GENERAL

The LA/LB line is a flexible performer. LA300, LB360 & 480 can be positioned in up to 12 different positions and suspended in various positions. The LB600 can be positioned in up to 7 different arrangements and suspended also. The LA/ LB line will give you the power to condition large amounts of building space and the ability to conform to almost any situation.

FEATURING

EASE OF SERVICE

PUMP-OUT ON START-UP

BASE SECTIONS (25, 30 & 40 Ton only)

SUSPENSION PACKAGES

HOT WATER COILS

STEAM COILS (LA300 & LB360 only)

WIDE RANGE OF BLOWER MOTORS

A VARIETY OF DRIVE PACKAGES

CONTROL BOX WITH LOW VOLTAGE TRANSFORMER AND MOTOR STARTER (motor, motor drive kit and motor overloads sold separately).

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 MODULAR DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-MOUNTED COMPONENTS . . . . . . . . . . 4 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 23

LIST OF FIGURES

Fig.

Pg.

1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 2 UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 4 3 DETAILS FOR SECURING BOTTOM MOUNTING

SUPPORTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4 LA300/LB360 WEIGHT DISTRIBUTION . . . . . . . . . 6 5 UNIT DIMENSIONS - LA300, LB360 & LB480 . . . . 11 6 25 TON LIQUID LINE SOLENOID

WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 7 30, 40 & 50 TON LIQUID LINE

SOLENOID WIRING . . . . . . . . . . . . . . . . . . . . . . . . 11 8 LA300 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12 9 LB360 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12 10 LB480 PIPING CONNECTIONS . . . . . . . . . . . . . . . 12 11 UNIT DIMENSIONS - LB600 . . . . . . . . . . . . . . . . . . 13 12 LB600 PIPING CONNECTIONS - END PANEL

DETAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 13 HOT WATER COIL DIMENSIONS . . . . . . . . . . . . . 14 14 STEAM COIL DIMENSIONS . . . . . . . . . . . . . . . . . . 14 15 BASE SECTION DIMENSIONS . . . . . . . . . . . . . . . 14 16 BLOWER CURVE LA300 & LB360 . . . . . . . . . . . . . 19 17 BLOWER CURVE LB480 . . . . . . . . . . . . . . . . . . . . 21 18 BLOWER CURVE LB600 . . . . . . . . . . . . . . . . . . . . 22

036-21335-002-A-1102

LIST OF TABLES

Tbl.

Pg.

1 STATIC RESISTANCES FOR UNIT ACCESSORIES . 5 2 UNIT MOUNTING DIMENSIONS . . . . . . . . . . . . . . . . . 5 3 CORNER WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4 ACCESSORY OPERATING WEIGHT DISTRIBUTION

(LBS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5 UNIT BLOWER MOTOR DATA . . . . . . . . . . . . . . . . . . 7 6 UNIT DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 7 MOTOR OVERLOAD ELEMENTS . . . . . . . . . . . . . . . . 8 8 HOT WATER COIL CAPACITIES. . . . . . . . . . . . . . . . . 9 9 CAPACITY CORRECTION & PRESSURE DROP

VS GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 10 STEAM COIL CAPACITIES (LA300 & LB360 ONLY) 10 11 CORRECTION FACTORS FOR HIGH STEAM . . . . . 10 12 UNIT DIMENSIONS - LA300, LB360 & LB480 . . . . . 11 13 HOT WATER COIL DIMENSIONS . . . . . . . . . . . . . . . 14 14 STEAM COIL DIMENSIONS . . . . . . . . . . . . . . . . . . . 14 15 BASE SECTIONS DIMENSIONS . . . . . . . . . . . . . . . . 15 16 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 17 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 17 18 FAN PERFORMANCE DATA (25 TON) . . . . . . . . . . . 18 19 FAN PERFORMANCE DATA (30 TON) . . . . . . . . . . . 18 20 FAN PERFORMANCE DATA (40 TON) . . . . . . . . . . . 20 21 FAN PERFORMANCE DATA (50 TON) . . . . . . . . . . . 20

2

Unitary Products Group

036-21335-002-A-1102

YORK SPLIT INDOOR PRODUCT NOMENCLATURE

L A 300 C 00 A 6 A AA 1 A

Model #

Model Number

Options

 

