Napoleon Fireplaces BGD36PTR, GD36NTR, BGD36NTR, GD36PTR User Manual

4.3 (3)

1

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.

CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS

DIRECT VENT MILLIVOLT SYSTEM

INSTALLATION AND OPERATION INSTRUCTIONS FOR

NATURAL GAS MODEL GD36NTR & BGD36NTR

PROPANE GAS MODEL GD36PTR & BGD36PTR

CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.

FOR YOUR SAFETY

Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

• Do not try to light any appliance.

• Immediately call your gas supplier from

• Do not touch any electrical switch.

a neighbour's phone. Follow the gas

• Do not use any phone in your build

supplier's instructions.

ing.

• If you cannot reach your gas supplier,

 

call the fire department.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

R-2000

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031 www.napoleonfireplaces.com • ask@napoleon.on.ca

W415-0210 / E / 06.25.03

2

TABLE of CONTENTS

PG 2-5 INTRODUCTION

Warranty

General Instructions

General Information

Care of Glass & Plated Parts Specifications

5-15 VENTING

Venting Lengths

Air Terminal Locations

Typical Vent Installations

Special Vent Installations Venting Application Flow Chart Venting Specifications Pre-Installation Preparation

16-22 INSTALLATION

Wall and Ceiling Protection Using Flexible Vent Components Fireplace Vent Connection

Using Rigid Vent Components Restricting Vertical Vents - GD36 only Gas Installation

Mobile Home Installation Framing

Mantle Clearances Nailing Tab Installation

23-24 FINISHING

Door Removal & Installation

Louvre Removal & Installation

Log Placement

Charcoal Embers

Vermiculite

Glowing Embers

Logo Placement

25OPTIONAL BLOWER INSTALLATION

26OPTIONAL FAN INSTALLATION

OPTIONAL THERMOSTATIC SENSOR

27-28 OPERATION / MAINTENANCE

Operating Instructions

Maintenance

28 ADJUSTMENTS

Pilot Burner Adjustment

Venturi Adjustment

29-30 REPLACEMENTS

Ordering Replacement Parts

Replacement Parts

Vent Kits

Terminal Kits

Accessories

31-32 TROUBLE SHOOTING GUIDE

PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE

WARNING

Do not burn wood or other materials in this fireplace.

Adults and especially children should be alerted to the hazards of high surface temperatures and sho stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room the fireplace.

Due to high temperatures, the fireplace should be located out of traffic and away from furniture and dra ies.

Clothing or other flammable material should not be placed on or near the fireplace.

Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace.

It is imperative that the control compartments, burners and circulating blower and its passageway in fireplace and venting system are kept clean. The fireplace and its venting system should be inspec before use and at least annually by a qualified service person. More frequent cleaning may be required to excessive lint from carpeting, bedding material, etc. The fireplace area must be kept clear and free f combustible materials, gasoline and other flammable vapours and liquids.

Under no circumstances should this fireplace be modified.

This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning applia

Do not use this fireplace if any part has been under water. Immediately call a qualified service technicia inspect the fireplace and to replace any part of the control system and any gas control which has b under water.

Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the gl should be done by a licensed or qualified service person. Use only with a glass door certified with fireplace.

Do not strike or slam shut the fireplace glass door.

This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocou supplied by Wolf Steel Ltd.

NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.

W415-0210 / E / 06.25.03

3

NAPOLEON gas fireplaces are manufactured under the strict Standard of the world recognized ISO 9001 : 2000 Quality Assurance Certificate.

NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. The complete fireplace is again thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON.

NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY

The following materials and workmanship in your new NAPOLEON gas fireplace are warranted against defects for as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components and aluminum extrusion trims.

Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON will provide replacement parts free of charge during the first year of the limited warranty.

Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requires the prior approval of an authorized company official. Labour costs to the account of NAPOLEON are based on a predetermined rate schedule and any repair work must be done through an authorized NAPOLEON dealer.

CONDITIONS AND LIMITATIONS

NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:

This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.

The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the product and all local and national building and fire codes.

This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this warranty.

This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.

NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.

In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated in accordance with the operation instructions and under normal conditions.

After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).

After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered by this warranty.

Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event extend to any incidental, consequential or indirect damages.

