White Rodgers 36C User Manual

5 (2)

36C

Cycle Pilot Gas Valve

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

The 36C cycle pilot gas valves with redundant pilot solenoid main gas regulator, integral gas pressure switch and electrical connection on the gas valve for mercury flame sensor connection.

SPECIFICATIONS

Electrical Rating: 0.6 amps

Maximum Pressure Rating: 1/2 PSI (14.0” W.C.)

End to End Dimensions: 315/16

Agency: A.G.A. and C.G.A. design certified

Ambient Operating Range: –40 to +175°F (–40 to 79°C)

 

Outlet Pressure

 

 

 

 

 

1" Pressure Drop Capacity

 

 

 

Rated Range of Regulation

 

 

 

 

 

 

 

 

BTU/HR

 

 

 

 

 

 

BTU/HR

 

 

 

 

 

AGA STD. NAT GAS

 

 

LP GAS

 

 

AGA STD. NAT GAS

 

 

 

LP GAS

 

Pipe Size

 

1000 BTU/CU. FT.

 

2500 BTU/CU. FT.

 

1000 BTU/CU. FT.

 

 

2500 BTU/CU. FT.

1/2 X 3/8

 

 

100,000

 

 

162,000

 

 

15,000-100,000

 

 

 

15,000-162,000

1/2 X 1/2

 

 

230,000

 

 

372,600

 

 

30,000-290,000

 

 

 

30,000-469,000

1/2 X 3/4

 

 

230,000

 

 

372,600

 

 

30,000-290,000

 

 

 

30,000-469,000

3/4 X 3/4

 

 

280,000

 

 

453,600

 

 

50,000-400,000

 

 

 

50,000-648,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LP

 

 

 

 

 

 

 

 

 

Internal

 

 

 

 

 

 

 

 

 

Regulator

 

 

 

Conversion

 

 

 

Reducer

 

Inlet

 

 

Wiring

Model

Coil

 

Gas

Pipe

 

Opening

Regulator

Adjustment

Convertible

 

Kit

Line

Flow

 

Bushing

 

Pressure

 

Side

See

Number

Voltage

 

Type

Size

 

Characteristic

 

Setting

Range

 

Nat./LP

 

Included

Interrupter

Direction

 

 

Kit

 

Tap

 

Taps

Figure

36C84-912

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

Yes

 

Yes

No

Str. Thru

 

Yes

 

Yes

 

No

5

36C84-913

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

Yes

 

Yes

No

Str. Thru

 

Yes

 

Yes

 

No

7

36C84-916

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

No

 

No

No

Str. Thru

 

Yes

 

No

 

No

8

36C84-921

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

Yes

 

Yes

No

Str. Thru

 

Yes

 

Yes

 

No

5

36C84-923

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

No

 

No

No

Str. Thru

 

 

No

 

Yes

 

No

9

36C84-926

24 VAC

Natural

3/4 x 3/4

 

Fast Open

 

3.5”

2.5”–5.0”

 

No

 

No

No

Str. Thru

 

Yes

 

No

 

No

4

36C84-936

24 VAC

 

LP

3/4 x 3/4

 

Fast Open

 

11.0”

7.5”–12.0”

 

No

 

No

No

Str. Thru

 

Yes

 

No

 

No

4

36C87-944

24 VAC

Natural

3/4 x 3/4

Step Open 1.0

1.0”/3.5”

2.5”–5.0”

 

No

 

No

No

Str. Thru

 

Yes

 

No

 

No

6

36C94-906

24 VAC

Natural

3/4 x 3/4

Slow Open

 

3.5”

2.5”–5.0”

 

No

 

No

No

Str. Thru

 

Yes

 

No

 

No

5

36C94-907

24 VAC

Natural

3/4 x 3/4

Slow Open

 

3.5”

2.5”–5.0”

 

Yes

 

Yes

No

Str. Thru

 

Yes

 

No

 

No

4

Wiring diagrams – see pages 3-6

PART NO. 37-6517A

www.white-rodgers.com

0618

PRECAUTIONS

DO NOT BEGIN INSTALLATION UNTIL YOU READ THE FOLLOWING PRECAUTIONS.

! WARNING

 

If you do not follow these instructions exactly, a fire or explosion

 

may result causing property damage, personal injury or loss of life.

 

 

 

1.Failure to turn off electric or main gas supply to heating system could cause personal injury and/or property damage by shock, gas suffocation, fire, and/or explosion.

2.Do not use this control on circuits exceeding specified voltage. Higher voltage will damage the control and may cause shock or fire hazard.

3.NEVER USE FLAME OR ANY KIND OF SPARK TO CHECK FOR GAS LEAKS–COULD CAUSE FIRE AND/OR EXPLOSION.

4.Do not use a control set for natural gas with LP gas, or a control set for LP gas with natural gas. Personal injury and/or property damage, gas suffocation, fire, and/or explosion may result.

!CAUTION

1.Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring can cause equipment damage, property damage and/or personal injury.

2.This control is not intended for use in locations where it may come in direct contact with water. Suitable protection must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.).

