Toshiba RAV-SM560XT-E, RAV-SM800XT-E User Manual

0 (0)

FILE NO. SVM-03021

SERVICE MANUAL

AIR-CONDITIONER

UNDER CEILING / CONSOLE TYPE

RAV-SM560XT-E / RAV-SM560AT-E RAV-SM800XT-E / RAV-SM800AT-E

R410A

Sep., 2003

 

CONTENTS

 

1.

SPECIFICATIONS.............................................................................................................

1

2.

CONSTRUCTION VIEWS .................................................................................................

4

3.

SYSTEMATIC REFRIGERATING CYCLE DIAGRAM ......................................................

7

4.

WIRING DIAGRAM ...........................................................................................................

9

5.

SPECIFICATION OF ELECTRICAL PARTS ..................................................................

12

6.

REFRIGERANT R410A ..................................................................................................

13

7.

CONTROL BLOCK DIAGRAM .......................................................................................

21

8.

OPERATION DESCRIPTION ..........................................................................................

22

9.

INSTALLATION PROCEDURE .......................................................................................

27

10.

TROUBLESHOOTING CHART ......................................................................................

46

11.

DETACHMENTS .............................................................................................................

60

12.

EXPLODED VIEWS AND PARTS LIST ..........................................................................

80

1. SPECIFICATIONS

1-1. Indoor Unit

Model name

 

 

 

 

RAV-SM560XT-E

 

 

RAV-SM800XT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Heating

 

Average

 

Cooling

Heating

 

Average

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard capacity (Note 1)

 

kW

5.0

 

5.6

 

 

 

6.7

8.0

 

 

 

 

 

 

 

(1.5 Ð 5.6)

 

(1.5 Ð 6.3)

 

 

 

(2.2 Ð 8.0)

(2.2 Ð 9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating low temp. capacity (Note 1) (kW)

 

 

 

4.9

 

 

 

 

5.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy consumption effect ratio (Cooling)

 

 

2.67 [D]

 

3.29 [C]

 

2.98

 

2.46 [E]

3.00 [D]

 

2.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

1 phase 220 Ð 240V 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

Running current

 

(A)

8.95 Ð 8.20

 

8.13 Ð 7.46

 

 

13.15 Ð 12.06

12.91 Ð 11.84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

1.87

 

1.7

 

 

 

2.72

2.67

 

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low temp.)

 

(kW)

2.18

 

 

 

2.29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

(%)

95

 

95

 

 

 

94

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

 

 

Pure white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

 

Model

 

 

 

 

 

ÐÐÐ

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel color

 

 

 

 

 

ÐÐÐ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

 

 

 

 

633

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

Width

(mm)

 

 

 

 

1093

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

Depth

(mm)

 

 

 

 

208

 

 

 

 

dimension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

Height

(mm)

 

 

 

 

ÐÐÐ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

 

 

 

 

ÐÐÐ

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

 

ÐÐÐ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

(kg)

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

 

ÐÐÐ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Multi blade fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow High (Mid./Low)

(m3/h)

 

800 (680/580)

 

 

 

900(750/550)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

 

Washable filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller (Sold separately)

 

 

 

 

 

Wireless remote control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

 

(mm)

 

 

12.7 (1/2Ó)

 

 

 

15.9 (5/8Ó)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions pipe

Liquid side

 

(mm)

 

 

6.4 (1/4Ó)

 

 

 

9.5 (3/8Ó)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain port

(Nominal dia.)

 

 

25 (Polyvinyl chloride tube)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

High (Mid./Low) (Note 2)

(dB¥A)

43

 

39

 

36

 

46

42

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1

: The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616

 

based on the reference piping length 7.5 m with 0 meter height.

Note 2

: The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values

 

measured in the actual operating environment become larger than the indicated values due to the effects of

 

external sound.

 

 

Note

: Rated conditions

Cooling

: Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB

 

 

Heating

: Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

Ð 1 Ð

• Operation characteristic curve

<Cooling>

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

RAV-SM800XT-E

 

 

 

 

 

 

RAV-SM800XT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

Current

8

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

RAV-SM560XT-E

 

 

 

 

 

RAV-SM560XT-E

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¥ Conditions

 

 

 

 

 

¥ Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Indoor : DB27ûC/WB19ûC

 

 

 

 

 

Indoor : DB20ûC

 

 

 

 

 

Outdoor : DB35ûC

 

 

2

 

 

Outdoor : DB7ûC/WB6ûC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

Pipe length : 7.5m

 

 

 

0

 

 

230V

 

 

 

 

0

 

 

230V

 

 

 

 

15 20

40

60

70

80

100

 

1520

40

60

80

90

100

 

0

 

0

Compressor speed (rps)

Compressor speed (rps)

• Capacity variation ratio according to temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Cooling>

 

 

 

 

<Heating>

 

 

 

 

 

 

 

 

 

 

 

 

105

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

85

 

 

 

 

 

(%)

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio

 

 

 

 

 

 

ratio

70

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

¥ Conditions

 

 

 

20

 

 

 

 

 

 

¥ Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

Indoor : DB27ûC/WB19ûC

 

 

10

 

 

 

 

 

 

Indoor : DB20ûC

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

50

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

32

33

34 35 36

37 38 39 40 41

42

43

 

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

8

10

Outsoor temp. (ûC)

Outsoor temp. (ûC)

Ð 2 Ð

1-2. Outdoor Unit

Model name

 

 

 

RAV-SM560AT-E

 

RAV-SM800AT-E

 

 

 

 

 

 

 

Appearance

 

 

 

Silky shade (Muncel 1Y8.5/0.5)

 

 

 

 

 

 

 

Power supply

 

 

 

1 phase 230V (220 Ð 240V) 50Hz

 

 

 

(Power exclusive to outdoor is required.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

Hermetic compressor

 

 

 

 

 

 

 

 

Compressor

 

Motor

(kW)

1.1

 

1.6

 

 

 

 

 

 

 

 

 

 

Pole

 

 

4 poles

 

 

 

 

 

 

 

Refrigerant charged

(kg)

R410A 0.9

 

R410A 1.5

 

 

 

 

 

 

Refrigerant control

 

Pulse motor valve

 

 

 

 

 

 

 

 

 

Standard length

 

20 (without additional charge)

 

 

 

 

 

 

 

 

 

 

Max. total length

(m)

30

 

50

 

 

 

 

 

 

 

 

Pipe

 

Over 20m

 

Add 20g/m (Max. 200g)

 

Add 40g/m (Max. 1200g)

 

 

 

 

 

 

 

 

 

 

Height difference

Outdoor lower

(m)

 

15

 

 

 

 

 

 

 

 

 

Outdoor higher

(m)

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

595

 

795

Outer

 

 

 

 

 

 

 

 

Width

(mm)

780

 

780

dimension

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

270

 

270

 

 

 

 

 

 

 

 

Total weight

 

 

(kg)

35

 

55

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

Fan

 

 

Propeller fan

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High

(m³/h)

2400

 

3400

 

 

 

 

 

 

 

 

 

 

Motor

(W)

43

 

63

 

 

 

 

 

 

 

 

Connecting

 

Gas side

(mm)

¯12.7 (1/2Ó)

 

¯15.9 (5/8Ó)

 

 

 

 

 

 

 

pipe

 

Liquid side

(mm)

¯6.4 (1/4Ó)

 

¯9.5 (3/8Ó)

 

 

 

 

 

 

 

 

 

 

Protection device

 

Discharge temp. sensor

 

Over-current sensor

 

 

 

 

 

Compressor thermo.

