POWERWARE® 9 PRESTIGE SERIES
User’s Guide
600 VA - 1800 VA
www.powerware.com
FCC Statement
The Powerware9 9 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding information applies:
Class A
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment in a residential area is likely to cause interference in which case the user will be required to correct the interference at his own expense.
Class B
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
:Reorient or relocate the receiving antenna.
:Increase the separation between the equipment and receiver.
:Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
:Consult the dealer or an experienced radio/TV technician for help.
European EMC Statement
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures.
EC Declaration of Conformity
Units that are labeled with a CE mark comply with the following EU directives:
73/23/EEC |
Council Directive on equipment designed for use within certain voltage limits. |
93/68/EEC |
Amending Directive 73/23/EEC. |
89/336/EEC |
Council Directive relating to electromagnetic compatibility. |
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452661
Fax: +358-9-452-66395
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarks of Powerware Corporation. IBM and AS/400 are registered trademarks of International Business Machines Corp.
Novell is a registered trademark of Novell, Inc.
3Com is a registered trademark of 3Com Corporation.
.Copyright 1993-99 Powerware Corporation, Raleigh, North Carolina, U.S.A. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.
120V MODEL QUICK INSTALLATION
1
2
230V MODEL QUICK INSTALLATION
NOTE For 208, 220, or 240V models, follow the instructions for changing the output voltage on page 32.
1
2
TABLE OF CONTENTS
1 |
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
1 |
|
UPS Model and Battery Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
2 |
|
Load Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
2 |
|
Battery Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
3 |
|
Special Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
7 |
2 |
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
9 |
|
Sikkerhedsanvisninger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
10 |
|
Belangrijke Veiligheidsinstructies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
|
Tarkeita Turvaohjeita . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
Consignes de sécurité . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
15 |
|
Sicherheitswarnungen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
16 |
|
РспейдпрпйЮуейт БуцЬлейбт . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
18 |
|
Avvisi di sicurezza . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
20 |
|
Viktig Sikkerhetsinformasion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
21 |
|
Regulamentos de Segurança . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
|
Предупреждения по мерам безопасности . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
Advertencias de Seguridad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
|
Säkerhetsföreskrifter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
27 |
3 |
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
29 |
|
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
29 |
|
UPS and Battery Cabinet Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
29 |
|
UPS and Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
29 |
|
UPS Startup for 120V Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
31 |
|
UPS Startup for 208V-240V Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
32 |
|
Troubleshooting Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
34 |
4 |
UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
|
UPS Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
|
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
|
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
|
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
37 |
|
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
37 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
i |
Table of Contents
|
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
38 |
|
Battery Test on Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
38 |
|
Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
|
UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
|
Changing the Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
|
Using the PowerPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
40 |
|
Using Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
5 |
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
45 |
|
Initial Communications Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
45 |
|
Front Panel Communications Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
46 |
|
UPS Serial Communications Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
48 |
|
Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
51 |
|
UPS Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
52 |
|
Communications Mode Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
53 |
6 |
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
55 |
|
Prestige UPS Model Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
55 |
|
Prestige UPS Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
56 |
|
Prestige UPS Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
56 |
7 |
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
57 |
|
Resetting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
59 |
|
Silencing the Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
59 |
|
Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
60 |
|
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
61 |
ii |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
C H A P T E R 1
INTRODUCTION
Congratulations on the purchase of your Powerware9 9 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available.
The Prestige provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power. Voltage spikes, power surges, brownouts, and power failures have the potential to corrupt critical data, destroy unsaved work sessions, and in some instances, damage expensive hardware.
With the Prestige, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. The optional PowerPass9 has a Maintenance Bypass feature that supplies power to your equipment even when the UPS electronics are removed for maintenance or upgrades. Figure 1 shows the Prestige UPS.
Figure 1. Prestige UPS
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
1 |
Introduction
UPS Model and Battery Configurations
This UPS is designed to work with single-phase, three-wire, AC power sources. There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment:
:Load requirements
:Battery times
Load Requirements
The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA). The total load VA should not exceed the UPS VA rating. To determine the total load requirements:
1.Obtain the load ratings from either the nameplate or operator’s manual of the equipment to be protected by the UPS. The ratings are listed in either watts (W), amperes or amperes
max (A), or volt-amperes.
