Vector 6SE70 VC User Manual

4.5 (11)

Quick Startup Guide for SIMOVERT MASTERDRIVES 6SE70 VC

Vector Control

Section 1: Parameterization of Base Drive

Section 2: Parameterization of Rectifier

Section 3: Simovis Trace Setup Method

Section 4: When Should a Drive be re-Tuned

DROM-02069

We reserve the right to modify functions, technical data, standards, drawings and parameters.

We have checked the contents of this document to ensure that they coincide with the described hardware and software. However, deviations cannot be completely ruled-out, so we cannot guarantee complete conformance. However, the information in this document is regularly checked and the necessary corrections will be included in subsequent editions. We are thankful for any recommendations or suggestions.

e-mail: mailto:drives.support@sea.siemens.com

Page 2

Version 1.0 March 1, 2000

NOTE:

These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, please contact your local Siemens office.

Further, the contents of these instructions shall neither become a part of nor modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy & Automation. The warranty contained in the contract between the parties is the sole warranty of Siemens Energy & Automation. Any statements contained herein do not create new warranties nor modify the existing warranty.

Note:

This Quick Startup Guide is not an autonomous document, but is intended to direct users to the section in the Operating Instructions which are important for start-up. Thus, these brief instructions can only be completely valid when used in conjunction with the Operating Instructions. It is especially important to observe the warning and information regarding potential hazards in the Operating Instructions.

Warning:

Electrical equipment has parts an components which are at hazardous voltage levels.

If the warning information in the detailed Operating Instructions is not observed, this can result in severe bodily injury or material damage.

Only appropriately qualified personnel may work with this equipment.

These personnel must be knowledgeable with all of the warning information and service/maintenance measures of the Operating Instruction.

Perfect and safe operation of this equipment assumes professional transport, storage, erection and installation as well as careful operating control and service.

Version 1.0 March 1, 2000

Page 3

Page 4

Version 1.0 March 1, 2000

Section 1:

Parameterization of Base Unit

SIMOVERT MASTERDRIVES

6SE70 VC

Vector Control

1.1 Power Section Defintion

1.2 Factory Reset

1.3 Basic Start-up

1.3.1 Volts/Hz without encoder feedback 1.3.2 Volts/Hz with encoder feedback

1.3.3 Vector Control without encoder feedback 1.3.4 Vector Control with encoder feedback 1.4 Drive Control Word

1.5 Communication Board Configuration

Note: Refer to Operating Instruction Manual for power and control connections.

Version 1.0 March 1, 2000

Page 5

Page 6

Version 1.0 March 1, 2000

1.1 Power Section Definition

Note: Power Section is pre-defined at the factory. Power Section Definition is required if a new board CUVC board is put into the drive or boards are switched between units with different ratings. Drive should be defaulted and re-parameterized after Power Section Definition.

P060 = 8

P070 = ?

P060 = 1

Select “Power Section Definition”

Menu

Input Code for unit (PWE) (Refer to Compendium section 6.3 or use the bookmark “PWE Listing” or check the following table)

Return to Parameter Menu

Version 1.0 March 1, 2000

Page 7

Unit List

 

 

 

 

 

P070:

Parameter Value (PWE)

 

 

P072:

Rated Output Current in Amps

In[A]

 

Frequency Converter

 

 

 

 

AC-AC type

 

 

 

 

3 AC 200V to 230V

PWE

Order Number

In[A]*1

 

 

14

6SE7021-1CA60

10.6

 

 

21

6SE7021-3CA60

13.3

 

 

27

6SE7021-8CB60

17.7

 

 

32

6SE7022-3CB60

22.9

 

 

39

6SE7023-2CB60

32.2

 

 

48

6SE7024-4CC60

44.2

 

 

54

6SE7025-4CD60

54.0

 

 

64

6SE7027-0CD60

69.0

 

 

70

6SE7028-1CD60

81.0

 

 

13

6SE7031-0CE60

100.0

 

 

29

6SE7031-3CE60

131.0

 

 

41

6SE7031-6CE60

162.0

 

 

87

6SE7032-0CE60

202.0

Frequency Inverter

 

 

 

 

DC-AC type

 

 

 

 

DC 270V to 310V

PWE

Order Number

In[A]*1

 

 

15

6SE7021-1R60

10.6

 

 

22

6SE7021-3RA60

13.3

 

 

28

6SE7021-8RB60

17.7

 

 