 

 

 

 

 

 

 

 

Sound level

 

High (Mid./Low)

(dB¥A)

46/48

 

48/50

(Note 2)

 

(Cooling/Heating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note 2 : Rated conditions Cooling : Indoor air temperature 27¡C DB/19¡C WB, Outdoor air temperature 35¡C DB Heating : Indoor air temperature 20¡C DB, Outdoor air temperature 7¡C DB/6¡C WB

Ð 3 Ð

Toshiba RAV-SM560XT-E, RAV-SM800XT-E User Manual

2. CONSTRUCTION VIEWS

2-1. Indoor Unit

Front panel

1093

208

 

633

Knock out system

Grille air inlet

Back body

For stud bolt

200 Min

(¯8 Ð ¯10)

For stud bolt (¯6)

330

165

 

1093

 

 

 

 

1015

 

 

 

 

742

 

 

 

 

450

 

 

 

20

20

 

 

 

 

 

¯74

UNDER CEILING & CONSOLE INSTALLATION

Installation plate

Mount plate

M10 Suspention bolt

633

 

 

460

 

 

 

 

160

Min

57

18

70

Wireless remote control

 

Knock out system

Ð 4 Ð

2-2. Outdoor Unit (RAV-SM560AT-E)

Drain hole (¯25)

Drain hole (2-¯20 x 88 long hole)

 

 

83

600

97

A legs

115.3 125

 

 

29

 

30

308

hole(Longpitch

anchorFor bolt)

302

hole¯6pitch

153

150

11

76

 

270

330

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

B legs

21

780

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49.5

147

 

(49.3)

115.3

Discharge guide mounting hole

216

21

 

 

Discharge guard

(4-¯4 embossing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

center dividing)

 

 

 

21

 

521

 

593 598

 

 

31

 

 

 

 

 

(Fan500

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90.6

132

 

25

220

 

 

500 (Fan center dividing)

Charge port 31

134

Protective net mounting hole (2-¯4 embossing)

43

707

30

Protective net mounting hole

 

 

(4-¯4 embossing)

 

60

 

 

Valve cover

Earth terminal

475

Refrigerant pipe connecting port

(¯12.7 flare at gas side) Refrigerant pipe connecting port (¯6.4 flare at liquid side)

Space required for service

 

 

600

 

 

52

 

 

36

11

R15

2-¯6 hole

308

302

Product

external line

 

 

 

¯11 x 14 U-shape hole

Details of A legs

 

¯11 x 14 U-

 

2-¯11 x 14 U-shape holes

 

shape holes

2-¯6 hole

 

(For ¯8Я10 anchor bolt)

308

302

external

 

150 moreor

 

 

Product

 

 

 

 

line

 

 

11

 

R15

365

150

36

or more

 

 

 

 

 

 

52

 

 

 

 

 

600

 

 

Details of B legs

 

 

500

 

 

or more

600

Suction port

 

300

 

or more

Discharge

(Minimum

port

distance up to wall)

Discharge

2-¯11 x 14 long hole

port

(For ¯8Я10 anchor bolt)

 

Ð 5 Ð

2-3. Outdoor Unit (RAV-SM800AT-E)

Knockout

(For draining) Drain hole (¯20 x 88 burring hole)

17.5

 

 

 

29

90

191

Drain hole (¯25 burring hole)

 

21

20

Part B

 

 

 

 

 

Suction

 

 

 

 

 

 

 

 

 

port

 

 

 

 

 

pitch

bolt)

70

Suction

43

 

40

 

 

 

365

hole(Long

anchorfor

40

Knockout

 

 

 

 

 

port

 

 

 

 

 

 

 

 

 

(For draining)

 

 

 

 

 

 

 

 

 

 

 

 

 

17.5

 

 

 

26

60

Discharge

 

43

39

47

 

 

21

port

Part A

 

 

 

 

 

150

300

95

 

 

 

 

 

 

 

 

900

 

 

 

 

 

 

 

 

 

314

 

 

 

 

 

 

 

Installation bolt hole

17.5

 

(¯12 x 17 U-shape holes)

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

Details of B part

 

Details of A part

 

 

 

 

 

 

 

 

 

17.5

 

 

 

 

40

 

 

 

 

Installation bolt hole

 

 

 

(¯12 x 17 U-shape holes)

 

 

101

 

Handles

 

 

 

 

 

 

(Both sides)

 

 

Refrigerant pipe connecting port

565

 

(¯9.5 flare at liquid side)

 

Refrigerant pipe connecting port

 

 

(¯15.9 flare at gas side)

 

 

2

 

 

 

 

60 67

154

264

Discharge guide

Z

60 27

1

 

300

96

 

 

mounting hole

 

 

(4-¯4 embossing)

307

 

 

Knockout for lower piping

 

 

 

86 7

28 320

Z views

58 7

1

90 60 27

 

 

 

 

 

Space required for service

 

 

795

 

 

2-¯12 x 17 U-shape holes

 

 

 

 

 

 

 

 

 

 

(For ¯8Я10 anchor bolt)

 

 

 

 

2

46

150 moreor

 

 

 

 

 

 

25

85

165

8060

365

150

 

 

 

 

 

 

or more

58

2

 

 

1 30

45

500

161

 

 

 

 

 

400

 

 

 

 

or more

600

Suction port

 

150

 

or more

Discharge

(Minimum

port

distance up to wall)

Discharge

2-¯12 x 17 long hole

port

(For ¯8Я10 anchor bolt)

 

Ð 6 Ð

3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

3-1. RAV-SM560XT-E / RAV-SM560AT-E

Indoor unit

TCJ sensor

Air heat exchanger

TC sensor

Outer diameter of refrigerant pipe

Gas side A

Liquid side B

 

 

6.4 mm

12.7 mm

 

 

TS sensor

TD sensor

4-way valve (VT7101D)

Muffler19 x L160

Rotary compressor (DA130A1F-23F)

Refrigerant pipe

Refrigerant pipe

at liquid side

at gas side

Outer dia. B

Outer dia. A

Max 30m

Packed valve

 

Packed valve

Outer dia. B

Outdoor unit

Outer dia. A

 

 

 

 

PMV

 

 

(SKV-18D26)

TO sensor

 

 

 

 

Strainer

 

TE

 

 

sensor

 

Heat exchanger8 multiple thread

ripple 1 row 22 stages FP1.3 flat fin

Distributor

R410A 0.9 kg

Cooling

Heating

 