2.If the rating is in watts, multiply by 1.4 to obtain the VA requirement (this is the typical relationship between watts and volt-ampere ratings in most computing equipment). However, in some new computing equipment, the power supply is power-factor corrected and the watts rating equals the VA requirement. Check with the manufacturer to determine applicability.
If the rating is in amperes or amperes max, multiply by the input voltage to obtain the VA requirement.
2 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Introduction
3.Add all of the resultant VA ratings together to obtain the total load requirements of the equipment to be protected (see Figure 2). If the load consists of the power-factor corrected supplies, it is recommended to use total watts for the load requirements.
|
COMPUTER |
|
|
MONITOR |
|
EXTERNAL |
|
|
|
|
|
|
|
MODEM |
|
|
100 WATTS |
|
|
2 AMPS |
|
50 VA |
|
|
|
|
|
|
|
|
|
100 WATTS x 1.4 = 140 VA |
2 AMPERES x 120 = 240 VA |
50 VA |
|||||
or 1 AMPERE x 240 = 240 VA |
|||||||
|
|
|
|
140 VA + 240 VA + 50 VA = 430 VA (Total Load Requirements)
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of the UPS, you must either reduce the number of pieces of equipment, or use a UPS with a larger load capacity.
When deciding on which pieces of equipment to remove from the UPS, select equipment that has a lower priority for power protection. Computers, monitors, and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs.
Battery Times
During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown. The duration of this time period is directly related to the UPS battery configuration. By adding battery cabinets (EXT models only), you can customize the UPS to provide enough battery time for normal processing activities.
The rating label on the UPS rear panel shows the model number. Model numbers with a “P2” are EXT units; numbers with “HV” are high voltage units (208 - 240V models). The following tables show the average battery times by product model.
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
3 |
Introduction
Prestige 600 - 1500 VA, 120V Models
Load |
Load |
|
|
Internal UPS Batteries (Rounded to the Nearest Minute) |
|
||||||||||||||
(VA) at |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(W) |
650 |
|
800 |
1000 |
|
750 EXT |
1000 EXT |
1250 EXT |
1500 EXT |
||||||||||
.7 PF* |
|
|
|||||||||||||||||
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
200 |
140 |
37 |
|
37 |
37 |
|
|
|
68 |
|
|
68 |
|
68 |
|
68 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
400 |
280 |
22 |
|
22 |
22 |
|
|
|
32 |
|
|
32 |
|
32 |
|
32 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
600 |
420 |
12 |
|
12 |
12 |
|
|
|
20 |
|
|
20 |
|
20 |
|
20 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
800 |
560 |
|
|
8 |
8 |
|
|
|
15A |
|
14 |
|
14 |
|
14 |
||||
1000 |
700 |
|
|
|
|
6 |
|
|
|
|
|
|
|
11 |
|
11 |
|
11 |
|
1250 |
875 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
8 |
|
1500 |
1050 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
Load |
Load |
|
|
External Battery Cabinet Configurations for EXT Models |
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
(VA) at |
1/2 |
|
1 |
1 1/2 |
|
2 |
2 1/2 |
|
3 |
|
3 1/2 |
|
4 |
||||||
(W) |
|
|
|
|
|
||||||||||||||
.7 PF* |
Cabinet |
Cabinet |
Cabinets |
Cabinets |
|
Cabinets |
Cabinets |
|
Cabinets |
Cabinets |
|||||||||
|
|
|
|||||||||||||||||
200 |
140 |
143 |
|
216 |
290 |
|
364 |
438 |
|
513 |
|
589 |
|
663 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
400 |
280 |
69 |
|
115 |
158 |
|
198 |
239 |
|
280 |
|
320 |
|
362 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
600 |
420 |
43 |
|
73 |
105 |
|
137 |
165 |
|
194 |
|
221 |
|
249 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
750 |
525 |
33 |
|
56 |
80 |
|
106 |
134 |
|
156 |
|
178 |
|
