TECHNICAL
GUIDE
SPLIT-SYSTEM HEAT PUMPS
13 SEER – R-22
MODELS: E*BD-F018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PHASE)
E*BD-(T,W)036 THRU 060
(2.5 THRU 5 NOMINAL TONS, 3 PHASE)
ISO 9001
Certified Quality
Management System
LISTED
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at www.ahridirectory.org
246819-BTG-H-0208
DESCRIPTION
The 13 SEER series heat pumps are designed for use with a variety of UPG evaporator sections to suit any application need. A full line of matching Add-On Coils are available for use with upflow, downflow or horizontal furnaces. Matching Air Handlers are also available for upflow, downflow or horizontal installation to provide a complete system. Electric heat may be installed in air handlers. All units are factory charged to assure easy installation.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compressor warranty.
Three Phase Units:
1-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
•DURABLE CONSTRUCTION - The outdoor unit is constructed of pre-painted steel that offers tough protection against corrosion and resists fading when exposed to sunlight. Drain holes are incorporated into the base pan to permit free drainage of moisture.
•QUALITY COILS - The coil is constructed of enhanced copper tube and aluminum fins.
•COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
•PROTECTED COMPRESSOR - The hermetic compressor is internally protected against high pressure and temperature by the simultaneous operation of a high pressure relief valve and temperature sensors which stop the compressor if operating temperatures go too high. Both protectors reset automatically. A discharge line solid core filter drier further protects the compressor.
•Complete System Control – These heat pumps utilize the unique microprocessor defrost control system to provide optimal comfort and to monitor the overall system for reliable operation. The defrost control system continuously monitors the space environment to maintain optimum efficiency. It initiates defrost only when necessary to further reduce heating costs and improve reliability. In the event improper operating conditions occur, the control will automatically shut the system down to extend the life of the heat pump. Rapid cycling is prevented by use of an internal anti-recycle timer.
•LOW OPERATING SOUND LEVEL - The compressor is mounted on rubber isolators to reduce operating sounds. The slow moving condenser fan keeps air turbulence and sound to a low level.
•EASY ACCESS - Removable panel affords accessibility to the electrical box.
•FULLY CHARGED AND FACTORY WIRED - to simply installation and reduce labor costs. Only power supply and control wiring and refrigerant lines must be connected. All models are sweat connect with reusable service valves.
•Factory tested - to verify system operation and control functioning before shipment.
•U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246819-BTG-H-0208
Physical and Electrical Data - 1 Phase
MODEL |
|
EABD-F018S |
EABD-F024S |
EABD-F030S |
EABD-F036S |
EABD-F042S |
EABD-F048S |
EABD-F060S |
Unit Supply Voltage |
|
|
208-230V, 1φ, 60Hz |
|
|
|||
|
|
|
|
|
|
|
|
|
Normal Voltage Range 1 |
|
|
|
187 to 252 |
|
|
|
|
Minimum Circuit Ampacity |
9.9 |
15.0 |
16.9 |
19.8 |
25.0 |
32.7 |
37.8 |
|
|
|
|
|
|
|
|
|
|
Max. Overcurrent Device Amps 2 |
15 |
25 |
25 |
30 |
40 |
50 |
60 |
|
Min. Overcurrent Device Amps 3 |
15 |
20 |
20 |
20 |
30 |
35 |
40 |
|
Compressor Type 4 |
Recip |
Recip |
Recip |
Recip |
Recip |
ScrollD |
ScrollD |
|
Compressor |
Rated Load |
7.5 |
10.7 |
12.4 |
14.6 |
18.8 |
25.0 |
29.1 |
Amps |
Locked Rotor |
41 |
44 |
60 |
78 |
78 |
115 |
150 |
|
|
|
|
|
|
|
|
|
Crankcase Heater |
Yes |
Yes |
Yes |
Yes |
Yes |
No |
No |
|
|
|
|
|
|
|
|
|
|
Fan Motor Amps |
Rated Load |
0.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
|
|
|
|
|
|
|
|
|
Fan Diameter Inches |
22 |
22 |
22 |
22 |
22 |
24 |
24 |
|
|
|
|
|
|
|
|
|
|
|
Rated HP |
1/15 |
1/4 |
1/4 |
1/4 |
1/4 |
1/4 |
1/4 |
Fan Motor |
|
|
|
|
|
|
|
|
Nominal RPM |
850 |
850 |
850 |
850 |
850 |
850 |
850 |
|
|
|
|
|
|
|
|
|
|
|
Nominal CFM |
2,000 |
3,250 |
3,450 |
3,500 |
3,500 |
3,400 |
3,500 |
|
|
|
|
|
|
|
|
|
|
Face Area Sq. Ft. |
15.72 |
18.34 |
20.96 |
23.58 |
23.58 |
24.00 |
27.00 |
Coil |
