
80 |
146 |
16.6 |
146 |
146 |
130 |
111 |
92 |
73 |
|
|
77 |
198 |
15.9 |
111 |
81 |
60 |
39 |
18 |
- |
188 |
17.4 |
111 |
80 |
56 |
35 |
14 |
- |
|
5250 |
72 |
183 |
15.7 |
133 |
113 |
92 |
71 |
51 |
30 |
173 |
17.2 |
130 |
109 |
88 |
67 |
46 |
25 |
|
67 |
167 |
15.5 |
156 |
145 |
124 |
103 |
83 |
62 |
159 |
17.0 |
150 |
142 |
121 |
100 |
79 |
58 |
||
|
62 |
156 |
15.3 |
156 |
156 |
144 |
124 |
103 |
82 |
151 |
16.8 |
149 |
149 |
139 |
118 |
97 |
76 |
|
|
57 |
156 |
15.2 |
156 |
156 |
148 |
127 |
106 |
86 |
150 |
16.7 |
150 |
150 |
141 |
120 |
99 |
78 |
|
|
77 |
204 |
16.0 |
130 |
88 |
65 |
42 |
19 |
- |
193 |
17.4 |
130 |
90 |
60 |
37 |
14 |
- |
|
6000 |
72 |
188 |
15.8 |
145 |
122 |
99 |
77 |
54 |
31 |
177 |
17.2 |
142 |
118 |
95 |
72 |
49 |
26 |
|
67 |
172 |
15.6 |
160 |
157 |
134 |
111 |
88 |
66 |
162 |
17.0 |
153 |
147 |
131 |
108 |
84 |
61 |
||
|
62 |
161 |
15.4 |
160 |
160 |
156 |
133 |
110 |
87 |
154 |
16.8 |
153 |
153 |
151 |
127 |
104 |
81 |
|
|
57 |
160 |
15.3 |
160 |
160 |
160 |
137 |
114 |
91 |
154 |
16.7 |
154 |
154 |
153 |
130 |
107 |
84 |
|
|
72 |
193 |
15.8 |
156 |
131 |
106 |
82 |
57 |
32 |
182 |
17.2 |
151 |
127 |
102 |
77 |
52 |
28 |
|
6750 |
67 |
176 |
15.6 |
165 |
163 |
144 |
119 |
94 |
69 |
166 |
17.0 |
157 |
154 |
139 |
115 |
90 |
65 |
|
62 |
165 |
15.4 |
165 |
165 |
163 |
138 |
113 |
89 |
158 |
16.8 |
157 |
157 |
156 |
131 |
107 |
82 |
||
|
||||||||||||||||||
|
57 |
165 |
15.3 |
165 |
165 |
164 |
140 |
115 |
90 |
157 |
16.7 |
157 |
157 |
157 |
133 |
107 |
83 |
|
|
72 |
198 |
15.8 |
167 |
140 |
113 |
87 |
60 |
34 |
186 |
17.1 |
161 |
135 |
108 |
82 |
55 |
29 |
|
7500 |
67 |
181 |
15.6 |
169 |
169 |
153 |
126 |
100 |
73 |
170 |
16.9 |
161 |
161 |
148 |
122 |
95 |
69 |
|
62 |
169 |
15.3 |
169 |
169 |
169 |
143 |
116 |
90 |
162 |
16.7 |
161 |
161 |
161 |
135 |
109 |
82 |
||
|
||||||||||||||||||
|
57 |
169 |
15.2 |
169 |
169 |
169 |
143 |
116 |
89 |
161 |
16.6 |
161 |
161 |
161 |
136 |
108 |
82 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group |
13 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
262292-YTG-B-0107 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TABLE 5: COOLING CAPACITIES FOR WR240 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air on Evaporator Coil |
|
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|
|
||||||
|
|
|
75°F |
|
|
|
|
|
|
|
85°F |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
|
90 |
85 |
|
80 |
75 |
70 |
65 |
90 |
85 |
|
80 |
|
75 |
70 |
65 |
|||||
|
|
|
|
|
||||||||||||||||
|
77 |
287 |
15.1 |
117 |
99 |
|
80 |
62 |
43 |
25 |
278 |
16.4 |
112 |
96 |
|
77 |
|
58 |
39 |
20 |
5000 |
72 |
263 |
14.6 |
152 |
134 |
|
115 |
96 |
78 |
59 |
254 |
16.0 |
150 |
131 |
|
112 |
|
93 |
74 |
55 |
67 |
238 |
14.2 |
187 |
168 |
|
150 |
131 |
113 |
94 |
230 |
15.6 |
187 |