 

Pressure

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

(MPa)

Discharge

Suction

Indoor heat

Outdoor heat

revolutions

Indoor

temp. conditions

 

 

exchanger

exchanger

per second

fan

(DB/WB) (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.1

0.9

85

13

10

47

74

HIGH

27/19

35/Ð

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.8

1.0

96

13

12

60

71

HIGH

32/24

43/Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

0.9

0.5

25

7

10

5

28

LOW

18/15.5

Ð5/Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.8

0.6

87

3

46

1

87

HIGH

20/Ð

7/6

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.3

1.1

78

22

55

16

55

LOW

30.Ð

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.7

0.2

110

Ð20

26

Ð22

110

HIGH

0

Ð20/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

Ð7 Ð

3-2. RAV-SM800XT-E / RAV-SM800AT-E

Indoor unit

Outer diameter of refrigerant pipe

Gas side A

Liquid side B

 

 

9.5 mm

15.9 mm

 

 

TS sensor

TD sensor

TCJ sensor

Air heat exchanger

TC sensor

 

Refrigerant pipe

 

Refrigerant pipe

 

 

at liquid side

 

at gas side

 

 

Outer dia. B

 

Outer dia. A

 

 

 

 

 

Max

 

 

 

 

50m

Pd

Packed valve

 

Packed valve

Ps

 

Outer dia. B

Outdoor unit

Outer dia. A

 

 

 

 

 

 

Strainer

 

Modulating (PMV)

 

 

 

(SKV-18D26)

 

 

 

 

 

 

TO sensor

 

 

 

 

 

 

Strainer

 

4-way valve

Accumulator

Muffler (STF-0213Z)

(1500cc)

25 x L210

 

 

25 x L160

 

Rotary compressor

 

(DA220A2F-20L)

TE sensor

Heat exchanger 8 1 row 30 stages FP1.3 flat fin

Capillary3 x 2

x L530

R410A 1.5 kg

Cooling

Heating

 

 

Pressure

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

(MPa)

Discharge

Suction

Indoor heat

Outdoor heat

revolutions

Indoor

temp. conditions

 

 

exchanger

exchanger

per second

fan

(DB/WB) (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.3

0.9

89

8

8

40

64

HIGH

27/19

35/Ð

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.7

1.1

87

17

14

46

45

HIGH

32/24

43/Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.0

0.8

22

2

1

1

24

LOW

18/15.5

Ð5/Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.3

0.6

93

0

54

0

70

HIGH

20/Ð

7/6

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.1

1.1

75

20

52

15

24

LOW

30.Ð

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

2.0

0.2

90

Ð26

25

Ð25

90

HIGH

0

Ð20/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

Ð8 Ð

4. WIRING DIAGRAM

4-1. Indoor Unit

SWITCH PCB MCC-1428B

CN101 1 2 3

GRY

GRY

WHI

HEAT

EXCHANGER

SENSOR (TCJ)

FOR FLOAT SWITCH

1

2

(OPTION)

When you use float

1

2

switch you should cut J401

1

RAYSINFRAREDRECEIVE

INDICATIONAND PARTS

 

 

 

 

 

LOUVER MOTOR

1

2

3

CN402

CN100 1

2

3

10 10

WHI

10 10

 

 

9

9

BLU

9

9

 

POWER

BLU

4

SUPPLY

8

8

BLU

8

8

CIRCUIT

7

7

7

7

 

6

6

BLUBLU

6

6

 

C02

5

5

BLU

5

5

 

 

4

4

4

4

 

DB01

3

3

BLU

3

3

 

 

 

2

2

BLU

2

2

 

 

1

1

BLU

1

1

 

R01

CN25

 

CN13

 

C01

BRW

1

1

5

 

 

RED

2

2

 

 

 

ORN

3

3

 

 

 

YEL

4

4

 

 

 

PNK

5

5

 

 

 

BLU

6

6

IC04

C15

 

CN07

 

 

 

 

 

 

 

R507

 

 

 

 

 

R09

 

R21

 

 

 

 

 

 

 

 

R22

FUSE

 

 

 

 

250VAC

 

 

 

 

 

 

 

 

 

SG01

F01

3

 

 

 

 

 

 

 

 

 

T6.3A

 

 

 

 

BLK

P04

CN30

 

 

 

 

 

 

 

 

 

 

BLK

2 1

1 2

CN05

1 2

CN03

BLK

 

 

THERMO

J401

 

 

2

2

 

 

SENSOR

DC12V

 

 

1

1

BLK

 

 

(TA)

IC03

 

2

2

BLK

 

 

HEAT

DC5V

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

1

1

 

 

EXCHANGER

 

 

 

CN01

 

 

 

SENSOR

 

 

R506

 

 

 

(TC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR502

CR501

 

1

1

 

 

 

 

 

 

WHI 1

1

WHI

 

 

 

2

2

 

 

 

3

3

 

2

2

 

RY501

 

 

4

4

RED

3

3

RED

 

 

 

5

5

 

4

4

 

 

C501

CN10

BLK

5

5

BLK

MCC-1428A

 

 

 

 

 

6

6

 

 

 

 

 

 

 

 

 

R405

CR401

RY401

 

3

3

BRW

3

3

BLU

2

2

2

2

1

1

GRY

1

1

PUR

CN11

YEL

 

 

GRY

 

 

 

FAN-MOTOR

 

 

 

 

 

100ÓC

32 FOR DRAIN PUMP

(OPTION)

1

CN401

 

CN31

CN23

WHI

RED

INDOOR

GRN&YEL

 

 

INDOOR

2 3

TERMINAL

BLOCK

UNIT

OUTDOOR

UNIT

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

Check items

Diagnosis result

 

 

 

1

OPERATION

Check to see if OPERATION indicator goes on and off when the main switch

indicator

or breaker is turned on.

 

 

 

 

 

 

 

2

Terminal

Check the power supply voltage between

1

- 2 (Refer to the name plate.)

block

Chack the fluctuate voltage between 2 -

3

(DC15 to 60V)

 

 

 

3

Fuse

Check to see if the fuse blows out. (Check the varistor. : R22, R21)

6.3A

 

 

 

 

 

 

4

DC 5V

Check the voltage at the No.8 pin on CN13 connector of the infrared receiver.

(Check the transformer and the power supply circuit of the rated voltage.)

 

 

 

5

DC 12V

Check the voltage at the brown lead of the louver motor.

(Check the transformer and the power supply circuit of the rated voltage.)

