Troy-Bilt 1919 User Manual

4 (1)
Troy-Bilt 1919 User Manual

Owner’s Manual / Manual del Propietario

Portable Generator / Generador Portátil

Model / Modelo 01919

CAUTION

Before using this product, read this manual and follow all Safety Rules and Operating Instructions.

PRECAUCIÓN

Antes de utilizar el producto, lea este manual y siga todas las Reglas de Seguridad e Instrucciones de Uso.

Questions? Preguntas?

Helpline - 1-888-611-6708 M-F 8-5 CT

Troy-Bilt® is a registered trademark of Troy-Bilt, LLC and is used under license to Briggs & Stratton Power Products. Troy-Bilt® es una marca registrada registrada de Troy-Bilt, LLC y se usa abajo licencia a Briggs & Stratton Power Products.

BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC

JEFFERSON,WISCONSIN, U.S.A.

Printed in USA

Manual No. 192258GS Revision 8 (04/12/2005)

Section

Safety Rules

 

1

SAVE THESE INSTRUCTIONS

TABLE OF CONTENTS

Safety Rules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4

Know Your Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

EQUIPMENT

DESCRIPTION

Read this manual carefully and become familiar with your generator. Know its applications, its limitations and any hazards involved.

This manual describes an engine–driven, revolving field, alternating current (AC) generator designed to supply electrical power for operating compatible electrical lighting, appliances, tools and motor loads.The generator’s revolving field is driven at about 3,600 rpm by a single-cylinder engine.

SAFETY RULES

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

The safety alert symbol () is used with a signal word (DANGER, CAUTION,WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. CAUTION, when used without the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.

WARNING

The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.

CAUTION! DO NOT exceed the generator’s wattage/amperage capacity. See “Don’t Overload Generator”.

Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter or otherwise improve the product and this document at any time without prior notice.

The Emission Control System for this generator is warranted for standards set by the Environmental Protection Agency. For warranty information refer to the engine owner’s manual.

Copyright © 2005 Briggs & Stratton Power Products Group, LLC. All rights reserved. No part of this material may be reproduced or transmitted in any form by any means without the express written permission of Briggs & Stratton Power Products Group, LLC.

Hazard Symbols and Meanings

Electrocution

Electrical Shock

Electrical Shock

Explosion

Fire

Toxic Fumes

Kickback

Hot Surface

2

Section 1: Safety Rules

WARNING

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide will cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).

WARNING

Generator produces powerful voltage.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.

Use a ground circuit fault interrupter (GFCI) in any damp or

highly conductive area, such as metal decking or steel work.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT operate generator in the rain.

DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

DO NOT allow unqualified persons or children to operate or service generator.

WARNING

Rapid retraction of starter cord (kickback) will pull hand and arm toward engine faster than you can let go.

Broken bones, fractures, bruises or sprains could result.

When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.

NEVER start or stop engine with electrical devices plugged in and turned on.

WARNING

Fuel and its vapors are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

WHEN ADDING OR DRAINING FUEL

Turn generator OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.

Fill or drain fuel tank outdoors.

DO NOT overfill tank.Allow space for fuel expansion.

Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.

DO NOT light a cigarette or smoke.

WHEN STARTING EQUIPMENT

• Ensure spark plug, muffler, fuel cap and air cleaner are in place.

DO NOT crank engine with spark plug removed.

If fuel spills, wait until it evaporates before starting engine.

WHEN OPERATING EQUIPMENT

Do not tip engine or equipment at angle which causes fuel to spill.

This generator is not for use in mobile equipment or marine applications.

WHEN TRANSPORTING OR REPAIRING EQUIPMENT

Transport/repair with fuel tank EMPTY or with fuel shutoff valve OFF.

Disconnect spark plug wire.

WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK

Store away from furnaces, stoves, water heaters, clothes dryers or other appliances that have pilot light or other ignition source because they can ignite fuel vapors.

WARNING

This generator does not meet U. S. Coast Guard Regulation 33CFR-183 and should not be used on marine applications.

Failure to use the appropriate U. S. Coast Guard approved generator could result in bodily injury and/or property damage.

3

Section 1: Safety Rules

WARNING

Unintentional sparking can result in fire or electric shock.

WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR

Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.

WHEN TESTING FOR ENGINE SPARK

Use approved spark plug tester.

DO NOT check for spark with spark plug removed.

WARNING

Running engines produce heat.Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).

Severe burns can occur on contact.

Combustible debris, such as leaves, grass, brush, etc. can catch fire.

DO NOT touch hot surfaces.

Allow equipment to cool before touching.

The generator must be at least 5 feet from structures having combustible walls and/or other combustible materials.

Keep at least 3 feet of clearance on all sides of generator for adequate cooling, maintenance and servicing.