165 |
|
146 |
|
127 |
108 |
89 |
|
|
|
|
|
|||||||||||||||||
|
62 |
219 |
13.8 |
215 |
198 |
|
176 |
157 |
139 |
120 |
212 |
15.3 |
210 |
198 |
|
172 |
|
153 |
134 |
115 |
|
77 |
304 |
15.2 |
133 |
111 |
|
89 |
67 |
45 |
23 |
294 |
16.5 |
130 |
108 |
|
85 |
|
63 |
41 |
19 |
6000 |
72 |
278 |
14.8 |
171 |
150 |
|
128 |
106 |
84 |
62 |
269 |
16.1 |
169 |
146 |
|
124 |
|
102 |
79 |
57 |
67 |
252 |
14.3 |
210 |
188 |
|
166 |
144 |
122 |
100 |
243 |
15.7 |
207 |
185 |
|
162 |
|
140 |
118 |
95 |
|
|
62 |
232 |
14.0 |
228 |
217 |
|
195 |
173 |
151 |
129 |
224 |
15.4 |
222 |
214 |
|
191 |
|
169 |
147 |
124 |
|
57 |
229 |
13.8 |
229 |
227 |
|
205 |
183 |
161 |
139 |
222 |
15.2 |
222 |
221 |
|
199 |
|
177 |
154 |
132 |
|
77 |
320 |
15.4 |
149 |
123 |
|
98 |
73 |
47 |
22 |
310 |
16.7 |
148 |
120 |
|
94 |
|
68 |
43 |
17 |
7000 |
72 |
293 |
14.9 |
190 |
165 |
|
140 |
115 |
90 |
64 |
283 |
16.3 |
187 |
162 |
|
136 |
|
111 |
85 |
59 |
67 |
265 |
14.4 |
233 |
207 |
|
182 |
157 |
132 |
107 |
256 |
15.9 |
226 |
204 |
|
179 |
|
153 |
127 |
102 |
|
|
62 |
244 |
14.1 |
241 |
235 |
|
214 |
189 |
164 |
138 |
236 |
15.5 |
234 |
230 |
|
210 |
|
185 |
159 |
134 |
|
57 |
241 |
13.9 |
241 |
240 |
|
225 |
200 |
175 |
149 |
234 |
15.3 |
234 |
234 |
|
219 |
|
193 |
167 |
142 |
|
77 |
337 |
15.5 |
165 |
135 |
|
107 |
78 |
50 |
21 |
325 |
16.8 |
167 |
131 |
|
102 |
|
74 |
45 |
16 |
8000 |
72 |
308 |
15.1 |
210 |
181 |
|
153 |
124 |
96 |
67 |
297 |
16.4 |
206 |
178 |
|
149 |
|
120 |
91 |
62 |
67 |
279 |
14.6 |
254 |
227 |
|
199 |
170 |
142 |
113 |
269 |
16.0 |
246 |
224 |
|
195 |
|
166 |
137 |
108 |
|
|
62 |
257 |
14.2 |
254 |
254 |
|
233 |
205 |
176 |
148 |
248 |
15.7 |
246 |
246 |
|
230 |
|
201 |
172 |
143 |
|
57 |
254 |
14.1 |
254 |
254 |
|
245 |
217 |
188 |
160 |
246 |
15.5 |
246 |
246 |
|
239 |
|
210 |
181 |
152 |
|
72 |
302 |
15.0 |
213 |
184 |
|
155 |
126 |
97 |
69 |
291 |
16.4 |
209 |
180 |
|
151 |
|
122 |
93 |
64 |
8500 |
67 |
274 |
14.5 |
249 |
230 |
|
202 |
173 |
144 |
115 |
264 |
16.0 |
241 |
227 |
|
198 |
|
169 |
140 |
110 |
62 |
252 |
14.2 |
249 |
249 |
|
239 |
210 |
181 |
152 |
243 |
15.6 |
241 |
241 |
|
233 |
|
204 |
174 |
145 |
|
|
|
|
|
|||||||||||||||||
|
57 |
249 |
14.0 |
249 |
249 |
|
245 |
216 |
187 |
158 |
241 |
15.4 |
241 |
241 |
|
237 |
|
208 |
179 |
150 |
|
72 |
296 |
14.9 |
216 |
187 |
|
157 |
128 |
99 |
70 |
285 |
16.3 |
212 |
183 |
|
153 |
|
124 |
95 |
65 |
9000 |
67 |
268 |
14.4 |
244 |
224 |
|
205 |
176 |
147 |
118 |
258 |
15.9 |
236 |
231 |
|
201 |
|
172 |
142 |
113 |
62 |
247 |
14.1 |
244 |
244 |
|
244 |
215 |
186 |
157 |
238 |
15.6 |
236 |
236 |
|
236 |
|
207 |
177 |
148 |
|
|
|
|
|
|||||||||||||||||
|
57 |
244 |
13.9 |
244 |
244 |
|
244 |
215 |
186 |
157 |
236 |
15.3 |
236 |
236 |
|
236 |
|
207 |
177 |
148 |
|
|
|
|
|
95°F |
|
|
|
|
|
|
|
105°F |
