GIF8-1

For the connection of 8 detector lines in addressable conventional technology

Individual detector addressing with optional address module

Individual setting of detector zone function

Lines monitored for wire breakage, short circuit, and short to earth

Description

The Conventional Detector Interface GIF8-1supports

call point, automatic fire detector with or without alarm

eight detector zones in addressable conventional tech-

verification, fault message contacts as well as contacts

nology in Fire Detection Control Panels Series BC216.

for technical messages), the function of the detector

Up to 64 detectors (addresses) per detector line can

zone can be set separately for each detector line.

be individually identified with the aid of an address mo-

 

dule.

The Conventional Detector Interface provides a proces-

 

sor of its own. At a possible central processing board

In the event of an alarm, the fire detection control panel

failure, the diversified redundancy concept thus ensures

indicates the number of the detector that is activated

reliable alarm recognition. Each input of the Conventio-

first and displays the optionally parameterised text in-

nal Detector Interface is protected against overvoltage

formation. Depending on the type of detector (manual

and thus provides high system stability.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

GIF8-1_DBL_LST_EN_0804.PDF• PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Specifi cations

Current consumption at 24V

typ. 50mA (8 zones terminated, without detectors)

Line voltage

typ. 20V

Line current

typ. 3.7mA

End-of-lineresistance

5.6kΩ

Line resistance

max. 50Ω per core

Ambient temperature

-5°Cto +50°C

Dimensions L × W × H

132 × 74 × 10 (mm)

Weight

80g

Part No.

214020

Order name

Conventional Detector Interface GIF8-1