202 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
1000 |
700 |
23 |
|
39 |
57 |
|
75 |
95 |
|
114 |
|
135 |
|
151 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
1250 |
875 |
17 |
|
30 |
42 |
|
56 |
70 |
|
86 |
|
102 |
|
118 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
1500 |
1050 |
14 |
|
23 |
32 |
|
43 |
55 |
|
67 |
|
78 |
|
91 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Typical Power Factor (PF); A750 VA, 525W
4 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Introduction
Prestige 600 - 1250 VA, 208 - 240V Models
Load |
Load |
|
|
|
|
Internal UPS Batteries (Rounded to the Nearest Minute) |
|
||||||||||
(VA) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
800 |
|
1000 |
|
1250 |
|||||
at |
(W) |
600 |
|
|
800 |
|
1000 |
|
|
||||||||
.7 PF* |
|
|
|
|
|
EXT |
|
|
EXT |
EXT |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||
200 |
140 |
33 |
|
|
|
33 |
|
33 |
56 |
|
|
56 |
|
56 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
400 |
280 |
21 |
|
|
|
21 |
|
21 |
29 |
|
|
29 |
|
29 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
600 |
420 |
11 |
|
|
|
11 |
|
11 |
19 |
|
|
19 |
|
19 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
800 |
560 |
|
|
|
|
|
7 |
|
7 |
13 |
|
|
13 |
|
13 |
||
1000 |
700 |
|
|
|
|
|
|
|
6 |
|
|
|
|
10 |
|
10 |
|
1250 |
875 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
Load |
|
|
|
|
|
External Battery Cabinet Configurations for EXT Models |
|
||||||||||
(VA) |
Load |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1/2 |
|
1 |
|
1 1/2 |
|
2 |
2 1/2 |
3 |
3 1/2 |
|
4 |
||||||
at |
(W) |
|
|
|
|
||||||||||||
.7 PF* |
|
Cabinet |
Cabinet |
Cabinets |
Cabinets |
Cabinets |
Cabinets |
|
Cabinets |
Cabinets |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
200 |
140 |
133 |
|
203 |
274 |
|
346 |
418 |
491 |
564 |
|
637 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
400 |
280 |
70 |
|
117 |
159 |
|
201 |
243 |
285 |
328 |
|
371 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
600 |
420 |
46 |
|
76 |
110 |
|
141 |
171 |
200 |
230 |
|
260 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
800 |
560 |
33 |
|
55 |
79 |
|
105 |
132 |
153 |
176 |
|
199 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
1000 |
700 |
25 |
|
42 |
61 |
|
81 |
102 |
124 |
147 |
|
161 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
1250 |
875 |
19 |
|
32 |
46 |
|
61 |
77 |
94 |
111 |
|
129 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Typical Power Factor (PF)
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
5 |
Introduction
Prestige 1500 - 1800 VA, 208 - 240V Models
Load |
|
UPS with External Battery Cabinet Configurations (Rounded to the Nearest Minute) |
||||||||
(VA) |
Load |
Internal |
1/2 |
1 |
1 1/2 |
2 |
2 1/2 |
3 |
3 1/2 |
4 |
at |
(W) |
UPS |
Cabinet |
Cabinet |
Cabinets |
Cabinets |
Cabinets |
Cabinets |
Cabinets |
Cabinets |
.7 PF* |
|
Battery |
|
|
|
|
|
|
|
|
200 |
140 |
59 |
128 |
194 |
260 |
327 |
393 |
460 |
527 |
595 |
|
|
|
|
|
|
|
|
|
|
|
400 |
280 |
29 |
64 |
107 |
149 |
186 |
224 |
263 |
302 |
339 |
|
|
|
|
|
|
|
|
|
|
|
600 |
420 |
19 |
42 |
71 |
102 |
135 |
161 |
189 |
217 |
244 |
|
|
|
|
|
|
|
|
|
|
|
800 |
560 |
14 |
32 |
52 |
76 |
100 |
125 |
148 |
169 |
191 |
|
|
|
|
|
|
|
|
|
|
|
1000 |
700 |
11 |
24 |
41 |
59 |
77 |
98 |
119 |
138 |
156 |
|
|
|
|
|
|
|
|
|
|
|
1250 |
900 |
8 |
19 |
32 |
45 |
59 |
76 |
92 |
108 |
125 |
|
|
|
|
|
|
|
|
|
|
|
1500 |
1050 |
7 |
14 |
25 |
36 |
48 |
60 |
73 |
86 |
101 |
|
|
|
|
|
|
|
|
|
|
|
1800 |
1200 |
5 |
12 |
20 |
29 |
38 |
48 |
59 |
69 |
80 |
|
|
|
|
|
|
|
|
|
|
|
*Typical Power Factor (PF)
6 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Introduction
Special Symbols
The following common symbols may be found on the UPS:
LOAD ON - Press the button with this symbol to energize the output receptacles (Output On).