|
|
|
|
|||
|
77 |
270 |
17.6 |
105 |
93 |
|
73 |
54 |
35 |
15 |
255 |
19.4 |
103 |
89 |
|
70 |
|
50 |
31 |
11 |
5000 |
72 |
246 |
17.3 |
147 |
127 |
|
108 |
89 |
69 |
50 |
234 |
19.1 |
143 |
124 |
|
104 |
|
85 |
65 |
46 |
67 |
222 |
17.0 |
188 |
162 |
|
143 |
123 |
104 |
84 |
212 |
18.8 |
183 |
158 |
|
139 |
|
119 |
100 |
80 |
|
|
|
|
|
|||||||||||||||||
|
62 |
206 |
16.7 |
205 |
197 |
|
169 |
149 |
130 |
111 |
195 |
18.5 |
192 |
190 |
|
164 |
|
144 |
125 |
105 |
|
77 |
285 |
17.8 |
127 |
104 |
|
82 |
59 |
36 |
14 |
269 |
19.6 |
127 |
101 |
|
78 |
|
55 |
32 |
9 |
6000 |
72 |
259 |
17.5 |
166 |
143 |
|
120 |
97 |
75 |
52 |
246 |
19.3 |
162 |
139 |
|
116 |
|
93 |
70 |
48 |
67 |
234 |
17.2 |
204 |
181 |
|
159 |
136 |
113 |
91 |
224 |
19.0 |
197 |
177 |
|
155 |
|
132 |
109 |
86 |
|
|
62 |
217 |
16.8 |
216 |
210 |
|
188 |
165 |
142 |
120 |
206 |
18.7 |
204 |
202 |
|
183 |
|
160 |
137 |
114 |
|
57 |
216 |
16.6 |
216 |
216 |
|
193 |
170 |
147 |
125 |
205 |
18.1 |
205 |
205 |
|
185 |
|
162 |
139 |
117 |
|
77 |
299 |
17.9 |
149 |
116 |
|
90 |
64 |
38 |
12 |
283 |
19.8 |
150 |
112 |
|
86 |
|
59 |
33 |
7 |
7000 |
72 |
273 |
17.6 |
184 |
158 |
|
132 |
106 |
80 |
54 |
259 |
19.5 |
180 |
154 |
|
128 |
|
102 |
76 |
49 |
67 |
247 |
17.3 |
220 |
201 |
|
175 |
149 |
123 |
97 |
236 |
19.2 |
211 |
197 |
|
170 |
|
144 |
118 |
92 |
|
|
62 |
228 |
17.0 |
227 |
224 |
|
207 |
181 |
155 |
129 |
217 |
18.8 |
216 |
214 |
|
201 |
|
175 |
149 |
123 |
|
57 |
227 |
16.7 |
227 |
227 |
|
212 |
186 |
160 |
134 |
216 |
18.3 |
216 |
216 |
|
204 |
|
178 |
152 |
125 |
|
77 |
314 |
18.1 |
171 |
128 |
|
98 |
69 |
40 |
10 |
297 |
19.9 |
173 |
123 |
|
94 |
|
64 |
34 |
5 |
8000 |
72 |
286 |
17.8 |
203 |
174 |
|
145 |
115 |
86 |
56 |
272 |
19.6 |
199 |
169 |
|
140 |
|
110 |
81 |
51 |
67 |
259 |
17.5 |
236 |
220 |
|
191 |
162 |
132 |
103 |
248 |
19.3 |
225 |
216 |
|
186 |
|
157 |
127 |
97 |
|
|
62 |
239 |
17.1 |
238 |
238 |
|
226 |
196 |
167 |
138 |
228 |
19.0 |
226 |
226 |
|
220 |
|
190 |
161 |
131 |
|
57 |
238 |
16.9 |
238 |
238 |
|
232 |
203 |
173 |
144 |
226 |
18.4 |
226 |
226 |
|
223 |
|
193 |
164 |
134 |
|
72 |
280 |
17.7 |
206 |
177 |
|
147 |
117 |
88 |
58 |
266 |
19.6 |
202 |
172 |
|
143 |
|
113 |
83 |
53 |
8500 |
67 |
253 |
17.4 |
232 |
224 |
|
194 |
165 |
135 |
105 |
242 |
19.3 |
220 |
212 |
|
190 |
|
160 |
130 |
100 |
62 |
234 |
17.1 |
233 |
233 |
|
227 |
197 |
168 |
138 |
223 |
18.9 |
222 |
222 |
|
218 |
|
188 |
159 |
129 |
|
|
|
|
|
|||||||||||||||||
|
57 |
233 |
16.8 |
233 |
233 |
|
230 |
200 |
171 |
141 |
222 |
18.4 |
222 |
222 |
|
220 |
|
190 |
160 |
130 |
|
72 |
274 |
17.7 |
209 |
179 |
|
150 |
120 |
90 |
60 |
261 |
19.5 |
206 |
175 |
|
145 |
|
115 |
85 |
55 |
9000 |
67 |
248 |
17.4 |
227 |
227 |
|
197 |
168 |
138 |
108 |
237 |
19.2 |
216 |
209 |
|
193 |
|
163 |
133 |
103 |