|
|
|
|
|
|
|
|
Rows Deep |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
Fin / Inches |
22 |
22 |
22 |
22 |
22 |
18 |
18 |
|
|
|
|
|
|
|
|
|
Liquid Line Set OD (Field Installed) |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
|
|
|
|
|
|
|
|
|
|
Vapor Line Set OD (Field Installed) |
3/4 |
3/4 |
7/8 |
7/8 |
7/8 |
7/8 |
1-1/8 |
|
|
|
|
|
|
|
|
|
|
Unit Charge (Lbs. - Oz.) 5 |
7 - 1 |
6 - 6 |
8 - 7 |
8 - 7 |
8 - 7 |
12 - 8 |
16 - 7 |
|
Charge Per Foot, Oz. |
0.68 |
0.68 |
0.70 |
0.70 |
0.70 |
0.70 |
0.76 |
|
|
|
|
|
|
|
|
|
|
Operating Weight Lbs. |
172 |
184 |
196 |
208 |
208 |
250 |
294 |
|
|
|
|
|
|
|
|
|
|
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
|
All dimensions are in inches. They are subject to change |
|||||
|
without notice. Certified dimensions will be provided upon |
|||||
|
request. |
|
|
|
|
|
|
C |
|
Dimensions |
|
Refrigerant |
|
|
Unit |
|
|
Connection |
||
|
|
(Inches) |
|
|||
|
Model |
|
|
|
Service Valve Size |
|
|
|
A1 |
B |
C |
Liquid |
Vapor |
|
018 |
27 |
37 |
27 |
|
3/4” |
|
024 |
31 |
37 |
27 |
|
|
A |
|
|
||||
030 |
35 |
37 |
27 |
|
|
|
|
|
|
||||
|
036 |
39 |
37 |
27 |
3/8” |
7/8” |
|
042 |
39 |
37 |
27 |
|
|
|
|
|
||||
|
048 |
34 |
43 |
32 |
|
|
|
060 |
38 |
43 |
32 |
|
7/8”* |
B |
1. Including Fan Guard. |
|
|
|
||
* Adapter fitting required for 1-1/8” line set. |
|
2 |
Unitary Products Group |
246819-BTG-H-0208
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase
Outdoor Unit |
EABD-F018S |
EABD-F024S |
EABD-F030S |
EABD-F036S |
EABD-F042S |
EABD-F048S |
EABD-F060S |
Required TXV |
1TVM2A1 |
1TVM2A1 |
1TVM2A1 |
1TVM2A1 |
1TVM2C1 |
1TVM2C1 |
1TVM2C1 |
Factory Charge, lbs-oz |
7 - 1 |
6 - 9 |
8 - 9 |
8 - 7 |
8 - 7 |
12 - 8 |
16 - 7 |
|
|
|
|
|
|
|
|
Indoor Coil1,2 |
|
|
Additional Charge, Oz |
|
|
||
FC/MC/PC/UC18A2A |
0 |
– |
– |
– |
– |
– |
– |
FC/MC/PC/UC18B2A |
0 |
– |
– |
– |
– |
– |
– |
FC/MC/PC/UC24A2A |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC24B2A |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC30A2A |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC30B2A |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC35B2A |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC35C2C |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC42B2C |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC42C2C |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC48C2C |
– |
– |
– |
9 |
14 |
– |
– |
FC/MC/PC/UC48D2C |
– |
– |
– |
9 |
14 |
– |
– |
FC/PC/UC60C2C |
– |
– |
– |
– |
– |
7 |
7 |
FC/MC/PC/UC60D2C |
– |
– |
– |
– |
– |
7 |
7 |
MC61D2C |
– |
– |
– |
– |
– |
7 |
7 |
HC18A2A |
0 |
– |
– |
– |
– |
– |
– |
HC30A2A |
– |
0 |
– |
– |
– |
– |
– |
HC36B2A |
– |
– |
0 |
– |
– |
– |
– |
HC42C2C |
– |
– |
– |
9 |
– |
– |
– |
HC60C2C |
– |
– |
– |
– |
– |
7 |
7 |
HD24A2A |
– |
0 |
– |
– |
– |
– |
– |
HD36B2A |
– |
– |
0 |
9 |
– |
– |
– |
HD48C2C |
– |
– |
– |
– |
14 |
– |
– |
HD60D2C |
– |
– |
– |
– |
– |
7 |
7 |
AHP18B2A |
0 |
– |
– |
– |
– |
– |
– |
AHP24B2A |
– |
0 |
– |
– |
– |
– |
– |
AHP30B2A |
– |
– |
0 |
– |
– |
– |
– |
AHP36C2A |
– |
– |
– |
9 |
– |
– |
– |
AHP42C2C |
– |
– |
– |
9 |
– |
– |
– |
AHP/SHP48D2C |
– |
– |
– |
– |
14 |
7 |
– |
AHP/SHP60D2C |
– |
– |
– |
– |
– |
7 |
7 |
AV24B2A |
0 |
0 |
– |
– |
– |
– |
– |
AV36C2A |
– |
– |
0 |
9 |
– |
– |
– |
AV/SV48D2C |
– |
– |
– |
– |
14 |
7 |
– |
AV/SV60D2C |
– |
– |
– |
– |
– |
– |
7 |
FC/MC/PC/UC18A3X |
0 |
– |
– |
– |
– |
– |
– |
FC/MC/PC/UC18B3X |
0 |
– |
– |
– |
– |
– |
– |
FC/MC/PC/UC24A3X |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC24B3X |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC30A3X |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC/UC30B3X |
– |
0 |
– |
– |
– |
– |
– |
FC/MC/PC35B3X |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC35X3X |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC42B3X |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC42X3X |
– |
– |
0 |
9 |
– |
– |
– |
FC/MC/PC/UC48C3X |
– |
– |
– |
9 |
14 |
– |
– |
FC/MC/PC/UC48D3X |
– |
– |
– |
9 |
14 |
– |
– |
FC/PC/UC60C3X |
– |
– |
– |
– |
– |
7 |
7 |
FC/MC/PC/UC60D3X |
– |
– |
– |
– |
– |
7 |
7 |
MC61D3X |
– |
– |
– |
– |
– |
7 |
7 |
HC18A3X |
0 |
– |
– |
– |
– |
– |
– |
HC30A3X |
– |
0 |
– |
– |
– |
– |
– |
HC36B3X |
– |
– |
0 |
– |
– |
– |
– |
HC42C3X |