LOAD OFF - Press the button with this symbol to de-energize the output receptacles (Output Off).
SAFETY EARTHING TERMINAL - Indicates the primary safety ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information.
This symbol indicates that the UPS batteries should not be discarded in the trash. The UPS contains sealed lead batteries and must be disposed of properly. For battery replacement or removal, call your Local Distributor or the Help Desk at one of the telephone numbers on page 60.
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
7 |
Introduction
8 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
C H A P T E R 2
SAFETY WARNINGS
I M P O R T A N T S A F E T Y I N S T R U C T I O N S
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation of the UPS. Please read all instructions before operating the equipment and save this manual for future reference.
D A N G E R
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
C A U T I O N
:Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions.
:Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
:This UPS contains its own energy source (batteries). The output receptacles may carry live voltage even when the UPS is not connected to an AC supply.
:Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
:Never open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be extremely toxic.
:Use only the power supply cord provided with this UPS. The power cord is wired in accordance with National Electrical Code (NEC) specifications. Be sure the wall outlet to be used with the UPS is wired in accordance with these same specifications in order to avoid damage to your equipment. Be sure that overcurrent protection for the AC outlet is provided at the time of installation. Be sure the input plug is completely inserted into the wall outlet. Use a single-phase, three-wire, grounded AC outlet only.
:To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 104•F (40•C). Do not operate near water or excessive humidity (95% max).
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
9 |
Safety Warnings
:Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground from the UPS and the equipment connected to the UPS.
:To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 2.75 milliamperes.
:The wall outlet must be within 2 meters of the equipment and accessible to the operator. The on/off switch on the UPS does not electrically isolate the internal parts. Unplug the input cord from the wall outlet when disconnecting the unit for long periods of time.
:Please note that the output sockets on the UPS are electrically live whenever the
UPS Output On button is pressed, even if the input cord is disconnected.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE
SIKKERHEDSANVISNINGER
F A R E
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
A D V A R S E L
:Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes.
:Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer.
:Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
:Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild.
:Batterierne bør aldrig åbnes eller skilles ad. Elektrolyt, der slipper ud, er skadelig for hud og øjne og kan være overordentlig giftig.
10 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Safety Warnings
:Brug kun den netledning, som blev leveret med UPS’en. Denne netledning er tilsluttet ifølge specifikationerne for NEC (National Electrical Code). Sørg for, at stikket, som skal bruges til UPS’en, er tilsluttet ifølge de samme specifikationer for at undgå skade på dit udstyr. Sørg for, at der er overstrømsbeskyttelse på AC-stikket på monteringstidspunktet. Sørg for, at stikket er sat helt ind i stikkontakten. Brug en enfaset, -treledet AC-kilde, som er jordet.
:Installér denne UPS i et temperaturog fugtighedskontrolleret indendørsmiljø, frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).
:Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
:I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 2,75 milliampere.
:Stikkontakten må højst være 2 meter fra udstyret og tilgængelig for brugeren. UPS’ens afbryderkontakt isolerer ikke elektrisk de indvendige dele. Træk derfor stikket ud af kontakten, hvis enheden er slukket i lang tid ad gangen.