62 |
229 |
17.1 |
228 |
228 |
|
228 |
198 |
168 |
139 |
218 |
18.9 |
217 |
217 |
|
217 |
|
186 |
156 |
126 |
|
|
|
|
|
|||||||||||||||||
|
57 |
228 |
16.8 |
228 |
228 |
|
228 |
198 |
169 |
139 |
217 |
18.3 |
217 |
217 |
|
217 |
|
187 |
157 |
126 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
14 |
Unitary Products Group |
262292-YTG-B-0107
TABLE 5: COOLING CAPACITIES FOR WR240 (CONTINUED)
Air on Evaporator Coil |
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|||||||
|
|
|
115°F |
|
|
|
|
|
|
125°F |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
90 |
85 |
80 |
75 |
70 |
65 |
90 |
85 |
80 |
75 |
70 |
65 |
||||||
|
|
|||||||||||||||||
|
77 |
240 |
21.3 |
101 |
86 |
66 |
46 |
27 |
- |
225 |
23.1 |
100 |
81 |
63 |
43 |
23 |
- |
|
5000 |
72 |
221 |
21.0 |
140 |
120 |
101 |
81 |
61 |
42 |
208 |
22.8 |
136 |
117 |
97 |
77 |
57 |
37 |
|
67 |
202 |
20.7 |
179 |
155 |
135 |
115 |
96 |
76 |
192 |
22.5 |
174 |
151 |
131 |
111 |
92 |
72 |
||
|
||||||||||||||||||
|
62 |
185 |
20.4 |
184 |
184 |
159 |
139 |
120 |
100 |
175 |
22.2 |
175 |
174 |
154 |
134 |
115 |
95 |
|
|
77 |
253 |
21.4 |
126 |
97 |
74 |
51 |
28 |
- |
238 |
23.3 |
126 |
93 |
70 |
47 |
23 |
- |
|
6000 |
72 |
233 |
21.1 |
158 |
135 |
112 |
89 |
66 |
43 |
220 |
23.0 |
154 |
131 |
108 |
85 |
62 |
38 |
|
67 |
214 |
20.8 |
190 |
173 |
150 |
127 |
104 |
81 |
203 |
22.7 |
183 |
169 |
146 |
123 |
100 |
77 |
||
|
62 |
195 |
20.5 |
194 |
194 |
177 |
154 |
131 |
108 |
185 |
22.3 |
184 |
184 |
172 |
149 |
126 |
103 |
|
|
57 |
194 |
19.7 |
194 |
194 |
177 |
154 |
131 |
108 |
184 |
21.2 |
184 |
184 |
170 |
147 |
123 |
100 |
|
|
77 |
267 |
21.6 |
151 |
108 |
81 |
55 |
29 |
- |
250 |
23.4 |
151 |
105 |
77 |
50 |
24 |
- |
|
7000 |
72 |
246 |
21.3 |
176 |
150 |
124 |
97 |
71 |
44 |
232 |
23.1 |
172 |
146 |
119 |
93 |
66 |
39 |
|
67 |
225 |
21.0 |
202 |
192 |
166 |
139 |
113 |
87 |
214 |
22.8 |
192 |
188 |
161 |
135 |
108 |
82 |
||
|
62 |
206 |
20.7 |
205 |
205 |
196 |
169 |
143 |
116 |
195 |
22.5 |
193 |
194 |
190 |
163 |
137 |
110 |
|
|
57 |
205 |
19.8 |
205 |
205 |
196 |
169 |
143 |
117 |
194 |
21.4 |
194 |
194 |
187 |
161 |
134 |
108 |
|
|
77 |
280 |
21.8 |
176 |
119 |
89 |
59 |
29 |
- |
263 |
23.6 |
176 |
117 |
84 |
54 |
24 |
- |
|
8000 |
72 |
258 |
21.5 |
195 |
165 |
135 |
105 |
76 |
46 |
244 |
23.3 |
190 |
160 |
130 |
100 |
70 |
41 |
|
67 |
236 |
21.1 |
213 |
211 |
181 |
152 |
122 |
92 |
225 |
23.0 |
204 |
204 |
177 |
147 |
117 |
87 |
||
|
62 |
216 |
20.8 |
215 |
215 |
214 |
184 |
154 |
124 |
205 |
22.7 |
204 |
204 |
205 |
178 |
148 |
118 |
|
|
57 |
215 |
20.0 |
215 |
215 |
214 |
184 |
154 |
125 |
204 |
21.5 |
204 |
204 |
204 |
175 |
145 |
115 |
|
|
72 |
252 |
21.4 |
198 |
168 |
138 |
108 |
78 |
48 |
238 |
23.2 |
194 |
164 |
134 |
103 |
73 |
43 |
|
8500 |
67 |
231 |
21.1 |
209 |
201 |
185 |