In the State of California a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands. If you equip the muffler with a spark arrester, it must be maintained in effective working order.

CAUTION

Excessively high operating speeds increase risk of injury and damage to generator.

Excessively low speeds impose a heavy load.

DO NOT tamper with governed speed. Generator supplies correct rated frequency and voltage when running at governed speed.

DO NOT modify generator in any way.

CAUTION

Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.

See “Don’t Overload Generator”.

Start generator and let engine stabilize before connecting electrical loads.

Connect electrical loads in OFF position, then turn ON for operation.

Turn electrical loads OFF and disconnect from generator before stopping generator.

CAUTION

Improper treatment of generator can damage it and shorten its life.

Use generator only for intended uses.

If you have questions about intended use, ask dealer or call 1-888-611-6708.

Operate generator only on level surfaces.

DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.

DO NOT insert any objects through cooling slots.

If connected devices overheat, turn them off and disconnect them from generator.

Shut off generator if:

-electrical output is lost;

-equipment sparks, smokes, or emits flames; -unit vibrates excessively.

4

Features and Controls Section

2

KNOW YOUR GENERATOR

Read this owner’s manual and safety rules before operating your generator.

Compare this illustration with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.

Data Tag

Fuel Tank

Spark Arrester Muffler

Choke Lever

 

 

Circuit

Air Cleaner

Breakers (AC)

 

120/240 Volt AC,

30 Amp

Receptacle

Recoil Starter

Grounding Fastener

120 Volt AC, 20 Amp

Duplex Receptacles

Rocker Switch (on engine shroud)

Oil Fill

120 Volt AC, 20 Amp, Duplex Receptacles — May be used to supply electrical power for the operation of

120 Volt AC, 20 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.

120/240 Volt AC, 30 Amp Locking Receptacle — May be used to supply electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.

Air Cleaner — Protects engine by filtering dust and debris out of intake air.

Choke Lever — Used when starting a cold engine.

Circuit Breakers (AC) — Push to reset circuit breakers are provided to protect the generator against electrical overload.

Data Tag — Provides model, revision and serial number of generator. Please have these readily available when calling for assistance.

Fuel Tank — Capacity of five (5) U.S. gallons.

Grounding Fastener — If required, please consult a qualified electrician, electrical inspector, or local agency having jurisdiction.

Oil Fill — Add engine oil here.

Recoil starter — Used to start the engine.

Rocker Switch — Set this switch to "On" before using recoil starter. Set switch to "Off" to switch off engine.

Spark Arrester Muffler — Exhaust muffler lowers engine noise and is equipped with a spark arrester screen.

5

Section Assembly

3

ASSEMBLY

Your generator requires some assembly and is ready for use after it has been properly serviced with the recommended oil and fuel.

If you have any problems with the assembly of your generator, please call the generator helpline at 1-888-611-6708.

Remove Generator From Carton

1.Set carton on a rigid flat surface with “This Side Up” arrows pointing upward.

2.Carefully open top flaps of shipping carton.

3.Cut down corners at one end of carton from top to bottom and lay that side of carton down flat.

4.Remove all packing material, carton fillers, etc.

5.Remove generator from shipping carton.

Install Wheel Kit

The wheel kit is designed to greatly improve the portability of your generator.

NOTE: Wheel kit is not intended for over-the-road use. You will need a socket wrench with 1/2" or 13mm sockets and a needle-nose pliers to install this kit.

1.Place bottom of generator cradle on a flat, even surface.Temporarily place unit on blocks to ease assembly.

2.Slide axle through both axle mounting brackets on cradle frame, as shown in Figure 1.

3.Slide a wheel over axle.

NOTE: Be sure to install both wheels with the air pressure valve on the outboard side.

4.Place e-ring onto groove in axle.You may add the flat washer if desired.

Figure 1 — Install Wheel Kit

Cap Screw

Hex Nut

Flat Washer

Handle Assembly

Axle

 

Support Leg

Cap Screw

 

 

 

Hex Nut

Wheel

E-Ring

 

 

6

Section 3: Assembly

5.Place one end of needle nose pliers on bottom of axle and other end of pliers on top of e-ring. Seat e-ring by pressing pliers closed.

6.Repeat step 3 through 5 to secure second wheel.

8.To aid support leg assembly, rest generator on cradle, engine end down. Attach support leg with two

M8 x 16mm cap screws and two locking hex nuts as shown.

9.Use two 13 mm wrenches to tighten leg hardware. Rest generator on wheels and support leg.

10.Center handle bracket on generator frame at support leg end of cradle, as shown.

11.Attach handle bracket with two M8 x 45mm cap screws and two locking hex nuts.

12.Check that all fasteners are tight and the tires are inflated to value marked on tire or within 15 and 40 psi.

BEFORE STARTING THE ENGINE

Add Engine Oil

• Place generator on a level surface.