– |
– |
– |
9 |
– |
– |
– |
HC60C3X |
– |
– |
– |
– |
– |
7 |
7 |
For Notes See Page 4. |
|
|
|
|
|
|
|
Unitary Products Group |
3 |
246819-BTG-H-0208
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)
Outdoor Unit |
EABD-F018S |
EABD-F024S |
EABD-F030S |
EABD-F036S |
EABD-F042S |
EABD-F048S |
EABD-F060S |
Required TXV |
1TVM2A1 |
1TVM2A1 |
1TVM2A1 |
1TVM2A1 |
1TVM2C1 |
1TVM2C1 |
1TVM2C1 |
Factory Charge, lbs-oz |
7 - 1 |
6 - 9 |
8 - 9 |
8 - 7 |
8 - 7 |
12 - 8 |
16 - 7 |
|
|
|
|
|
|
|
|
Indoor Coil1,2 |
|
|
Additional Charge, Oz |
|
|
||
HD24A3X |
– |
0 |
– |
– |
– |
– |
– |
HD36B3X |
– |
– |
0 |
9 |
– |
– |
– |
HD48C3X |
– |
– |
– |
– |
14 |
– |
– |
HD60D3X |
– |
– |
– |
– |
– |
7 |
7 |
AHP18B3X |
0 |
– |
– |
– |
– |
– |
– |
AHP24B3X |
– |
0 |
– |
– |
– |
– |
– |
AHP30B3X |
– |
– |
0 |
– |
– |
– |
– |
AHP36C3X |
– |
– |
– |
9 |
– |
– |
– |
AHP42C3X |
– |
– |
– |
9 |
– |
– |
– |
AHP/SHP48D3X |
– |
– |
– |
– |
14 |
7 |
– |
AHP/SHP60D3X |
– |
– |
– |
– |
– |
7 |
7 |
AV24B3X |
0 |
0 |
– |
– |
– |
– |
– |
AV36C3X |
– |
– |
0 |
9 |
– |
– |
– |
AV/SV48D3X |
– |
– |
– |
– |
14 |
7 |
– |
AV/SV60D3X |
– |
– |
– |
– |
14 |
7 |
7 |
F*FP024H06T2A |
0 |
– |
– |
– |
– |
– |
– |
F*FP030H06T2A |
– |
0 |
– |
– |
– |
– |
– |
F*FP040H06T2A |
– |
– |
0 |
9 |
– |
– |
– |
F*FP042H06T2A |
– |
– |
– |
9 |
– |
– |
– |
F*FV060H06T2C |
– |
– |
– |
– |
– |
7 |
7 |
FOOTNOTES: |
|
|
|
|
|
|
|
1.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
*This loose coil match does not achieve 13 SEER.
PROCEDURES:
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.
2.Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base charge (as shipped) + adder for evaporator + adder for line set.
5.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice/TXV size.
4 |
Unitary Products Group |
246819-BTG-H-0208
Physical and Electrical Data - 3 Phase
MODEL |
|
EABD- |
EABD- |
EABD- |
|
EABD- |
EABD- |
EABD- |
EABD- |
EABD- |
|
EABD- |
EABD- |
|
|
T030S |
T036S |
T042S |
|
T048S |
T060S |
W030S |
W036S |
W042S |
|
W048S |
W060S |
||
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||
Unit Supply Voltage |
|
|
208- |
230V, 3φ, |
60Hz |
|
|
460V, 3φ, 60Hz |
|
|||||
Normal Voltage Range 1 |
|
|
187 to 252 |
|
|
|
|
432 to 532 |
|
|
||||
Minimum Circuit Ampacity |
12.1 |
14.3 |
14.4 |
|
20.2 |
23.1 |
5.6 |
6.9 |
7.2 |
|
9.5 |
11.2 |
||
Max. Overcurrent Device Amps 2 |
20 |
20 |
20 |
|
35 |
40 |
15 |
15 |
15 |
|
15 |
15 |
||
Min. Overcurrent Device Amps 3 |
15 |
15 |
15 |
|
25 |
25 |
15 |
15 |
15 |
|
15 |
15 |
||
Compressor Type |
|
Recip |
Recip |
Recip |
|
Scroll |
Scroll |
Recip |
Recip |
Recip |
|
Scroll |
Scroll |
|
Compressor Amps |
|
Rated Load |
8.5 |
10.2 |
10.4 |
|
15.0 |
16 |
3.9 |
4.9 |
6.1 |
|
6.1 |
8 |
|
Locked Rotor |
62 |
72 |
71 |
|
95 |
123 |
30 |
45 |
45 |
|
45 |
70 |
|
|
|
|
|
|||||||||||
Crankcase Heater |
|
|
Yes |
Yes |
Yes |
|
No |
No |
Yes |
Yes |
Yes |
|
No |
No |
Fan Motor Amps |
|
Rated Load |
1.5 |
1.5 |
1.5 |
|
1.5 |
1.5 |
0.7 |
0.7 |
0.7 |
|
0.7 |
0.7 |
Fan Diameter Inches |
|
|
22 |
22 |
22 |
|
24 |
24 |
22 |
22 |
22 |
|
24 |
24 |
|
|
Rated HP |
1/4 |
1/4 |
1/4 |
|
1/4 |
1/4 |
1/4 |
1/4 |
1/4 |
|
1/4 |
1/4 |
Fan Motor |
|
Nominal RPM |
850 |
850 |
850 |
|
850 |
850 |
850 |
850 |
850 |
|
850 |
850 |
|
|
Nominal CFM |
3450 |
3500 |
3500 |
|
3400 |
3500 |
3450 |
3500 |
3500 |
|
3400 |
3500 |
|
|
Face Area Sq. Ft. |
20.96 |
23.58 |
23.58 |
|
24.00 |
27.00 |
20.96 |
23.58 |
23.58 |
|
24.00 |
27.00 |
Coil |
|
Rows Deep |
1 |
1 |
1 |
|
2 |
2 |
1 |
1 |
1 |
|
2 |
2 |
|
|
Fin / Inches |
22 |
22 |
22 |
|
18 |
18 |
22 |
22 |
22 |
|
18 |
18 |
Liquid Line Set OD |
(Field Installed) |
3/8 |
3/8 |
3/8 |
|
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
|
3/8 |
3/8 |
|
Vapor Line Set OD (Field Installed) |
7/8 |
7/8 |
7/8 |
|
7/8 |
1-1/8 |
7/8 |
7/8 |
7/8 |
|
7/8 |
1-1/8 |
||
Unit Charge (Lbs. - Oz.) 4 |
8 - 7 |
8 - 7 |
8 - 7 |
|
12 - 8 |
16 - 7 |
8 - 7 |
8 - 7 |
8 - 7 |
|
12 - 8 |
16 - 7 |
||
Charge Per Foot, Oz. |
0.70 |
0.70 |
0.70 |
|
0.70 |
0.76 |
0.70 |
0.70 |
0.70 |
|
0.70 |
0.78 |
||
Operating Weight Lbs. |
196 |
208 |
208 |
|
250 |
294 |
196 |
208 |
208 |
|
250 |
294 |
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25 feet, you may refer to publications software 036-68001-001 for proper line sizing.
