Pentair MiniMax 200 User Manual

4.5 (2)

1 1

MiniMax® NT Pool & Spa Heaters

OPERATION & INSTALLATION MANUAL

To

Consumer

Retain For

Future

Reference

U.S. Patent Numbers 6,295,980 5,318,007 - 5,228,618 5,201,307 - 4,595,825

WARNING

FOR YOUR SAFETY - READ BEFORE OPERATING

If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury or loss of life.

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this heater or other appliances.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

For additional free copies of this manual; call (800) 831-7133.

Pentair Pool Products, Inc.

1620 Hawkins Ave., Sanford, NC 27330 (919) 774-4151

10951 W. Los Angeles Ave., Moorpark, CA 93021 (805) 523-2400

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

 

2

Table of Contents

 

Section I. Heater Identification Information ...........................................................

3

Section II. Introduction ............................................................................................

4

Important Notices .........................................................................................................................................................................

4

Warranty Information ....................................................................................................................................................................

4

Code Requirements ......................................................................................................................................................................

5

Consumer Information and Safety................................................................................................................................................

5

Section III. Installation ..............................................................................................

6

Specifications ................................................................................................................................................................................

6

Plumbing Connections ..................................................................................................................................................................

7

Valves ...........................................................................................................................................................................................

7

Manual By-Pass ............................................................................................................................................................................

7

Below Pool Installation .................................................................................................................................................................

7

Water Connections .......................................................................................................................................................................

8 - 9

Gas Connections ..........................................................................................................................................................................

10

Sediment Traps .............................................................................................................................................................................

10

Gas Pipe Sizing ............................................................................................................................................................................

11

Testing Gas Pressure/Gas Pressure Requirements ....................................................................................................................

12

Indoor Venting—General Requirements ......................................................................................................................................

13

Indoor (USA) / Outdoor (Canada) Installations ............................................................................................................................

14

Combustion Air Supply .................................................................................................................................................................

15

Vent Adaptors ...............................................................................................................................................................................

15

Indoor Installations —Venting Guidelines .....................................................................................................................................

16

Outdoor Installations —Venting Guidelines ..................................................................................................................................

17

Outdoor Vent Kit ...........................................................................................................................................................................

17

Electrical Connections ..................................................................................................................................................................

18

Wiring Schematic for all Dual Voltage Blowers ............................................................................................................................

19

Wiring Diagram—NT STD & TSI with DDTC ................................................................................................................................

20

Section IV. Operation ................................................................................................

21

Basic System Operation ...............................................................................................................................................................

21

HSI (Hot-Surface Ignition) Lighting/Operation ..............................................................................................................................

21

Safety Controls .............................................................................................................................................................................

22 - 23

Digital Display Temperature Controller (DDTC) ...........................................................................................................................

24 - 28

Section V. Troubleshooting .......................................................................................

28

Troubleshooting (DDTC)...............................................................................................................................................................

28

Troubleshooting (General) ............................................................................................................................................................

29

Service Checks - Ignition Module .................................................................................................................................................

29

Section VI. Maintenance .........................................................................................................

30

Maintenance Instructions..............................................................................................................................................................

30

Pressure Relief Valve ...................................................................................................................................................................

30

Energy Saving Tips .......................................................................................................................................................................

30

Spring, Fall and Winter Operation ................................................................................................................................................

31

Chemical Balance .........................................................................................................................................................................

32

Replacement Parts — NT STD& TSI w/DDTC .............................................................................................................................

33 - 35

Chauffe-eau pour piscine et spa MiniMax® NT/Guide d'Installation et de Fonctionnement ..........................

36-72

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section I.Heater Identification Information

3

 

 

 

 

Heater Identification Information

To identify the heater, see rating plate on the inner front panel of the heater. There are two designators for each heater, one is the Model Number and the other is the Heater Identification Number (HIN).

a.Heater Identification Number (HIN)

The following example simplifies the identification system:

1)HTR : Heater

2)(200, 250, 300 or 400) : Input rating (Btu/hr) X 1000

3)NT : MiniMax NT Series

4)STD or TSI : Series Character

5)NH : Gas type (Natural gas) and ignition system (Hot Surface Ignition)

6)Options :

Blank: Standard Model

ASME: ASME Certified (Bronze Headers)

ASHI: ASME Certified Bronze Header and High Altitude Rating HALT: High Altitude Rating

HEATER IDENTIFICATION INFORMATION — (HIN)

Rev. G • Rév. G

5-27-04

P/N • Réf.

472090

Section II. Introduction

4

Introduction

MiniMax® NT

Pool and Spa Heaters

Congratulations on your purchase of a MiniMax NT high performance heating system. Proper installation and service of your new heating system and correct chemical maintenance of the water will ensure years of enjoyment. The MiniMax NT is a compact, lightweight, efficient, induced-draft, gas fired high

performance pool and spa heater that can be directly connected to schedule 40 PVC pipe. The MiniMax NT also comes equipped with the Pentair multifunction temperature controller which shows, at a glance,

the proper functioning of the heater. All MiniMax NT heaters are designed with a direct ignition device, HSI (hot-surface ignition), which eliminates the need for a standing pilot. The MiniMax NT requires an external power source (120/240 VAC 60 Hz) to operate.

This instruction manual provides operating instructions, installation and service information for the MiniMax NT high performance heater. The information in this manual applies to all MiniMax NT models. It is very important that the owner/installer read and understand the section covering installation instructions, and recognize the local and state codes before installing the MiniMax NT. History and experience has shown that most heater damage is caused by improper installation practices.

IMPORTANT NOTICES

...For the installer and operator of the MiniMax NT pool and spa heater. The manufacturer’s warranty may be void if, for any reason, the heater is improperly installed and/or operated. Be sure to follow the instructions set forth in this manual. If you need any more information, or if you have any questions regarding to this pool heater, please contact Pentair Pool Products, Inc. at (800) 831-7133.