 

Description

 

 

 

 

 

 

L

Product Category

L = Air Handling Unit - Cooling

F = Air Handling Unit - Heat Pump

 

 

 

A

Product Identifier

A = R-22 Standard Efficiency 2-Pipe

B = R-22 Standard Efficiency 4-Pipe

 

 

 

 

 

 

 

Nominal Cooling

300 = 25 Ton

 

 

360 = 30 Ton

 

300

Capacity

 

480 = 40 Ton

 

 

MBH

 

 

600 = 50 Ton

 

 

 

 

 

 

 

 

C

Heat Type

C = Cooling Only

 

 

 

 

 

00

Nominal Heating

00 = No Heat Installed

 

Capacity

 

 

 

 

 

 

 

 

 

A

Airflow Options

A = None

 

 

 

 

 

6

Voltage

0 = None

6 = 208/230-460-3-60

5 = 575-3-60

 

 

 

 

 

 

 

 

A

Factory Options

A = None

 

 

 

 

 

AA

Special Options

AA = None

 

 

 

 

 

1

Product Generation

1 = First Generation

2 = Second Generation

 

 

 

 

FIGURE 1: PRODUCT NOMENCLATURE

NOTE: LB600 matches with both HB480 and HB600 Outdoor Condensing Units for maximum efficiency.

NOTE: LB480 Indoor and HB480 Outdoor Units do match up, but do not meet ASHRAE 90.1 standards for efficiency.

Unitary Products Group

3

DESCRIPTION

Evaporator blower units are designed with two distinct modules to provide maximum application flexibility. The 25, 30 and 40 ton units are shipped as single packages with the blower module mounted on top of the coil module, The blower module can be repositioned in the field to meet almost any installation requirement. Blower and coil modules for the 50 ton units are shipped separately to simplify handling. These modules can be connected in the field with the same flexibility as the smaller units.

The blower module includes the blower wheels and room for a field-mounted motor and drive. The coil module includes direct expansion coils, 2 in. throwaway filters, liquid line solenoid valves for both capacity reduction and pumpdown, thermal expansion valves, distributors and a condensate drain pan.

Every evaporator coil is pressurized with air to 325 psig and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressurized with a combination of Refrigerant-22 and nitrogen to 150 psig for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it is pressurized with a holding charge of Refrigerant-22 for storage and/or shipping.

Steam coils, hot water coils, base sections, suspension hardware, blower motors and drive packages are available as field-installed accessories to provide additional application flexibility.

These evaporator blowers, combined with condensing units, provide years of quiet, efficient and dependable operation. These units are manufactured under ISO 9001 Quality System Certification.

For Indoor Unit Installation details, please see document 035- 18496-000.

MODULAR DESIGN

These evaporator blowers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position.

FIGURE 2: UNIT INSTALLATION

036-21335-002-A-1102

Figure 2 shows three of the common installation arrangements. Refer to the unit installation instructions for other possibilities.

Units may be bottom-supported or ceiling-suspended and can be arranged to meet almost any space or duct requirements. Each unit is available with a choice of blower motors, drive packages and other accessories to make them suitable for most applications.

FACTORY-MOUNTED COMPONENTS

PART LOAD OPERATION These evaporator blowers have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacity reduction not only provides economical operation, but also maintains more even temperature and humidity levels in the conditioned space.

EASY SERVICE Serviceable expansion valves are provided on every unit. These superior valves are factory-installed to provide many years of trouble-free operation. If service is required, it is not necessary to unbraze any joints.

PUMP-OUT Evaporator blowers include a solenoid valve for non-recycling pump-out. When a cooling requirement in the conditioned space is needed, the refrigerant is pumped into the high side of the system before unit start-up.

ACCESSORIES

BASE SECTIONS (25, 30 and 40 ton only: Base sections can be used to elevate units above the floor. If desired, outdoor air may be introduced through these sections by cutting an access opening to accommodate the outdoor air duct connection. These bases have a durable finish to match the evaporator blower unit. They may have to be insulated for certain applications.