 

 

 

 

 

Color

Identification

BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE

GRN&YEL : GREEN& YELLOW

GRN : GREEN

PUR : PURPLE

Ð 9 Ð

4-2. Outdoor Unit (RAV-SM560AT-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q200

 

 

 

 

 

 

 

 

 

DB01

 

 

 

REACTOR

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

CONVERTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGBT MODULE

 

 

 

 

 

 

 

 

 

 

FOR

 

 

 

 

 

 

 

 

 

 

 

 

MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

 

 

 

EW

BW

 

 

 

BRW

 

 

 

 

ORN

 

2

1

2

1 CN500

 

 

 

 

 

BZ

BY

BX

EV BV

EU

BU

 

+ ~

 

 

 

 

 

 

2

1

 

 

 

 

 

 

Ð

~ A E G

P10

 

P09

2

1

 

 

TE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P17 P18

 

 

 

 

 

 

 

 

P20

P19

 

 

 

 

 

P08

P07

CN600

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

TD

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRONIC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CT

 

 

 

CN601 2

2

 

 

P23

P22

P21

 

 

 

 

 

 

 

 

 

STARTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

WHI

RED

 

 

 

 

 

 

 

 

 

 

 

 

RELAY

 

 

 

 

 

 

1

1

TO

 

 

P.C. BOARD

 

 

 

 

 

 

 

 

 

 

 

 

CN602

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

4

3

2

1

 

 

(MCC-813)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS

3

2

1

 

 

 

 

 

 

 

 

 

 

Ð

+

C12

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

CN603 2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ð

+

C13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

CM

 

 

 

 

 

 

 

 

 

 

Ð

+

C14

 

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

Q300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN701 2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COIL FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P06

 

BLK

4-WAY VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

F04

 

 

 

 

 

 

 

SURGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

2

 

 

 

 

 

ABSORBER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T3. 15A

 

 

 

 

 

 

 

1

1

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250V~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VARISTOR

 

2

2

YEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

ORN PMV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

2

 

5

5

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T25A

F01

 

6

6

GRY

PULSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250V~

 

 

 

 

CN703

MODULATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P14

P13

 

 

P02

 

P03 P01

 

 

 

 

 

 

 

 

 

CN301 5

 

4

3

2

1

3

2

1

CN300

P12

P11

WHI

ORN

BLK

 

 

 

 

 

 

 

 

 

 

 

5

 

4

3

2

1

3

2

1

 

PUR

2

1

 

 

 

 

 

TERMINAL OF COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRY

PNK

 

YEL

BLK WHI

RED

 

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE (S)

 

BLACK (C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

FM

 

 

 

 

 

1

2 3 L N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REACTOR

 

 

 

 

 

 

 

 

 

 

 

 

RED (R)

FAN MOTOR

TO

POWER

The sign in ( ) is displayed

 

INDOOR

SUPPLY

 

in the terminalcover

 

UNIT

220 to 240

 

 

 

 

50Hz

 

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

Check

Diagnosis result

items

 

 

 

1

TERMINAL BLOCK

 

 

There is no supply voltage

 

Power supply and connecting

(AC220 to 240V) between L - N , 1 - 2

 

cable check

 

There is no voltage (DC15 to 25V) 2 - 3

 

 

 

 

 

 

 

FUSE

 

 

2

T25A 250V to fuse (F01) blown

 

Converter module (DB01) and

T3.15A 250V to fuse (F04) blown

 

electrolytic capacitor (C12 to C14) check

 

IGBT module (Q200) check

 

 

 

Fan motor check

 

 

 

3

ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14)

DC320V not available between

 

T25A fuse (F01) check

+ Ð terminal of electrolytic capacitor

 

P.C. board and converter

 

 

 

 

module (DB01) check

 

 

 

 

INVERTER OUTPUT (Inverter and compressor connector out of position)

4

(Please confirm within six minutes after instructing in the drive.)

Voltage between each line of inverter side

 

IGBT module and

 

conector pins are not equal.

 

P.C. board check

 

 

 

 

Color Identification

BLK : BLACK

WHI : WHITE

BLU : BLUE

BRW : BROWN

RED : RED

ORN : ORANGE

GRY : GRAY

YEL : YELLOW

PNK : PINK

PUR : PURPLE

GRN : GREEN

 

 

 

NOTE

 

CM

 

 

: Compressor

PMV

: Pulse modulating valve

FM

: Fan motor

TE

: Heat exchanger Temp. Sensor

TD

: Discharge Temp. Sensor

TO

: Outdoor Temp. Sensor

TS

: Suction Temp. Sensor

IGBT

: Insulated Gate Bipolar Transistor

DB01

: Converter module

CT

: Curreut Transformer

Q300

: Fan motor driver module

 

 

 

 

Ð 10 Ð

4-3. Outdoor Unit (RAV-SM800AT-E)

THERMOSTAT

 

 

 

 

Compressor

CM

 

 

 

 

 

 

FOR

 

 

 

 

 

 

 

COMPRESSOR

 

CN604 2 2

 

TE

ORN

 

 

 

2 2

CN500

 

1

1

 

 

 

 

 

 

 

 

 

 

 

ORN 1 1

 

CN605 2 2

GRN

TS

4-WAY VALVE COIL

 

 

1

1

 

 

 

 

 

 

 

 

 

 

3 3

3

 

 

3

3

 

TD

 

 

CN700

CN600 2

 

 

1 1

1

 

 

1

1

 

 

FAN MOTOR

5 5

 

CN601 2 2

 

TO

 

 

1

1

 

 

 

 

 

 

FM

4 4

 

Fan

 

 

 

 

3 3 CN300

 

 

 

 

 

2 2

 

circuit

 

 

BLU

 

 

1 1

2

 

3 3

 

 

 

CN302

 

 

 

3 3

1 1

YEL

 

 

 

 

 

 

2 2 CN301

F300

 

 

 

 

 

 

 

 

1 1

 

FUSE

5 5

BLK

 

 

 

 

T5A

WHI

 

 

 

 

 

4

4

 

 

6 6

 

CN800

BLU

 

 

 

3 3

 

 

5 5

 

RED

 

 

 

 

2

2

 

PMV

4 4

 

 

PNK

 

CN702

 

1

1

 

3 3

 

 

 

 

 

 

 

 

 

 

2 2

 

CN04

2 2

 

 

 

1 1

 

ORN

 

 

 

 

 

1 1

 

 

 

 

 

 

5

5

BLK

 

 

 

PHOTO COUPLER

 

 

 

 

4

4

WHI

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

CN01 2 2

RED

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

T03

+

 

 

RED

CN09

 

BU

 

 

 

CT

 

 

 

EU

 

 

 

 

 

 

 

 

 

WHI

CN10

 

 

BV

 

 

 

 

EV

IGBT

 

 

 

 

 

T04

 

BLK

CN11

 

CT

BW

module

 

 

 

 

 

 

EW

 

 

 

 

 

4

BX

 

 

 

POWER SUPPLY CIRCUIT

BY

 

 

 

 

 

 

 

(FOR P.C. BOARD)

 

 

BZ

 

 

 

 

 

 

 

 

 

F04

2

 

 

 

Q200

 

 

 

 

 

 

 

 

FUSE

 

 

 

 

 

 

3.15A

 

 

 

 

 

 

 

 

 

 

 

P20

 

 

 

 

C13

3

 

P19

YEL

 

 

 

C12

 

P18

BLU

 

 

 

C11

 