33

6SE7022-3RB60

22.9

 

 

40

6SE7023-2RB60

32.2

 

 

49

6SE7024-4RC60

44.2

 

 

55

6SE7025-4RD60

54.0

 

 

65

6SE7027-0RD60

69.0

 

 

71

6SE7028-1RD60

81.0

 

 

20

6SE7031-0RE60

100.0

 

 

34

6SE7031-3RE60

131.0

 

 

86

6SE7031-6RE60

162.0

 

 

92

6SE7032-0RE60

202.0

Page 8

Version 1.0 March 1, 2000

Frequency Converter AC-AC type

3 AC

380V to 460V

PWE

PWE

Order Number

In[A]*1

Air Cooled

Water

 

 

 

Cooled

 

 

3

 

6SE7016-1EA61

6.1

9

 

6SE7018-0EA61

8.0

11

 

6SE7021-0EA61

10.2

18

 

6SE7021-3EB61

13.2

25

 

6SE7021-8EB61

17.5

35

 

6SE7022-6EC61

25.5

42

 

6SE7023-4EC61

34.0

46

 

6SE7023-8ED61

37.5

52

 

6SE7024-7ED61

47.0

56

 

6SE7026-0ED61

59.0

66

 

6SE7027-2ED61

72.0

74

 

6SE7031-0EE60

92.0

82

 

6SE7031-2EF60

124.0

90

 

6SE7031-5EF60

146.0

98

 

6SE7031-8EF60

186.0

102

 

6SE7032-1EG60

210.0

108

 

6SE7032-6EG60

260.0

112

 

6SE7033-2EG60

315.0

116

 

6SE7033-7EG60

370.0

147

233

6SE7035-1EK60

510.0

151

237

6SE7036-0EK60

590.0

164

168

6SE7037-0EK60

690.0

*1

Based on 3kHz carrier frequency setting, larger frames have maximum carrier

 

frequency restrictions

Version 1.0 March 1, 2000

Page 9

Frequency Inverter DC-AC type

DC 510V to 650V

PWE

PWE

Order Number

In[A]*1

Air Cooled

Water

 

 

 

Cooled

 

 

4

 

6SE7016-1TA61

6.1

10

 

6SE7018-0TA61

8.0

12

 

6SE7021-0TA61

10.2

19

 

6SE7021-3TB61

13.2

26

 

6SE7021-8TB61

17.5

36

 

6SE7022-6TC61

25.5

43

 

6SE7023-4TC61

34.0

47

 

6SE7023-8TD61

37.5

53

 

6SE7024-7TD61

47.0

57

 

6SE7026-0TD61

59.0

67

 

6SE7027-2TD61

72.0

75

 

6SE7031-0TE60

92.0

83

 

6SE7031-2TF60

124.0

91

 

6SE7031-5TF60

146.0

99

 

6SE7031-8TF60

186.0

103

 

6SE7032-1TG60

210.0

109

 

6SE7032-6TG60

260.0

113

 

6SE7033-2TG60

315.0

117

 

6SE7033-7TG60

370.0

120

206

6SE7035-1TJ60

510.0

123

209

6SE7036-0TJ60

590.0

126

212

6SE7037-0TK60

690.0

127

213

6SE7038-6TJ60

860.0

134

 

6SE7041-1TM60

1100.0

135

221

6SE7041-1TK60

1100.0

140

226

6SE7041-3TM60

1300.0

150

236

6SE7041-6TM60

1630.0

153

239

6SE7042-1TQ60

2090.0

154

199

6SE7041-3TL60

1300.0

163

167

6SE7037-0TJ60

690.0

181

247

6SE7038-6TS60

6450.0

185

250

6SE7041-1TS60

6270.0

194

244

6SE7042-5TN60

2470.0

Page 10

Version 1.0 March 1, 2000

Frequency Converter AC-AC type

3 AC

500V to 575V

PWE

PWE

Order Number

In[A]*1

Air Cooled

Water

 

 

 

Cooled

 

 

1

 

6SE7014-5FB61

4.5

5

 

6SE7016-2FB61

6.2

7

 

6SE7017-8FB61

7.8

16

 

6SE7021-1FB61

11.0

23

 

6SE7021-5FB61

15.1

30

 

6SE7022-2FC61

22.0

37

 

6SE7023-0FD61

29.0

44

 

6SE7023-4FD61

34.0

50

 

6SE7024-7FD61

46.5

60

 