155 |
125 |
95 |
220 |
22.9 |
198 |
189 |
181 |
151 |
120 |
90 |
|
62 |
211 |
20.8 |
210 |
210 |
209 |
179 |
149 |
119 |
200 |
22.6 |
199 |
199 |
200 |
170 |
140 |
110 |
||
|
||||||||||||||||||
|
57 |
210 |
19.9 |
210 |
210 |
210 |
180 |
149 |
119 |
199 |
21.5 |
199 |
199 |
199 |
169 |
139 |
108 |
|
|
72 |
247 |
21.3 |
202 |
172 |
141 |
111 |
80 |
50 |
233 |
23.1 |
194 |
168 |
137 |
106 |
76 |
45 |
|
9000 |
67 |
226 |
21.0 |
205 |
190 |
190 |
159 |
129 |
98 |
215 |
22.8 |
194 |
171 |
186 |
155 |
124 |
94 |
|
62 |
206 |
20.7 |
205 |
205 |
205 |
175 |
144 |
114 |
195 |
22.5 |
194 |
194 |
194 |
163 |
132 |
101 |
||
|
||||||||||||||||||
|
57 |
205 |
19.8 |
205 |
205 |
205 |
175 |
144 |
114 |
194 |
21.4 |
194 |
194 |
194 |
163 |
132 |
102 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group |
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
262292-YTG-B-0107 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TABLE 6: COOLING CAPACITIES FOR WR300 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air on Evaporator Coil |
|
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|
|
||||||
|
|
|
75°F |
|
|
|
|
|
|
|
85°F |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
|
90 |
85 |
|
80 |
75 |
70 |
65 |
90 |
85 |
|
80 |
|
75 |
70 |
65 |
|||||
|
|
|
|
|
||||||||||||||||
|
77 |
331 |
17.7 |
186 |
162 |
|
137 |
113 |
88 |
64 |
322 |
20.0 |
168 |
144 |
|
119 |
|
95 |
70 |
46 |
6250 |
72 |
315 |
17.2 |
212 |
187 |
|
163 |
138 |
114 |
90 |
303 |
19.4 |
199 |
175 |
|
151 |
|
126 |
102 |
78 |
67 |
299 |
16.7 |
237 |
213 |
|
188 |
164 |
140 |
115 |
284 |
18.8 |
231 |
206 |
|
182 |
|
158 |
133 |
109 |
|
|
|
|
|
|||||||||||||||||
|
62 |
273 |
16.3 |
265 |
257 |
|
231 |
207 |
182 |
158 |
259 |
18.4 |
253 |
249 |
|
223 |
|
198 |
174 |
149 |
|
77 |
380 |
20.7 |
217 |
189 |
|
160 |
131 |
102 |
73 |
371 |
23.3 |
197 |
168 |
|
139 |
|
110 |
82 |
53 |
7500 |
72 |
362 |
20.1 |
247 |
218 |
|
189 |
161 |
132 |
103 |
349 |
22.6 |
234 |
205 |
|
176 |
|
147 |
118 |
89 |
67 |
343 |
19.5 |
277 |
248 |
|
219 |
190 |
161 |
133 |
327 |
21.9 |
271 |
242 |
|
213 |
|
184 |
155 |
126 |
|
|
62 |
313 |
19.0 |
305 |
299 |
|
269 |
240 |
211 |
182 |
298 |
21.4 |
292 |
289 |
|
260 |
|
231 |
202 |
173 |
|
57 |
305 |
18.5 |
305 |
305 |
|
288 |
259 |
230 |
201 |
292 |
20.9 |
292 |
292 |
|
279 |
|
250 |
221 |
192 |
|
77 |
378 |
21.0 |
220 |
190 |
|
161 |
131 |
102 |
73 |
370 |
23.4 |
200 |
170 |
|
141 |
|
111 |
82 |
52 |
7750 |
72 |
360 |
20.3 |
249 |
220 |
|
191 |
161 |
132 |
102 |
348 |
22.7 |
237 |
207 |
|
178 |
|
148 |
119 |
89 |
67 |
342 |
19.7 |
279 |
250 |
|
221 |
191 |
162 |
132 |
326 |
22.0 |
274 |
245 |
|
215 |
|
186 |
156 |
127 |
|
|
62 |
312 |
19.2 |
304 |
301 |
|
270 |
241 |
212 |
182 |
298 |
21.5 |
292 |
290 |
|
263 |
|
233 |
204 |
174 |
|
57 |
304 |
18.7 |
304 |