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
|
DIMENSIONS |
|
|
|
|||
|
C |
Dimensions |
Refrigerant Connection |
||||
|
Unit |
||||||
|
|
(Inches) |
|
Service Valve Size |
|||
|
Model |
A1 |
B |
C |
Liquid |
Vapor |
|
|
|
||||||
|
030 |
35 |
37 |
27 |
|
|
|
A |
036 |
39 |
37 |
27 |
|
7/8” |
|
042 |
39 |
37 |
27 |
3/8” |
|||
|
|
||||||
|
048 |
34 |
43 |
32 |
|
|
|
|
060 |
38 |
43 |
32 |
|
7/8”* |
|
|
1. |
Including Fan Guard. |
|
|
|||
|
* Adapter fitting required for 1-1/8” line set. |
|
B
Unitary Products Group |
5 |
246819-BTG-H-0208
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase
Outdoor Unit |
EABD-(T,W)030S |
EABD-(T,W)036S |
|
EABD-(T,W)042S |
|
EABD-(T,W)048S |
EABD-(T,W)060S |
Required TXV |
1TVM2A1 |
1TVM2A1 |
|
1TVM2C1 |
|
1TVM2C1 |
1TVM2C1 |
Factory Charge, lbs-oz |
8 - 9 |
8 - 7 |
|
8 - 7 |
|
12 - 8 |
16 - 9 |
|
|
|
|
|
|
|
|
Indoor Coil1 |
|
|
Additional Charge, Oz |
|
|
||
FC/MC/PC/UC35B2C |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC35C2C |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC42B2C |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC42C2C |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC48C2C |
– |
9 |
|
14 |
|
– |
– |
FC/MC/PC/UC48D2C |
– |
9 |
|
14 |
|
– |
– |
FC/PC/UC60C2C |
– |
– |
|
– |
|
7 |
5 |
FC/MC/PC/UC60D2C |
– |
– |
|
– |
|
7 |
5 |
MC61D2C |
– |
– |
|
– |
|
7 |
5 |
HC36B2A |
0 |
– |
|
– |
|
– |
– |
HC42C2C |
– |
9 |
|
– |
|
– |
– |
HC60C2C |
– |
– |
|
– |
|
7 |
5 |
HD36B2A |
0 |
9 |
|
– |
|
– |
– |
HD48C2C |
– |
– |
|
14 |
|
– |
– |
HD60D2C |
– |
– |
|
– |
|
7 |
5 |
AHP30B2A |
0 |
– |
|
– |
|
– |
– |
AHP36C2A |
– |
9 |
|
– |
|
– |
– |
AHP42C2C |
– |
9 |
|
– |
|
– |
– |
AHP/SHP48D2C |
– |
– |
|
14 |
|
7 |
– |
AHP/SHP60D2C |
– |
– |
|
– |
|
7 |
5 |
FC/MC/PC/UC42B3X |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC42X3X |
0 |
9 |
|
– |
|
– |
– |
FC/MC/PC/UC48C3X |
– |
9 |
|
14 |
|
– |
– |
FC/MC/PC/UC48D3X |
– |
9 |
|
14 |
|
– |
– |
FC/PC/UC60C3X |
– |
– |
|
– |
|
7 |
5 |
FC/MC/PC/UC60D3X |
– |
– |
|
– |
|
7 |
5 |
MC61D3X |
– |
– |
|
– |
|
7 |
5 |
HC36B3X |
0 |
– |
|
– |
|
– |
– |
HC42C3X |
– |
9 |
|
– |
|
– |
– |
HC60C3X |
– |
– |
|
– |
|
7 |
5 |
HD36B3X |
0 |
9 |
|
– |
|
– |
– |
HD48C3X |
– |
– |
|
14 |
|
– |
– |
HD60D3X |
– |
– |
|
– |
|
7 |
5 |
AHP30B3X |
0 |
– |
|
– |
|
– |
– |
AHP36C3X |
– |
9 |
|
– |
|
– |
– |
AHP42C3X |
– |
9 |
|
– |
|
– |
– |
AHP/SHP48D3X |
– |
– |
|
14 |
|
7 |
– |
AHP/SHP60D3X |
– |
– |
|
– |
|
7 |
5 |
F*FP040H06T2A |
0 |
9 |
|
– |
|
– |
– |
F*FP042H06T2A |
– |
9 |
|
– |
|
– |
– |
FOOTNOTES: |
|
|
|
|
|
|
|
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
PROCEDURES:
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-con- necting line tubing.