WARRANTY INFORMATION

The MiniMax NT pool heater is sold with a limited factory warranty. Specific details are described on the warranty registration card which is included with the product. Return the warranty registration card after filling in the serial number from the rating plate inside the heater.

Pentair Pool Products’ high standards of excellence include a policy of continuous product improvement resulting in your state-of-the-art heater. We reserve the right to make improvements which change the specifications of the heater without incurring an obligation to update the current heater equipment.

These heaters are designed for the heating of swimming pools and spas, and should never be used as space heating boilers, general purpose water heaters, in non-stationary installations, or for the heating of salt water. The manufacturer’s warranty may be void if, for any reason, the heater is improperly installed and/or operated. Be sure to follow the instructions set forth in this manual.

CAUTION

OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND VOID THE WARRANTY. Do not use

the heater to protect pools or spas from freezing if the final maintenance temperature desired is below 68° F., as this will cause condensation related problems.

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section II. Introduction

5

 

 

CODE REQUIREMENTS

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes. The heater, when installed, must be electrically grounded and bonded in accordance with local codes or, in the absence of local codes, in the USA, with the National Electrical Code, ANSI/NFPA 7; in Canada, with Canadian Electric Code, CSA C22.1.

CONSUMER INFORMATION AND SAFETY

WARNING

The U.S. Consumer Product Safety Commission warns that elevated water temperature can be hazardous. See below for water temperature guidelines before setting temperature.

1.Spa or hot tub water temperatures should never exceed 104° F. A temperature of 100° F. is considered safe for a healthy adult. Special caution is suggested for young children. Prolonged immersion in hot water can induce hyperthermia.

2.Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning.

3.Pregnant women beware! Soaking in water above 100° F. can cause fetal damage during the first three months of pregnancy (resulting in the birth of a brain-damaged or deformed child). Pregnant women should stick to the 100° F. maximum rule.

4.Before entering the spa or hot tub, the user should check the water temperature with an accurate thermometer. Spa or hot tub thermostats may err in regulating water temperatures by as much as 4° F.

5.Persons with a medical history of heart disease, circulatory problems, diabetes or blood pressure problems should obtain their physician's advice before using spas or hot tubs.

6.Persons taking medication which induce drowsiness, such as tranquilizers, antihistamines or anticoagulants should not use spas or hot tubs.

WARNING

Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the heater. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of control system and gas control which has been under water.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

6

Installation Instructions

SPECIFICATIONS

These installation instructions are designed for use by qualified personnel only, trained especially for installation of this type of heating equipment and related components. Some states require installation and repair by licensed personnel. If this applies in your state, be sure your contractor bears the appropriate license. See Figure 1 for Outdoor and Indoor Installations.

 

 

 

24.05

 

 

 

Heater

 

 

 

Depth

 

 

 

3.50

 

 

 

14.50

LEG

6.64

8.84

4.88

 

 

"A" DIM.

 

 

 

DIMENSIONS IN INCHES

 

 

 

 

 

 

 

MODEL

"A" DIM.

 

 

 

 

 

200

21.63

 

 

 

 

 

250

24.63

 

 

 

 

 

300

27.63

 

 

 

 

 

400

34.13

 

 

 

 

 

OUTDOOR INSTALLATION

15.50

7.35

2 in. SOCKET

30.63

24.05

LEG

INDOOR INSTALLATION

INDOOR VENT ADAPTOR

 

 

P/N 460506

4 in. Kit

VENT ADAPTOR

 

 

 

 

P/N 460507

5 in. Kit

(See Indoor Venting

2.00

 

15.50

Instructions)

 

7.35

 

 

 

 

2 in. SOCKET

 

 

 

24.05

 

30.63

Figure 1.

LEG

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section III. Installation

7

 

 

 

 

TO

PUMP

 

 

POOL

POOL

 

FILTER

MANUAL

 

HEATER

 

 

BY-PASS

 

 

 

 

 

 

CHECK

GATE

 

 

VALVE

 

 

VALVE

 

 

Figure 2.

 

 

CHECK

 

 

FROM

 

 

 

VALVE

 

 

 

POOL

PLUMBING CONNECTIONS

The MiniMax NT heater has the unique capability of direct schedule 40 PVC plumbing connections. A set of bulkhead fittings is included with the MiniMax NT to insure conformity with Pentair’s recommended PVC plumbing procedure. Other plumbing connections can be used. See Figure 2 for plumbing connections.

CAUTION

Before operating the heater on a new installation, turn on the circulation pump and bleed all the air from the filter using the air relief valve on top of the filter. Water should flow freely through the heater. Do not operate the heater unless water in the pool/spa is at the proper level. If a manual by-pass is installed, temporarily close it to insure that all air is purged from the heater.

VALVES

When any equipment is located below the surface of the pool or spa, valves should be placed in the circulation piping system to isolate the equipment from the pool or spa. Check valves are recommended to prevent back siphoning.

CAUTION

Exercise care when installing chemical feeders so as to not allow back siphoning of chemical into the heater, filters or pump. When chemical feeders are installed in the circulation of the piping system, make sure the feeder outlet line is down stream of the heater, and is equipped with a positive seal noncorrosive “Check Valve”, (P/N R172288), between the feeder and heater.

MANUAL BY-PASS

Where the flow rate exceeds the maximum 120 GPM,

a manual bypass should be installed and adjusted. After adjustments are made, the valve handle should be removed to avoid tampering. See Figure 2.

Model

Min. (GPM)

Max. (GPM) *

 

 

 

 

 

200

20

120

 

 

 

 

 

250

30

120

 

 

 

 

 

300

30

120

 

 

 

 

 

400

40

120

 

 

 

 

 

* Do not exceed the maximum recommended

 

flow rate for the connecting piping.

 

 

 

 

 

 

 

Table 1.

See page 30 for Pressure Relief Valve Installations.

BELOW POOL INSTALLATION

If the heater is below water level, the pressure switch must be adjusted. This adjustment must be done by a qualified service technician.

