Lennox G61MP User Manual

5 (3)

G61MP

Service Literature

Corp. 0308−L6

Revised 10−2004

G61MP SERIES UNITS

G61MP series units are high−efficiency multi−position (upflow, downflow, horizontal right and left) gas furnaces manufactured with Lennox Duralok Plust heat exchangers formed of aluminized steel. G61MP units are available in heating capacities of 44,000 to 132,000 Btuh (13.0.0 to 38.6 kW) and cooling applications from 2 to 5 tons (7.0 kW to 17.5 kW)) up to 5 tons. Refer to Engineering Handbook for proper sizing.

Units are factory equipped for use with natural gas. Kits are available for conversion to LPG operation. G61MP model units are equipped with the Two−Stage Integrated SureLight control. All G61MP units meet the California Nitrogen Oxides (NOx) Standards and California Seasonal Efficiency requirements. All units use a redundant gas valve to assure safety shut−off as required by C.S.A.

All specifications in this manual are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (except where noted) are recommendations only and do not constitute code.

TABLE OF CONTENTS

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Parts Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

I Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

II Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

III Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

IV Heating System Service Checks . . . . . . . . . . . . . . 31

V Typical Operating Characteristics . . . . . . . . . . . . . . 34

VI Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

VII Wiring and Sequence of Operation . . . . . . . . . . . . 38

VIII Field Wiring and Jumper Setting . . . . . . . . . . . . . 46

IX Control Board Troubleshooting . . . . . . . . . . . . . . . . 48

IMPORTANT

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

WARNING

Sharp edges.

Be careful when servicing unit to avoid sharp edges which may result in personal injury.

Page 1

2003 Lennox Industries Inc.

SPECIFICATIONS

Gas

 

Model No.

G61MP−36B−045

G61MP−36B−070

G61MP−48C−090

G61MP−60C−090

Heating

High

Input − Btuh (kW)

44,000 (12.9)

66,000 (19.3)

88,000 (25.8)

88,000 (25.8)

Performance

Fire

Output − Btuh (kW)

41,000 (12.0)

62,000 (18.2)

83,000 (24.3)

84,000 (24.6)

 

 

 

 

Temperature rise range − _F (_C)

25 − 55 (14 − 31)

35 − 65 (21 − 39)

35 − 65 (21 − 39)

25 − 55 (14 − 31)

 

 

 

 

 

 

 

 

Low

Input − Btuh (kW)

30,000 (8.8)

45,000 (13.2)

60,000 (17.6)

60,000 (17.6)

 

Fire

Output − Btuh (kW)

28,000 (8.2)

43,000 (12.6)

57,000 (16.7)

58,000 (17.0)

 

 

 

Temperature rise range − _F (_C)

10 − 40 (6 − 24)

20 − 50 (12 − 30)

25 − 55 (14 − 31)

15 − 45 (9 − 27)

 

 

 

 

 

 

 

 

 

1 AFUE

94.1%

94.1%

94.1%

94.1%

 

 

California Seasonal Efficiency

83.5%

86.0%

87.3%

84.4%

 

High static (CSA) − in. w.g. (Pa)

0.5

0.5

0.5

0.5

 

 

 

 

 

 

 

Connections

 

2 Intake Pipe (PVC)

2

2

2

2

in.

 

2 Exhaust Pipe (PVC)

2

2

2

2

 

Condensate Drain Trap (PVC pipe) −

1/2

1/2

1/2

1/2

 

 

i.d.

 

 

 

 

 

with field supplied (PVC coupling) − o.d.

3/4

3/4

3/4

3/4

 

hose with hose clamp − i.d. x o.d.

1−1/4 x 1

1−1/4 x 1

1−1/4 x 1

1−1/4 x 1

 

 

Gas pipe size IPS

1/2

1/2

1/2

1/2

 

 

 

 

 

 

Indoor

Wheel nominal diameter x width − in.

