Comet EXtreme

4.5/6/9/12 kVA

Installation

and user manual

R

E

T

N

I

N

U

E

H

T

R

U

 

 

 

 

I

D

E

R

 

 

 

V

 

 

 

 

 

 

 

 

O

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

R

E

 

W

P

O

 

 

 

L

E

 

 

 

 

 

 

 

 

 

 

 

 

I

B

 

 

 

 

 

 

 

 

 

 

 

 

P

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51033212EN/AC - Page 1

Introduction

Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.

The Comet EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.

MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Comet EXtreme a reference in environmental protection include:Production in an ISO 14001 certified factory;

Recycling of Comet EXtreme at the end of its service life.

To discover the entire range of MGE UPS SYSTEMS products and the options available for the Comet EXtreme range:

We invite you to visit our Web site at www.mgeups.com

(page: www.mgeups.com/products/pdt230/smallups/extreme/extrem10.htm),Or contact your MGE UPS SYSTEMS representative.

Page 2 - 51033212EN/AC

Foreword

Using this document

Information may be found primarily by consulting:the contents,

the index.

Pictograms

Important instructions that must always be followed.

Information, advice, help.

Visual indication.

Action.

Audio indication.

In the illustrations on the following pages, the symbols below are used:

LED off.

LED on.

LED flashing.

51033212EN/AC - Page 3

Contents

1.Presentation

1.1

Comet EXtreme range ..................................................................................................................

6

 

4.5 and 6 kVA tower models ...........................................................................................................

6

 

4.5 and 6 kVA rack models .............................................................................................................

6

 

9 and 12 kVA tower models ............................................................................................................

7

 

9 and 12 kVA rack models ..............................................................................................................

7

1.2

Back ...............................................................................................................................................

8

 

Comet EXtreme 4.5 and 6 kVA ......................................................................................................

8

 

Comet EXtreme 9 and 12 kVA .......................................................................................................

8

1.3

Options ..........................................................................................................................................

9

 

EPO (Emergency Power Off) ..........................................................................................................

9

 

Transformer for galvanic isolation or earthing arrangement change ..............................................

9

 

Battery extensions for UPS backup times of 80 minutes ................................................................

9

 

CLA module (Long backup time charger) for backup times of 2 to 8 hours ..................................

10

1.4

Control panel ...............................................................................................................................

11

2.Installation

2.1

Unpacking and checks ...............................................................................................................

12

 

Comet EXtreme 4.5 and 6 kVA ....................................................................................................

12

 

Comet EXtreme 9 and 12 kVA .....................................................................................................

13

2.2

Installation of the rack version ..................................................................................................

14

2.3

Battery-module connections .....................................................................................................

15

 

Comet EXtreme 4.5 and 6 kVA ....................................................................................................

15

 

Comet EXtreme 9 and 12 kVA .....................................................................................................

15

2.4

Connection to the RS 232 communications port (optional) ...................................................

16

2.5

Installation of the communications-card option ......................................................................

16

2.6

Connection to the connection modules ...................................................................................

17

3.Operation

3.1

ON LINE operating mode ...........................................................................................................

18

3.2

Start-up ........................................................................................................................................

19

3.3

Bargraph indications ..................................................................................................................

19

Page 4 - 51033212EN/AC

 

 

Contents

3.4 Failure of AC input power and operation on battery power

.................................................... 20

 

Transfer to battery power ..............................................................................................................

20

 

Threshold for the low-battery shutdown warning ..........................................................................

20

 

End of backup time .......................................................................................................................

20

 

Sleep mode ...................................................................................................................................

20

 

Return of AC input power ..............................................................................................................

20

3.5

Personalization ...........................................................................................................................

21

 

Function ........................................................................................................................................

21

 

"ON / OFF conditions" tab .............................................................................................................

21

 

"Battery" tab ..................................................................................................................................

22

 

"Output" tab ...................................................................................................................................

22

 

"By-pass" tab ................................................................................................................................

22

3.6

Shutdown.....................................................................................................................................

23

 

Shutdown of connected equipment...............................................................................................

23

 

Complete shutdown of the UPS ....................................................................................................

23

4.Maintenance

4.1

Troubleshooting ..........................................................................................................................

24

4.2

Replacement of the electronic module .....................................................................................

26

 

Disconnecting the connection module ..........................................................................................

26

 

Reconnecting the connection module ...........................................................................................

27

5. Environment .....................................................................................................................................

28

6.Appendices

6.1

Glossary.......................................................................................................................................

29

6.2

Index.............................................................................................................................................

31

51033212EN/AC - Page 5

1. Presentation

1.1Comet EXtreme range

4.5and 6 kVA tower models

4.5 and 6 kVA rack models

 

Dimensions in mm

 

(H x W x D)

Electronic module

443 x 173 x 465

Battery module

443 x 173 x 465

 

 

 

 

 

Weight in kg

 

 

Electronic module

14

Battery module

48

 

Dimensions in mm

 

(H x W x D)

Electronic module

177 (4U) x 483 x 462

Battery module

177 (4U) x 483 x 462

 

 

 

Weight in kg

 

 

Electronic module

18

Battery module

51

Page 6 - 51033212EN/AC

1. Presentation

9 and 12 kVA tower models

9 and 12 kVA rack models

 

Dimensions in mm

 

(H x W x D)

Electronic module

443 x 216 x 465

Battery module

443 x 173 x 465

 

 

 

Weight in kg

 

 

Electronic module

22

Battery module

48

 

Dimensions in mm

 

(H x W x D)

Electronic module

221 (5U) x 483 x 462

Battery module

177 (4U) x 483 x 462

 

 

 

Weight in kg

 

 

Electronic module

27

Battery module

51

51033212EN/AC - Page 7

1. Presentation

1.2 Back

Comet EXtreme 4.5 and 6 kVA

1 RS232 communications port.

2

Battery circuit breaker.

