Optical-ThermalDetector

AMS-58000-700

ADM loop technology with Apollo/Discovery protocol

Combination of optical and thermal characteristics of fi re

Alarm temperature 58°C

Several sensitivity levels as well as thermal-onlyandoptical-onlyoperation selectable

Constant response sensitivity

Sealed electronics

Description

The addressable Optical-ThermalDetector AMS-58000-700uses the scattered light principle as well as a separate thermal detection unit. It was developed to detect the characteristics of fire in a wide range of applications, and to avoid deceptive alarms. The modern design of both measurement systems and the analysis of the parameters by means of a defined algorithm allow to reliably evaluate the characteristics of fire.

The response sensitivity and the operating mode of the detector can be selected in 5 steps (optical-onlyoperation,thermal-onlyoperation as well as three multisensor levels), via the fire detection control panel.

The proven ADM loop technology with Apollo/Discovery protocol establishes a permanent communication between the fire detection control panel and the de-

tector. That ensures a periodical function testing of the detector.

The influence of contamination of the optical measurement system is compensated for by using intelligent evaluation algorithms. With that, the response sensitivity of the detector is kept constant for a long time – a further effective step to avoid false alarms.

The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is selected by means of a code card in the detector base. Therefore the detector can be changed without additional tools.

The detector can be attached to various bases and it can be protected against theft.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231WIEN • WIEGELESTRASSE 36 • TEL +43 152114-0• FAX +43 152114-27

AMS-58000-700_DBL_LST_EN_0804.PDF• PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption

typ. 500µA (quiescent)

Alarm temperature

58°C (maximum-heatcomponent)

Ambient temperature

-20°Cto +60°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ø × H

100 × 50 (mm)

Colour

white

Weight

105g

Approvals

VdS G299038

Order number

241022

Order name

Optical-ThermalDetector/Anal./Disc/ApoAMS-58000-700