 

P17

 

 

 

 

 

 

 

 

 

 

C10

2

F02

 

 

 

 

 

 

FUSE

G

 

 

 

 

 

 

15A

 

3

3

 

 

 

 

E

 

CN04

 

 

 

A

Converter

 

 

 

 

 

1

1

 

 

 

~

 

POWER

 

 

 

module

 

 

 

 

 

~

 

5

5

 

RELAY

 

 

 

 

 

 

 

+

DB01

4

4

CN06

RY01

 

P10

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

ORN

2

2

P.C. BOARD

R05

 

P11

 

1

1

 

REACTOR

 

 

 

 

(MCC-1359)

R06

 

P13

2 2

 

2 2

 

 

 

CN05

 

 

P12

1 1

 

1 1

T02

 

REACTOR

 

 

 

CT

 

P09

2 2

 

5

5

 

 

 

 

 

 

 

P08

1 1

 

4

4

 

 

 

 

 

 

 

 

P15

 

 

3

3

 

 

 

 

BRN

 

 

 

 

 

2

2

 

 

 

P14

 

 

 

 

 

 

1

1

CN13

 

 

 

 

 

 

 

 

 

SUB

2

F01

 

 

 

 

 

 

 

 

P.C. BOARD

 

FUSE

 

 

 

 

F01

VARISTOR

SURGE

 

(MCC-1398)

 

T3.15A

 

 

 

2

FUSE

 

 

 

 

 

 

25A

 

ABSORBER

 

 

CN02

1 2 3

 

REACTOR

 

CN01

CN02

CN03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

WHI

BLK

 

 

 

1 2 3 GRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

RED

 

 

 

 

 

 

 

 

 

1

1 2 3 L N

 

 

TERMINAL OF COMPRESSOR

 

 

 

 

 

TO

POWER

 

WHITE(S)

BLACK(C)

The sign in ( )

 

 

 

 

INDOOR SUPPLY

 

 

 

 

 

 

UNIT

220-240V

 

 

 

 

is displayed

 

 

 

 

 

~50Hz

 

 

 

 

in the terminal

RED(R) cover

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

Check

Diagnosis result

items

 

 

 

1

TERMINAL BLOCK

 

There is no supply voltage

Connecting cable check

(AC220 to 240V) between L - N , 1 - 2

 

 

There is no voltage (DC15 to 25V) 2 - 3

 

 

 

 

 

 

FUSE

 

2

25A fuse (F01) blown, 15A fuse (F02) blown

Converter module (DB01) and electrolytic

3.15A fuse (F04) blown,

capacitor (C10 to C13) check IGBT

T5A fuse (F300) blown (SUB P.C. board)

 

module (Q200) check, Fan motor check

 

T3.15A fuse (F01) blown (SUB P.C. board)

SUB P.C. board check

 

 

 

3

ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13)

DC320V not available between

25A fuse (F01) check

+ terminal of electrolytic capacitor

 

P.C. board and coverter

 

 

 

 

module (DB01) check

 

 

 

 

 

INVERTER OUTPUT (CN09, CN10, CN11)

 

4

(Please confirm within six minutes after instructing in the drive.)

Voltage between each line of inverterside

IGBT module and

 

conector pins are not equal.

 

P.C. board check

 

 

 

 

Color Identification

BLK

: BLACK

WHI : WHITE

BLU

: BLUE

BRN : BROWN

RED

: RED

ORN : ORANGE

GRY

: GRAY

YEL : YELLOW

PNK

: PINK

PUR : PURPLE

GRN

: GREEN

 

Ð 11 Ð

5. SPECIFICATION OF ELECTRICAL PARTS

5-1. Indoor Unit

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor (for indoor)

AFP-220-50-4A

Output (Rated) 50 W, 220 Ð 240 V

 

 

 

 

2

Grille motor

MP35EA12

DC 12 V

 

 

 

 

3

Thermo. sensor (TA-sensor)

550 mm

10 kΩ at 25°C

 

 

 

 

4

Heat exchanger sensor (TC-sensor)

6 mm, 500 mm

10 kΩ at 25°C

 

 

 

 

5

Heat exchanger sensor (TCJ-sensor)

6 mm, 500 mm

10 kΩ at 25°C

 

 

 

 

5-2. Outdoor Unit (RAV-SM560AT-E)

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor

ICF-140-43-1

Output (Rated) 40 W

 

 

 

 

2

Compressor

DA130A1F-23F

3 phase, 4P, 1100 W

 

 

 

 

3

Reactor

CH-57

1=10 mH, 16A

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

Ñ

50 kΩ at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

Ñ

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

Ñ

25 A, AC 250 V

 

 

 

 

10

4-way valve solenoid coil

STF-0108G

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

5-3. Outdoor Unit (RAV-SM800AT-E)

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor

ICF-140-63-1

Output (Rated) 63 W, 220 Ð 240 V

 

 

 

 

2

Compressor

DA220A2F-20L

3 phase, 4P, 1600 W

 

 

 

 

3

Reactor

CH-47

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

Ñ

10 kΩ at 25°C

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

Ñ

50 kΩ at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

Ñ

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

Ñ

25 A, AC 250 V

 

 

 

 

10

4-way valve solenoid coil

DKV-M0ZS743B0

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

Ð 12 Ð

6. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

6-1. Safety During Installation/Servicing

As R410AÕs pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/ servicing safely while taking the following precautions into consideration.

(1)Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.

(2)Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A. The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22

(3)If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

(4)When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture of personal injury may be caused.

(5)After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

(6)When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.

(7)Be sure to carry out installation or removal according to the installation manual. Improper installation may cause refrigeration

trouble, water leakage, electric shock, fire, etc.

(8)Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repairÕs may result in water leakage, electric shock and fire, etc.

6-2. Refrigerant Piping Installation

6-2-1. Piping materials and joints used

For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

(1)Copper pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 6-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.

Ð 13 Ð

Table 6-2-1 Thicknesses of annealed copper pipes

 

 

 

Thickness (mm)

 

 

 

 

 

Nominal diameter

Outer diameter (mm)

R410A

 

R22

 

 

 

 

 

1/4

6.35

0.80

 

0.80

 

 

 

 

 

3/8

9.52

0.80

 

0.80

 

 

 

 

 

1/2

12.70

0.80

 

0.80

 

 

 

 

 

5/8

15.88

1.00

 

1.00

 

 

 

 

 

(2)Joints

For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.

a)Flare joints

Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.

Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6-2-6 below.

b)Socket joints

Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.

Thicknesses of socket joints are as shown in Table 6-2-2.

Table 6-2-2 Minimum thicknesses of socket joints

Nominal diameter

Reference outer diameter of

Minimum joint thickness

copper pipe jointed (mm)

(mm)

 

 

 

 

1/4

6.35

0.50

 

 

 

3/8

9.52

0.60

 

 

 

1/2

12.70

0.70

 

 

 

5/8

15.88

0.80

 

 

 

6-2-1. Processing of piping materials

When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.