SUSPENSION PACKAGES: These accessories can be used to suspend horizontal units from above without interfering with access to the unit. They can also be used for elevating a floor-mounted unit (either horizontal or vertical) to provide additional height for the installation of a trap at the condensate drain connection. All suspension packages can be used with vibration isolators.

HOT WATER COILS: Drainable water coils are available for field installation between the blower and the coil modules of both horizontal and vertical units. Since their casings match the dimensions and the finish of the basic units, they become an integral part of the unit after installation. The coils slide out of their casings for easy installation. Coils have copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. Coils are leak-tested at 325 psig under water and dried before their connections are capped for storage and shipping.

4

Unitary Products Group

036-21335-002-A-1102

STEAM COILS (LA300 & LB360 only): A steam coil is available on the 25 & 30 Ton for installation between the blower and coil modules of both horizontal and vertical units. Since the casing matches the dimensions and the finish of the basic unit, it becomes an integral part of the unit after installation. The coil slides out of the casings for easy installation and is pitched in the casings to facilitate condensate drainage. The coil has copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. The coil is leak-tested at 325 psig and dried before the connections are capped for storage and shipping.

BLOWER MOTORS: Different HP motors are available for each unit to meet almost any air delivery requirement. All motors are UL approved, have permanently lubricated ball bearings and are field-mounted within the insulated cabinet of the units to minimize the transmission of sound to the sur-

rounding space. 5 HP motors are inherently protected. 7.5 HP - 15 HP require motor overload protection.

DRIVE PACKAGES: Different size pulleys and belts are available for each unit to provide a blower RPM range to meet almost any air delivery requirement. Variable pitch motor pulleys can be adjusted to provide the proper blower RPM. All drive packages are rated at least 25% above the nominal HP rating of the blower motor. Two-groove pulleys and two belts are provided on every drive package rated at 5 HP and above.

STARTERS AND HEATER ELEMENTS (7.5 - 15 HP): The blower motors that are available for the units do not have inherent protection and require external motor overload protection. See details in Table 7.

TABLE 1: STATIC RESISTANCES FOR UNIT ACCESSORIES

UNIT MODEL

ACCESSORY

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

8,000

9,000

10,000

11,000

12,000

LA300

 

 

 

 

 

 

Hot Water Coil

0.06

0.07

0.08

0.09

0.10

 

Steam Coil

0.11

0.14

0.17

0.20

0.23

 

 

 

 

 

 

 

 

 

10,000

11,000

12,000

13,000

14,000

LB360

 

 

 

 

 

 

Hot Water Coil

0.08

0.09

0.10

0.12

0.14

 

Steam Coil

0.17

0.20

0.23

0.27

0.31

 

 

 

 

 

 

 

LB480

 

12,800

14,400

16,000

17,600

19,200

 

 

 

 

 

 

Hot Water Coil

0.11

0.13

0.15

0.17

0.20

 

 

 

 

 

 

 

 

LB600

 

16,000

18,000

20,000

22,000

24,000

 

 

 

 

 

 

Hot Water Coil

0.15

0.18

0.21

0.24

0.28

 

 

 

 

 

 

 

 

TABLE 2: UNIT MOUNTING DIMENSIONS1

LA/LB

 

DIMENSIONS, INCHES

 

UNIT

AX

BX

CX

 

 

 

 

300

69-1/4

49-1/16

26-5/8

 

 

 

 

 

 

 

360

69-1/4

49-1/16

26-5/8

 

 

 

 

 

 

 

480

84

50-9/16

34

 

 

 

1. See Figure 4 for dimensions AX, BX and CX.

Unitary Products Group

5

York LA300, 480, 600, LB360 User Manual

036-21335-002-A-1102

NOTE: The following illustration shows how the channels

should be secured to the unit using the hardware

provided with the suspension accessory.

(2)9/16 HOLES FOR 1/2 HANGER RODS

 

 

SUSPENSION

 

 

CHANNEL

5/16 NUT,

3

5/16 NUT,

LOCKWASHER,

 

FLATWASHER

 

FLATWASHER

3/8 NUT (USED

 

 

AS SPACER)

 

 

 

 

UNIT PANEL

 

 

5/16 BOLT,

 

 

FLAT-WASHER

SIDE

 

UNIT ANGLE

PANEL

 

 

FIGURE 3 : DETAILS FOR SECURING BOTTOM MOUNTING SUPPORTS

 

D

 

 

 

AX

BX

VERTICAL LA300, LB360, LB480

 

 

 

UNIT SUPPORTED FROM BELOW

A

 

BX

 

 

 

 

 

 

3

 

 

 

 

 

 

C

 

 

 

 

B LOWE R

 

B LOWE R

 

 

S E C T IO N

 

1-1/2

 

 

S E C T IO N

 

 

 

 

E V AP . C OIL

B

 

E V AP .