6SE7026-1FE60

61.0

62

 

6SE7026-6FE60

66.0

68

 

6SE7028-0FF60

79.0

78

 

6SE7031-1FF60

108.0

84

 

6SE7031-3FG60

128.0

94

 

6SE7031-6FG60

156.0

100

 

6SE7032-0FG60

192.0

104

 

6SE7032-3FG60

225.0

136

222

6SE7033-0FK60

297.0

141

227

6SE7033-5FK60

354.0

143

229

6SE7034-5FK60

452.0

*1

Based on 3kHz carrier frequency setting, larger frames have maximum carrier

 

frequency restrictions

Version 1.0 March 1, 2000

Page 11

Frequency Inverter DC-AC type

DC 675V to 810V

PWE

PWE

Order Number

In[A]*1

Air Cooled

Water

 

 

 

Cooled

 

 

2

 

6SE7014-5UB61

4.5

6

 

6SE7016-2UB61

6.2

8

 

6SE7017-8UB61

7.8

17

 

6SE7021-1UB61

11.0

24

 

6SE7021-5UB61

15.1

31

 

6SE7022-2UC61

22.0

38

 

6SE7023-0UD61

29.0

45

 

6SE7023-4UD61

34.0

51

 

6SE7024-7UD61

46.5

61

 

6SE7026-1UE60

61.0

63

 

6SE7026-6UE60

66.0

69

 

6SE7028-0UF60

79.0

79

 

6SE7031-1UF60

108.0

85

 

6SE7031-3UG60

128.0

95

 

6SE7031-6UG60

156.0

101

 

6SE7032-0UG60

192.0

105

 

6SE7032-3UG60

225.0

110

200

6SE7033-0UJ60

297.0

114

202

6SE7033-5UJ60

354.0

118

204

6SE7034-5UJ60

452.0

121

207

6SE7035-7UK60

570.0

124

210

6SE7036-5UK60

650.0

128

214

6SE7038-6UK60

860.0

130

216

6SE7041-0UM60

990.0

132

218

6SE7041-1UM60

1080.0

138

224

6SE7041-2UM60

1230.0

144

230

6SE7041-4UM60

1400.0

 

 

6SE7041-4UQ60

 

148

234

6SE7042-1TQ60

1580.0

 

 

6SE7041-6UQ60

 

155

195

6SE7041-1UL60

1080.0

157

 

6SE7042-4ULJ60

2450.0

159

197

6SE7041-1UL60

1230.0

Page 12

Version 1.0 March 1, 2000

Frequency Inverter

 

 

 

 

DC-AC type

 

 

 

 

 

DC

PWE

PWE

Order Number

 

In[A]*1

675V to 810V

Air Cooled

Water

 

 

 

 

 

Cooled

 

 

 

 

161

 

6SE7043-3UR60

3270.0

 

165

 

6SE7044-1UR60

4090.0

 

169

 

6SE7044-8UR60

4900.0

 

173

 

6SE7045-7UR60

5720.0

 

177

 

6SE7046-5UR60

6540.0

 

179

245

6SE7036-5UR60

4940.0

 

182

248

6SE7038-6US60

6540.0

 

186

251

6SE7041-1US60

6160.0

 

188

253

6SE7041-2US60

5840.0

 

190

240

6SE7042-1UN60

2050.0

 

192

242

6SE7042-3UN60

2340.0

Frequency Converter

 

 

 

 

AC-AC type

 

 

 

 

 

3 AC

PWE

PWE

Order Number

 

In[A]*1

660V to 690V

Air Cooled

Water

 

 

 

 

 

Cooled

 

 

 

 

58

 

6SE7026-0HF60

55.0

 

72

 

6SE7028-2HF60

82.0

 

76

 

6SE7031-0HG60

97.0

 

80

 

6SE7031-2HF60

118.0

 

88

 

6SE7031-5HF60

145.0

 

96

 

6SE7031-7HG60

171.0

 

106

 

6SE7032-1HG60

208.0

 

137

223

6SE7033-0HK60

297.0

 

142

228

6SE7033-5HK60

354.0

 

146

232

6SE7034-5HK60

452.0

Frequency Inverter

 

 

 

 

DC-AC type

 

 

 

 

 

DC

PWE

PWE

Order Number

 

In[A]*1

890V to 930V

Air Cooled

Water

 

 

 

 

 

Cooled

 

 

 

 

59

 

