Control Panel Extension

Bcnet216: BCE216-3LG

BCnet sectional control panel with two integrated loop interfaces

Extends a BCnet sectional control panel BC216-2 or BC216-3 by two loops

Analogue ringbus technology with unshielded detector cabling

Easy installation, also possible later on

Fire is a permanent threat to life and property. Therefore, immediate response to a fire is imperative. The main objective of the fire detection control panel Series BC216 is to alarm and to react in time and, consequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realize new innovations in the security area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.

Using a 32-bit multiprocessor system, the fire detection control panel Series BC216 ensures topmost efficiency and speed – prerequisites for saving lives and minimizing damage to property.

Description

The BCnet Sectional Control Panel/Extension BCE2163LG allows for the extension of a fire detection control panel BCnet216 by two ADM loops. The extension is integrated into the fire detection control panel BCnet216 by installing it in a BCnet sectional control panel BC216- 2 or BC216-3 and connecting it to the GSSnet cabling via the GSSnet interface on the extension.

The 24V supply of the BCnet Sectional Control Panel/Extension BCE216-3LG is powered from the BCnet sectional control panel in whose cabinet it has been installed; it does not have a power supply or battery charger of its own. The extension is designed as compact unit and mounted on a pivoting sheet steel carrier.

The loop processing functions of the BCE216-3LG fully correspond to the functions of a BCnet Sectional Control Panel BC216-2 equipped with two Loop Interfaces LIF64-1.

The ADM loop principle offers intelligent analogue ringbus technology with bi-directional data transfer. Each loop provides for the software-aided administration of up to 198 physical address points in a maximum of 128 detector zones.

Easy parameterisation by means of PC software enables you to optimally adapt the control panel to your individual requirements.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

BCE216-3LG_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Clear Concept

The BCnet Sectional Control Panel/Extension BCE216-3LG extends a BCnet sectional control panel BC216-2 or BC216-3, respectively, by two ADM loops. It provides the following features:

Detectors and modules in ADM loop technology can be connected to each Loop Interface LIF64-1. Depending on the parameterisation, either the Apollo/Discovery protocol or the System Sensor/200 protocol is used to achieve bi-directional data transfer.

Logical combinations of detectors and detector zones for the activation of external controls and alarming devices facilitate maximum fl exibility. Thus, no additional expenses arise for external relays, logic gates or timers. Thanks to the wide range of parameterisation possibilities, individual requirements even under the most difficult ambient conditions can be combined into a reasonable fire protection strategy.

By integrating input and output modules on any position in the loop you can realize enablements or disablements as well as control tasks in your system without having to care for additional wires.

The free combination of detectors and modules into logic sectors allows for the joint operation of defined parts of the system even beyond the limits of loops or sectional control panels.

The use of unshielded loop cables allows for costsaving and uncomplicated installation as well as for the possibility of reusing the existing cabling.

At a possible breakdown of the central processing unit which is integrated on the extension, the diversified redundancy concept ensures secure alarm recognition.

The parameter data can be created by means of the PC software PARSOFT and loaded into the control panel in a comfortable way. Thus, a quick and efficient transfer of the system configuration into the control panel is guaranteed.

AUTO setup facilitates parameterisation when the control panel is commissioned or expanded and thus helps to save time.

The BCnet Sectional Control Panel/Extension BCE216-3LG is suitable for later installation in the wall mount cabinet.

Owing to the compact design, a maximum of four loops can be centralized in one single place. The required batteries are accommodated in the wall mount cabinet or in an external auxiliary case. Series BC216 thus stands for modularity and easy expansion.

This product complies with all relevant standards of EN 54 and is VdS-certified. In addition, the product also holds several country-specific approvals and certificates. LST‘s high quality level is secured by a permanently monitored quality management system certified by ISO 9001.