White Rodgers 1F80-361 User Manual

4.5 (2)

1F80-361

Programmable Electronic Digital Thermostat

INSTALLATION AND

OPERATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE

PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

Your new White-Rodgers 5-Day/1-Day/1-Day Digital Thermostat uses the technology of a solid-state microcomputer to provide precise time/temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs.

Features:

Separate 5-day (weekday), 1-day (Sat) and 1-day (Sun) programming with four separate time/temperature periods per day

Simultaneous heat and cool program storage

Preprogrammed temperature control

Backlit display

LCD continuously displays setpoint, and alternately displays time and room temperature

Temperature override until next program period

Manual program override (HOLD temperature)

Temporary HOLD

°F/°C convertibility

Temperature range 45° to 90°F

RC, RH, C, W, Y, G , O and B terminals

Optional C terminal (Dual Power option)

B and O terminals for single stage heat pumps (no auxiliary heat) or damper operation

Program storage in case of power loss

2 “AA” Energizer® alkaline batteries included

PRECAUTIONS

This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

! CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

! WARNING

Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.

Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.

Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.

SPECIFICATIONS

ELECTRICAL DATA

Electrical Rating:

8 to 30 VAC 50/60 Hz. or D.C.

0.05to 1.0 Amps (Load per terminal)

1.5Amps Maximum Total Load (All terminals combined)

THERMAL DATA

Setpoint Temperature Range:

45°F to 90°F (7°C to 32°C)

Operating Ambient Temperature Range:

32°F to 105°F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-4°F to 149°F

APPLICATIONS

For use with:

Standard heat/cool or heat only systems

Electric heat systems

Gas or oil fired systems

Gas systems with intermittent ignition devices (I.I.D.) and/or vent dampers

Hydronic (hot water or steam) systems

Single-stage heat pump systems (no auxiliary heat)

Millivolt systems

DO NOT USE WITH:

Multi-stage systems

Systems exceeding 30 VAC and 1.5 amps

3-wire zoned hydronic heating systems

White-Rodgers is a division

PART NO. 37-6621B

Replaces 37-6621A

of Emerson Electric Co.

0512

www.white-rodgers.com

 

INSTALLATION

REMOVE OLD THERMOSTAT

1.Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.

2.Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.

3.Identify each wire attached to the old thermostat using the labels enclosed with the new thermostat.

4.Disconnect the wires from old thermostat one at a time. DO

NOT LET WIRES FALL BACK INTO THE WALL.

5.Install new thermostat using the following procedures.

ATTENTION!

This product does not contain mercury. However, this product may replace a unit which contains mercury.

Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing nonabsorbent gloves, take up the spilled mercury with sand or other absorbent material and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.

Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.

ELECTRIC HEAT OR SINGLE-STAGE

HEAT PUMP SYSTEMS

This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If your system is an electric heat or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the ELECTRIC/GAS switch on the back of the thermostat (see fig. 1) and switch it to the ELECTRIC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person.

ATTACH THERMOSTAT BASE TO WALL

1.Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit. If necessary, move the electric heat switch (see ELECTRIC HEAT SYSTEMS, above).

2.Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 7).

3.Place base over hole in wall and mark mounting hole locations on wall using base as a template.

4.Move base out of the way. Drill mounting holes.

5.Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.

Screw anchors

Mounting

holes Mounting holes

Electric/Gas switch

Figure 1. Thermostat Base

6.Push excess wire into wall and plug hole with a fire-resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.

BATTERY LOCATION

2 "AA" alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries.

If “BATT” is displayed, the batteries are low and should be replaced with fresh "AA" Energizer® alkaline batteries. To replace batteries, install the batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.

HYDRONIC (HOT WATER OR STEAM)

HEATING SYSTEMS

This thermostat is set to operate properly with a forced-air heating system. If you have a hydronic heating system (a system that heats with hot water or steam), you must set the thermostat to operate properly with your system. Change the second option in the configuration menu to SL (see CONFIGURATION MENU, page 4).

CHECK THERMOSTAT OPERATION

If at any time during testing your system does not operate properly, contact a qualified service person.

Turn on power to the system.

Fan Operation

If your system does not have a G terminal connection, skip to

Heating System.

1.Move FAN switch to ON position. The blower should begin to operate.

2.Move FAN switch to AUTO position. The blower should stop immediately.

2

White Rodgers 1F80-361 User Manual

JUMPER

WIRE

THERMOSTAT

C

B

O

 

Y

G

W

 

 

RC

 

RH

SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

 

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

120 VAC

For 2-wire Heat only,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

attach to RH and W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2. Typical wiring diagram for

 

 

 

 

 

 

 

 

 

 

heat only,

3-wire, single transformer systems

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JUMPER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

THERMOSTAT

B

O

 

 

 

G

W

RC

RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

Figure 3. Typical wiring diagram for

 

 

cool only, 3-wire, single transformer systems

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED jumper wire (provided with thermostat) must be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connected between thermostat RH and RC terminals

 

JUMPER

 

 

 

 

 

 

 

 

for proper thermostat operation with this system.

 

 

 

 

 

 

 

 

 

 

 

 

WIRE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

B

O

 

 

G

W

 

 

RC

RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

Fan

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

 

Relay

 

System

 

 

 

 

 

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

 

120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

THERMOSTAT

CB O

Y

 

G

 

W

RC RH

 

SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

Cooling

 

Fan

 

Heating

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

120 VAC

 

System

 

Relay

 

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING TRANSFORMER

 

Figure 5. Typical wiring diagram for

heat/cool, 5-wire, two-transformer systems

 

 

 

 

JUMPER

JUMPER

 

 

 

 

 

 

 

 

 

 

WIRE

WIRE

 

 

 

 

 

 

CB O

Y

G

Reversing Compressor Fan

Valve* Contactor Relay

*Reversing valve is energized when the system switch is in the COOL position

THERMOSTAT

W RC RH

SYSTEM

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

24 VAC

 

 

 

 

120 VAC

 

 

 

 

 

 

 

Neutral

TRANSFORMER

Figure 6. Typical wiring diagram for heat pump with reversing valve energized in COOL

JUMPER

JUMPER

WIRE

WIRE

C

B O

Y

G

Reversing Compressor Fan

Valve* Contactor Relay

*Reversing valve is energized when the system switch is in the HEAT position

THERMOSTAT

W RC RH

SYSTEM

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

24 VAC

 

 

 

 

120 VAC

 

 

 

 

 

 

 

Neutral

TRANSFORMER

Figure 4. Typical wiring diagram for heat/cool, 4-wire, single transformer systems

Figure 7. Typical wiring diagram for heat pump with reversing valve energized in HEAT

The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year with fresh "AA" Energizer® alkaline batteries.

Heating System

1.Move SYSTEM switch to HEAT position. If the heating system has a standing pilot, be sure to light it.

2.Pressto adjust thermostat setting above room temperature. The heating system should begin to operate.

3.Press to adjust temperature setting below room temperature. The heating system should stop operating.

Cooling System

! CAUTION

To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.

1.Move SYSTEM switch to COOL position.

2.Press to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation

3.Press to adjust temperature setting above room temperature. The cooling system should stop operating.

3