See following CAUTION before installation.

CAUTION

BELOW OR ABOVE POOL INSTALLATION

The water pressure switch is set in the factory at 1½ PSI. This setting is for a heater installed at pool level or within 3’ above or 3’ below. If the heater is to be installed more that 3’ above or 3’ below, the water pressure switch must be adjusted by a qualified service technician. See page 22, Figure 22.

FLOW SWITCH

If the heater is installed more the 6’ above the pool or more than 10’ below the pool level, you will be beyond the limits of the pressure switch and a flow switch must be installed. Locate and install the flow switch externally on the outlet piping from the heater, as close as possible to the heater. Connect the flow switch wires in place of the water pressure switch wires.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

8

 

 

WATER CONNECTIONS

Reversing Headers —

Reversible Inlet/Outlet Connection

The MiniMax NT Series heater is factory assembled with right side inlet/outlet water connections. The inlet/outlet header can be reversed for left side water connections without removing the heat exchanger.

Reversing Water Connections

Tools required:

Phillips Screw Driver

9/16 in. Socket and Wrench 1/2 in. & 9/16 in. Open Wrench

1.Remove the right and left large access doors. It is not necessary to remove the top of the heater to gain access to the headers.

2.Disconnect all wires from the high-limit switches except the short jumper wire.

NOTE

Do NOT remove the high-limit and pressure switches or the thermistor from the front header during the reversing procedure, as they will be in the proper location when installed on the left side.

3.Disconnect the water pressure switch wiring.

4.Disconnect the temperature sensor wires from the circuit board and feed them back to the header.

5.Remove the 8 bolts holding the main inlet/outlet head.

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section III. Installation

9

 

 

Reversible Inlet/Outlet Connection, cont’d.

On the MiniMax NT Series heater there is insulation installed by the factory on the return head side of the heaters. This insulation is there so that if the heads are reversed in the field, during initial installation of the heater, the high limits will be insulated from the heat radiating from the flue collector.

6.Return head in position before removal. This view shows the insulation installed by the factory. Remove the 8 bolts holding the return head in place.

7.When heads are removed, replace the heat exchanger tube seal gaskets.

8.Exchange the inlet/outlet header with the return header. Lift the insulation to allow the main head to be installed. Align header with the heat exchanger. When head is placed into position, release the insulation; it will now shield the high limits from the heat produced by the flue collector. Install header bolts, and tighten snugly by hand. (This will help avoid cross threading.) When tightening, use a cross pattern starting from the center of the header. DO NOT over tighten.

9.Install the temperature sensing probe by passing the wires through the hole provided on the left side of the brace panel. Route wires through the support bracket.

10.Reconnect all the high limit wires and the pressure switch wiring, routing the wires through the same hole as the thermostat sensor wires.

11.Pump and bleed system to check the head for leaks.

12.Reinstall the two large inspection plates on the appropriate side.

Remember: The inlet and outlet markings on the header are still correct.

Do not plumb the heater backwards.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

10

 

 

GAS CONNECTIONS

GAS LINE INSTALLATIONS

Before installing the gas line, be sure to check which gas the heater has been designed to burn. This is important because different types of gas require different gas pipe sizes. The rating plate on the heater will indicate which gas the heater is designed to burn. The tables, shown on page 11, show which size pipe is required for the distance from the gas meter to the heater. The table is for natural gas at a specific gravity of .65 and propane at a specific gravity of 1.55.

When sizing gas lines, calculate three (3) additional feet of straight pipe for every elbow used. When installing the gas line, avoid getting dirt, grease or other foreign material in the pipe as this may cause damage to the gas valve, which may result in heater failure.

The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that may be used on the same meter. The gas line from the meter will usually be of a larger size than the gas valve supplied with the heater. Therefore a reduction of the connecting gas pipe will be necessary. Make this reduction as close to the heater as possible.

The heater and any other gas appliances must be disconnected from the gas supply piping system during any pressure testing on that system, (greater that ½ PSIG). The heater and its gas connection must be leak tested before placing the heater in operation. Do not use flame to test the gas line. Use soapy water or another nonflammable method.

NOTE

A manual main shut-off valve must be installed externally to the heater.

WARNING

DO NOT INSTALL THE GAS LINE UNION INSIDE THE HEATER CABINET. THIS WILL VOID YOUR WARRANTY.

SEDIMENT TRAPS

Install a sediment in front of the gas controls. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet which can be removed for cleaning, as illustrated in Figure 3, or a other device recognized as an effective sediment trap. All gas piping should be tested after installation in accordance with local codes.

 

GAS

GAS

VALVE

 

SUPPLY

UNION

 

TEE

 

FITTING

MANUAL

 

SHUT OFF

3 INCHES

VALVE

MINIMUM

 

NIPPLE

HEATER CABINET

CAP

 

Figure 3.

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section III. Installation

11

 

 

GAS PIPE SIZING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE SIZING FOR GAS LINE CONNECTIONS

 

 

 

 

 

 

 

 

 

MAXIMUM EQUIVALENT PIPE LENGTH (Ft.)

 

 

 

 

 

 

 

 

 

 

 

Natural Gas at 1000 B.T.U. per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Propane Gas at 2500 B.T.U. per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2”

3/4”

1”

1-1/4”

1-1/2”

 

2”

2-1/2”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

NAT

PRO

NAT

 

PRO

NAT

PRO

NAT

PRO

NAT

 

PRO

 

NAT

PRO

NAT

PRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

-

20’

30’

 

80’

125’

250’

450’

600’

-

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

-

10’

20’

 

50’

70’

150’

250’

500’

600’

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

-

-

10’

 

30’

50’

100’

200’

350’

400’

 

600’

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

-

-

-

 

10’

20’

60’

100’

150’

200’

 

450’

 

400’

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“RESIDENTIAL” PROPANE GAS 2 STAGE REGULATION

In many Propane gas line installations, the gas supplier and/or installer will utilize a two stage regulation process where by at the supply tank they will install the first stage gas regulator, which would be at a higher pressure, usually 10 psi. This higher pressure allows for a much longer distance and in a much smaller pipe size. Then within a short distance of the pool heater, usually around 24 inches, they will install a second regulator, which is the second stage, and this would be set at the required inlet pressure of the heater.