10 x 8 (254 x 203)

10 x 8 (254 x 203)

10 x 10 (254 x 254)

11−1/2 x 10 (292 x 229)

Blower

 

(mm)

 

 

 

 

 

 

Motor output − hp (W)

1/3 (249)

1/3 (249)

1/2 (373)

1 (746)

 

 

Tons (kW) of add-on cooling

2.5 − 3 (8.8 − 10.5)

2.5 − 3.5 (8.8 − 12.3)

3 − 4 (10.5 − 14.0)

4 − 5 (14.0 − 17.5)

 

 

 

 

 

 

 

Shipping Data

 

lbs. (kg) − 1 package

136 (62)

146 (66)

168 (76)

176 (80)

 

 

 

 

 

 

Electrical characteristics

 

120 volts − 60 hertz − 1 phase (less than 12 amps)

 

 

 

 

 

 

 

OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA

 

3 Air Filter and Rack Kit

Horizontal (end)

87L96 − 18 x 25 x 1 in.

87L97 − 20 x 25 x 1 in.

 

Size of filter

 

 

(457 x 635 x 25 mm)

(508 x 635 x 25 mm)

 

 

 

Side Return

Single 44J22 or Ten Pack 66K63 − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)

 

 

 

 

 

 

 

 

 

Condensate Drain Heat

6 ft. (1.8 m)

26K68

26K68

26K68

26K68

 

Cable

 

24 ft. (7.3 m)

26K69

26K69

26K69

26K69

 

 

 

 

 

 

50 ft. (15.2 m)

26K70

26K70

26K70

26K70

 

 

 

 

 

 

 

 

Heat Cable Tape Fiberglass − 1/2 in. (38 mm) x 66 ft. (20 m)

39G04

39G04

39G04

39G04

 

 

Aluminum foil − 2 in. (25 mm) x 60 ft. (18

39G03

39G03

39G03

39G03

 

 

 

m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EZ Filter Base

Catalog Number − Ship. Weight − lbs.

73P56 − 7 (3)

73P56 − 7 (3)

73P57 − 8 (4)

73P57 − 8 (4)

 

 

 

(kg)

 

 

 

 

 

 

 

Dimensions − H x W x D − in. (mm)

4 x 17−5/8 x 28−5/8

4 x 17−5/8 x 28−5/8

4 x 21−5/8 x 28−5/8

4 x 21−5/8 x 28−5/8

 

 

 

 

(102 x 448 x 727)

(102 x 448 x 727)

(102 x 549 x 727)

(102 x 549 x 727)

 

 

Size of field provided filter − in. (mm)

16 x 25 x 1

 

16 x 25 x 1

20 x 25 x 1

20 x 25 x 1

 

 

 

 

 

 

 

(406 x 635 x 25)

 

(406 x 635 x 25)

(508 x 635 x 25)

(508 x 635 x 25)

 

 

 

 

 

 

 

 

 

Down−Flow Additive Base

 

11M60

 

11M60

11M61

11M61

 

 

 

 

 

 

 

 

4 High Altitude Orifice Kit − Natural Gas

59M16

59M16

59M16

59M16

 

4 High Altitude Pressure Switch Kit − Order two each

− − −

56M06

− − −

− − −

 

 

 

7501−10,000ft. (2286−3048m

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Support Frame Kit − Ship. Weight − lbs. (kg)

56J18 − 18 (8)

56J18 − 18 (8)

56J18 − 18 (8)

56J18 − 18 (8)

 

 

 

 

 

 

 

 

 

LPG/Propane Kit

 

0−7500 ft. (0−2286 m)

59M13

59M13

59M13

59M13

 

 

 

7501−10,000 ft. (2286−3048 m)

59M14

59M14

59M14

59M14

 

 

 

 

 

 

 

 

Natural to LPG/Propane Kit

 

59M87

59M87

59M87

59M87

 

 

 

 

 

 

 

 

RAB Return Air Base

 

− − −

− − −

− − −

RAB60C (12M71)

 

 

 

 

 

 

 

 

5 Termination Kits Concen-

1−1/2 inch (38 mm)

60G77

60G77

− − −

− − −

 

Direct Vent

tric

2 inch (51 mm)

− − −

− − −

33K97

33K97

 

 

Applications Only

 

 

 

3 inch (76 mm)

− − −

− − −

60L46

60L46

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

Close Couple − 2 inch (51 mm)

22G44

22G44

− − −

− − −

 

 

 

3 inch (76 mm)

44J40

44J40

44J40

44J40

 

 

 

 

 

Close Couple WTK − 2 inch (51 mm)

30G28

30G28

− − −

− − −

 

 

 

 

 

 

 

 

 

 

 

5,6 Termination Kits

Roof

2 inch (51 mm)

15F75

15F75

15F75

15F75

 

Direct Vent or

 

3 inch (76 mm)

44J41

44J41

44J41

44J41

 

Non−Direct Vent

 

 

 

 

 

 

 

 

 

 

Wall

Wall Ring Kit 2 inch (51 mm)

15F74

15F74

15F74

15F74

 

 

 

 

 

 

 

NOTE − Filters and provisions for mounting are not furnished and must be field provided.