INSTALLATION

NOTE

All piping must comply with local codes, ordinances, and/or national fuel gas codes.

1.Turn off electrical power to the system at the fuse box or circuit breaker. Also turn off the main gas supply.

2.If replacing an existing valve, disconnect all plumbing and electrical connections from the old control.

3.The control may be installed in any position except upside down (see figure 1). The arrow on the bottom plate indicates the direction of gas flow through the valve.

4.You should use new pipe that is properly chamfered, reamed, and free of burrs and chips. If you are using old pipe, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.

5.Apply pipe joint compound (pipe dope) or teflon tape that is approved for all gases, only to the male threads of the pipe joints. DO NOT apply compound or teflon tape to the first two threads (see figure 2 for typical piping connections).

6.If you are using a vise or open-end wrench to hold the valve while installing piping, do not tighten excessively, as this may damage the valve.

7.See wiring pages 3-6 when making electrical connections. After all gas and electrical connections are completed, turn gas on and check for gas leaks with leak detection solution or soap suds. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.

Upright, 90° from upright or vertical

 

INLET BOSS

UPRIGHT

UP OR DOWN

 

LEFT OR RIGHT

NOTE: Control shown may not be identical to replacement control.

Figure 1. Mounting positions

Drop

Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve

 

 

 

 

NOTE:

 

 

Riser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 in.

 

 

 

 

 

 

 

 

 

 

 

 

Always Include

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A Drip Leg In Piping

 

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tubing Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

Gas Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Riser

Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

minimum

 

 

 

 

 

 

 

 

 

 

Piped Gas

 

 

 

 

 

 

 

 

 

 

 

 

Piped Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2. Typical gas valve piping

2

White Rodgers 36C User Manual

INSTALLATION

PILOT GAS CONNECTION

Install fitting into pilot gas outlet (see figure 3), turning until finger-tight. Insert clean, deburred tubing all the way through the fitting. While holding the tubing securely, slowly tighten fitting until you feel a slight "give". Tighten the fitting an additional 1½ turns.

Pilot gas

PRESS

outlet

PILOT

 

TAP

Gas outlet

 

Figure 3

SYSTEM WIRING

NOTE

REFER TO AND FOLLOW THE APPLIANCE MANUFACTURER'S WIRING DIAGRAM. USE THE TABLE ON PAGE 1 TO IDENTIFY THE PROPER TERMINAL IDENTIFICATION FIGURE FOR THE GAS VALVE.

All wiring should be installed in accordance with local and national electrical codes and ordinances.

Always check that the electrical power supply used agrees with the voltage and frequency shown on the gas control.

Wiring for 36C84-926, -936 & 36C94-907 Gas Valves

Figure 4

GREEN

 

RED

WHITE

4

2

 

TAN

 

PRESSURE

REDUNDANT

SWITCH

 

COIL

TAN

 

TAN

RELAY COIL

C

36C84 GAS VALVE

S

 

 

 

 

 

MAIN VALVE RELAY

 

 

 

PILOT/REDUNDANT

PRESSURE

 

 

 

SWITCH

 

 

 

SOLENOID VALVE

 

 

 

 

 

 

 

N.O.

 

 

6

3

2

 

5

4

5059

 

 

Pilot

 

 

Relight

 

 

Control

T1

T2

 

 

24 VAC

LIMIT

 

THERMOSTAT

 

Cycle Pilot System

LINE

 

- For Natural Gas -

 

3098 MERCURY FLAME SENSOR

HOT

2

4

3 COLD

WIRING

HARNESS

Wiring Harness Available

For Natural Gas

Type Number

Length

F115-0060

12 in.

F115-0061

18 in.

F115-0062

24 in.

F115-0063

30 in.

F115-0064

36 in.

Wiring Harness consists of two wires, one tan the other black. Both leads are terminated with 1/4 inch female piggyback terminals

C

36C84 GAS VALVE

S

3098 MERCURY

 

 

 

 

 

FLAME SENSOR

 

MAIN VALVE RELAY

 

HOT

 

 

 

 

 

2

 

 

 

 

 

4

PILOT/REDUNDANT

PRESSURE

 

3

 

SOLENOID VALVE

 

SWITCH

 

COLD

 

 

 

N.O.

 

 

6

3

2

 

5

4

WIRING

HARNESS

Wiring Harness Available

For All Gases

Type Number

Length

F115-0055

12 in.

F115-0056

18 in.

F115-0057

24 in.

F115-0058

30 in.

F115-0059

36 in.

Wiring Harness consists of five wire cable in black sheathing. One end terminated in five-terminal connector for mating to 5022 or 50A22. Other end terminated with six terminal connector to mate with gas manifold.

BLUE

RED

TAN

5

4

2

WARP

 

 

SWITCH

 

 

DIODE

SCR

 

C

 

 

 

A

G

 

 

WARP SWITCH

 

 

HEATER

 

 

YELLOW ORANGE

3 1

5022 SAFETY

RESISTOR TIMER

5059 Pilot Relight

Control T1 T2

24 VAC

THERMOSTAT LIMIT

LINE

Cycle Pilot System

- For All Gases -