(1)Flare Processing procedures and precautions

a)Cutting the pipe

By means of a pipe cutter, slowly cut the pipe so that it is not deformed.

b)Removing burrs and chips

If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.

c)Insertion of flare nut

d)Flare processing

Make certain that a clamp bar and copper pipe have been cleaned.

By means of the clamp bar, perform the flare processing correctly.

Use either a flare tool for R410A or conventional flare tool.

Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure Òdimension AÓ by using a gauge for size adjustment.

D

A

Fig. 6-2-1 Flare processing dimensions

Ð 14 Ð

Table 6-2-3 Dimensions related to flare processing for R410A

 

Outer

 

 

 

 

 

 

A (mm)

 

 

Nominal

Thickness

 

 

 

 

 

 

 

 

 

 

diameter

Flare tool for R410A

 

 

Conventional flare tool

diameter

(mm)

 

 

(mm)

 

 

 

 

 

 

 

 

clutch type

 

Clutch type

 

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

 

0 to 0.5

 

 

1.0 to 1.5

 

1.5 to 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

 

0 to 0.5

 

 

1.0 to 1.5

 

1.5 to 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

 

0 to 0.5

 

 

1.0 to 1.5

 

2.0 to 2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

15.88

1.0

 

0 to 0.5

 

 

1.0 to 1.5

 

2.0 to 2.5

 

 

 

 

 

 

 

 

 

 

 

Table 6-2-4 Dimensions related to flare processing for R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

 

 

 

A (mm)

 

 

Nominal

Thickness

 

 

 

 

 

 

 

 

 

 

diameter

Flare tool for R22

 

 

Conventional flare tool

diameter

(mm)

 

 

(mm)

 

 

 

 

 

 

 

 

clutch type

 

Clutch type

 

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

 

0 to 0.5

 

 

0.5 to 1.0

 

1.0 to 1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

 

0 to 0.5

 

 

0.5 to 1.0

 

1.0 to 1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

 

0 to 0.5

 

 

0.5 to 1.0

 

1.5 to 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

15.88

1.0

 

0 to 0.5

 

 

0.5 to 1.0

 

1.5 to 2.0

 

 

 

 

 

 

 

 

 

 

 

Table 6-2-5 Flare and flare nut dimensions for R410A

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

Outer

Thickness

 

 

Dimension (mm)

 

Flare nut

diameter

 

 

 

 

 

 

 

 

 

width

diameter

(mm)

A

 

B

 

 

C

 

D

 

(mm)

 

 

 

 

 

(mm)

 

 

 

 

 

 

 

1/4

6.35

0.8

9.1

 

9.2

 

6.5

 

13

17

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.2

 

13.5

 

9.7

 

20

22

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.6

 

16.0

 

12.9

 

23

26

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

15.88

1.0

19.7

 

19.0

 

16.0

 

25

29

 

 

 

 

 

 

 

 

 

 

 

Table 6-2-6 Flare and flare nut dimensions for R22

 

 

 

 

 

 

 

 

 

 

Nominal

Outer

Thickness

 

 

Dimension (mm)

 

Flare nut

diameter

 

 

 

 

 

 

 

 

 

width

diameter

(mm)

A

 

B

 

 

C

 

D

 

(mm)

 

 

 

 

 

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

9.0

 

9.2

 

6.5

 

13

17

 

 

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.0

 

13.5

 

9.7

 

20

22

 

 

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.2

 

16.0

 

12.9

 

20

24

 

 

 

 

 

 

 

 

 

 

 

5/8

15.88

1.0

19.4

 

19.0

 

16.0

 

23

27

 

 

 

 

 

 

 

 

 

 

 

3/4

19.05

1.0

23.3

 

24.0

 

19.2

 

34

36

 

 

 

 

 

 

 

 

 

 

 

 

 

Ð 15 Ð

° 46 °to 45

43

 

°

 

to 45

 

°

Fig. 6-2-2 Relations between flare nut and flare seal surface

(2)Flare connecting procedures and precautions

a)Make sure that the flare and union portions do not have any scar or dust, etc.

b)Correctly align the processed flare surface with the union axis.

c)Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.

When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 6-2-7 shows reference values.

Note:

When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.

Table 6-2-7 Tightening torque of flare for R410A [Reference values]

Nominal

Outer diameter

Tightening torque

Tightening torque of torque

wrenches available on the market

diameter

(mm)

N·m (kgf·cm)

N·m (kgf·m)

 

 

 

 

 

 

 

1/4

6.35

14 to 18 (140 to 180)

16 (160), 18 (180)

 

 

 

 

3/8

9.52

33 to 42 (330 to 420)

42 (420)

 

 

 

 

1/2

12.70

50 to 62 (500 to 620)

55 (550)

 

 

 

 

5/8

15.88

63 to 77 (630 to 770)

65 (650)

 

 

 

 

Ð 16 Ð

6-3. Tools

6-3-1. Required tools

The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For 12.70 copper pipe) of the refrigerant piping are lengthened.

The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

(1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

(2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

(3)Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

R410A air conditioner

Conventional air

 

 

 

installation

conditioner installation

No.

Used tool

Usage

 

 

 

Existence of

Whether

Whether new equipment

 

 

 

new equipment

conventional

can be used with

 

 

 

for R410A

equipment can

conventional refrigerant

 

 

 

 

be used

 

 

 

 

 

 

 

1

Flare tool

Pipe flaring

Yes

*(Note 1)

 

 

 

 

 

 

 

2

Copper pipe gauge

Flaring by

 

 

 

 

for adjusting projection

conventional flare

Yes

*(Note 1)

*(Note 1)

 

margin

tool

 

 

 

 

 

 

 

 

 

3

Torque wrench

Connection of

Yes

 

 

flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Gauge manifold

Evacuating,

 

 

 

 

 

refrigerant charge,

Yes

 

 

5

Charge hose

 

 

run check, etc.

 

 

 

 

 

 

 

 

 

6

Vacuum pump adapter

Vacuum evacuating

Yes

 

 

 

 

 

 

 

 

7

Electronic balance for

Refrigerant charge

Yes

 

 

refrigerant charging

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Refrigerant cylinder

Refrigerant charge

Yes

 

 

 

 

 

 

 

 

9

Leakage detector

Gas leakage check

Yes

 

 

 

 

 

 

 

 

!

Charging cylinder

Refrigerant charge

(Note 2)

 

 

 

 

 

 

 

 

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as

the general tools.

 

 

 

Hole core drill ( 65)

(1)

Vacuum pump

(4)

Reamer

(9)

 

Use vacuum pump by

(5)

Pipe bender

(10)

Hexagon wrench

 

attaching vacuum pump adapter.

(6)

Level vial

 

(Opposite side 4 mm)

(2)

Torque wrench

(7)

Screwdriver (+, Ð)

(11)

Tape measure

(3)

Pipe cutter

(8)

Spanner of Monkey wrench

(12)

Metal saw

Also prepare the following equipments for other installation method and run check.