 

 

 

1

Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.

2

Determine from venting tables proper exhaust pipe size and termination kit required.

 

 

 

3

Cleanable polyurethane frame type filter.

 

 

 

 

 

4

Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).

 

 

 

5

See Installation Instructions for specific venting information.

 

 

 

 

 

6

Kits contain enough parts for two, non−direct vent installations.

 

 

 

 

 

Page 2

SPECIFICATIONS

Gas

 

Model No.

G61MP−48C−110

G61MP−60C−110

G61MP−60D−135

Heating

High Fire

Input − Btuh (kW)

110,000 (32.2)

110,000 (32.2)

132,000 (38.7)

Performance

 

Output − Btuh (kW)

104,000 (30.5)

104,000 (30.5)

124,000 (36.3)

 

 

 

Temperature rise range − _F (_C)

45 − 75 (25 − 42)

35 − 65 (21 − 39)

40 − 70 (24 − 42)

 

 

 

 

 

 

 

Low Fire

Input − Btuh (kW)

75,000 (22.0)

75,000 (22.0)

90,000 (26.4)

 

 

Output − Btuh (kW)

72,000 (21.1)

72,000 (21.1)

86,000 (25.2)

 

Temperature rise range − _F (_C)

30 − 60 (18 − 36)

25 − 55 (14 − 31)

30 − 60 (18 − 36)

 

 

 

 

 

 

 

 

1 AFUE

94.1%

94.1%

94.1%

 

 

California Seasonal Efficiency

88.4%

87.0%

87.7%

 

High static (CSA) − in. w.g. (Pa)

0.5

0.5

0.5

 

 

 

 

 

 

Connections

 

2 Intake Pipe (PVC)

2

2

3

in.

 

2 Exhaust Pipe (PVC)

2

2

3

 

 

 

Condensate Drain Trap (PVC pipe) − i.d.

1/2

1/2

1/2

 

with field supplied (PVC coupling) − o.d.

3/4

3/4

3/4

 

hose with hose clamp − i.d. x o.d.

1−1/4 x 1

1−1/4 x 1

1−1/4 x 1

 

 

Gas pipe size IPS

1/2

1/2

1/2

 

 

 

 

 

Indoor

Wheel nominal diameter x width − in. (mm)

10 x 10 (254 x 254)

11−1/2 x 10 (292 x 229)

11−1/2 x 10 (292 x 229)

Blower

 

Motor output − hp (W)

1/2 (373)

1 (746)

1 (746)

 

 

 

 

Tons (kW) of add-on cooling

3 − 4 (10.5 − 14.0)

4 − 5 (14.0 − 17.5)

4 − 5 (14.0 − 17.5)

 

 

 

 

 

 

Shipping Data

 

lbs. (kg) − 1 package

178 (81)

186 (84)

206 (93)

 

 

 

 

 

Electrical characteristics

 

120 volts − 60 hertz − 1 phase (less than 12 amps)

 

 

 

 

 

 

OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA

 

3, 4 Air Filter and Rack Kit −

Horizontal (end)

87L97 − 20 x 25 x 1 in. (508 x 635 x 25 mm)

87L98 − 25 x 25 x 1 in.

 

Size of filter

 

 

 

 

(635 x 635 x 25 mm)

 

 

 

Side Return

5 Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)

 

Condensate Drain Heat

6 ft. (1.8 m)

26K68

26K68

26K68

 

Cable

 

24 ft. (7.3 m)

26K69

26K69

26K69

 

 

 

 

 

 

50 ft. (15.2 m)

26K70

26K70

26K70

 

 

 

 

 

 

 

Heat Cable Tape

Fiberglass − 1/2 in. (38 mm) x 66 ft. (20 m)

39G04

39G04

39G04

 

 

Aluminum foil − 2 in. (25 mm) x 60 ft. (18 m)

39G03

39G03

39G03

 

