LST BC06-1EXT, BC06-2EXT User Manual

Size:
325.85 Kb
Download

Extinguishing Control Panel

BC06-1EXT,BC06-2EXT

For application in single-zoneextinguishing systems

4 detector zones in conventional technology

Differentiation between the activation of automatic detectors and manual call points on the same detector line

Clear display and operation on the panel front

Tested to EN 54-2,-4,EN12094-1by VdS

Fire is a permanent threat to life and property. Therefore, immediate response to a fire is imperative. The main objective of the Fire Detection Control Panel Series BC06 is to alarm and to react in time and, consequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realise new innovations in the security area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.

Using a powerful processor system and a large number of integrated functions, the Fire/Extinguishing Control Panels Series BC06 ensure topmost efficiency and speed – prerequisites for saving lives and minimising damage to property.

Description

Already in the basic version the combined Fire/Extinguishing Control Panels BC06-1EXTandBC06-2EXTare equipped with four detector lines and the Extinguishing BoardEXB1-1and, owing to its sophisticated factory settings, are immediately ready for operation. This allows for quick and efficient application of the product.

The conventional technology allows for the connection of automatic and non-automaticfire detectors as well as a wide range of special detectors with contact output. Alarms from manual call points and from automatic detectors that are connected together to one detector line can be differentiated and thus evaluated differently by the fire/extinguishing control panel, by means of an optional coding module.

Thanks to the two auxiliary inputs whose parameters can be freely set as well as the eight open-collectoroutputs, manifold tasks in the field of fire alarm technology can be realised.

The optional evacuation function serves for the actuation of alarming devices independent from activated alarms.

Thanks to the integrated extinguishing module, the BC06 can be used as an extinguishing control panel according to EN 12094-1with one fl ooding zone. The module provides appropriate inputs and outputs for controlling and monitoring a fl ooding zone. The display and operating elements that are necessary for the status indication and the operation of the extinguishing module are integrated into the keypad.

A printer for the event log can be connected via the optional Serial Interface Modul SIM06-1.

The Fire/Extinguishing Control Panel BC06-2EXTdiffers from theBC06-1EXTby the additionally integrated4-digitelectronic alarm counter.

Building Safety. Building Security.

0786–CPD–20300

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Clear concept

The combined Fire/Extinguishing Control Panels BC06-1EXTandBC06-2EXThave been designed for use in small fire detection and extinguishing control systems with one fl ooding zone, and already in the basic version they provide the following features:

4 conventional detector lines permit the connection of automatic detectors and manual call points in conventional technology as well as special detectors with contact output. Each detector line can be individually parameterised as detector zone for fire alarms, as detector zone for fault messages or as input for a disable device or a fl ooding switch.

If automatic detectors and manual call points are connected together on one detector line, their activations can be differentiated and evaluated differently by the control panel. To this aim, the manual call points must be equipped with a special coding module.

Two individually monitored, separately actuated siren outputs with an output current of 1A and 0.5A respectively, allow for the connection of acoustic or optical signalling devices.

Dry relay outputs indicate the alarm and fault conditions of the control panel. In addition, 8 open-collectoroutputs whose parameters can be freely set as well as two auxiliary inputs are available for general control tasks.

The Extinguishing Board EXB1-1,which is already installed in the control panel, allows for the actuation of an extinguishing system according to EN12094-1with one fl ooding zone. In the course of commissioning the control panel, the required functions and delay times are parameterised according to the used extinguishing agent as well as the country specific regulations.

The extinguishing board provides 8 further open-coll-ector outputs with fixed preset functions.

Logical combinations of detector zones for the activation of external alarming devices and for the actuation of the extinguishing system allow for a high degree of fl exibility. Thus, no additional expenses arise for external relays or logic gates. Thanks to the wide range of parameterisation possibilities, individual requirements even under the most difficult ambient conditions can be combined into a reasonable fire protection strategy.

Building Safety. Building Security.

All events that occur can be output in English via a connected printer or PC. Thus, all system conditions and user operations that occurred are documented in a clearly laid out way.

The Fire/Extinguishing Control Panel BC06-2EXTincludes a4-digit,non-resettablealarm counter which indicates the total number of alarms by means of an LC display in the operating field.

Apossiblebreakdownofthecentralprocessingboard is securely detected and displayed by the system.

The processor-monitoredpower supply ensures permanent supervision and charging of the batteries. This way, even during a power failure the untroubled and uninterrupted operation (for more than 72 hours depending on the design of the batteries) is guaranteed.

Three hierarchised authorization levels for operation and parameterisation provide a high degree of security against unauthorized access.

The control panel is easily operated and the parameters are set via the display and operating field. LEDs indicate the current menu and the selected parameter. This facilitates user guidance during commissioning, operation and maintenance.