See “Gas Pressure Requirement Charts”

Stage One "High Pressure" Gas Pipe Sizing

 

 

 

Stage Two "Low Pressure" Gas Pipe Sizing

 

10 PSI @ 2500 B.T.U. Per CU. FT.

 

 

 

Stage 2 set at 14 in. W.C.

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM EQUIVALENT PIPE LENGTH

 

 

 

MAXIMUM EQUIVALENT PIPE LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

Model

0 to 50 Ft.

50 to 100 Ft.

100 to 150 Ft.

 

 

 

Model

0 to 10 Ft.

10 to 20 Ft.

 

 

 

 

 

200 through 400

1/2 in.

1/2 in.

1/2 in.

 

 

 

200 through 400

3/4 in.

3/4 in.

 

 

 

 

Table 3.

 

 

Table 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“RESIDENTIAL” NATURAL GAS 2 STAGE REGULATION

In many Natural gas line installations, the gas supplier and/or installer may utilize a two stage regulation process where by at the streets main gas supply they will install the first stage gas regulator, which would be at a higher pressure. This higher pressure is usually set at 2 psi or 5 psi and can be for long distances and in a much smaller pipe size. Then within a short distance of the pool heater, generally around 24 inches, they will install a second regulator, which is the second stage. This second stage regulator would be set at the minimum operating pressure for the heater. For “Natural Gas Pentair Pool Heaters” the minimum is 7 inches W.C.

See “Gas Pressure Requirement Charts”

Stage One "High Pressure" Gas Pipe Sizing

2 PSI @ 1000 B.T.U. Per CU. FT.

MAXIMUM EQUIVALENT PIPE LENGTH

 

Model

0 to 50 Ft.

50 to 100

Ft.

100 to 150 Ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

through 300

1/2

in.

1/2

in.

 

1/2 in.

 

 

 

 

 

 

 

 

 

 

 

400

3/4 in.

3/4 in.

 

3/4 in.

 

 

 

 

 

 

 

 

 

 

5 PSI @ 1000 B.T.U. Per CU. FT.

 

 

 

 

 

 

 

 

 

 

 

 

200

through 400

1/2

in.

1/2

in.

 

1/2 in.

 

 

 

 

 

 

 

 

 

 

 

 

Table 5.

Stage Two "Low Pressure" Gas Pipe Sizing

Stage 2 set at 7 in. W.C.

MAXIMUM EQUIVALENT PIPE LENGTH

Model

0 to 10 Ft.

10 to 20 Ft.

 

 

 

200 through 300

3/4 in.

3/4 in.

 

 

 

400

3/4 in.

1 in.

 

 

 

Stage 2 set at 7 in. W.C.

200 through 400

3/4 in.

1 in.

 

 

 

Table 6.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

12

 

 

TESTING GAS PRESSURE

 

 

 

 

Inlet

 

 

 

Manifold

Inlet

 

 

 

Manifold

1.

Push the power switch to “OFF”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Turn the gas valve knob to “OFF”.

 

 

 

 

 

 

 

 

 

 

3.

Remove 1/8 in. NPT plug on the outlet

 

 

 

 

 

 

 

 

 

 

 

side of the valve and screw in the

 

 

 

 

 

 

 

 

 

 

 

fitting from the Manometer kit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Connect the Manometer hose to the

 

 

 

 

 

 

 

 

 

 

 

fitting.

 

 

 

 

 

 

 

 

 

 

5.

Turn the gas valve knob to “ON”.

 

 

 

 

 

 

 

 

 

 

6.

Turn on the heater and read the

 

 

 

 

 

 

 

 

 

 

 

Manometer.

 

 

 

 

 

 

 

 

 

 

7.

The Manometer must read per the

 

 

 

 

 

 

 

 

 

 

 

values of the Gas Pressure

 

 

 

 

 

 

 

 

 

 

 

Requirement Table, on manifold side

 

 

 

 

 

 

 

 

 

 

 

of the gas valve, while operating.

 

 

 

 

 

 

 

 

 

 

 

 

 

MiniMax NT TSI

MiniMax NT STD

8.

If reading is below specified; check the

 

 

Illustrations above are for Natural Gas, for Propane requirements, see Table 7.

 

inlet pressure while the heater is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

running to make sure of proper supply before attempting adjustments.

 

 

 

 

 

9.For adjustment, remove the Regulator Adjustment Cap and using a screwdriver turn the screw clockwise to increase - counterclockwise to decrease gas pressure.

CAUTION

The use of Flexible Connectors (FLEX) is NOT recommended as they cause excessive high gas pressure drops.

GAS PRESSURE REQUIREMENTS

 

 

Gas Pressure

Model

Natural

Propane

 

 

Inches W.C.

 

Regulator Adjustment Cap

 

 

 

 

 

 

 

1/8" NPT Plug

 

Maximum Inlet

STD

10

14

(Inlet Press)

 

TSI

10

N/A

 

 

 

 

 

Minimum Inlet

STD

5*

12

 

 

 

 

 

 

 

 

TSI

4

N/A

 

ON

Manifold

STD

4

11

 

 

 

 

 

 

 

 

TSI

2

N/A

 

OFF

NOTE: All readings must be taken while heater is

 

1/8" NPT Plug

 

operating. Any adjustments or readings made while

Figure 4.

(Manifold Press)

heater is off will result in performance problems.

 

 

 

 

All Values are +/- 0.2 inch W.C.

 

 

 

 

* 6 inch. W.C. for STD 400 Model.

 

 

 

 

 

 

 

Table 7.