:Bemærk venligst, at stikkontakterne på UPS’en er strømførende, når knappen UPS
“Output On” er trykket ned, selvom indgangsnedledningen ikke er tilsluttet.
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
11 |
Safety Warnings
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZE INSTRUCTIES
DEZE HANDLEIDING BEVAT BELANGRIJKE
VEILIGHEIDSINSTRUCTIES
G E V A A R
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
O P G E L E T
:Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
:De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften.
:Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
:Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
:Nooit batterijen openen of beschadigen. Vrijkomend elektrolyt is schadelijk voor de huid en ogen, en kan uiterst giftig zijn.
:Uitsluitend het elektriciteitssnoer gebruiken dat bij deze UPS wordt geleverd. Het snoer is volgens de specificaties van de IEC (International Electrical Code) bedraad. Controleer of wandcontactdoos waarop de UPS wordt aangesloten, volgens deze zelfde specificaties is bedraad teneinde schade aan uw apparatuur te voorkomen. Controleer of het wandcontactdoos voldoende is afgezeherd. Controleer of de voedingsstekker goed in het stopcontact is gestoken. Gebruik uitsluitend een enkelfasig geaard wandcontactdoos met randaarde.
:Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuuren vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40EC niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
12 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Safety Warnings
:Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
:Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 2,75 milliampère hebben.
:De hoofdvoedingcontactdoos moet zich op minder dan 2 meter van de apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker. De aan/uit-schakelaar op de UPS biedt geen elektrische isolatie voor de inwendige onderdelen. De stekker uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt gebruikt.
:Neem er nota van dat de uitgangaansluit punten op de UPS altijd onder stroom staan wanneer de belastingschakelaar ( | ) wordt ingedrukt, ongeacht de aanwezigheid van de voeding.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
V A A R A
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
V A R O
:Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita.
:Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.
:Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
:Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
:Älä avaa tai riko akkuja. Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla erittäin myrkyllistä.
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
13 |
Safety Warnings
:Käytä vain tämän UPS-laitteen mukana toimitettua virtakaapelia, joka on kytketty kansallisten määräysten mukaisesti. Varmista, että UPS-laitteen kanssa käytetty pistorasia on johdotettu näiden samojen määritysten mukaisesti, jotta laitteet eivät vahingoittuisi. Varmista myös, että asennuksen yhteydessä vaihtovirran pistorasia varustetaan ylivirtasuojauksella. Työnnä kosketin kokonaan pistorasiaan. Käytä pelkästään yksivaihteista, kolmijohtoista, maadoitettua verkkopistorasiaa.
:Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin, joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 •C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi).
:Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
:Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä
2,75 milliampeeria (mA).
:Päävirtapistokkeen täytyy olla 2 m:n säteellä laitteistosta ja käyttäjän saatavilla. UPS-laitteen virtakytkin ei erota sisäosia verkkojännitteestä. Irrota sisääntulopistoke, jos kytket laitteen pois käytöstä pitkähköksi ajaksi.
:Ota myös huomioon, että UPS-laitteen ulostuloliittimissä on jännite aina kun painetaan UPSin lähtöteho PÄÄLLÄ -painiketta ( | ), riippumatta siitä, onko tulokaapeli kytkettynä tai ei.
14 |
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |
Safety Warnings
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ
IMPORTANTES
D A N G E R !
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
A T T E N T I O N !
:Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions nécessaires.
:Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité.
:Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
:Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser.
:Ne jamais ouvrir ou mutiler des batteries. L’électrolyte dégagé est nuisible à la peau et aux yeux et peut s’avérer extrêmement toxique.
:Utiliser uniquement le cordon d’alimentation fourni avec l’onduleur. Ce cordon est câblé conformément aux spécifications du Code électrique international (CEI). S’assurer que le câblage de la prise secteur devant être utilisée avec l’onduleur est lui aussi conforme à ces spécifications pour éviter d’endommager le matériel. S’assurer que la prise secteur est protégée contre les surcharges au moment de l’installation. S’assurer que la prise d’entrée est insérée à fond dans la prise secteur. Utiliser uniquement une prise secteur à trois fils, monophasée et mise à la terre.
:Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum).
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com |