The initial commissioning of the control panel is significantly facilitated by the practical factory settings. This guarantees easy and time-savingcommissioning.

The extremely fl at wall-mountcabinet allows for an easy mounting in virtually any place of the building. Thanks to its modern, ageless design, architectural requirements and demands of the respective regulations are ideally combined. Thanks to the compact design, the standard case can accommodate batteries with up to 7Ah also in the event of full extension (central processing board, extinguishing board and an auxiliary module) of the control panel. Series BC06 thus stands for modularity and easy expansion.

This product complies with all relevant standards of EN 54 and EN 12094-1and is tested by the VdS. LST‘s high quality level is secured by a permanently monitored quality management system certified to ISO 9001.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 2

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Extinguishing control

By means of the Extinguishing Board EXB1-1,the Fire/Extinguishing Control PanelsBC06-1EXTandBC06-2EXTprovide numerous inputs and outputs with fixed or parameterisable function. With that, the following components of an extinguishing system can be actuated and monitored in accordance with EN12094-1:

• Activation devices for the manual activation of the

ooding process

Emergency hold devices for the manual delay of the

ooding process

Emergency abort devices for aborting the fl ooding process

Fault detection devices for monitoring the compon-

ents of the extinguishing system

A disable device for the indication of the mechanical blocking of the extinguishing agent‘s network

A fl ooding switch that indicates the fl ow of the extinguishing agent

A device for switching to the manual mode – for example, a key switch

Signalling devices for indicating the activated condition and the released condition

The control device for activating the fl ooding – for example, a solenoid valve

Auxiliary outputs for actuating fl aps or for turning off devices and systems

Display and operating elements

The operating field of the Fire/Extinguishing Control Pa-

 

 

nels BC06-1EXTandBC06-2EXTprovides 13 LEDs for

The buttons on the operating field have the following

displaying the operating conditions and 4 buttons for

functions:

the operation of the extinguishing system.

Disable/enable the extinguishing module

 

 

• Start/terminate the manual mode

The LEDs indicate the following operating conditions:

Disable/enable the activation devices

Pre-activation/activationof the extinguishing module

Disable/enable the signal output

Released condition of the extinguishing output

 

 

Extinguishing output fault

 

 

Extinguishing module fault/disablement

 

 

Extinguishing medium fault/fault of the fault input

 

 

• Emergency hold/emergency hold device fault

 

 

Activation device fault/disablement

 

 

Signal output activated/signal output faulty/disabled

 

 

• Manual mode of the extinguishing module

 

 

Fault of the activated condition output

 

A

 

Building Safety. Building Security.

 

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Functions of EN 12094-1

All mandatory functions of EN 12094-1are integrated into the Fire/Extinguishing Control PanelsBC06-1EXTandBC06-2EXT.Furthermore, the most important optional functions of this standard are supported:

Parameterisable pre-discharge-warningtime for the delay of the activation

Detector zone „extinguishing medium active“ selectable for detecting the fl ow of the extinguishing medium

Monitoring of components of the extinguishing system

Input for connection of an emergency hold device

Monitoring of a disable device

Parameterisable fl ooding time

Possibility to switch to the „manual only mode“

Transmission of the triggering signal to further actuations within the extinguishing system – for example, warning devices

Transmission of the triggering signal to further actuations outside the extinguishing system – for example, for turning off the air conditioning system

Emergency abort device can be connected

Activation of alarming devices with different alarm signals

Specifi cations

Mains voltage

230VAC +10/-20%,47...63Hz

Output/nominal voltage

typ. 27.6VDC

Output current

max. 2.2A

Output current siren outputs

 

output 1

max. 1A

output 2

max. 0.5A

(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)

Output current, extinguishing output

max. 1A

Output current, activated condition output/signal output

max. 500mA per output

Own current consumption (incl. extinguishing board) at 24V

typ. 80mA (without optional componentries, line termination 5.6kΩ)

 

typ. 65mA (without optional componentries, line termination 47µF)

Line voltage

typ. 20V (line termination 5.6kΩ)

 

typ. 23V (line termination 47µF)

Line current without fire detectors

typ. 3.7mA (line termination 5.6kΩ)

 

typ. 0mA (line termination 47µF)

Line termination

5.6kΩ or 47µF

Line resistance

max. 50Ω per core

Ambient temperature

-5°Cto +50°C

Relative humidity

max. 95% (no condensation)

Dimensions W × H × D

330 × 330 × 90 (mm)

Colour

grey-white,RAL 9002

Weight without batteries

approx. 3kg

Approvals

0786-CPD-20300

 

VdS pending

Fire Detection Control Panel BC06-1EXT

 

Order number

210223

Order name

Fire Detection Control Panel BC06-1EXT/INT1

Fire Detection Control Panel BC06-2EXT

 

Order number

210224

Order name

Fire Detection Control Panel BC06-2EXT/INT1