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section III. Installation

13

 

 

INDOOR VENTING — General Requirements

The vent pipe must be the same size or larger. The MiniMax NT heaters are capable of a 360-degree discharge rotation and operate with a positive vent static pressure and with a vent gas temperature less than 400° F. The total length of the horizontal run must not exceed the length that is listed below in the tables.

NOTE

The allowable vent runs for each stack pipe diameter are different and can not be exceeded.

Each 90-degree elbow reduces the maximum horizontal vent run by 8 feet and each 45-degree elbow in the vent run reduces the maximum vent run by 4 feet. See the tables below for the maximum vent lengths using 90-degree and 45-degree elbows.

The MiniMax NT is a “Category III” appliance and is an induced-draft pool and spa heater which uses positive pressure to push flue gases through the vent pipe to the outside. This requires a completely sealed vent system—single wall vent pipe with sealed-seams and joints. Flue gases under positive pressure may escape into the dwelling with any cracks or loose joints in the vent pipe, or improper vent installation. The vent pipe must be of a sealed-seam construction, such as those listed for use with “Category III Appliances”, and for operating temperatures above 350° F. The use of listed thimbles, roof jacks and/or side vent terminals are required; and the proper clearances to combustible materials must be maintained in accordance with type of vent pipe employed—in the absence of a clearance recommendation by the vent pipe manufacturer, the requirements of the Uniform Mechanical Code should be met. The ventilation air requirements for the MiniMax NT heater can be

4 inch Vent Pipe

Number of

Maximum

Elbows

Vent Run

 

 

90°

45°

(Feet)

 

 

 

1

22

 

 

 

1

1

18

 

 

 

1

2

14

 

 

 

2

14

 

 

 

found on page 15. It is recommended that vent runs over 18 feet be insulated to reduce condensation related problems and/or the use of a condensate trap in the vent run close to the heater may be necessary in certain installations such as cold climates. The MiniMax NT heater is suitable for through-the- wall venting, see table and dimensions below.

Recommended sources for Side-wall vent hood terminals include: The Field Controls Co. (2308 Airport Road, Kingston, NC 28501, (800)742-8368) and Tjernlund Products Inc. (1601 Ninth Street, White Bear Lake, MN 55110, (800) 255-4208)— consult manufacturer for model information and availability.

CAUTION

Do NOT combine exhaust vent pipes to a common exhaust vent in multiple unit installations. Run separate vent pipes.

 

 

 

 

 

Table 8.

 

 

 

 

 

 

5 inch Vent Pipe

5 inch Vent Pipe

 

 

 

 

 

 

Number of

Maximum

Number of

Maximum

Elbows

Elbows

Vent Run

Vent Run

 

 

 

 

90°

45°

(Feet)

90°

45°

(Feet)

 

 

 

 

 

 

0

2

45

2

2

29

 

 

 

 

 

 

1

45

2

3

25

 

 

 

 

 

 

1

1

41

2

4

21

 

 

 

 

 

 

1

2

37

3

29

 

 

 

 

 

 

1

3

33

3

1

25

 

 

 

 

 

 

2

37

3

2

21

 

 

 

 

 

 

2

1

33

4

21

 

 

 

 

 

 

 

 

 

 

 

Table 9.

 

THROUGH WALL VENT KITS FOR HEATERS

 

C

F

Part

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

 

 

Number

A

 

 

 

 

 

 

 

 

 

 

B

E

 

 

 

 

 

 

 

 

 

 

 

 

471532

4

in. Dia.

6

in. Dia.

8½ in.

6 5/16 in.

12

5/8 in.

10

5/8 in.

 

 

471543

5

in. Dia.

8

in. Dia.

8½ in.

8 in.

12

5/8 in.

10

5/8 in.

 

D

Table 10.

 

 

 

 

 

 

 

 

Figure 5.

 

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

14

 

 

INDOOR INSTALLATION (USA ONLY)

OUTDOOR SHELTER INSTALLATION (CANADA)

See page 15 for Vent Adaptors

All products of combustion and vent gases must be completely removed to the outside atmosphere through a vent pipe which is connected to the stack adaptor. A vent pipe extension of the same size must be connected to the vent adaptor and extended at least 2 feet higher than highest point of the roof within a 10 foot horizontal radius, and at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code; see Figures 6, 7 and 12. The vent should terminate with an approved vent cap (weather cap) for protection against rain or blockage by snow. Insulated vent pipe and an approved roof jack shall be employed through the roof penetration.

The heater must be located as close as practical to a chimney or gas vent.

CAUTION

The heater should be installed at least 5 feet away from the pool or spa.

The heater must be placed in a suitable room with adequate ventilation and on a leveled floor, where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan with adequate drainage, be installed under the heater. The pan must not restrict air flow.

It is recommended to install the heater on fire-resistance slabs. Do not install the heater directly on a combustible wood floor without placing a non-combustible material between the floor and the heater. Heaters must NEVER be installed directly on carpeting.

Installations in basements, garages, or underground structures where flammable liquids may be stored must have the heater elevated 18 inches from the floor. The following minimum clearances from combustible materials must be provided.

 

 

INSTALLATION

 

 

SIDE

 

 

 

INDOOR

 

 

 

OF

OUTDOOR

 

 

(Outrdoor Shelter)

 

 

HEATER

 

 

 

 

 

 

 

 

INCHES

INCHES

 

 

 

 

 

 

 

WATER PIPING

18

18

 

 

 

 

 

 

 

BLANK

6

6

 

 

 

 

 

 

 

REAR

6

6

 

 

 

 

 

 

 

TOP *

18

Open Un-roofed Area

 

 

 

 

 

 

 

FRONT

24

24

 

 

 

 

 

 

 

* To ceiling or roof.

 

Table 11.

 

 

 

 

P/N • Réf. 472090

 

 

 

 

 

 

 

 

 

Chimney or Gas Vent

 

 

 

 

 

 

Vent Cap and

 

 

 

 

 

 

 

 

 

 

Riser Furnished

 

 

 

 

by Installer

 

 

 

 

 

 

 

 

 

 

 

Outlet Air

Opening

Optional

Side

Wall Vent

Inlet Air

Opening

Heater

Figure 6.

