PLATINUM ® • CONDENSING GAS WATER HEATER
STAINLESS STEEL TANK
TANKSERIES70GALLONS
MODEL NUMBER X |
199 SS A-PN |
299 SS A-PN |
399 SS A-PN |
Input Btu/h |
199,000 |
299,000 |
399,000 |
GPH Recovery Rate at 40°F to 140°F |
221 |
340 |
444 |
Storage Capacity - gallons |
80 |
70 |
70 |
1st Hour Delivery (100°F T) - gallons |
289 |
397 |
501 |
|
|
|
|
Hot Outlet and Cold Inlet - NPT |
2 |
2 |
2 |
Flue Connection Diameter - inches |
3 * |
4 |
4 |
Approximate Shipping Weight - lbs |
1000 |
1100 |
1100 |
Dimensions are in inches unless otherwise noted.
For standard and optional equipment, see form # PV 6811.
* When connected with field provided 3” x 4” adapter of the same material as required for venting (see I&M).
STANDARD GAS PRESSURE REQUIREMENTS
MINIMUM FLOW GAS PRESSURE: 4.5" W.C. MAXIMUM STATIC GAS PRESSURE: 10.5" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE, CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS
120V, 1Ø, 60 HZ.
MAXIMUM AMP DRAW (TRIAL FOR IGNITION): 6 CONTINUOUS AMP DRAW WHEN FIRING: 1.3 CONTINUOUS AMP DRAW DURING STANDBY: 0.03
VENTING REQUIREMENTS
CATEGORY IV - POSITIVE PRESSURE, CONDENSING.
UL CLASSIFIED FOR SCHEDULE 40, SOLID-WALL PVC OR CPVC PIPE. “SANI” TEMPERATURE HEATER REQUIRES CPVC VENT PIPE
SEE INSTALLATION MANUAL FOR VENTING
AND DIRECT COMBUSTION AIR GUIDELINES.
This product is protected by patents in the U.S., Canada and Mexico.
PV 6812 09/08
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111 (800) 784-8326 y www.pvi.com