(1)

Clamp meter

(3)

Insulation resistance tester

 

 

(2)

Thermometer

(4)

Electroscope

 

 

 

 

 

 

 

 

 

 

 

Ð 17 Ð

 

 

6-4. Recharging of Refrigerant

When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.

Recover the refrigerant, and check no refrigerant remains in the equipment.

Connect the charge hose to packed valve service port at the outdoor unitÕs gas side.

Connect the charge hose of the vacuum pump adapter.

Open fully both packed valves at liquid and gas sides.

When the compound gaugeÕs pointer has indicated -0.1 Mpa (-76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pumpÕs power switch.

Keep the status as it is for 1 to 2 minutes, and ensure that the compound gaugeÕs pointer does not return.

Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.

Place the handle of the gauge manifold Low in

(For refrigerant charging, see the figure below.)

the fully opened position, and turn on the vacuum

 

pumpÕs power switch. Then, evacuating the

 

refrigerant in the cycle.

 

 

 

1 Never charge refrigerant exceeding the specified amount.

2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.

3Do not carry out additional charging.

When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.

(INDOOR unit)

(Liquid side)

(OUTDOOR unit)

Opened

(Gas side)

Refrigerant cylinder (With siphon pipe)

Check valve

Closed

Open/Close valve for charging

Service port

Electronic balance for refrigerant charging

Fig. 6-4-1 Configuration of refrigerant charging

Ð 18 Ð

1 Be sure to make setting so that liquid can be charged.

2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.

It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.

[Cylinder with siphon]

[Cylinder without siphon]

Gauge manifold

Gauge manifold

OUTDOOR unit

OUTDOOR unit

Refrigerant

cylinder

Electronic

balance

cylinder Refrigerant

Electronic

balance

Siphon

R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.

Fig. 6-4-2

6-5. Brazing of Pipes

6-5-1. Materials for brazing

(1)Silver brazing filler

Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.

(2)Phosphor bronze brazing filler

Phosphor bronze brazing filler is generally used to join copper or copper alloy.

(3)Low temperature brazing filler

Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.

1Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.

2When performing brazing again at time of servicing, use the same type of brazing filler.

6-5-2. Flux

(1)Reason why flux is necessary

By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.

In the brazing process, it prevents the metal surface from being oxidized.

By reducing the brazing fillerÕs surface tension, the brazing filler adheres better to the treated metal.

Ð 19 Ð

(2)Characteristics required for flux

Activated temperature of flux coincides with the brazing temperature.

Due to a wide effective temperature range, flux is hard to carbonize.

It is easy to remove slag after brazing.

The corrosive action to the treated metal and brazing filler is minimum.

It excels in coating performance and is harmless to the human body.

As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.

(3)Types of flux

Noncorrosive flux

Generally, it is a compound of borax and boric acid.

It is effective in case where the brazing temperature is higher than 800°C.

Activated flux

Most of fluxes generally used for silver brazing are this type.

It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.

(4)Piping materials for brazing and used brazing filler/flux

Piping

Used brazing

Used

material

filler

flux

 

 

 

Copper - Copper

Phosphor copper

Do not use

 

 

 

Copper - Iron

Silver

Paste flux

 

 

 

Iron - Iron

Silver

Vapor flux

 

 

 

1 Do not enter flux into the refrigeration cycle.

2 When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chloring.

3When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).

4 Remove the flux after brazing.

6-5-3. Brazing

As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.

In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.

Never use gas other than Nitrogen gas.

(1)Brazing method to prevent oxidation

1 Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.

2Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.

3Apply a seal into the clearance between the piping material and inserted copper pipe for

Nitrogen in order to prevent backflow of the Nitrogen gas.

4When the Nitrogen gas is flowing, be sure to keep the piping end open.

5 Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/ cm2) by means of the reducing valve.

6After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes

are touchable with hands).

7 Remove the flux completely after brazing.

M Flow meter

Stop valve

Nitrogen gas cylinder

From Nitrogen cylinder

Pipe Nitrogen gas

Rubber plug

Fig. 6-5-1 Prevention of oxidation during brazing

Ð 20 Ð

7. CONTROL BLOCK DIAGRAM

 

 

 

 

 

 

 

 

Indoor Unit Control Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M.C.U.

8 MHz

 

Heat Exchanger Sensor (TCJ)

 

 

 

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Louver Control

 

 

 

Heat Exchanger Sensor (TC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-minute Delay at Restart for Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Sensor

 

 

 

 

 

 

 

 

Motor Revolution Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Infrared Rays Signal Receiver

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Processing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Temperature Processing)

 

 

 

 

 

 

Initiallizing Circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Infrared

 

 

 

 

 

 

 

 

Timer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rays

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clock Frequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36.7 kHz

 

Oscillator Circuit

 

 

 

Drain Pump ON/OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial Signal Communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

Louver ON/OFF Signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

Circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Louver Driver

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise Filter

 

 

Serial Signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmitter/

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Receiver

 

 

RY401

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From Outdoor Unit

Serial Signal Communication

Hi POWER

Display

FILTER Sign

Display

PRE DEF.

Sign Display

TIMER

Display

OPERATION

Display

Indoor Fan

Motor

Louver Motor

Float

Switch

Drain

Pump

REMOTE CONTROL

Infrared Rays

Remote Control

Operation (START/STOP)

Operation Mode Selection

AUTO, COOL, DRY, HEAT, FAN ONLY

Temperature Setting

Fan Speed Selection

ON TIMER Setting

OFF TIMER Setting

Louver Auto Swing

Louver Direction Setting

ECO

Hi power

Filter Reset

Ð 21 Ð

8. OPERATION DESCRIPTION

8-1. When power supply is reset

(1)Distinction of outdoor units

When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result.

(2)Setting of the indoor fan speed

Based on EEPROM data, rspeed of the indoor fan is selected.

Remarks: Air speed

8-2. Operation mode selection

(1)Based on the operation mode selecting command from the remote control, the operation mode is selected.

 

Table 8-2-1

 

 

Remote control

Outline of control

command

 

 

 

STOP

Air conditioner stops.

 

 

FAN

Fan operation

 

 

COOL

Cooling operation

 

 

DRY

Dry operation

 

 

HEAT

Heating operation

 

 

AUTO

Automatic operation

 

 

(2)Automatic Operation

The air conditioner selects and operates in one of the operating modes of cooling, heating or fan only, depending on the room temperature.

If the AUTO mode is uncomfortable, you can select the desired conditions manually.

8-3. Air volume control

(1)Operation with [HIGH (H)], [MED (M)], [LOW (L)], or [AUTO] mode is performed by the command from the remote control.

(2)When [FAN] button is set to AUTO, the indoor fan motor operates as shown in Fig. 8-3-1, Fig. 8-3-2 and Table 8-3-1.

<COOL>

temp.)

 

°C

+3

 

 

 

(Preset

 

M+

+2.5

 

 

 

 

*1

+2

 

*1

temp.)