 

 

 

 

 

 

 

 

4 EZ Filter Base

Catalog Number − Shipping Weight

73P57 − 8 lbs. (4 kg)

73P58 − 10 lbs. (5 kg)

73P58 − 10 lbs. (5 kg)

 

 

Dimensions − H x W x D − in. (mm)

4 x 21−5/8 x 28−5/8

4 x 24−5/8 x 28−5/8

4 x 24−5/8 x 28−5/8

 

 

 

 

(102 x 549 x 727)

(102 x 625 x 727)

(102 x 625 x 727)

 

 

Size of field provided filter − in. (mm)

20 x 25 x 1

24 x 24 x 1

24 x 24 x 1

 

 

 

 

 

 

(508 x 635 x 25)

(610 x 610 x 25)

(610 x 610 x 25)

 

 

 

 

 

 

 

Down−Flow Additive Base

 

11M61

11M61

11M62

 

 

 

 

 

 

5 High Altitude Orifice Kit − Natural Gas Only

59M16

59M16

59M16

 

6 High Altitude Pressure Switch Kit − Order two each

− − −

− − −

56M93

 

 

 

4501−10,000 ft. (1372−3048 m)

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Support Frame Kit − Ship. Weight − lbs. (kg)

56J18 − 18 (8)

56J18 − 18 (8)

56J18 − 18 (8)

 

 

 

 

 

 

 

 

LPG/Propane Kit

 

0−7500 ft. (0−2286 m)

59M13

59M13

59M13

 

 

 

7501−10,000ft. (2286−3048m)

59M14

59M14

59M14

 

 

 

 

 

 

 

Natural to LPG/Propane Kit

 

59M87

59M87

59M87

 

 

 

 

 

 

 

RAB Return Air Base

 

− − − −

RAB60C (12M71)

RAB60D (12M72)

 

 

 

 

 

 

7 Termination Kits −

Concentric

2 inch (51 mm)

33K97

33K97

− − −

Direct Vent

Roof/Wall

3 inch (76 mm)

60L46

60L46

60L46

Applications

 

 

 

 

 

 

Wall Close−Coupled 3 inch (76 mm)

44J40

44J40

44J40

 

 

 

 

 

 

 

 

7,8 Termination Kits

Roof

2 inch (51 mm)

15F75

15F75

− − −

Direct Vent or Non−

 

3 inch (76 mm)

44J41

44J41

44J41

Direct Vent

 

 

 

 

 

 

 

 

Wall

Ring Kit 2 inch (51 mm)

15F74

15F74

9 15F74

NOTE − Filters and provisions for mounting are not furnished and must be field provided.

 

 

1

Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.

2

Determine from venting tables proper exhaust pipe size and termination kit required.

 

 

3

Cleanable polyurethane frame type filter.

 

 

 

4Not for use with RAB Return Air Base or with 60C and 60D size units with air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance tables for additional information.

5

Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).

6

Required for proper operation at altitudes over 4500 ft. (1370 m).

7

See Installation Instructions for specific venting information.

8

Kits contain enough parts for two, non−direct vent installations.

9

Non−direct vent applications only.

Page 3

BLOWER DATA

G61MP−36B−045 PERFORMANCE (Less Filter)

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

25

1555

735

630

1410

665

585

1190

560

520

1030

485

435

0.10

25

1515

715

605

1385

655

555

1190

560

485

1020

480

415

0.20

50

1470

695

580

1345

635

520

1170

550

455

1010

475

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

1410

665

555

1310

620

495

1155

545

440

1000

470

385

0.40

100

1350

640

535

1250

590

465

1120

530

410

980

465

360

0.50

125

1290

610

505

1205

570

450

1080

510

390

950

450

345

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

1220

575

485

1145

540

420

1020

480

365

905

430

320

0.70

175

1145

540

460

1080

510

400

975

460

345

860

405

300

0.80

200

1050

495

425

985

465

365

870

410

320

785

370

285

0.90

225

945

445

410

900

425

345

825

390

305

730

345

270

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

 

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

 

 

 

 

 

G61MP−36B−070 PERFORMANCE (Less Filter)