HOR IZONT AL

S E C T IO N

 

 

C OIL

 

 

 

S E C T IO N

LE U360 O R 4 80

 

 

 

 

HE AT IN G C OIL

2

B

UNIT S US P E NDE D

 

 

 

 

 

F R OM A B OV E 3

 

 

 

 

 

 

 

A

CX 4 C

 

 

S US P E NS IO N

 

 

 

ANG LE S

1

BX

 

 

 

 

 

 

 

D

BX

T he s ame c hannels c an be used in e ither position. W hen used to

1support at vertical unit, these c hannels s hould be c ut to match the bottom dimension of the e vaporator c oil s ection.

T he s uspension c hannels have two s ets of mounting holes to

2accommodate horizontal units with or without a heating c oil. O n a horizontal unit without a heating c oil, th e s uspension c hannels will e xtend 3" beyond both e nds of the unit.

3

T he s ame c hannels c an be used to s upport a horizontal, fl oor-

mounted unit from below.

 

4

After these bottom c hannels a re c ut per N ote 1, a new h ole will have

to be drilled a t the c ut end if the unit is to be mounted on isolators .

 

FIGURE 4 : LA300/LB360 WEIGHT DISTRIBUTION

6

Unitary Products Group

036-21335-002-A-1102

TABLE 3: CORNER WEIGHTS

UNIT-

 

Unit Weight

 

 

 

 

 

MODEL

Shipping

 

Operation

Configuration

A

B

C

D

LA300

1180

 

1125

HORIZONTAL

276

317

285

247

 

 

 

 

 

 

 

VERTICAL

262

301

301

262

 

 

 

 

 

 

 

 

 

 

 

 

 

LB360

1180

 

1146

HORIZONTAL

281

323

290

252

 

 

 

 

 

 

 

VERTICAL

266

307

307

266

 

 

 

 

 

 

 

 

 

 

 

 

 

LB480

1510

 

1426

HORIZONTAL

348

414

361

303

 

 

 

 

 

 

 

VERTICAL

292

348

427

359

 

 

 

 

 

 

 

 

 

 

 

 

 

LB600

1572

 

1640

HORIZONTAL

451

386

370

433

 

 

 

 

 

 

 

VERTICAL

484

414

342

400

 

 

 

 

TABLE 4: ACCESSORY OPERATING WEIGHT DISTRIBUTION (LBS)1

ACCESSORY

LA300

LB360

LB480

LB600

 

 

 

 

 

BASE2

25

25

30

45

HOT WATER COIL

35

35

45

35

 

 

 

 

 

STEAM COIL 1 ROW

30

30

35

50

1.These weights should be added to each point load in table 3.

2.This accessory can only be applied on units installed in the vertical position.

TABLE 5: UNIT BLOWER MOTOR DATA

UNIT MODEL

HP

MOTOR KIT

FRAMESIZE

VOLTAGE

MODEL NUMBER

(3PH-60HZ)

 

 

 

 

 

 

 

 

 

 

2LR04605032

 

230/460

 

 

 

 

 

 

5

2LR04605023

184

208

LA300

 

 

 

 

 

2LR04605158

 

575

 

 

 

 

 

 

7.5

2LP04607133

213

230/460

 

 

 

 

2LP04607158

575

 

 

 

 

 

 

 

 

 

 

2LR04605032

 

230/460

 

 

 

 

 

 

5

2LR04605023

184

208

 

 

 

 

 

 

 

2LR04605158

 

575

LB360

 

 

 

 

7.5

2LP04607133

213

208/230/460

 

 

 

 

2LP04607158

575

 

 

 

 

 

 

 

 

 

10

2LP04610133

215

208/230/460

 

 

 

 

