LST IBSOU-DD-P02, IBSOU-DD-P01 User Manual

Size:
178.25 Kb
Download

Integrated Base Sounder

IBSOU-DD-P01,IBSOU-DD-P02

ADM loop technology with System Sensor/200 protocol

Can be activated with two different tone types, 32 tone types selectable

Sound level selectable in three steps

– up to 95dB(A)

Low power consumption

Versions with or without integrated dual-isolatoravailable

Two base types available – IP24, IP44

Description

The loop powered sounder incorporates a detector base and is fitted into a round, white plastic case. It is powered and actuated as a module through the ADM loop with System Sensor/200 protocol. Fire Detectors Series 200 can be fitted into the integrated base.

The sounder can be activated by a Fire Detection Control Panel Series BC216 with two different tone types, depending on the parameter setup. One of 32 different tone type combinations can be selected with a DILswitch. The following tones are available, for example:

Continuous tone 660Hz,

Emergency signal according to DIN 33404,

Slow whoop tone according to NEN 2575,

Alternating tone 800/970Hz, and many more.

The sound level can be selected in 3 steps. The address of the sounder is selected with two decadic rotary switches located at the bottom of the device.

The base sounder is designed for indoor surface mounting. For this purpose a special base is needed. Two different base types for protection classes IP24 or IP44 are available, depending on the application. An optional mounting plate can be supplied for surface mounted cabling.

The sounder is available in two different versions: With or without integrated dual-isolatormodule.

Specifi cations

Operating voltage

Supply through loop voltage

Sound level (detector installed)

typ. 70dB(A) at 1m distance (low)

 

typ. 79dB(A) at 1m distance (medium)

 

typ. 87dB(A) at 1m distance (high)

 

max. 95dB(A) at 1m distance (high)

Ambient temperature

-25°Cto +70°C

Dimensions ø × H

112 × 42 (mm) (without detector, incl. base LPBW)

Weight

134g

Colour

cream, RAL 9001

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

IBSOU-DD-P0x_DBL_LST_EN_0804.PDF• PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Loop sounder without isolator

 

Current consumption from loop

max. 450µA (sounder off)

 

max. 1.9mA (low sound level)

 

max. 3.1mA (medium sound level)

 

max. 6.8mA (high sound level)

Approval

VdS G206072

Order number

355164

Order name

Sounder with Base/200/White/Multitone IBSOU-DD-P01

Loop sounder with isolator

 

Current consumption from loop

max. 450µA (sounder off)

 

max. 2.1mA (low sound level)

 

max. 3.3mA (medium sound level)

 

max. 7.0mA (high sound level)

Approval

VdS G206076

Order number

355165

Order name

Sounder with Base/200ISM/White/Multitone IBSOU-DD-P02

Base and accessories

For surface mounting of the sounder, two different base types with protection classes IP24 or IP44 are available.

For surface mounted cabling with base LPBW, an optional mounting plate is available.

Specifi cations

Base IP24

 

Order number

359040

Order name

Base Sounder & Strobe/IP24/White LPBW

Base IP44

 

Order number

359043

Order name

Base Sounder & Strobe/IP44/White SDBW

Mounting plate for surface mounted cabling with base LPBW, 5 Pieces

Order number

359049

Order name

Mounting Plate for Sounder/200/5 pcs. DBSPD/5

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

IBSOU-DD-P0x_DBL_LST_EN_0804.PDF• PAGE 2