*1

 

+1.5

 

(Room

+1

 

+0.5

 

 

 

 

Preset

 

0

 

 

 

temp.

−0.5

 

NOTE :

*1: The values marked with *1 are calculated and controlled by the difference in motor speed between M+ and LÐ.

Fig. 8-3-1

 

 

Table 8-2-2

 

 

 

 

Room temperature in operation

 

 

Operating condition

 

 

 

 

The set temperature +1¡C or higher

Cooling

 

Performs the cooling operation at a temperature 1¡C

(in case that the room is hot)

operation

 

higher than the setting.

 

 

 

 

The set temperature Ð1¡C to +1¡C

Fan only

 

Performs the fan only operation (low speed) while

 

operation

 

monitoring the room temperature. When the room

 

 

 

temperature changes, the air conditioner will select the

 

 

 

cooling or heating mode.

 

 

 

 

The set temperature Ð1¡C or lower

Heating

 

Performs the heating operation at a temperature 1¡C

(in case that the room is cold)

operation

 

lower than the setting.

 

 

 

 

Ð 22 Ð

<HEAT>

Preset

°C

 

 

0

L

temp.

−0.5

 

temp.)

−1

*1

−2

 

−1.5

*2

 

 

 

(Preset

 

 

M+

 

 

 

temp.)

−5.0

 

(Room

−5.5

H

[FAN AUTO]

 

 

 

NOTE :

*1, *2 : The values marked with *1 and *2 are calculated and controlled by the difference in motor speed between M+ and L.

8-4. Cool air discharge preventive control

In heating operation, the indoor heat exchanger restricts revolving speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 8-4-1 and Table 8-4-1.

 

 

 

 

Manual

 

 

 

AUTO

(One of

 

46

34

5 steps)

 

45

33

 

 

 

 

 

*4

L−H

 

33

21

 

 

 

(Up to

 

32

20

 

 

 

setting

 

 

 

 

 

 

 

SUL*3

speed)

*2

A+4

A+4

SUL*1

 

 

A−8

A−8

 

 

Stop

 

 

 

 

 

 

*6

*5

 

 

 

 

 

 

 

Fig. 8-3-2

Table 8-3-1

 

 

RAV-SM560XT-E

RAV-SM800XT-E

MODEL

 

 

 

 

Motor speed

Air flow level

Motor speed

Air flow level

 

 

(rpm)

 

(m3/h)

(rpm)

(m3/h)

Cooling

HIGH

1060

 

800

1190

900

 

 

 

 

 

 

 

and

MED

950

 

690

1010

750

 

 

 

 

 

 

 

Fan only

LOW

800

 

580

850

650

 

HIGH

1120

 

830

1300

980

Heating

MED

970

 

730

1070

800

 

LOW

820

 

600

860

650

 

 

 

 

 

 

 

 

 

LOW+

=

LOW+MED

 

 

 

 

 

2

 

 

 

 

MED+

= MED+HIGH

 

 

 

 

 

2

 

 

NOTES :

*1: The fan stops for 2 minutes after thermostat-OFF.

*2: A is 24°C when the preset temperature is 24°C or more and A is the preset temperature when it is under 24°C.

*3: SUL means Super Ultra Low.

*4: Calculated from difference in motor speed between SUL and HIGH.

Fig. 8-4-1 Cold draft preventing control

*5 and *6:

Table 8-4-1

Fan

*5

 

*6

 

speed

 

Starting period

 

Stabilized period

 

 

 

 

 

AUTO

Up until 12 minutes

From 12 to 25 minutes

 

 

passed after starting

 

passed after starting

 

the unit

 

the unit and room

 

From 12 to 25 minutes

 

temperature is

 

 

passed after starting

 

between preset

 

 

the unit and room

 

temperature and 3°C

 

 

temperature is 3°C

 

lower than preset

 

 

lower than preset

 

temperature

 

 

temperature

25 minutes or more

 

 

 

 

passed after starting

 

 

 

 

the unit

Manual

Room temperature

Room temperature

(L Ð H)

 

< Preset temperature

 

Preset temperature

 

 

Ð4°C

 

Ð3.5°C

Ð 23 Ð

8-5. Freeze preventive control (Low temperature release)

The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor.

When [J] zone is detected for T1 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 2 minutes while operation is performed in [J] zone.

T1

Normal

1 minute

In [K] zone, time counting is interrupted and the operation is held.

When [I] zone is detected, the timer is cleared and the operation returns to the normal operation.

(°C)

 

 

 

7

 

I

A

 

6

 

 

K

 

 

 

5

 

 

J

 

 

 

 

 

Fig. 8-5-1

In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the condition is satisfied.

Remarks:

Tcj : Indoor heat exchanger sensor temperature

8-6. High-temp release control

The heating operation is performed as follows based on the detected temperature of Tc sensor.

When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone.

In [N] zone, the commanded frequency is held.

When [L] zone is detected, the commanded frequency is returned to the original value by approx. 6Hz every 60 seconds.

8-7. Louver control

(1)Vertical air flow louver

Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button.

The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.

(2)Swing

If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.

8-8. Filter sign display

(1)The operation time of the indoor fan is calculated, the filter lamp (Orange) on the display part of the main unit goes on when the specified time (240H) has passed. When a wired remote controller is connected, the filter reset signal is sent to the remote controller, and also it is displayed on LCD of the wired remote control.

(2)When the filter reset signal has been received from the wired remote control after [FILTER] lamp has gone on or when the filter check button (Temporary button) is pushed, time of the calculation timer is cleared. In this case, the measurement time is reset if the specified time has passed, and display on LCD and the display on the main unit disappear.

Remarks:

[FILTER] goes on

Tc (°C)

M

55 A

 

 

 

 

 

 

N

52

 

 

48 B

L

Fig. 8-6-1

Ð 24 Ð

8-9. Auto Restart Function

The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored.

This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.

When the unit is on standby (Not operating)

8-9-1. How to set auto restart function

To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off.

Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.

Operation

Push [TEMPORARY] button for more than three seconds.

 

0

Hi POWER FILTER PRE.D

3S

TEMPORARY button

When the unit is in operation

Operation

Push [TEMPORARY] button for more than three seconds.

 

0

Hi POWER FILTER PRE.D

3S

TEMPORARY button

 

 

Motions

The unit is on standby.

 

 

 

The unit starts to operate.

The green lamp is on.

After approx. three seconds,

The unit beeps three times

The lamp changes from

and continues to operate.

green to orange.

If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.

 

 

Motions

The unit is in operation.

The green lamp is on.

 

 

The unit stops operating.

The green lamp is turned off.

After approx. three seconds,

The unit beeps three times.

If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on.

While this function is being set, if the unit is in

While the filter check lamp is on, the

operation, the orange lamp is on.

TEMPORARY button has the function of filter

This function can not be set if the timer operation

reset button.

 

has been selected.

 

When the unit is turned on by this function, the louver will not swing even though it was swinging automatically before shutting down.

Ð 25 Ð

Loading...
+ 61 hidden pages