LST BC06-1EXT, BC06-2EXT User Manual

0 (0)
LST BC06-1EXT, BC06-2EXT User Manual

Extinguishing Control Panel

BC06-1EXT, BC06-2EXT

For application in single-zone extinguishing systems

4 detector zones in conventional technology

Differentiation between the activation of automatic detectors and manual call points on the same detector line

Clear display and operation on the panel front

Tested to EN 54-2, -4, EN 12094-1 by VdS

Fire is a permanent threat to life and property. Therefore, immediate response to a fire is imperative. The main objective of the Fire Detection Control Panel Series BC06 is to alarm and to react in time and, consequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realise new innovations in the security area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.

Using a powerful processor system and a large number of integrated functions, the Fire/Extinguishing Control Panels Series BC06 ensure topmost efficiency and speed – prerequisites for saving lives and minimising damage to property.

Description

Already in the basic version the combined Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT are equipped with four detector lines and the Extinguishing Board EXB1-1 and, owing to its sophisticated factory settings, are immediately ready for operation. This allows for quick and efficient application of the product.

The conventional technology allows for the connection of automatic and non-automatic fire detectors as well as a wide range of special detectors with contact output. Alarms from manual call points and from automatic detectors that are connected together to one detector line can be differentiated and thus evaluated differently by the fire/extinguishing control panel, by means of an optional coding module.

Thanks to the two auxiliary inputs whose parameters can be freely set as well as the eight open-collector outputs, manifold tasks in the field of fire alarm technology can be realised.

The optional evacuation function serves for the actuation of alarming devices independent from activated alarms.

Thanks to the integrated extinguishing module, the BC06 can be used as an extinguishing control panel according to EN 12094-1 with one fl ooding zone. The module provides appropriate inputs and outputs for controlling and monitoring a fl ooding zone. The display and operating elements that are necessary for the status indication and the operation of the extinguishing module are integrated into the keypad.

A printer for the event log can be connected via the optional Serial Interface Modul SIM06-1.

The Fire/Extinguishing Control Panel BC06-2EXT differs from the BC06-1EXT by the additionally integrated 4-digit electronic alarm counter.

Building Safety. Building Security.

0786–CPD–20300

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Clear concept

The combined Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT have been designed for use in small fire detection and extinguishing control systems with one fl ooding zone, and already in the basic version they provide the following features:

4 conventional detector lines permit the connection of automatic detectors and manual call points in conventional technology as well as special detectors with contact output. Each detector line can be individually parameterised as detector zone for fire alarms, as detector zone for fault messages or as input for a disable device or a fl ooding switch.

If automatic detectors and manual call points are connected together on one detector line, their activations can be differentiated and evaluated differently by the control panel. To this aim, the manual call points must be equipped with a special coding module.

Two individually monitored, separately actuated siren outputs with an output current of 1A and 0.5A respectively, allow for the connection of acoustic or optical signalling devices.

Dry relay outputs indicate the alarm and fault conditions of the control panel. In addition, 8 open-collector outputs whose parameters can be freely set as well as two auxiliary inputs are available for general control tasks.

The Extinguishing Board EXB1-1, which is already installed in the control panel, allows for the actuation of an extinguishing system according to EN 12094-1 with one fl ooding zone. In the course of commissioning the control panel, the required functions and delay times are parameterised according to the used extinguishing agent as well as the country specific regulations.

The extinguishing board provides 8 further open-coll- ector outputs with fixed preset functions.

Logical combinations of detector zones for the activation of external alarming devices and for the actuation of the extinguishing system allow for a high degree of fl exibility. Thus, no additional expenses arise for external relays or logic gates. Thanks to the wide range of parameterisation possibilities, individual requirements even under the most difficult ambient conditions can be combined into a reasonable fire protection strategy.

Building Safety. Building Security.

All events that occur can be output in English via a connected printer or PC. Thus, all system conditions and user operations that occurred are documented in a clearly laid out way.

The Fire/Extinguishing Control Panel BC06-2EXT includes a 4-digit, non-resettable alarm counter which indicates the total number of alarms by means of an LC display in the operating field.

Apossiblebreakdownofthecentralprocessingboard is securely detected and displayed by the system.

The processor-monitored power supply ensures permanent supervision and charging of the batteries. This way, even during a power failure the untroubled and uninterrupted operation (for more than 72 hours depending on the design of the batteries) is guaranteed.

Three hierarchised authorization levels for operation and parameterisation provide a high degree of security against unauthorized access.

The control panel is easily operated and the parameters are set via the display and operating field. LEDs indicate the current menu and the selected parameter. This facilitates user guidance during commissioning, operation and maintenance.

The initial commissioning of the control panel is significantly facilitated by the practical factory settings. This guarantees easy and time-saving commissioning.

The extremely fl at wall-mount cabinet allows for an easy mounting in virtually any place of the building. Thanks to its modern, ageless design, architectural requirements and demands of the respective regulations are ideally combined. Thanks to the compact design, the standard case can accommodate batteries with up to 7Ah also in the event of full extension (central processing board, extinguishing board and an auxiliary module) of the control panel. Series BC06 thus stands for modularity and easy expansion.

This product complies with all relevant standards of EN 54 and EN 12094-1 and is tested by the VdS. LST‘s high quality level is secured by a permanently monitored quality management system certified to ISO 9001.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 2