 

 

 

 

 

 

Chimney or Gas Vent

 

 

 

 

 

 

Vent Cap and

 

 

 

 

 

 

 

 

 

 

Riser Furnished

 

 

 

 

by Installer

 

 

 

 

 

 

 

 

 

 

 

Outlet Air Opening

Optional

Side

Wall Vent

Inlet Air Opening

Heater

Figure 7.

The heater should not be installed closer than 6 inches to any fences, walls or shrubs at any side or back, nor closer than 18 inches at the plumbing side. A minimum clearance of 24 inches must be maintained at the front of the heater.

 

 

6"

 

 

DOOR

6"

 

24"

 

 

 

 

 

18"

 

Figure 8.

 

 

 

 

 

Rev. G • Rév. G

5-27-04

Section III. Installation

15

 

 

 

COMBUSTION AIR SUPPLY

For indoor installation, the heater location must provide sufficient air supply for proper combustion and ventilation of the surrounding area.

The requirements for the air supply specify that the room in which a heater is installed should be provided with two permanent air supply openings; one within 12 inches of the ceiling, the other within 12 inches of the floor. These openings shall directly, or through duct, connect to outdoor air.

Pentair Pool Products, Inc. does not recommend indoor installations that do not provide combustion air from outside the building.

Air Supply Requirements Guide

for MiniMax NT Heaters

Net Free open Area for Each Opening * (Square Inches)

Heater

Ducted from

Direct from

Size

Outside

Outside

 

 

 

200

100

50

 

 

 

250

125

63

 

 

 

300

150

75

 

 

 

400

200

100

 

 

 

* Area indicated is for one of two openings; one at floor level and one at the ceiling.

NOTE: If using louvered type or screen type openings, check with Louver/Screen Manufacturers to correct for the Louver/Screen resistance.

Table 12.

CAUTION

Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.

VENT ADAPTORS

(FITS ALL MODELS)

The proper vent adaptor must be installed on the heater as shown below in Figure 9.

Product No.

Vent Dia.

 

 

460506

4 in.

 

 

460507

5 in.

 

 

Vent

Adaptor

1.Remove the six (6) retaining screws from the old exhaust grill and discard the screws, gasket, and exhaust grill as shown in Figure 10.

EXHAUST GRILL

SCREWS (6)

GASKET

Figure 10.

2.Install the Vent Adaptor as shown in Figure 11. Make sure the holes in the gasket, metal flange of the main vent assembly, and heater cover are aligned before securing into place using the six

(6) screws provided in the Vent Adaptor Kit.

METAL FLANGE

SCREWS (6)

GASKET

Figure 9.

Figure 11.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

472090 .Réf • P/N

04-27-5 G .Rév • G .Rev

 

vent terminated at least 24"

 

above any object within 10 ft.

 

More Than10 ft.

Ridge

Vent Cap

 

2 ft. min.

 

3 ft. min. J

Detail H

K

L

JackRoof

 

Chimney

Vent for roof penetration installations:

Jmust extend at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code.

Kmust use a roof thinble or double-wall vent pipe through the roof penetration.

Lmust terminate with an approved (listed) roof jack, storm collar, and vent/weather cap.

Vent pipe extension:

must be the same diameter as the vent connector.

must be suitable for use with category III appliances which have flue gas temperatures of less than 400 deg. F.

may use a single wall vent pipe with permanently sealed seams and joints.

INDOOR INSTALLATIONS

MINIMAX NT VENTING GUIDELINES

H

 

 

F 1' min.

 

 

E

Air Supply

1' min.

 

Vent Hood

F

 

 

 

Ventilation

 

 

 

4'

 

 

 

 

 

G

B

C

Vent Hood

 

3'

 

Air Supply

4' D

 

 

A

 

 

1' min.

Combustion

 

 

Vent Hood

 

above grade

 

7'

 

 

G

Walkway

Recommended sources for

side wall Vent Hood; see page 13, Section Venting.

Vent termination for side wall installations:

Amust be not less than 7 ft. above public walkways.

Bmust be at least 3 ft. above any outside air intake located within a 10 ft. radius.

must NOT be within 3 ft. of an inside corner of the structure.

C must be at least 1 ft. above grade.

must be located the following distances away from any door, window, or gravity air inlet:

D4 ft. below

E4 ft. horizontally

F1 ft. above

Air Supply

G Clearances indicated are for non-mechanical air supply inlet to the building. For mechanical air supply inlet, a minimum horizontal clearance of 10 feet

should be maintained away from the vent termination.

Figure 12.

Installation .III Section

16

Section III. Installation

17

 

 

OUTDOOR INSTALLATION (Outdoor Shelter Installation in Canada, see page 14)

For outdoor installation with an exhaust grill, the heater must be placed in a suitable area on a level, noncombustible surface. Do not install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be open on three sides.

IMPORTANT!

In an outdoor installation it is important to ensure water is diverted from overhanging eves with a proper gutter/drainage system. The heater must be set on a level foundation for proper drainage.

Under certain conditions, “heavy rains or unusually high winds”, it may be necessary to install an outdoors vent. In this situation, use Outdoor Vent Kit, P/N 460424, (see below).

This unit shall not be operated outdoors at temperatures below -20o F.

OUTDOOR INSTALLATION

VENTING GUIDELINES

4'

 

3'

B

SIDE VIEW

A

 

 

4'

 

 

Property Line

4 ft.

 

C

D

 

 

Window

 

4'

 

4 ft.

Exhaust Grill

 

 

 

(Vent)

 

 

Building

 

 

 

 

 

Vent Termination:

Heater

A Must be at least 3 ft. above any forced

(side view)

air inlet located within a 10 ft. radius.

 

 

 

Figure 13.

Must be located 4 feet away from the building wall,

 

and at the following distances away from any door,

 

 

window, or gravity air inlet:

 

 

B

4 ft. below,

C 4 ft. horizontally, or

D Check local building codes for setback requirements.