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

1640

775

660

1415

665

575

1160

545

485

1005

475

410

0.10

25

1600

755

635

1395

660

550

1160

545

460

1000

470

385

0.20

50

1540

725

605

1370

650

525

1160

545

445

995

470

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

1495

705

580

1345

635

505

1145

540

425

990

465

365

0.40

100

1420

670

545

1275

605

480

1125

530

395

965

455

345

0.50

125

1360

640

525

1245

590

450

1080

510

375

945

445

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

1275

600

490

1165

550

410

1025

485

350

900

425

305

0.70

175

1170

555

465

1085

515

385

965

430

335

860

405

295

0.80

200

1080

510

440

1010

475

360

865

410

310

775

365

270

0.90

225

945

445

400

840

395

320

765

360

275

710

335

245

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

 

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

 

 

 

 

 

G61MP−48C−090 PERFORMANCE (Less Filter)

External Static

 

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

High

 

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

in. w.g.

Pa

cfm

L/s

Watts

 

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2180

1030

930

 

1835

865

790

1520

715

630

1280

605

510

0.10

25

2135

1005

885

 

1825

860

750

1510

710

610

1275

600

495

0.20

50

2085

985

840

 

1810

855

720

1505

710

580

1270

600

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2030

955

800

 

1775

835

685

1500

705

565

1265

595

460

0.40

100

1940

915

760

 

1735

820

650

1480

700

535

1250

590

440

0.50

125

1865

880

725

 

1660

785

600

1430

675

505

1215

575

425

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

1740

820

670

 

1590

750

575

1380

650

475

1175

555

410

0.70

175

1645

775

640

 

1475

695

520

1290

610

450

1105

520

375

0.80

200

1540

725

600

 

1340

630

465

1175

555

405

1020

480

355

0.90

225

1335

630

540

 

1170

555

440

1070

505

375

950

450

330

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

 

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

 

 

 

 

 

G61MP−48C−110 PERFORMANCE (Less Filter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static

 

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

Pressure

 

High

 

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

 

 

 

 

 

 

 

 

 

in. w.g.

Pa

cfm

L/s

Watts

 

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2160

1020

880

 

1880

890

755

1490

705

602

1235

580

485

0.10

25

2100

990

850

 

1855

875

730

1480

700

585

1230

580

475

0.20

50

2035

960

805

 

1815

860

690

1475

695

560

1225

580

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

1965

925

750

 

1755

830

650

1475

695

545

1220

575

445

0.40

100

1885

890

725

 

1715

810

625

1465

690

510

1215

575

430

0.50

125

1780

840

680

 

1630

770

580

1420

670

490

1150

540

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

1690

800

660

 

1550

735

550

1360

640

460

1110

525

380

0.70

175

1575

745

620

 

1410

665

505

1210

570

405

1035

490

350

0.80

200

1375

650

550

 

1230

580

450

1125

530

380

970

460

325

0.90

225

1225

580

520

 

1120

530

415

1050

495

365

885

420

310

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

 

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

 

 

 

 

 

Page 4

BLOWER DATA

G61MP−60C−090 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2835

1335

1495

2340

1105

1155

1800

850

895

1440

680

695

0.10

25

2785

1315

1475

2345

1105

1135

1805

855

865

1515

715

690

0.20

50

2715

1280

1435

2275

1075

1080

1825

860

845

1560

735

685

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2620

1235

1380

2260

1065

1035

1840

870

825

1600

755

680

0.40

100

 

1205

1350

 

1055

1015

 

870

815

 

765

670

2550

2230

1845

1620

0.50

125

2450

1155

1305

2175

1025

990

1850

870

790

1615

765

655

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2365

1115

1270

2130

1005

940

1830

865

775

1615

760

640

0.70

175

2240

1060

1205

2070

975

915

1815

855

760

1595

755

620

0.80

200

2185

1030

1190

1965

925

865

1775

840

745

1555

735

605

0.90

225

2015

950

1150

1820

860

820

1690

800

715

1440

680

580

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

G61MP−60C−090 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2840

1340

1450

2345

1105

1105

1895

895

900

1515

715

700

0.10

25

 

1305

1415

 

1115

1080

 

920

885

 