2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
6 |
Unitary Products Group |
246819-BTG-H-0208
COOLING CAPACITY - With Air Handler Coils
UNIT |
AIR HANDLER |
|
|
|
|
COOLING |
|
|
|
|
|
|
COIL MODEL1 |
|
|
|
|
|
|
|
|
|
RATED |
NET MBH |
|
|
|||
MODEL |
MODEL |
W |
|
SEER |
EER |
||||
|
|
CFM |
TOTAL |
SENS. |
|||||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
& 3 PH 13 SEER HP |
WITH MA |
|
|
|
|
EABD-F018S |
MA08B |
17 |
|
FC/MC18B |
600 |
18.0 |
12.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F024S |
MA08B |
17 |
|
FC/MC24B |
800 |
23.2 |
16.8 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA08B |
17 |
|
FC/MC30B |
800 |
23.2 |
16.8 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-F030S |
MA12B |
17 |
|
FC/MC35B |
1000 |
28.4 |
20.3 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC42B |
1000 |
28.4 |
20.3 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)030S |
MA12B |
17 |
|
FC/MC35B |
1000 |
28.0 |
20.0 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC42B |
1000 |
28.0 |
20.0 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC35B |
1200 |
34.6 |
25.3 |
13.00 |
11.00 |
EABD-F036S |
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC42B |
1200 |
34.6 |
25.3 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
MA14D |
24 |
|
FC/MC48D |
1200 |
35.0 |
25.6 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC35B |
1200 |
34.0 |
24.8 |
13.00 |
11.00 |
EABD-(T,W)036S |
|
|
|
|
|
|
|
|
|
MA12B |
17 |
|
FC/MC42B |
1200 |
34.0 |
24.8 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
MA14D |
24 |
|
FC/MC48D |
1200 |
34.4 |
25.1 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F042S |
MA16C |
21 |
|
FC/MC48C |
1400 |
41.0 |
30.8 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA14D |
24 |
|
FC/MC48D |
1400 |
41.0 |
30.8 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)042S |
MA16C |
21 |
|
FC/MC48C |
1400 |
40.0 |
30.0 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA14D |
24 |
|
FC/MC48D |
1400 |
40.0 |
30.0 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
MA16C |
21 |
|
FC60C |
1600 |
46.0 |
35.4 |
13.00 |
11.00 |
EABD-F048S |
|
|
|
|
|
|
|
|
|
MA20D |
21 |
|
FC/MC60D |
1600 |
46.0 |
35.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
MA20D |
24 |
|
MC61D |
1600 |
46.0 |
35.5 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
MA16C |
21 |
|
FC60C |
1600 |
45.0 |
34.6 |
13.00 |
11.00 |
EABD-(T,W)048S |
|
|
|
|
|
|
|
|
|
MA20D |
21 |
|
FC/MC60D |
1600 |
45.0 |
34.6 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
MA20D |
24 |
|
MC61D |
1600 |
45.0 |
34.7 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F060S |
MA20D |
24 |
|
FC/MC60D |
1800 |
55.0 |
40.7 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA20D |
24 |
|
MC61D |
1800 |
55.5 |
41.0 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)060S |
MA20D |
24 |
|
FC/MC60D |
1800 |
54.5 |
40.3 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MA20D |
24 |
|
MC61D |
1800 |
55.0 |
40.6 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
1 PH 13 SEER HP WITH MV - VARIABLE SPEED |
|
|
|
||||
EABD-F018S |
MV12B |
17 |
|
FC/MC18B |
600 |
18.0 |
12.6 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F024S |
MV12B |
17 |
|
FC/MC24B |
800 |
23.6 |
16.7 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
MV12B |
17 |
|
FC/MC30B |
800 |
23.6 |
16.7 |
14.00 |
12.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
MV12B |
17 |
|
FC/MC35B |
1000 |
29.0 |
20.1 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F030S |
MV16C |
21 |
|
FC/MC35C |
1000 |
29.0 |
20.1 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
MV12B |
17 |
|
FC/MC42B |
1000 |
29.0 |
20.1 |
14.00 |
12.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
MV16C |
21 |
|
FC/MC42C |
1000 |
29.0 |
20.1 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
|
MV12B |
21 |
|
FC/MC35C |
1200 |
35.2 |
25.0 |
13.50 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
MV16C |
21 |
|
FC/MC35C |
1200 |
35.2 |
25.0 |
14.00 |
12.00 |
EABD-F036S |
|
|
|
|
|
|
|
|
|
MV16C |
21 |
|
FC/MC42C |
1200 |
35.4 |
25.2 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
|
|
MV16C |
21 |
|
FC/MC48C |
1200 |
35.4 |
25.2 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