304 |
|
290 |
260 |
231 |
201 |
292 |
21.0 |
292 |
292 |
|
282 |
|
253 |
223 |
194 |
|
77 |
376 |
21.2 |
222 |
192 |
|
162 |
132 |
102 |
72 |
370 |
23.6 |
203 |
172 |
|
142 |
|
112 |
82 |
52 |
8000 |
72 |
358 |
20.6 |
252 |
222 |
|
192 |
162 |
132 |
102 |
348 |
22.9 |
240 |
210 |
|
180 |
|
150 |
119 |
89 |
67 |
340 |
19.9 |
282 |
252 |
|
222 |
192 |
162 |
132 |
326 |
22.1 |
278 |
248 |
|
217 |
|
187 |
157 |
127 |
|
|
62 |
310 |
19.4 |
303 |
303 |
|
272 |
242 |
212 |
182 |
297 |
21.7 |
292 |
292 |
|
266 |
|
236 |
205 |
175 |
|
57 |
303 |
18.9 |
303 |
303 |
|
291 |
261 |
231 |
201 |
292 |
21.1 |
292 |
292 |
|
285 |
|
255 |
225 |
195 |
|
72 |
356 |
20.6 |
259 |
228 |
|
197 |
166 |
135 |
104 |
347 |
23.0 |
248 |
216 |
|
185 |
|
154 |
123 |
92 |
8650 |
67 |
338 |
20.0 |
290 |
259 |
|
228 |
197 |
166 |
135 |
326 |
22.3 |
284 |
255 |
|
224 |
|
193 |
162 |
131 |
62 |
309 |
19.4 |
301 |
300 |
|
279 |
248 |
217 |
187 |
297 |
21.8 |
291 |
291 |
|
274 |
|
243 |
211 |
180 |
|
|
|
|
|
|||||||||||||||||
|
57 |
301 |
18.9 |
301 |
301 |
|
295 |
264 |
233 |
202 |
291 |
21.3 |
291 |
291 |
|
288 |
|
257 |
226 |
195 |
|
72 |
354 |
20.7 |
266 |
234 |
|
202 |
170 |
139 |
107 |
347 |
23.1 |
255 |
223 |
|
191 |
|
159 |
126 |
94 |
9300 |
67 |
336 |
20.1 |
299 |
265 |
|
234 |
202 |
170 |
138 |
325 |
22.4 |
291 |
263 |
|
230 |
|
198 |
166 |
134 |
62 |
307 |
19.5 |
299 |
299 |
|
286 |
255 |
223 |
191 |
296 |
21.9 |
291 |
291 |
|
282 |
|
250 |
217 |
185 |
|
|
|
|
|
|||||||||||||||||
|
57 |
299 |
19.0 |
299 |
299 |
|
299 |
267 |
235 |
203 |
291 |
21.4 |
291 |
291 |
|
291 |
|
259 |
227 |
194 |
|
|
|
|
|
95°F |
|
|
|
|
|
|
|
105°F |
|
|
|
|
|||
|
77 |
313 |
22.2 |
150 |
125 |
|
101 |
77 |
53 |
28 |
297 |
24.4 |
139 |
117 |
|
92 |
|
68 |
44 |
20 |
6250 |
72 |
291 |
21.5 |
187 |
163 |
|
138 |
114 |
90 |
66 |
276 |
23.7 |
180 |
155 |
|
131 |
|
107 |
83 |
59 |
67 |
268 |
20.8 |
200 |
200 |
|
176 |
151 |
127 |
103 |
256 |
23.1 |
220 |
194 |
|
170 |
|
146 |
122 |
98 |
|
|
|
|
|
|||||||||||||||||
|
62 |
245 |
20.5 |
241 |
241 |
|
214 |
190 |
165 |
141 |
232 |
22.6 |
230 |
225 |
|
199 |
|
175 |
151 |
127 |
|
77 |
362 |
25.8 |
177 |
148 |
|
119 |
90 |
61 |
32 |
343 |
28.3 |
166 |
137 |
|
109 |
|
80 |
51 |
22 |
7500 |
72 |
336 |
25.0 |
220 |
192 |
|
163 |
134 |
105 |
76 |
319 |
27.6 |
212 |
183 |
|
154 |
|
125 |
97 |
68 |
67 |
310 |
24.2 |
264 |
235 |
|
206 |
178 |
149 |
120 |
295 |
26.8 |
257 |
229 |
|
200 |
|
171 |
142 |
113 |
|
|
62 |
283 |
23.8 |
279 |
279 |
|
251 |
222 |
194 |
165 |
268 |
26.3 |
266 |
262 |
|
234 |
|
205 |
177 |
148 |
|
57 |
279 |
23.2 |
279 |
279 |
|
270 |
241 |
213 |
184 |
266 |
25.8 |
266 |
266 |
|
256 |
|
227 |
198 |
170 |
|
77 |
362 |
25.9 |
180 |
150 |
|
121 |
91 |
61 |
32 |
343 |
28.5 |
171 |
140 |
|
110 |
|
81 |
51 |
22 |
7750 |
72 |
337 |
25.1 |
224 |
195 |
