PVI Industries 1000P900A-TPGO, TurboPower Tank, 2500P900A-TPGO, 750 P 900A-TPGO, 1250P900A-TPGO User Manual

...
0 (0)
PVI Industries 1000P900A-TPGO, TurboPower Tank, 2500P900A-TPGO, 750 P 900A-TPGO, 1250P900A-TPGO User Manual

 

 

TURBOPOWER® GAS/OIL

PACKAGED WATER HEATER

 

 

 

 

POLYSHIELD® POLYMER-LINED STORAGE TANK

 

 

 

 

 

 

 

 

 

 

TANK SERIES 900 GALLONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recovery gph

 

 

Min. Inlet Flow

 

Dimensions (inches)

 

Blower

Shipping

 

Model

Input

#2 Oil

 

Motor

 

Number

 

 

Btu/h

Gas Pressure

gph

 

 

 

 

 

 

 

Weight

 

 

 

 

 

 

 

 

 

Volt/Ph/

 

40°- 120°F

40°- 140°F

"W.C.

 

A

B

C

J

HP

 

lbs

 

 

 

 

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

P 900A-TPGO

750

600

600,000

4.5

 

4.3

46

6

1

31

1/2

 

115/1 /10

3320

1000

P 900A-TPGO

1000

800

800,000

6.0

 

5.7

46

8

1

31

1/2

 

115/1 /10

3360

1250

P 900A-TPGO

1250

1000

1,000,000

7.5

 

7.2

46

8

1

31

3/4

 

115/1 /14

3450

1500

P 900A-TPGO

1500

1200

1,200,000

7.5

 

8.6

46

8

1-1/4

31

1

 

115/1 /16

3530

2000

P 900A-TPGO

2000

1600

1,600,000

6.5

 

11.4

60

10

2

36

2

 

115/1/ 24

3740

2500

P 900A-TPGO

2500

2000

2,000,000

8.0

 

14.3

60

10

2

36

2

 

115/1 /24

3860

Recoveries based on 83% thermal efficiency. "J" dimension is for the burner housing only. Standard gas train.

ASHRAE 90.1 compliant for efficiency and standby loss. Gas train may exceed this dimension.

*The information presented is for Natural gas 0.6 S.G.— For operation with propane (LP gas), consult factory. Dimensions are in inches unless otherwise specified.

Higher inputs available. Consult the factory.

For standard and optional equipment, see form PV 6047.

* GAS PRESSURE REQUIREMENTS

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.

MAXIMUM STATIC INLET PRESSURE: 14" W.C.

FOR PRESSURES OTHER THAN LISTED, CONSULT FACTORY.

Pressure shown is for standard UL gas train. Additional controls may increase pressure requirements.

VENTING REQUIREMENTS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE)

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER SIZING, CONSULT

THE NATIONAL FUEL GAS CODE UNDER “FAN-ASSISTED.”

* REAR ACCESS MODULE

MODEL PREFIX

M

L

STD or OPTIONAL

 

 

 

 

750-1500

23"

8"

OPTIONAL

 

 

 

 

2000-2500

23"

8"

STANDARD

 

 

 

 

STANDARD ELECTRICAL REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS. MOTOR VOLTAGE:

208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN OPTIONAL CONTROL CIRCUIT TRANSFORMER.

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN

AND SPECIFICATION WITHOUT NOTICE.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 5480 03/04

(800) 784-8326 (817) 335-9531 www.pvi.com

Product is patented in the U.S., Canada, and Mexico.

 

 

Loading...