|
MV20D |
24 |
|
FC/MC48D |
1200 |
35.4 |
25.2 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F042S |
MV16C |
21 |
|
FC/MC48C |
1400 |
41.0 |
30.3 |
13.75 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F048S |
MV20D |
24 |
|
FC/MC60D |
1600 |
46.0 |
34.6 |
13.50 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MV20D |
24 |
|
MC61D |
1600 |
46.5 |
34.8 |
13.75 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-F060S |
MV20D |
24 |
|
FC/MC60D |
1800 |
54.0 |
39.7 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
MV20D |
24 |
|
MC61D |
1800 |
55.0 |
39.9 |
13.25 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
For Notes See Page 8
Unitary Products Group |
7 |
246819-BTG-H-0208
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT |
AIR HANDLER |
|
|
|
COOLING |
|
|
||
|
|
|
COIL MODEL1 |
|
|
|
|
|
|
|
|
|
RATED |
NET MBH |
|
|
|||
MODEL |
MODEL |
|
W |
SEER |
EER |
||||
|
|
CFM |
TOTAL |
SENS. |
|||||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
1 PH 13 SEER AC WITH AV / SV - VARIABLE SPEED |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
EABD-F018S |
AV24 |
|
17 |
– |
600 |
18.0 |
12.6 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F024S |
AV24 |
|
17 |
– |
800 |
23.8 |
16.7 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F030S |
AV36 |
|
17 |
– |
1000 |
29.2 |
20.1 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F036S |
AV36 |
|
21 |
– |
1200 |
35.0 |
25.2 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F042S |
AV/SV48 |
|
21 |
– |
1400 |
41.5 |
30.3 |
14.00 |
12.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F048S |
AV/SV48 |
|
24 |
– |
1600 |
46.5 |
34.8 |
13.75 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F060S |
AV/SV60 |
|
24 |
– |
1800 |
55.0 |
39.9 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
1 & 3 PH |
13 SEER HP WITH AHP / F*FP / F*FV |
|
|
|
||
EABD-F018S |
F*FP024 |
|
17 |
– |
600 |
18.0 |
11.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP18 |
|
17 |
– |
600 |
18.0 |
11.4 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-F024S |
F*FP030 |
|
17 |
– |
800 |
23.2 |
16.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP24 |
|
17 |
– |
800 |
23.0 |
16.4 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-F030S |
F*FP040 |
|
21 |
– |
1000 |
28.0 |
19.5 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP30 |
|
17 |
– |
1000 |
28.4 |
19.5 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
F*FP040 |
|
21 |
– |
1000 |
27.6 |
19.2 |
13.00 |
11.00 |
EABD-(T,W)030S |
|
|
|
|
|
|
|
|
|
AHP30 |
|
17 |
– |
1000 |
28.0 |
19.2 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
AHP30 |
|
17 |
– |
1000 |
28.0 |
19.2 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
F*FP040 |
|
21 |
– |
1200 |
34.6 |
25.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F036S |
F*FP042 |
|
21 |
– |
1200 |
34.6 |
25.4 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP36 |
|
21 |
– |
1200 |
34.4 |
25.4 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
AHP42 |
|
21 |
– |
1200 |
34.6 |
25.3 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
F*FP040 |
|
21 |
– |
1200 |
34.0 |
24.9 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)036S |
F*FP042 |
|
21 |
– |
1200 |
34.0 |
24.9 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP36 |
|
21 |
– |
1200 |
33.8 |
24.9 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
AHP42 |
|
21 |
– |
1200 |
34.0 |
24.8 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F042S |
AHP/SHP48 |
|
24 |
– |
1400 |
41.0 |
30.7 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)042S |
AHP/SHP48 |
|
24 |
– |
1400 |
40.0 |
29.9 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
F*FV060 |
|
24 |
– |
1600 |
46.0 |
34.6 |
13.50 |
11.00 |
EABD-F048S |
|
|
|
|
|
|
|
|
|
AHP/SHP48 |
|
24 |
– |
1600 |
46.0 |
35.3 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
AHP/SHP60 |
|
24 |
– |
1600 |
46.0 |
34.6 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
F*FV060 |
|
24 |
– |
1600 |
45.0 |
33.8 |
13.50 |
11.00 |
EABD-(T,W)048S |
|
|
|
|
|
|
|
|
|
AHP/SHP48 |
|
24 |
– |
1600 |
45.0 |
34.5 |
13.00 |
11.00 |
|
|
|
|
|
|
|
|
|
|
|
|
AHP/SHP60 |
|
24 |
– |
1600 |
45.0 |
33.8 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