OUTDOOR VENT KIT

1.Remove the six (6) retaining screws from the old exhaust grill and discard the screws, gasket, and exhaust grill as shown in Figure 14.

2.Install the Outdoor Vent Kit, (P/N 460424), as shown in Figure 15. Make sure the holes in the gasket, metal flange of the main vent assembly, and heater cover are aligned before securing into place using the six (6) screws provided in the Outdoor Vent Kit.

 

EXHAUST GRILL

METAL FLANGE

 

SCREWS (6)

 

SCREWS (6)

 

 

GASKET

 

GASKET

 

 

Figure 14.

Figure 15.

CAUTION

If installing the heater next to or near an air conditioning unit or a heat pump, allow a minimum of 36 in. between the air conditioning unit and the heater.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section III. Installation

18

 

 

 

 

ELECTRICAL CONNECTIONS

 

 

 

 

 

 

 

 

Electrical Rating 60 Hz

120 / 240 Volts AC, single phase

CAUTION

This heater is designed to operate at 120 or 240 VAC. It is not recommended to be connected to OR operate on a 208 VAC.

NOTE

The MiniMax NT heater is prewired for 240 volt AC connection using the “RED/BROWN” female connector and the “WHITE” common male connector; see below, Figure 16. If you require the heater to be connected to 120 volts AC, remove the “RED/BROWN” female connector from the “WHITE” common connector; now locate the “BLUE” female connector and plug it into the “WHITE” common connector.

When connecting the home wiring to the “Line Terminal Block” inside the junction box, follow the polarity as shown below. Connecting to 120 VAC, make sure that you connect the positive wire to the positive terminal (L), the neutral wire is connected to the neutral terminal (N) and the ground is connected to the ground terminal (GND); see below, Figure 17.

If any of the original wiring supplied with this heater must be replaced, installer must supply (No. 18 AWG, 600V, 105° C. U.L. approved AWM low energy stranded) copper wire or it’s equivalent. Thermal fuse wiring must be replaced with 18 AWG, 600V, 150° C. temp. rating.

CAUTION

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes. If an external electrical source is utilized, the heater, when installed, must be electrically grounded and bonded in accordance with local codes or, in the absence of local codes, in the USA, with the National Electrical Code, ANSI/NFPA 7; in Canada, with

Canadian Electric Code, CSA C22.1.

Always use crimp type connectors when connecting two wires.

 

 

RED/BROWN

WHITE

 

 

FM CONNECTOR

COMMON MALE

 

 

FOR USE WITH

CONNECTOR

 

 

240 VAC

 

 

 

 

 

BLUE

 

 

 

 

 

 

TERMINAL BLOCK

 

 

 

 

FM CONNECTOR

 

 

 

 

 

 

FOR AC INPUT

 

 

 

 

FOR USE WITH

 

 

 

 

 

 

120 / 240 VOLT SINGLE

 

 

 

 

120 VAC

 

 

 

 

 

 

PHASE "See Below"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You might need to open

 

 

 

 

 

 

 

 

 

 

 

 

the right door then remove

 

 

 

 

 

 

 

 

Figure 16.

 

the control panel cover for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

servicing the Line Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE TERMINAL BLOCK

 

 

 

 

 

 

Block as shown in Figures

 

 

 

 

 

 

 

 

 

 

16 & 17, (see item 40 in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exploded view on page 33).

 

 

 

 

 

 

GROUND

 

 

 

 

GREEN WIRE

 

 

 

 

CONNECTION

 

 

INTERNAL

WHITE WIRE

FACTORY WIRES

N

 

 

BLACK WIRE

 

L

NEUTRAL / WHITE 120 VAC LINE #1 FOR 240 VAC

HOT / BLACK 120 VAC

LINE #2 FOR 240 VAC

Figure 17.

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Section III. Installation

19

 

 

 

WIRING SCHEMATIC FOR ALL DUAL VOLTAGE BLOWERS

120 VOLTS AC

240 VOLTS AC

WHITE

LINE # 1

WHITE

LINE # 1

YELLOW

JOINED

YELLOW

CAP OFF

ORANGE

ORANGE

 

 

JOINED

 

 

 

 

 

BLACK

LINE # 2

BLACK

 

 

 

 

 

LINE # 2

PURPLE

PURPLE

 

BROWN

 

BROWN

 

=

CAPACITOR

=

CAPACITOR

BROWN

 

BROWN

 

NOTE FOR TEST OF THE BLOWER:

1.In reference to the above terms, "CAP OFF" means to no connection.

2.The term "JOINED" means the two wires are connected together and no external connection.

Figure 18.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Pentair MiniMax 200 User Manual

472090 .Réf • P/N

04-27-5 G .Rév • G .Rev

MiniMax NT TSI/DDTC Wiring Diagram

CON-FEM(BL)

 

FOR 120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

CON-MAL(W)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R/W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERM

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERM

B

 

 

 

BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK/W

 

BK

 

BK

 

BLOCK

 

 

 

G

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

W

 

 

 

W

 

 

 

 

120 VAC

 

 

 

 

HIGH LIMITS

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMAL FUSE

 

 

PR

 

W

 

 

W

 

W

N

W

OR

 

 

 

 

115˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

W

W

 

W

 

BK

 

2

 

BK

 

BK

BK

240 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

GAS VALVE

 

 

 

 

 

 

 

L

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

R

 

 

 

BK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

MV

G

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150˚F

 

 

 

 

 

 

 

 

 

BL

 

 

 

W

4

 

 

 

 

 

 

 

 

 

BK/W

W

 

 

 

 

W

 

 

 

MV

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CON-FEM(BR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR 240 VAC

 

 

 

 

BOND LOG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

(ON THE SIDE JACKET)

 

 

 

 

 

 

WATER PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

R/W

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTACH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

WIRE HERE

 

 

 

 

 

 

 

 

GY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PR

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

PR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEE OPERATION

 

 

 

 

 

W

 

 

 

HOT SURFACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& INSTALLATION

 

 

 

 

 

 

 

 

 

 

O

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MANUAL FOR

 

 

 

 

 

 

O

 

BR

FLAME SENSOR

PR

BK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

{

 

 

P4

P7

PI0

P11

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

COM

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GY

 

 

 

 

 

 

 

 

 

 

IGNITION MODULE

 

 

 

 

 

 

 

 

 

 

 

O

O

 

 

J5

J8

J6

J1

J2

J4

 

JI0

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

J7

J11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POOL

 

 

 

FAN

24V

TFUSE/HLMT/PRESS

VLV

IGN MOD

 

 

F1

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

SPA

24VAC

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGN/120

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

BL

 

F2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR PRESSURE SW.