This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product, its components or accessories are excluded.

NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.

Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.

The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.

NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.

ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.

W415-0210 / E / 06.25.03

4

GENERAL INSTRUCTIONS

THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:

The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.

The appliance off valve must be a “T” handle gas cock.

The flexible connector must not be longer than 36 inches.

The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.

WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts.

In absence of local codes, install the GD36 and BGD36 to the current National Fuel Gas Code, ANSI Z223.1, or the current CAN/CGA B149, Installation Codes. Mobile home installation must conform with local codes or in the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA ZA240 MH Series in Canada or the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the Fire Safety Criteria for Manufactured Home Installations, Sites and Communities Standard ANSI/NFPA 501A in the United States.

The fireplace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth.

If the optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States.

GENERAL INFORMATION

FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!

Maximum input is 26,000 BTU/hr for natural gas and propane for the GD36. Maximum input for the BGD36 is 17,000 BTU/h for natural gas and propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.

GD36

Maximum output for natural gas is 22,360 BTU/hr at an efficiency of 86% with the fan on, and 22,880 BTU/hr for propane at an efficiency of 88% with the fan on. The A.F.U.E. (annual fuel utilization efficiency) rating is 64% for natural gas and 65% for propane.

BGD36

Maximum output for natural gas and propane is 10,900 BTU/ hr at an efficiency of 64% with the fan on. The A.F.U.E. (annual fuel utilization efficiency) rating is 53% for natural gas and propane.

Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. Manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane. This fireplace is approved for bathroom, bedroom and bedsitting room installations and is suitable for mobile home installation.

No external electricity (110 volts or 24 volts) is required for the gas system operation.

Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.

CARE OF GLASS, AND PLATED PARTS

Do not use abrasive cleaners to clean plated parts. Buff lightly with a clean dry cloth. The GD36 is factory equipped with ceramic glass. The BGD36 is factory equipped with tempered glass. The glass thickness is 3/16" for both models. Use only replacement glass available from your Napoleon dealer. DO NOT SUBSTITUTE MATERIALS. Clean the glass after the first 10 hours of operation with a recommended gas fireplace glass cleaner. Thereafter clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and / or blemishes may result.

Use only accessories designed for and listed with your specific fireplace.

Provide adequate ventilation air. Provide adequate accessibility clearance for servicing and operating the fireplace. Never obstruct the front opening of the fireplace.

For safe and proper operation of the fireplace follow the venting instruction exactly.

Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning. Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed. Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.

Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.

W415-0210 / E / 06.25.03

5

GD36 SPECIFICATIONS

 

BGD36 SPECIFICATIONS

 

 

 

FIGURE 1a

FIGURE 1b

VENTING

MODELS GD36 AND BGD36 MAY BE VENTED EITHER AS A TOP VENT OR A REAR VENT.

REFER TO THE SECTION APPLICABLE TO YOUR INSTALLATION.

VENTING LENGTHS

Use only Wolf Steel or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting components.

When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following termination kits: WALL TERMINAL KIT GD222, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD110, 8/12 TO 12/12 ROOF TERMINAL KIT GD111, FLAT ROOF TERMINAL KIT GD112 or PERISCOPE KIT GD201 (for wall penetration below grade). With flexible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330.

Wolf Steel rigid and flexible venting systems must not be combined.

Wolf Steel and Simpson Dura-Vent venting systems must not be combined.

These vent kits allow for either horizontal or vertical venting of the fireplace. FIGURES 3 & 5. The maximum allowable horizontal run is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of 4" vent connections is two horizontally or three vertically (excluding the fireplace and the air terminal connections) when using aluminum flexible venting.

For optimum flame appearance and fireplace performance, keep the vent length and number of elbows to a minimum.

The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.

Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.

Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.

Six (6") inches is the minimum bend radius allowed for the 7" diameter flexible liner.

For optimum performance it is recommended that all horizontal runs have a 1 inch rise per foot when using Napoleon flexible vent components.

A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap all around between the inner liner and outer liner is required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.