3 Communications-card option.

4

EXB battery module connectors.

5

Connector for battery extension modules.

6

Rating plate.

7

Manual by-pass switch.

8

Connection module.

9

Output terminal block.

10

Input terminal block.

Comet EXtreme 9 and 12 kVA

4 EXB battery modules connectors.

Page 8 - 51033212EN/AC

1. Presentation

1.3 Options

EPO (Emergency Power Off)

Available for both tower and rack versions of UPSs with standard backup times and for the battery extensions, the EPO (Emergency Power Off) option lets you simultaneously switch off the UPS battery circuit breaker and the upstream circuit breaker of your installation by connecting both of them to a single emergency off button (not supplied).

For more details, visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/epo.htm

Transformer for galvanic isolation or earthing arrangement change

 

Comet EXtreme

Comet EXtreme

 

Transfo 4.5 - 6 kVA

Transfo 9 - 12 kVA

 

 

 

Nominal power

6 kVA

12 kVA

 

 

 

Nominal current

32 A

63 A

Input voltage

230V (+15%, -20%)

230V (+15%, -20%)

Voltage drop

2.2%

1.7%

Frequency

50/60 Hz (+/-10%)

50/60 Hz (+/-10%)

 

 

 

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

3.75 kV / 5 M ohms

 

 

 

Operating temperature

From 0° to +40° C

From 0° to +40° C

 

 

 

Max. operating rel. humidity

95%

95%

Derating / altitude

Pn-10% > 1000 m

Pn-10% > 1000 m

Natural ventilation

IP20 ANAN

IP20 ANAN

Dimensions HxWxD (tower)

443 x 173 x 465 mm

443 x 216 x 465 mm

Dimensions HxWxD (rack 4U)

177 x 483 x 462 mm

177 x 483 x 462 mm

Weight (tower)

44 kg

62 kg

Weight (rack)

48 kg

67 kg

 

 

 

Important: to simplify installation, connect the Comet EXtreme Transformer downsteam of the UPSs. Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm

Battery extensions for UPS backup times of 80 minutes

Battery extensions for 4.5 or 6 kVA Comet EXtreme:

 

 

 

 

 

Comet

 

 

Comet

 

 

Comet

Comet

Comet

EXtreme

+

EXtreme

+

EXtreme

+

EXtreme

EXtreme

EXB

EXB

EXB

EXB

4.5 /

6 kVA

 

 

 

 

 

4.5 /

 

 

4.5 /

 

 

 

4.5 /

4.5 /

 

 

 

 

 

 

6 kVA

 

 

6 kVA

 

 

6 kVA

6 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comet EXtreme offers a standard backup time of 9/12 minutes.

To increase backup time, it is possible to connect Comet EXtreme EXB modules to the UPSs.

Visit our Web site: www.mgeups.com/ products/pdt230/smallups/extreme/ guide.htm.

4.5 kVA:

12 min

30 min

54 min

80 min

6 kVA:

9 min

23 min

40 min

75 min

51033212EN/AC - Page 9

1. Presentation

Battery extensions for 9 or 12 kVA Comet EXtreme:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comet

 

 

Comet

 

 

 

Comet

Comet

 

Comet EXtreme

+

+

 

+

 

EXtreme

EXtreme

 

EXtreme

EXtreme

 

9 / 12 kVA

EXB

EXB

 

EXB

EXB

 

 

 

 

 

 

 

9 / 12 kVA

 

 

9 / 12 kVA

 

 

 

9 / 12 kVA

9 / 12 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 kVA:

12 min

30 min

45 min

80 min

12 kVA:

9 min

23 min

40 min

75 min

The Comet EXtreme EXB modules are available in "tower" and in "rack" models.

The Comet EXtreme EXB modules come with their connection cables.

CLA module (Long backup time charger) for backup times of 2 to 8 hours

Very long backup times, from 2 to 8 hours at full load, require a Comet EXtreme CLA module.

Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/cla/cla2.htm.

Comet

EXtreme

-65Ah 12V

Comet

EXtreme

CLA

25A

2

1

-65Ah 12V

-65Ah 12V

19

-65Ah 12V

2 h

20

-65Ah 12V

1

2

-65Ah

 

 

12V

-65Ah

-65Ah

12V

12V

 

-65Ah

12V

 

20

19

-65Ah

 

 

12V

-65Ah

-65Ah

12V

12V

 

-65Ah

12V

4 h

1

2

-65Ah

 

 

12V

-65Ah

-65Ah

12V

12V

12V

-65Ah

12V

 

-65Ah

 

12V

20

 

19

-65Ah

 

12V

-65Ah

12V

12V

-65Ah

-65Ah

12V

12V

-65Ah

12V

 

8 h

Page 10 - 51033212EN/AC