2LP04610158

575

 

 

 

 

 

 

 

 

 

7.5

2LP04607133

213

208/230/460

 

 

 

LB480

2LP04607158

575

 

 

 

 

 

 

10

2LP04610133

215

208/230/460

 

 

 

 

 

2LP04610158

575

 

 

 

 

 

 

 

 

 

10

2LP04610133

215

208/230/460

 

 

 

LB600

2LP04610158

575

 

 

 

 

 

 

15

2LP04615133

254

208/230/460

 

 

 

 

 

2LP04615158

575

 

 

 

 

 

 

 

 

Unitary Products Group

7

036-21335-002-A-1102

TABLE 6: UNIT DRIVE DATA

 

 

 

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

 

BELTS

 

DRIVE KIT

BLOWER

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

PITCH

 

MODEL

RPM

PITCH DIA.

BORE

PITCH DIA.

BORE

 

LENGTH

 

MODEL

NUMBER

RANGE

(IN.)

(IN.)

(IN.)

 

(IN.)

QTY.

(IN.)

DESIGNATION

 

 

 

 

 

 

 

 

 

 

 

 

1LD0440

600 - 750

4.0 - 5.0

1 1/8

12.0

1

3/16

2

63.3

A62

LA300

 

 

 

 

 

 

 

 

 

 

1LD0407

700 - 850

4.2 - 5.2

1 3/8

11.0

1

3/16

2

63.3

A62

 

 

 

 

 

 

 

 

 

 

 

 

1LD0442

780 - 940

5.3 - 6.3

1 3/8

12.0

1

3/16

2

63.3

A62

 

 

 

 

 

 

 

 

 

 

 

 

1LD0415

636 - 795

4.0 - 5.0

1 1/8

11.0

1

3/16

2

63.3

A62

LB360

 

 

 

 

 

 

 

 

 

 

1LD0407

668 - 827

4.2 - 5.2

1 3/8

11.0

1

3/16

2

63.3

A62

 

 

 

 

 

 

 

 

 

 

 

 

1LD0408

827 - 986

5.3 - 6.3

1 3/8

11.0

1

3/16

2

59.7

A59

 

 

 

 

 

 

 

 

 

 

 

LB480

1LD0409

607 - 776

4.3 - 5.5

1 3/8

12.4

1

3/16

2

85.1

B84

 

 

 

 

 

 

 

 

 

 

 

 

1LD0410

776 - 917

5.4 - 6.6

1 3/8

12.4

1

3/16

2

86.8

B85

 

 

 

 

 

 

 

 

 

 

 

LB600

1LD0411

692 - 833

4.8 - 6.0

1 3/8

12.4

1

3/16

2

78.6

B78

 

 

 

 

 

 

 

 

 

 

 

 

1LD0412

762 - 931

5.4 - 6.6

1 5/8

12.4

1

3/16

2

76.8

B75

 

 

 

 

 

 

 

 

 

 

 

TABLE 7: MOTOR OVERLOAD ELEMENTS1

MOTOR HP

VOLTAGE

MODEL NUMBER

 

 

 

 

208

2MP04704600

 

 

 

5

230

2MP04704600

 

 

460

2MP04704900

 

 

 

 

 

575

2MP04705000

 

 

 

 

208

2MP04703700

 

 

 

7.5

230

2MP04704500

 

 

460

2MP04704300

 

 

 

 

 

575

2MP04704000

 

 

 

 

208

2MP04701600

 

 

 

10

230

2MP04704100

 

 

460

2MP04704200

 

 

 

 

 

575

2MP04704300

 

 

 

 

208

2MP04704400

 

 

 

15

230

2MP04701700

 

 

460

2MP04704500

 

 

 

 

 

575

2MP04704600

 

 

 

1.These units are equipped from the factory with a correctly sized motor starter; overload elements are not factory supplied.

Do not operate the supply air blower motor above its nominal HP rating when a unit is equipped with a hot water coil accessory. Do not use steam in hot water coils.

Do not operate the supply air blower above its nominal HP rating when a unit is equipped with a steam coil accessory.

Although these coils are suitable for a much higher pressure, steam above 25 psig provides too much heat that could damage the blower motor.

Note: Three elements required per unit.