Minimum clearance to combustible construction from fireplace and vent surfaces:

sides, back, bottom and top of the unit

0 inch

recessed depth

14 inches

top, sides and bottom of the vent pipe*

1 inch

top of the vent pipe - rear vent only*

2 inches

* REAR VENT - A clearance to combustibles of 1" at the bottom of the vent and 2" at the top must be maintained during the first 12" of venting when penetrating combustible walls. The firestop spacer (W615-044) supplied with the unit should be used to maintain this clearance. Thereafter a 1" clearance to combustibles may be maintained using firestop spacer (W500-0096).

TOP VENT - Only a clearance to combustibles of 1" all around the vent pipe is required.

REQUIRED RISE ON HORIZONTAL VENTING

BGD36

GD36

 

 

 

REAR VENT

RIGID VENTING

0"/FT

1"/FT*

FLEXIBLE VENTING

0"/FT

1"/FT*

 

 

 

 

 

TOP VENT

RIGID VENTING

0"/FT

0"/FT

FLEXIBLE VENTING

0"/FT

0"/FT

 

 

 

 

 

CORNER

RIGID VENTING

0"

6"

 

 

 

FLEXIBLE VENTING

6"

6"

 

 

 

 

 

* When a vertical rise is used as part of the venting configuration, a 0" rise per foot is acceptable.

W415-0210 / E / 06.25.03

6

AIR TERMINAL INSTALLATIONS

FIGURE 2

 

INSTALLATIONS

 

 

 

 

 

 

CANADIAN

U.S.A.

 

 

 

 

 

A

12 INCHES

12 INCHES

Clearance above grade, veranda porch, deck or balcony.

 

 

 

 

B

12 INCHES

9 INCHES

Clearance to windows or doors that open.

 

 

 

 

C

12 INCHES*

12 INCHES*

Clearance to permanently closed windows.

 

 

 

 

D

18 INCHES**

18 INCHES**

Vertical clearance to ventilated soffit located above the terminal within

a horizontal distance of 2 feet from the centerline of the terminal.

 

 

 

 

E

12 INCHES**

12 INCHES**

Clearance to unventilated soffit.

 

 

 

 

F

0 INCHES

0 INCHES

Clearance to an outside corner wall.

 

 

 

 

 

0 INCHES***

0 INCHES***

Clearance to an inside non-combustible corner wall or protruding

 

non-combustible obstructions (chimney, etc.).

G

 

 

 

2 INCHES***

2 INCHES***

Clearance to an inside combustible corner wall or protruding com-

 

 

bustible obstructions ( vent chase, etc.).

 

 

 

 

H

3 FEET

3 FEET****

Clearance to each side of the centerline extended above the meter

/ regulator assembly to a maximum vertical distance of 15ft.

 

 

 

 

 

 

 

I

3 FEET

3 FEET****

Clearance to a service regulator vent outlet.

 

 

 

 

J

12 INCHES

9 INCHES

Clearance to a non-mechanical air supply inlet to the building or a

combustion air inlet to any other appliance.

 

 

 

 

 

 

 

K

6 FEET

3 FEET†

Clearance to a mechanical air supply inlet.

 

 

 

 

L

7 FEET‡

7 FEET****

Clearance above a paved sidewalk or paved driveway located on

public property unless fitted with a heat shield kit GD-301.

 

 

 

 

 

 

 

 

M

12 INCHES††

12 INCHES****

Clearance under a veranda, porch, deck or balcony.

 

 

 

 

N

16 INCHES

16 INCHES

Clearance above the roof.

 

 

 

 

O

2 FEET†*

2 FEET†*

Clearance from an adjacent wall including neighbouring buildings.

 

 

 

 

 

 

*Recommended to prevent condensation on windows and thermal breakage

**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.

***The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.

****This is a recommended distance. For additional requirements check local codes.

Three feet above if within 10 feet horizontally.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single dwellings and serves both dwellings.

††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor. †* Recommenced to prevent recirculation of exhaust products. For additional requirements check local cod

W415-0210 / E / 06.25.03

Napoleon Fireplaces BGD36PTR, GD36NTR, BGD36NTR, GD36PTR User Manual

7

TYPICAL VENT INSTALLATIONS

REAR EXIT

TOP EXIT

 

FIGURES 3a-d

*

For optimum performance, it is recommended that all horizontal runs have a 1 inch rise per foot.

When terminating vertically, the vertical rise is a minimum 36 inches and a maximum 40 feet from the centre of the fireplace flue outlet.