|
165 |
136 |
106 |
76 |
319 |
27.7 |
216 |
186 |
|
156 |
|
127 |
97 |
68 |
67 |
311 |
24.3 |
269 |
239 |
|
210 |
180 |
150 |
121 |
296 |
26.9 |
260 |
232 |
|
203 |
|
173 |
144 |
114 |
|
|
62 |
283 |
23.9 |
280 |
280 |
|
255 |
226 |
196 |
166 |
268 |
26.4 |
266 |
264 |
|
238 |
|
208 |
179 |
149 |
|
57 |
280 |
23.3 |
280 |
280 |
|
275 |
245 |
215 |
186 |
266 |
25.9 |
266 |
266 |
|
260 |
|
230 |
201 |
171 |
|
77 |
363 |
26.0 |
183 |
153 |
|
123 |
92 |
62 |
31 |
343 |
28.6 |
176 |
142 |
|
112 |
|
82 |
51 |
21 |
8000 |
72 |
338 |
25.2 |
229 |
198 |
|
168 |
137 |
107 |
77 |
320 |
27.8 |
219 |
189 |
|
159 |
|
129 |
98 |
68 |
67 |
312 |
24.3 |
274 |
243 |
|
213 |
183 |
152 |
122 |
296 |
27.1 |
263 |
236 |
|
206 |
|
175 |
145 |
115 |
|
|
62 |
284 |
23.9 |
281 |
281 |
|
259 |
229 |
198 |
168 |
269 |
26.6 |
266 |
266 |
|
241 |
|
211 |
181 |
150 |
|
57 |
281 |
23.4 |
281 |
281 |
|
279 |
248 |
218 |
188 |
266 |
26.1 |
266 |
266 |
|
264 |
|
233 |
203 |
173 |
|
72 |
339 |
25.3 |
236 |
205 |
|
173 |
142 |
111 |
79 |
321 |
27.9 |
227 |
196 |
|
165 |
|
133 |
102 |
71 |
8650 |
67 |
313 |
24.5 |
278 |
252 |
|
220 |
189 |
157 |
126 |
297 |
27.1 |
266 |
245 |
|
213 |
|
182 |
151 |
119 |
62 |
285 |
24.1 |
282 |
282 |
|
268 |
237 |
205 |
174 |
270 |
26.6 |
267 |
267 |
|
250 |
|
219 |
187 |
156 |
|
|
|
|
|
|||||||||||||||||
|
57 |
282 |
23.6 |
282 |
282 |
|
281 |
249 |
218 |
187 |
267 |
26.1 |
267 |
267 |
|
266 |
|
235 |
203 |
172 |
|
72 |
340 |
25.5 |
244 |
211 |
|
179 |
147 |
114 |
82 |
322 |
28.0 |
235 |
203 |
|
170 |
|
138 |
106 |
73 |
9300 |
67 |
314 |
24.7 |
283 |
260 |
|
227 |
195 |
163 |
130 |
298 |
27.2 |
268 |
253 |
|
221 |
|
189 |
156 |
124 |
62 |
286 |
24.3 |
283 |
283 |
|
277 |
244 |
212 |
180 |
271 |
26.7 |
268 |
268 |
|
259 |
|
226 |
194 |
162 |
|
|
|
|
|
|||||||||||||||||
|
57 |
283 |
23.8 |
283 |
283 |
|
283 |
250 |
218 |
185 |
268 |
26.2 |
268 |
268 |
|
268 |
|
236 |
203 |
171 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
16 |
Unitary Products Group |
262292-YTG-B-0107
TABLE 6: COOLING CAPACITIES FOR WR300 (CONTINUED)
Air on Evaporator Coil |
|
|
|
|
|
Temperature of Air on Condenser Coil |
|
|
|
|
|
|||||||
|
|
|
115°F |
|
|
|
|
|
|
125°F |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
WB |
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
Total |
Total2 |
|
Sensible Capacity (MBH)* |
|
|||||||
CFM |
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
Cap.1 |
Input |
|
Return Dry Bulb (°F) |
|
||||||||
|
(°F) |
(MBH) |
(kW) |
|
|
|
|
|
|
(MBH) |
(kW) |
|
|
|
|
|
|
|
|
90 |
85 |
80 |
75 |
70 |
65 |
90 |
85 |
80 |
75 |
70 |
65 |
||||||
|
|
|||||||||||||||||
|
77 |
281 |
26.6 |
128 |
108 |
84 |
60 |
36 |
12 |
265 |
28.8 |
122 |
99 |
75 |
51 |
27 |
- |
|
6250 |
72 |
262 |
26.0 |
172 |
148 |
124 |
100 |
76 |
52 |
248 |
28.2 |
165 |