EABD-F060S |
F*FV060 |
|
24 |
– |
1800 |
54.0 |
39.7 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP/SHP60 |
|
24 |
– |
1800 |
55.0 |
39.7 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
EABD-(T,W)060S |
F*FV060 |
|
24 |
– |
1800 |
53.5 |
39.3 |
13.25 |
11.00 |
|
|
|
|
|
|
|
|
|
|
AHP/SHP60 |
|
24 |
– |
1800 |
54.5 |
39.3 |
13.00 |
11.00 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
—= Not Applicable.
Go to www.ari.org/aridirectory for the latest additional matches.
8 |
Unitary Products Group |
246819-BTG-H-0208
COOLING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils
|
FURNACE** |
|
COIL |
|
|
COOLING |
|
|
|
UNIT MODEL |
CFM RANGE |
|
|
RATED |
NET MBH |
|
|
||
|
W |
MODEL |
SEER1 |
EER |
|||||
|
(MIN.-MAX.) |
|
CFM |
|
|
||||
|
|
TOTAL |
SENS. |
||||||
|
|
|
|
|
|
||||
EABD-F018S |
450 |
|
14,17 |
FC/MC/PC/UC18 |
600 |
18.0 |
12.4 |
13.00 |
11.00 |
750 |
|
|
|
|
|
|
|
|
|
|
14 |
HC18 |
600 |
17.8 |
12.1 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
14,17 |
FC/MC/PC/UC24 |
800 |
23.2 |
16.7 |
13.00 |
11.00 |
|
600 |
|
14,17 |
FC/MC/PC/UC30 |
800 |
23.2 |
16.7 |
13.00 |
11.00 |
EABD-F024S |
|
14 |
HC30 |
760 |
23.4 |
16.6 |
13.00 |
11.00 |
|
1000 |
|
||||||||
|
|
– |
HD24 |
800 |
23.2 |
16.7 |
13.00 |
11.00 |
|
|
|
|
|||||||
|
|
|
17,21 |
FC/MC/PC35 |
1000 |
28.4 |
20.3 |
13.00 |
11.00 |
|
800 |
|
17,21 |
FC/MC/PC/UC42 |
1000 |
28.4 |
20.3 |
13.00 |
11.00 |
EABD-F030S |
|
17 |
HC36 |
950 |
28.0 |
19.6 |
13.00 |
11.00 |
|
1200 |
|
||||||||
|
|
– |
HD36 |
1000 |
28.6 |
20.3 |
13.00 |
11.00 |
|
|
|
|
|||||||
|
|
|
17,21 |
FC/MC/PC35 |
1000 |
28.0 |
20.0 |
13.00 |
11.00 |
EABD-(T,W)030S |
800 |
|
17,21 |
FC/MC/PC/UC42 |
1000 |
28.0 |
20.0 |
13.00 |
11.00 |
1200 |
|
|
|
|
|
|
|
|
|
|
17 |
HC36 |
950 |
27.6 |
19.3 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD36 |
1000 |
28.2 |
20.0 |
13.00 |
11.00 |
|
|
|
17,21 |
FC/MC/PC35 |
1200 |
34.6 |
25.3 |
13.00 |
11.00 |
|
|
|
17,21 |
FC/MC/PC/UC42 |
1200 |
34.6 |
25.3 |
13.00 |
11.00 |
EABD-F036S |
1000 |
|
21,24 |
FC/MC/PC/UC48 |
1200 |
35.0 |
25.6 |
13.00 |
11.00 |
1400 |
|
|
|
|
|
|
|
|
|
|
21 |
HC42 |
1140 |
34.4 |
24.5 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD36 |
1200 |
34.4 |
25.2 |
13.00 |
11.00 |
|
|
|
17,21 |
FC/MC/PC35 |
1200 |
34.0 |
24.8 |
13.00 |
11.00 |
|
1000 |
|
17,21 |
FC/MC/PC/UC42 |
1200 |
34.0 |
24.8 |
13.00 |
11.00 |
EABD-(T,W)036S |
|
|
|
|
|
|
|
|
|
|
21,24 |
FC/MC/PC/UC48 |
1200 |
34.4 |
25.1 |
13.00 |
11.00 |
||
1400 |
|
||||||||
|
|
21 |
HC42 |
1140 |
33.8 |
24.0 |
13.00 |
11.00 |
|
|
|
|
|||||||
|
|
|
– |
HD36 |
1200 |
33.8 |
24.7 |
13.00 |
11.00 |
EABD-F042S |
1200 |
|
21,24 |
FC/MC/PC/UC48 |
1400 |
41.0 |
30.8 |
13.00 |
11.00 |
1000 |
|
|
|
|
|
|
|
|
|
|
– |
HD48 |
1400 |
40.5 |
30.3 |
13.00 |
11.00 |
||
|
|
||||||||
EABD-(T,W)042S |
1200 |
|
21,24 |
FC/MC/PC/UC48 |
1400 |
40.0 |
30.0 |
13.00 |
11.00 |
1600 |
|
|
|
|
|
|
|
|
|
|
– |
HD48 |
1400 |
39.5 |
29.5 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
21,24 |
FC/MC/PC/UC60 |
1600 |
45.0 |
35.4 |
13.00 |
11.00 |
EABD-F048S |
1400 |
|
24 |
MC61 |
1600 |
46.0 |
35.5 |
13.00 |
11.00 |
1800 |
|
|
|
|
|
|
|
|
|
|
24 |
HC60 |
1520 |
45.5 |
34.3 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD60 |
1600 |
45.0 |
34.7 |
13.00 |
11.00 |
|
|
|
21,24 |
FC/MC/PC/UC60 |
1600 |
44.0 |
34.6 |
13.00 |
11.00 |
EABD-(T,W)048S |
1400 |
|
24 |
MC61 |
1600 |
45.0 |
34.7 |
13.00 |
11.00 |
1800 |
|
|
|
|
|
|
|
|
|
|
24 |
HC60 |
1520 |
44.5 |
33.5 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD60 |
1600 |
44.0 |
33.9 |
13.00 |
11.00 |
|
|
|
21,24 |
FC/MC/PC/UC60 |
1800 |
55.0 |
40.7 |
13.00 |
11.00 |
EABD-F060S |
1600 |
|
24 |
MC61 |
1800 |
55.5 |
41.0 |
13.00 |
11.00 |
2000 |
|
|
|
|
|
|
|
|
|
|
24 |
HC60 |
1710 |
54.5 |
39.7 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD60 |
1800 |
54.0 |
39.9 |
13.00 |
11.00 |
|
|
|
21,24 |
FC/MC/PC/UC60 |
1800 |
54.5 |
40.3 |
13.00 |
11.00 |
EABD-(T,W)060S |
1600 |
|
24 |
MC61 |
1800 |
55.0 |
40.6 |
13.00 |
11.00 |
2000 |
|
|
|
|
|
|
|
|
|
|
24 |
HC60 |
1710 |
54.0 |
39.3 |
13.00 |
11.00 |
||
|
|
||||||||
|
|
|
– |
HD60 |
1800 |
53.5 |
39.5 |
13.00 |
11.00 |
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.
