SNAP ON/OFF TOP COVERS:
Hides mounting screws
and protects the reader
OmniProx™ Reader
Installation Instructions Model Series OP10/20/30/40/45/90
WHAT IS THE Honeywell OmniProx™ READER?
The
OmniProx Reader is an RFID proximity card reader to
be installed for use with access control systems.
These installation instructions contain the following
information:
Mounting Instructions
Connecting the reader to the host
Testing and operation of the reader
Visit www.omniprox.com f or the latest information and
technical support.
HOW TO MOUNT THE READER
Figure 1 shows the front view of the OmniProx. When
mounting models OP10/20/30/40/45, the snap-off cover
must be removed to access the screw holes.
Figure 1
Check all electrical codes for proper installation.
U
L
Card Reader Models OP10/20/30/40/45/90 are to be
used with control panels whose power supply is UL
listed Class 2 or equivalent.
HOW TO CONNECT THE READER TO THE HOST
The OmniProx Reader is supplied with an 18-inch pigtail,
having a 6-conductor cable. To connect the reader to the
host, perform the following steps:
1. If there is a connector on the end of the cable (used
during manufacture for testing purposes), cut it off.
Prepare both the reader cable and host cables by
cutting the cable jacket back 1¼ inches and strip the
wires
½ inch.
2. Splice the reader pigtail wires to the corresponding
host wires and cover each connection (see Figure 2).
3. If the tamper output is being utilized, connect the
purple wire to the correct input on the host.
4. Trim and cover all conductors that are not used.
Figure 2 below shows how you should wire the reader to the
host.
The model OP90 uses a security screw on the bottom of the
reader to secure the cover. Remove this security screw
using the supplied tool. Then slide the back plate down
slightly and then lift it up from the bottom. Select the
desired mounting holes and drill them out.
Figure 2
Mount the reader with the appropriate screws (not
supplied) as indicated on the template.
Wiring Notes:
1. The individual wires coming out of the reader are colo
r
coded according to the recommended Wiegand standard.
2. If either 5 or 12 volts are available, use 12 volts for bette
r
performance.
3. When using a separate power supply for the reader, the
reader, power supply and host must have a common ground.
4. The recommended cable depends on the distance from
the reader to the host. See Table 1 on the next page fo
r
the correct wire gage based upon distance. Larger wire
gauges are acceptable. The wire must be stranded with
an overall shield, either foil or braided. If the tamper is not
being used, 5 conductor cable is required; otherwise 6
conductor cable is required.
5. The cable shield wire on the reader should be attached to
an Earth ground (best) or signal ground connection at the
panel or power supply end of the cable. This configuration
is best for shielding the reader cable from external
interference.
To surface mount the reader, perform the following:
1. Determine an appropriate mounting position for the
reader.
2. Peel off the back of the self-stick mounting label
template included with the unit and place at the
desired mounting position. (Additional templates can
be downloaded from www.omniprox.com.)
3. Using the template as a guide, drill two holes (hole size
is indicated on mounting template) for mounting the
reader to the surface.
4. Drill a 1/2” (13 mm) hole for the cable. If mounting on
metal, place a grommet or electrical tape around the
edge of the hole.
5. Route the interface cable from the reader and/or power
supply to the host. A linear type power supply is
recommended.
TABLE 1: WIRE GAGE SPECIFICATIONS SPECIFICATIONS
Electrical Characteristics:
Distance Gage 5 Conductor 6 Conductor
200 ft. (61m) 22 Alpha 1295C Alpha 1296C
300 ft. (91m) 20 Alpha 58126 Alpha 58126
500 ft. (153 m) 18 Alpha 58136 Alpha 58136
Note: Recommended cable is only a guideline, use any
manufacturer that meets the gage and shield specifications.
Power Supply Type:
Linear type Recommended
Operating Voltage Range:
5.0 – 16 VDC (Operational down to 4.25 VDC)
Maximum input current:
OP10, OP20, OP90
Standby: 35 mA
Read: 50 mA
OP30, OP40, OP45
HOW TO TEST AND OPERATE THE READER
Standby: 35 mA
The reader should be tested after wiring it to a power supply
and the host. Do this by performing the following steps:
Read: 100 mA
Tamper Output
Open collector, active low, max.sink current is 16 mA
1. Power up the reader. The LED and beeper will
activate three times. This indicates that the
reader is working properly.
Maximum Cable Distance to Host:
500 ft. (150 meters)
2. Present the appropriate type of ID card to the
reader. (See Table 2 for the correct card type
based on the reader model.) The LED will
momentarily flash green and a short beep will be
emitted. This indicates that the card was read
properly by OmniProx.
Card Read Distance:
See Table 2
Regulatory Approvals:
USA: UL 294 Listed & FCC Part 15 B
(Model OP90 is not yet UL listed)
Europe: CE Listed
3. After the card data is processed by the host, the
host can then turn the LED green or yellow.
Refer to the host description of the LED
operation if the reader LED is controlled by the
host.
Operating Temperature Range:
-25° F to 145° F (-31°C to 63°C)
Operating Humidity:
0 to 95% (non condensing)
Suitable for outdoor use
Dimensions:
OP10:
Table 2: Model Number vs. Feature Matrix
3.15” (80mm) L x 1.58” (40mm) W x 0.50” (12.8mm) D
Model
Number
UL Listing
Part #
Card
Type
Output
Format
Read
Range
(Max.)
*
OP10-FW AY-K10 HID Wiegand 3”
OP20-FW AY-J10 HID Wiegand 4”
OP30-FW AY-L10 HID Wiegand 5”
OP40-FW AY-H10 HID Wiegand 4”
OP45-FW AY-M10 HID Wiegand 4”
OP90-FW AY-Q10 HID Wiegand 1.5”
*Measured using HID Corp. Prox Card II (P/N 1326LSSMV)
or equivalent and the corresponding OmniProx reader
powered at 12 volts. Range also depends on electrical
environment and/or proximity to metal.
OP20:
4.73” (120mm) L x 1.65” (42mm) W x 0.55” (14mm) D
OP30:
5.71” (145mm) L x 1.69” (43mm) W x 0.79” (20mm) D
OP40:
4.33” (110mm) L x 2.96” (75mm) W x 0.59” (15mm) D
OP45:
3.5” (89mm) L x 3.5” (89mm) W x 0.59” (15mm) D
OP90:
4.72” (120mm) L x 3” (76mm) W x 1” (27mm) D
For additional information on the Wiegand™ Protocol, see
“Access Control Standard – Wiegand Card Reader Interface
SIA AC-01 (1996.10)” which can be purchased from SIA (see
www.siaonline.org)
OmniProx models with HID
compatibility are capable of reading
genuine HID cards under the terms o
f
a license agreement between HID
Corp. and the ADEMCO Group.