PVI Industries 299 SS A-PN, 399 SS A-PN, 199 SS A-PN User Manual

0 (0)
PVI Industries 299 SS A-PN, 399 SS A-PN, 199 SS A-PN User Manual

PLATINUM ® • CONDENSING GAS WATER HEATER

STAINLESS STEEL TANK

TANKSERIES70GALLONS

MODEL NUMBER X

199 SS A-PN

299 SS A-PN

399 SS A-PN

Input Btu/h

199,000

299,000

399,000

GPH Recovery Rate at 40°F to 140°F

221

340

444

Storage Capacity - gallons

80

70

70

1st Hour Delivery (100°F T) - gallons

289

397

501

 

 

 

 

Hot Outlet and Cold Inlet - NPT

2

2

2

Flue Connection Diameter - inches

3 *

4

4

Approximate Shipping Weight - lbs

1000

1100

1100

Dimensions are in inches unless otherwise noted.

For standard and optional equipment, see form # PV 6811.

* When connected with field provided 3” x 4” adapter of the same material as required for venting (see I&M).

STANDARD GAS PRESSURE REQUIREMENTS

MINIMUM FLOW GAS PRESSURE: 4.5" W.C. MAXIMUM STATIC GAS PRESSURE: 10.5" W.C.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE, CONTACT YOUR PVI REPRESENTATIVE.

STANDARD ELECTRICAL REQUIREMENTS

120V, 1Ø, 60 HZ.

MAXIMUM AMP DRAW (TRIAL FOR IGNITION): 6 CONTINUOUS AMP DRAW WHEN FIRING: 1.3 CONTINUOUS AMP DRAW DURING STANDBY: 0.03

VENTING REQUIREMENTS

CATEGORY IV - POSITIVE PRESSURE, CONDENSING.

UL CLASSIFIED FOR SCHEDULE 40, SOLID-WALL PVC OR CPVC PIPE. “SANI” TEMPERATURE HEATER REQUIRES CPVC VENT PIPE

SEE INSTALLATION MANUAL FOR VENTING

AND DIRECT COMBUSTION AIR GUIDELINES.

This product is protected by patents in the U.S., Canada and Mexico.

PV 6812 09/08

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN

AND SPECIFICATION WITHOUT NOTICE.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111 (800) 784-8326 y www.pvi.com