* When using rigid venting, this minimum vertical length may be reduced to 8½".

SPECIAL VENT INSTALLATIONS

PERISCOPE TERMINATION

CORNER TERMINATION

Use the GD201 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12 inches above grade. The maximum allowable vent length depends on the model of fireplace, as illustrated.

FIGURES 4

MODELS GD36: The maximum vent length for a corner installation is 24 inches, where only 6 inches of vertical rise is used. All corner installations require a minimum 6 inch rise. See FIGURE 5A.

MODELS BGD36: The maximum vent length for a corner installation is 20 inches of horizontal run, in addition to the 45° offset. In this case zero rise is acceptable when using rigid. Flexible venting must maintain a 6" rise. See FIGURE 5B.

FIGURE 5A - GD36 ONLY

20" MAX

TOP EXIT INSTALLATION

FIGURE 5B - BGD36 ONLY

REAR EXIT INSTALLATION

W415-0210 / E / 06.25.03

03.25.06 / E / 0210-W415

8

VENTING APPLICATION FLOW CHART

 

 

 

 

 

 

 

 

 

 

 

 

 

fireplace vent exit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

top exit

 

 

 

 

 

 

 

 

 

 

rear exit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

horizontal termination

 

 

vertical termination

 

horizontal termination

 

 

 

vertical termination

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vertical rise

 

 

v e r t i c a l

 

 

vertical rise

 

 

v e r t i c a l

 

vertical rise

 

 

vertical rise

 

 

vertical rise

 

 

v e r t i c a l

is equal to

 

 

rise is less

 

 

is equal to

 

 

rise is less

 

is equal to

 

 

is less than

 

 

is equal to

 

 

rise is less

or greater

 

 

than

hori-

 

 

or greater

 

 

than

 

hori-

 

or greater

 

 

horizontal

 

 

or greater

 

 

than

hori-

than the

 

 

zontal run

 

 

than the

 

 

zontal run

 

than the

 

 

run

 

 

than the

 

 

zontal run

horizontal

 

 

 

 

 

 

horizontal

 

 

 

 

 

 

horizontal

 

 

 

 

 

 

 

 

horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

run

 

 

 

 

 

 

run

 

 

 

 

 

 

run

 

 

 

 

 

 

 

 

run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

horizontal

 

 

horizontal

 

 

horizontal

 

 

horizontal

 

horizontal

 

 

horizontal

 

 

horizontal

 

 

horizontal

 

 

run + verti-

 

 

 

 

run + verti-

 

 

 

run + verti-

 

 

 

 

 

run + verti-

run + verti-

 

 

 

 

run + verti-

 

 

 

 

 

 

 

 

 

 

 

cal rise to

 

 

 

 

cal rise to

 

run + verti-

 

 

cal

rise to

 

 

 

run + verti-

 

 

cal rise to

cal rise to

 

 

 

 

cal rise to

 

 

 

 

 

 

 

 

 

 

 

maximum of

 

 

 

 

m a x i m u m

 

cal rise to

 

 

maximum of

 

 

 

cal rise to

 

 

m a x i m u m

m a x i m u m

 

 

 

 

m a x i m u m

 

 

 

 

 

 

 

 

 

 

 

24.75 feet

 

 

 

 

of 40 feet

 

m a x i m u m

 

 

24.75 feet

 

 

 

m a x i m u m

 

 

of 40 feet

of 40 feet

 

 

 

 

of 40 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of 40 feet

 

 

 

 

 

 

 

 

of 40 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

times

 

 

 

 

 

 

3 times the

 

 

 

 

 

 

4.2

 

times

 

 

 

 

 

 

3 times the

 

 

 

 

 

the vertical

 

 

 

 

 

 

vertical rise

 

 

 

 

 

 

the vertical

 

 

 

 

 

 

vertical rise

 

 

 

 

 

rise equal to

 

 

 

 

 

 

equal to or

 

 

 

 

 

 

rise equal to

 

 

 

 

 

 

equal to or

 

 

 

 

 

or greater

 

 

 

 

 

 

g r e a t e r

 

 

 

 

 

 

or

greater

 

 

 

 

 

 

g r e a t e r

 

 

 