Unitary Products Group |
9 |
246819-BTG-H-0208
COOLING CAPACITY - With Variable Speed Furnaces
|
VARIABLE SPEED |
COIL |
|
|
|
COOLING |
|
|
|
UNIT MODEL |
FURNACE MODEL |
MODEL1 |
W |
RATED |
NET MBH |
SEER |
EER |
||
|
|
|
|
CFM |
TOTAL |
SENS. |
|
|
|
|
1 PH 13 SEER HP WITH VARIABLE SPEED FURNACES2 |
|
|
|
|||||
|
(F,L)L8VA12 |
FC/MC/PC18A |
14 |
600 |
18.0 |
12.5 |
14.00 |
12.00 |
|
|
FL9VA12 |
FC/MC/PC18A |
14 |
600 |
18.0 |
12.5 |
14.00 |
12.00 |
|
EABD-F018S |
|
|
|
|
|
|
|
|
|
FL9(C,V)B12 |
FC/MC/PC18B |
17 |
600 |
18.0 |
12.6 |
14.00 |
12.00 |
||
|
(F,L)L8VA12 |
HC18 |
14 |
600 |
18.0 |
12.5 |
14.00 |
12.00 |
|
|
FL9VA12 |
HC18 |
14 |
600 |
18.0 |
12.5 |
14.00 |
12.00 |
|
|
(F,L)L8VA12 |
FC/MC/PC24A |
14 |
800 |
23.2 |
16.7 |
14.00 |
12.00 |
|
|
FL9VA12 |
FC/MC/PC24A |
14 |
800 |
23.2 |
16.7 |
14.00 |
12.00 |
|
|
FL9(C,V)B12 |
FC/MC/PC24B |
17 |
800 |
23.2 |
16.6 |
14.00 |
12.00 |
|
|
(F,L)L8VA12 |
FC/MC/PC30A |
14 |
800 |
23.2 |
16.7 |
14.00 |
12.00 |
|
EABD-F024S |
FL9VA12 |
FC/MC/PC30A |
14 |
800 |
23.2 |
16.7 |
14.00 |
12.00 |
|
FL9(C,V)B12 |
FC/MC/PC30B |
17 |
800 |
23.2 |
17.2 |
14.00 |
12.00 |
||
|
|||||||||
|
(F,L)L8VA12 |
HC30 |
14 |
800 |
23.2 |
17.2 |
14.00 |
12.00 |
|
|
FL9VA12 |
HC30 |
14 |
800 |
23.2 |
16.9 |
14.00 |
12.00 |
|
|
(F,L)L8VA12 |
HD30 |
– |
800 |
23.2 |
16.9 |
14.00 |
12.00 |
|
|
FL9VA12 |
HD30 |
– |
800 |
23.2 |
16.9 |
14.00 |
12.00 |
|
|
(F,L)L8VB16 |
FC/MC/PC35B |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
FL9(C,V)B12 |
FC/MC/PC35B |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
(F,L)L8VC16 |
FC/MC/PC35C |
21 |
1000 |
29.0 |
20.3 |
14.00 |
12.00 |
|
|
FL9(C,V)C16 |
FC/MC/PC35C |
21 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
(F,L)L8VB16 |
FC/MC/PC42B |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
EABD-F030S |
FL9(C,V)B12 |
FC/MC/PC42B |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
(F,L)L8VC16 |
FC/MC/PC42C |
21 |
1000 |
29.0 |
20.3 |
14.00 |
12.00 |
||
|
|||||||||
|
FL9(C,V)C16 |
FC/MC/PC42C |
21 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
(F,L)L8VB16 |
HC36 |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
FL9(C,V)B12 |
HC36 |
17 |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
(F,L)L8VB16 |
HD36 |
– |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
FL9(C,V)B12 |
HD36 |
– |
1000 |
29.0 |
20.4 |
14.00 |
12.00 |
|
|
(F,L)L8VB16 |
FC/MC/PC42B |
17 |
1200 |
35.2 |
25.7 |
13.50 |
11.00 |
|
|
FL9(C,V)B12 |
FC/MC/PC42B |
17 |
1200 |
35.2 |
25.7 |
13.25 |
11.00 |
|
|
(F,L)L8VC16 |
FC/MC/PC42C |
21 |
1200 |
35.2 |
25.6 |
13.75 |
11.00 |
|
|
(F,L)L8VC20 |
FC/MC/PC42C |
21 |
1200 |
35.2 |
25.6 |
14.00 |
12.00 |
|
|
FL9(C,V)C16 |
FC/MC/PC42C |
21 |
1200 |
35.0 |
25.5 |
13.25 |
11.00 |
|
|
FL9(C,V)C20 |
FC/MC/PC42C |
21 |
1200 |
35.0 |
25.4 |
13.50 |
11.00 |
|
|
(F,L)L8VC20 |
FC/MC/PC48C |
21 |
1200 |
35.4 |
25.7 |
14.00 |
12.00 |
|
EABD-F036S |
FL9(C,V)C16 |
FC/MC/PC48C |
21 |
1200 |
35.4 |
25.7 |
14.00 |
12.00 |
|
FL9(C,V)C20 |
FC/MC/PC48C |
21 |
1200 |
35.4 |
25.4 |
14.00 |
12.00 |
||
|
|||||||||
|
FL9(C,V)D20 |
FC/MC/PC48D |
24 |
1200 |
35.4 |
25.6 |
14.00 |
12.00 |
|
|
(F,L)L8VC20 |
HC42 |
21 |
1200 |
35.2 |
25.4 |
14.00 |
12.00 |
|
|
FL9(C,V)C16 |
HC42 |
21 |
1200 |
35.0 |
25.6 |
13.25 |
11.00 |
|
|
FL9(C,V)C20 |
HC42 |
21 |
1200 |
35.0 |
25.6 |
13.50 |
11.00 |
|
|
(F,L)L8VC20 |
HD36 |
– |
1200 |
35.2 |
25.8 |
14.00 |
12.00 |
|
|
FL9(C,V)C16 |
HD36 |
– |
1200 |
35.0 |
25.5 |
13.25 |
11.00 |
|
|
FL9(C,V)C20 |
HD36 |
– |
1200 |
35.0 |
25.6 |
13.50 |
11.00 |
|
|
(F,L)L8VC20 |
FC/MC/PC48C |
21 |
1400 |
41.0 |
30.9 |
13.50 |
11.00 |
|
|
FL9(C,V)C16 |
FC/MC/PC48C |
21 |
1400 |
41.0 |
30.9 |
13.50 |
11.00 |
|
|
FL9(C,V)C20 |
FC/MC/PC48C |
21 |
1400 |
41.0 |
30.9 |
13.50 |
11.00 |
|
EABD-F042S |
|
|
|
|
|
|
|
|
|
FL9(C,V)D20 |
FC/MC/PC48D |
24 |
1400 |
41.0 |
30.9 |
13.50 |
11.00 |
||
|
(F,L)L8VC20 |
HD48 |
– |
1400 |
40.0 |
30.2 |
13.50 |
11.00 |
|
|
FL9(C,V)C16 |
HD48 |
– |
1400 |
40.5 |
30.6 |
13.25 |
11.00 |
|
|
FL9(C,V)C20 |
HD48 |
– |
1400 |
40.0 |
30.1 |
13.25 |
11.00 |
For Notes See Page 11
10 |
Unitary Products Group |