CAUTION

Any attempt to crank or start the engine before it has been properly filled with the recommended oil will result in equipment failure.

Refer to engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void warranty.

Refer to engine owner’s manual and follow oil recommendations and instructions.

NOTE: Check oil often during engine break–in. Refer to engine owner’s manual for recommendations.

NOTE: The generator assembly rotates on a prelubricated and sealed ball bearing that requires no additional lubrication for the life of the bearing.

Add Fuel

NOTE: This gasoline engine is certified to operate on gasoline. Exhaust Emission Control System: EM (Engine Modifications).

WARNING

Fuel and its vapors are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

WHEN ADDING FUEL

Turn generator OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.

Fill fuel tank outdoors.

DO NOT overfill tank.Allow space for fuel expansion.

Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.

DO NOT light a cigarette or smoke.

1.Use clean, fresh, regular UNLEADED fuel with a minimum of 85 octane. DO NOT use fuel which contains Methanol. DO NOT mix oil with fuel.

2.Clean area around fuel fill cap, remove cap.

3.Slowly add regular unleaded fuel to fuel tank. Be careful not to overfill. Allow about 1.5" of tank space for fuel expansion (Figure 2).

Figure 2 - Fuel Expansion

AirSpace

Tank

Fuel

1.5”

 

4.Install fuel cap and wipe up any spilled fuel.

7

Section Operation

4

USING THE GENERATOR

System Ground

The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles.The system ground is connected to the AC neutral wire (see “Equipment Description”, earlier in this manual).

Special Requirements

There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction.

In some areas, generators are required to be registered with local utility companies.

If the generator is used at a construction site, there may be additional regulations which must be observed.

Connecting to a Building’s Electrical System

Connections for standby power to a building’s electrical system must be made by a qualified electrician.The connection must isolate the generator power from utility power, and must comply with all applicable laws and electrical codes.

WARNING

Generator produces powerful voltage.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.

Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT operate generator in the rain.

DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

DO NOT allow unqualified persons or children to operate or service generator.

Generator Location

Generator Clearance

WARNING

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide will cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).

The generator must be at least 5 ft. (152 cm) from structures having combustible walls and/or other combustible materials. Leave at least 3 ft. (92 cm) all around generator including overhead, for adequate cooling, maintenance and servicing.

Place generator in a well ventilated area, which will allow for removal of deadly exhaust gas. DO NOT place generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 3). Prevailing winds and air currents should be taken into consideration when positioning generator.

Figure 3 — Generator Clearance

Exhaust Port

8

Section 4: Operation

OPERATING THE

GENERATOR

CAUTION

Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.

See “Don’t Overload Generator”.

Start generator and let engine stabilize before connecting electrical loads.

Connect electrical loads in OFF position, then turn ON for operation.

Turn electrical loads OFF and disconnect from generator before stopping generator.

Starting the Engine

Disconnect all electrical loads from the generator. Use the following start instructions:

1.Make sure unit is on a level surface.

IMPORTANT: Failure to start and operate unit on a level surface will cause the unit not to start or shut down during operation.

2.Turn fuel valve to “On” position (Figure 4).

Figure 4 — Fuel Valve

“Off”

“On”

Position

Position

3.Start engine according to instructions given in engine owner’s manual.

WARNING

Rapid retraction of starter cord (kickback) will pull hand and arm toward engine faster than you can let go.

Broken bones, fractures, bruises or sprains could result.

When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.

NEVER start or stop engine with electrical devices plugged in and turned on.

NOTE: If engine starts but fails to run, or if unit shuts down during operation, make sure unit is on a level surface and check for proper oil level in crankcase.This unit may be equipped with a low oil protection device. See engine manual.

WARNING

Running engines produce heat.Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).

Severe burns can occur on contact.

Combustible debris, such as leaves, grass, brush, etc. can catch fire.

DO NOT touch hot surfaces.

Allow equipment to cool before touching.

The generator must be at least 5 feet from structures having combustible walls and/or other combustible materials.

Keep at least 3 feet of clearance on all sides of generator for adequate cooling, maintenance and servicing.

In the State of California a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands. If you equip the muffler with a spark arrester, it must be maintained in effective working order.

Connecting Electrical Loads

Let engine stabilize and warm up for a few minutes after starting.

Plug in and turn on the desired 120 and/or 240 Volt AC, single phase, 60 Hz electrical loads.

DO NOT connect 240 Volt loads to the 120 Volt duplex receptacles.

DO NOT connect 3–phase loads to the generator.

DO NOT connect 50 Hz loads to the generator.

DO NOT OVERLOAD GENERATOR. See “Don’t Overload Generator”.

Stopping the Engine

1.Unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to engine owner’s manual.

4.Move fuel valve to “Off” position.

9

Loading...
+ 19 hidden pages