6SE7026-0WF60

 

60.0

 

73

 

6SE7028-2WF60

 

82.0

Version 1.0 March 1, 2000

Page 13

DC

PWE

PWE

Order Number

In[A]*1

890V to 930V

Air Cooled

Water

 

 

 

 

Cooled

 

 

 

 

 

 

 

 

77

 

6SE7031-0WG60

97.0

 

81

 

6SE7031-2WF60

118.0

 

89

 

6SE7031-5WF60

145.0

 

97

 

6SE7031-7WG60

171.0

 

107

 

6SE7032-1WG60

208.0

 

111

201

6SE7033-0WJ60

297.0

 

115

203

6SE7033-5WJ60

354.0

 

119

205

6SE7034-5WJ60

452.0

 

122

208

6SE7035-7WK60

570.0

 

125

211

6SE7036-5WK60

650.0

 

129

215

6SE7038-6WK60

860.0

 

131

217

6SE7041-0WM60

990.0

 

133

219

6SE7041-1WM60

1080.0

 

139

225

6SE7041-2WM60

1230.0

 

145

231

6SE7041-4WM60

1400.0

 

 

 

6SE70414WQ60

 

 

149

235

6SE7041-6WM60

1580.0

 

 

 

6SE7041-6WM60

 

 

152

238

6SE7034-5WK60

452.0

 

156

196

6SE7041-1WL60

1080.0

 

158

 

6SE7042-4WR60

2450.0

 

160

198

6SE7041-2WL60

1230.0

 

162

 

6SE7043-3WR60

3270.0

 

166

 

6SE7044-1WR60

4090.0

 

170

 

6SE7044-8WR60

4900.0

 

174

 

6SE7045-7WR60

5720.0

 

178

 

6SE7046-5WR60

6540.0

 

180

246

6SE7036-5WS60

4940.0

 

183

249

6SE7038-6WS60

6540.0

 

187

252

6SE7041-1WS60

6160.0

 

189

254

6SE7041-2WS60

5840.0

 

191

241

6SE7042-1WN60

2050.0

 

193

243

6SE7042-3WN60

2340.0

Page 14

Version 1.0 March 1, 2000

1.2 Factory Reset

P053 = 6

P060 = 2

P366 = 0

P970 = 0

6: Parameter Changes permitted via PMU and Serial Interface (OP1 and PC)

2: Menu Select = Fixed Settings

Select Factory Setting

0: Standard

Start Parameter Reset

0:Parameter Reset

1:No Parameter Change

Version 1.0 March 1, 2000

Page 15

Page 16

Version 1.0 March 1, 2000

1.3 Basic Start-up without Motor Connected to Load

1.3.1 Volts/Hz without Encoder

P060 = 5

P071 = ?

P095 = ?

 

 

 

 

 

P095 =

2

10 or 11

 

 

 

 

 

P097 = ?

P101 = 460

P102 = xxx

P060=5

Select “Drive Settings”

P071 = Input Line Voltage AC-AC Converter=460Volt DC-AC Inverter = 620Volt

P095 = Select Motor Type

2: Asynchronous 1PH7 Motor

10:IEC Induction Motor

11:NEMA Induction Motor

P097 = Motor Code number for 1PH7 motor (See Appendix)

Motor Nameplate Information

P101= Motor Voltage (V)

P102 = Motor Rated Current (A)

P095 =

10

 

11

 

P104

= Cos (phi) per nameplate

 

 

 

 

 

 

 

 

 

 

 

 

P105

= Rated Horsepower

P104 = ?

 

P105 = ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Version 1.0 March 1, 2000

Page 17

Vector 6SE70 VC User Manual

 

P106 = ?

P107

= 60

P108 = xxxx

P115

= 1

P340 = 3

P383 = xxxx

P452 = 100

P106 = NEMA Motor Nameplated efficiency (if unknown set =0.8)

P107 = Rated Motor Frequency

P108 = Nameplated Rotor RPM

P115 = 1

“Automatic Parameterization”

P340 = Carrier Frequency

Low # = Cooler Motor and Drive High # = Lower Motor Noise

P383 = Motor Thermal Time Constant. If constant unknown use general guidelines;

2 Pole Motor = 480 seconds

4 Pole Motor = 600 seconds

6 Pole Motor = 720 seconds

P452 = Maximum Forward Speed in

Percentage (usually 100%)

Page 18

Version 1.0 March 1, 2000