 

 

 

 

 

 

 

 

 

 

P9

BK

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE COLOR

 

 

 

 

 

 

 

 

 

 

 

 

 

J9

Y

 

FC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGN/240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMISTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PR

 

FS

 

 

 

 

 

BK

 

 

: BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GY

 

PS

 

 

 

 

 

BL

 

 

: BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BR

 

 

: BROWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

VLV

 

 

 

 

 

G

 

 

: GREEN

 

 

 

 

 

DDTC

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GY

 

 

: GRAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

: ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PR

 

 

: PURPLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

: RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IF ORIGINAL FACTORY WIRING MUST BE REPLACED,

Y

 

 

: YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLER MUST SUPPLY UL/CSA APPROVED WIRE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

: WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WITH 18 AWG, 600V, 105˚C TEMP. RATING.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMAL FUSE WIRING MUST BE REPLACED WITH

 

R/W

 

: RED W/WHITE TRACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK/W : BLACK W/WHITE TRACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 AWG, 600V, 150˚C TEMP. RATING.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 19.

WIRING

.III Section

NT–DIAGRAM

Installation

DDTC WITH TSI & STD

 

20

Section IV. Operation

21

Operation Instruction

BASIC SYSTEM OPERATION

1.Start pump, make sure the pump is running and is primed, to close the water pressure switch and supply power to heater. Be sure the pool and/or spa is properly filled with water. Follow the Lighting/Operating instructions below.

MINIMAX NT HSI ELECTRONIC IGNITION LIGHTING/OPERATION

FOR YOUR SAFETY: READ BEFORE LIGHTING

WARNING

If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

Do not attempt to light the heater if you suspect a gas leak. Lighting the heater can result in a fire or explosion which can cause personal injury, death, and property damage.

A.This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

B.BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

-Do not try to light any appliance.

-Do not touch any electrical switch; do not use any phone in your building.

-Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

-If you cannot reach your gas supplier, call the Fire Department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

OPERATING INSTRUCTIONS

1.STOP! Read the safety information above, (A through D).

2.Open the access doors. Set power switch to ”OFF”, (see Figure 25).

3.Set the thermostat to ”OFF”, (see page 27).

4.This appliance is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

5.Push in gas control knob slightly and turn clockwise to “OFF”.

NOTE: Knob cannot be turned to “OFF” unless knob is pushed in slightly. Do not force.

6.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.

7. Turn gas control knob counterclockwise

to “ON”.

See Figure 20.

 

8.Close the access doors and set the thermostat to desired Mode: “POOL, SPA or REMOTE”.

9.Set the thermostat to the desired temperature setting.

a.Ignition module is energized and the pre-purge cycle is started, approximately 15 seconds.

b.Fan motor starts, which closes Vacuum Air Pressure (fan) switch.

c.Check for powering-up the (glow coil) hot-surface ignitor by viewing through the glass window or opening on the burner face plate.

10.If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.

Gas

 

Inlet

ON

 

OFF

Figure 20.

Gas control knob shown in “ON” position.

 

TO TURN OFF GAS TO APPLIANCE

1.Turn off all electric power to the appliance if service is to be performed.

2.Set the thermostat to “OFF”.

3.Open access doors.

4.Push in gas control knob slightly and turn clockwise to "OFF". Do not force.

5.Close access doors.

Rev. G • Rév. G 5-27-04

P/N • Réf. 472090

Section IV. Operation

22

SAFETY CONTROLS

 

 

Figure 21.

VACUUM AIR PRESSURE (FAN)

 

SWITCH

 

The air pressure switch, (see Figure 21), is a safety

 

device used to insure that the combustion air blower

 

(fan) is operating and has been designed to monitor

 

the vacuum (negative) pressure within the blower

 

housing. The air pressures switch is factory set and is

 

connected upstream of the ignition module. The

 

ignition module does not operate unless the air

 

pressure switch and all safety switches are closed.

 

 

AIR PRESSURE SWITCH

WATER PRESSURE SWITCH

Air Pressure Switch

 

The water pressure switch, (see Figure 22), closes when there is a sufficient flow of water to the heat exchanger to safely operate the heater. The switch has been preset by the Factory at 1 PSIG for operation.

NOTE: See, Below Pool Level Installation instructions on page 7. The switch may remain closed with no water flow if there is more than a 3 ft. elevation difference between the heater (heat exchanger) and the pool water line—if this is the case, the water pressure switch must be reset by a qualified service technician to maintain open switch contacts with no water flow.

NOTE

If the pool is more than one floor above or one floor below the heater, the water pressure switch may have to be replaced with a flow switch.

Figure 22.

Adjustment Knob

Typical Water Pressure Switch

THERMAL FUSE

This is a single-use switch, mounted on combustion chamber jacket divider (inner front panel). The fuse, (see Figure 23), is activated by excessive temperature due to abnormal operating conditions. Upon detection of excessive heat within the inner front panel, the fuse will open the safety circuit causing shutdown of the heater.

Figure 23.

Thermal Fuse

P/N • Réf. 472090

Rev. G • Rév. G 5-27-04

Loading...
+ 50 hidden pages