 

 

than

the

 

 

 

 

 

 

than

 

the

 

 

 

 

 

 

than the

 

 

 

 

 

 

than

the

 

 

 

 

 

horizontal

 

 

 

 

 

 

horizontal

 

 

 

 

 

 

horizontal

 

 

 

 

 

 

horizontal

 

 

 

 

 

run

 

 

 

 

 

 

 

run

 

 

 

 

 

 

 

 

run

 

 

 

 

 

 

 

 

 

run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

DEFINITIONS

for the following symbols used in the venting calculations and examples are:

>- greater than

>- equal to or greater than

<- less than

<- equal to or less than

HT - total of both horizontal vent lengths (HR) and offsets (HO) in feet

HR - combined horizontal vent lengths in feet

HO - offset factor: .03(total degrees of offset - 90°*) in feet

VT - combined vertical vent lengths in feet

ELBOW VENT LENGTH VALUES

 

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°

1.35

16.0

90°*

2.7

32.0

* the first 90° offset has a zero value and is shown in the formula as -90°

TOP EXIT / HORIZONTAL TERMINATION

when (HT) < (VT)

Simple venting configuration (only one 90° elbow)

FIGURE 6

For vent configurations requiring more than one 90° elbow, the following formulas apply:

Formula 1: HT < VT Formula 2: HT + VT < 40 feet

Example 1:

90°

H2

FIGURE 7

V2

 

 

90°

See graph to determine the required vertical rise VT for the required horizontal run HT.

VERTICAL

RISE IN

FEET

VT

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

 

 

90°

H1

 

 

V1

 

V1

=

3 ft

 

V2

=

8 ft

 

VT

= V1 + V2 = 3 + 8 = 11 ft

 

H1

=

2.5 ft

 

H2

=

2 ft

 

HR

= H1 + H2 = 2.5 + 2 = 4.5 ft

 

HO

= .03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft

HT

= HR + HO = 4.5 + 5.4 = 9.9 ft

 

HT + VT = 9.9 + 11 = 20.9 ft

Formula 1: HT < VT

9.9 < 11

Formula 2: HT + VT < 40 feet

20.9 < 40

Since both formulas are met, this vent configuration is acceptable.

W415-0210 / E / 06.25.03

HO
HT
V1
H1
H2
HR

10

TOP EXIT / HORIZONTAL TERMINATION

when (HT) > (VT)

Example 3:

Simple venting configuration (only one 90° elbow)

 

FIGURE 8

See graph to determine the required vertical rise VT for the required horizontal run HT.

90°

 

H

H

1

4

V2

 

H2

H

90°

3

 

V1

 

 

FIGURE 10

REQUIRED

VERTICAL

RISE IN

INCHES

VT

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

For vent configurations requiring more than one 90° elbow the following formulas apply:

Formula 1: HT < 4.2

VT

 

Formula 2: HT + VT

<

24.75 feet

 

 

 

H1

H2

Example 2:

 

 

 

 

 

V1 90°

FIGURE 9

V1

= 4 ft

V2

= 1.5 ft

VT

= V1 + V2 = 4 + 1.5 = 5.5 ft

H1

= 2 ft

H2

= 1 ft

H3

= 1 ft

H4

= 1.5 ft

HR

= H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft

HO

= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft

HT

= HR + HO = 5.5 + 8.1 = 13.6 ft

HT + VT = 13.6 + 5.5 = 19.1 ft

Formula 1: HT < 4.2 VT

4.2VT = 4.2 x 5.5 = 23.1 ft

13.6< 23.1

Formula 2: HT + VT < 24.75 feet

19.1 < 24.75

Since both formulas are met, this vent configuration is acceptable.

= VT = 6 ft = 3 ft

= 5 ft

= H1 + H2 = 3 + 5 = 8 ft

= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft

= HR + HO = 8 + 2.7 = 10.7 ft HT + VT = 10.7 + 6 =16.7

Formula 1: HT < 4.2 VT

4.2VT = 4.2 x 6 = 25.2 ft

10.7< 25.2

Formula 2: HT + VT < 24.75 feet

16.7 < 24.75

Since both formulas are met, this vent configuration is acceptable.

W415-0210 / E / 06.25.03

Loading...