141 |
117 |
93 |
69 |
45 |
|
67 |
243 |
25.3 |
216 |
188 |
164 |
140 |
116 |
92 |
230 |
27.5 |
207 |
183 |
159 |
135 |
111 |
87 |
||
|
||||||||||||||||||
|
62 |
220 |
24.8 |
218 |
209 |
185 |
161 |
137 |
113 |
208 |
26.9 |
207 |
193 |
170 |
146 |
122 |
98 |
|
|
77 |
324 |
30.9 |
155 |
127 |
98 |
70 |
41 |
12 |
305 |
33.5 |
149 |
116 |
88 |
59 |
31 |
- |
|
7500 |
72 |
302 |
30.2 |
203 |
174 |
146 |
117 |
88 |
60 |
285 |
32.8 |
194 |
166 |
137 |
109 |
80 |
52 |
|
67 |
280 |
29.4 |
250 |
222 |
193 |
164 |
136 |
107 |
265 |
32.0 |
239 |
215 |
186 |
158 |
129 |
101 |
||
|
62 |
254 |
28.8 |
252 |
245 |
217 |
188 |
159 |
131 |
239 |
31.3 |
239 |
228 |
199 |
171 |
142 |
114 |
|
|
57 |
252 |
28.4 |
252 |
252 |
241 |
213 |
184 |
155 |
239 |
30.9 |
239 |
239 |
227 |
198 |
170 |
141 |
|
|
77 |
324 |
31.1 |
162 |
129 |
100 |
70 |
41 |
11 |
304 |
33.7 |
157 |
118 |
89 |
60 |
31 |
- |
|
7750 |
72 |
302 |
30.4 |
207 |
177 |
148 |
118 |
89 |
60 |
284 |
33.0 |
198 |
168 |
139 |
110 |
80 |
51 |
|
67 |
280 |
29.6 |
251 |
225 |
196 |
166 |
137 |
108 |
264 |
32.3 |
238 |
218 |
189 |
160 |
130 |
101 |
||
|
62 |
254 |
29.0 |
252 |
249 |
220 |
190 |
161 |
132 |
239 |
31.6 |
238 |
233 |
202 |
173 |
143 |
114 |
|
|
57 |
252 |
28.5 |
252 |
252 |
245 |
215 |
186 |
157 |
238 |
31.1 |
238 |
238 |
230 |
201 |
171 |
142 |
|
|
77 |
323 |
31.3 |
168 |
131 |
101 |
71 |
41 |
11 |
303 |
34.0 |
164 |
120 |
90 |
60 |
30 |
- |
|
8000 |
72 |
302 |
30.5 |
210 |
180 |
150 |
120 |
89 |
59 |
284 |
33.2 |
201 |
171 |
141 |
111 |
81 |
51 |
|
67 |
280 |
29.8 |
252 |
229 |
199 |
168 |
138 |
108 |
264 |
32.5 |
238 |
222 |
191 |
161 |
131 |
101 |
||
|
62 |
253 |
29.2 |
252 |
252 |
223 |
193 |
163 |
132 |
238 |
31.8 |
238 |
238 |
205 |
175 |
145 |
115 |
|
|
57 |
252 |
28.7 |
252 |
252 |
248 |
218 |
188 |
158 |
238 |
31.4 |
238 |
238 |
233 |
203 |
173 |
143 |
|
|
72 |
303 |
30.5 |
218 |
187 |
156 |
125 |
93 |
62 |
284 |
33.1 |
209 |
178 |
147 |
116 |
85 |
53 |
|
8650 |
67 |
281 |
29.8 |
253 |
238 |
206 |
175 |
144 |
113 |
265 |
32.4 |
239 |
231 |
200 |
168 |
137 |
106 |
|
62 |
254 |
29.2 |
253 |
253 |
232 |
201 |
169 |
138 |
239 |
31.7 |
239 |
239 |
214 |
182 |
151 |
120 |
||
|
||||||||||||||||||
|
57 |
253 |
28.7 |
253 |
253 |
251 |
220 |
189 |
157 |
239 |
31.3 |
239 |
239 |
236 |
205 |
174 |
143 |
|
|
72 |
304 |
30.5 |
226 |
194 |
162 |
129 |
97 |
65 |
285 |
33.0 |
218 |
185 |
153 |
121 |
89 |
56 |
|
9300 |
67 |
282 |
29.8 |
254 |
247 |
214 |
182 |
150 |
117 |
265 |
32.3 |
239 |
239 |
208 |
176 |
143 |
111 |
|
62 |
255 |
29.1 |
254 |
254 |
241 |
208 |
176 |
144 |
240 |
31.6 |
239 |
239 |
222 |
190 |
158 |
126 |
||
|
||||||||||||||||||
|
57 |
254 |
28.7 |
254 |
254 |
254 |
221 |
189 |
157 |
239 |
31.2 |
239 |
239 |
239 |
207 |
175 |
143 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group |
17 |