745

700

2765

2365

1950

1580

0.20

50

2695

1270

1385

2345

1105

1050

1985

935

870

1620

765

695

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2605

1230

1335

2315

1090

1030

1990

940

850

1645

775

690

0.40

100

2530

1195

1300

2265

1070

990

1990

940

825

1665

785

675

0.50

125

2420

1140

1260

2210

1045

955

1970

930

800

1675

790

665

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2330

1100

1220

2145

1010

925

1930

910

775

1665

785

650

0.70

175

2250

1060

1190

2050

965

885

1875

885

745

1645

775

630

0.80

200

2135

1010

1140

2000

945

865

1810

855

715

1620

765

615

0.90

225

2030

960

1090

1885

890

830

1720

810

685

1560

735

590

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

G61MP−60C−110 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2625

1240

1350

2310

1090

1080

1885

890

885

1515

715

700

0.10

25

2570

1215

1330

2325

1095

1060

1910

900

865

1575

745

700

0.20

50

2410

1135

1305

2285

1080

1035

1930

910

845

1620

765

690

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2425

1145

1265

2230

1055

990

1925

905

825

1635

770

675

0.40

100

2335

1100

1220

2175

1025

950

1910

900

810

1640

775

660

0.50

125

2270

1070

1195

2120

1000

935

1895

895

785

1640

775

640

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2170

1025

1155

2045

965

885

1860

875

765

1630

770

630

0.70

175

2110

995

1130

1950

920

855

1795

845

730

1590

750

610

0.80

200

2035

960

1090

1885

890

820

1745

825

705

1540

725

580

0.90

225

1900

895

1055

1760

830

780

1665

785

680

1470

695

565

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

Page 5

BLOWER DATA

G61MP−60C−110 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2720

1285

1385

2410

1135

1090

2055

970

935

1620

765

710

0.10

25

2665

1255

1355

2385

1125

1075

2025

955

885

1730

815

735

0.20

50

 

1220

1315

 

1110

1015

 

955

865

 

795

690

2585

2350

2030

1680

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2505

1180

1275

2290

1080

990

2025

955

840

1695

800

675

0.40

100

2435

1150

1250

2235

1055

940

2030

960

830

1695

800

660

0.50

125

2350

1110

1205

2170

1025

930

1975

930

790

1735

820

665

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2255

1065

1185

2100

990

895

1915

905

765

1720

810

650

0.70

175

2160

1020

1150

2005

945

840

1865

880

730

1680

795

635

0.80

200

2020

955

1090

1905

900

825

1810

855

710

1625

765

610

0.90

225

1910

900

1050

1820

860

795

1705

805

675

1540

725

590

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

G61MP−60D−135 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2665

1260

1440

2325

1095

1100

1865

880

890

1410

665

690

0.10

25

2615

1235

1405

2310

1090

1065

1915

905

865

1465

690

685

0.20

50

2530

1195

1370

2280

1075

1055

1925

910

850

1570

740

675

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2470

1165

1330

2235

1055

1015

1920

905

825

1590

750

670

0.40

100

2380

1125

1290

2175

1025

985

1910

900

805

1590

750

655

0.50

125

2310

1090

1265

2120

1000

965

1890

890

790

1595

755

645

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2200

1035

1230

2055

970

935

1835

865

765

1580

745

630

0.70

175

2120

1000

1190

1970

930

900

1790

845

740

1545

730

605

0.80

200

2025

955

1160

1890

890

875

1720

810

710

1515

715

590

0.90

225

1930

910

1110

1800

850

835

1655

780

685

1440

680

570

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

G61MP−60D−135 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.

External Static

 

 

 

Air Volume / Watts at Different Blower Speeds

 

 

 

Pressure

 

High

 

 

Medium−High

 

 

Medium−Low

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

0

2730

1290

1465

2425

1145

1125

2055

970

915

1560

735

680

0.10

25

2670

1260

1440

2400

1135

1100

2065

975

890

1590

750

675

0.20

50

2600

1225

1400

2365

1115

1070

2045

965

865

1620

765

665

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

75

2525

1190

1360

2315

1095

1045

2035

960

845

1615

760

655

0.40

100

2445

1155

1325

2260

1065

1015

2020

955

820

1615

760

645

0.50

125

2360

1115

1280

2195

1035

985

1960

925

790

1610

760

635

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

150

2290

1080

1255

2130

1005

965

1900

895

755

1600

755

615

0.70

175

2205

1040

1220

2035

960

910

1825

860

730

1570

740

600

0.80

200

2110

995

1195

1945

915

880

1765

830

710

1540

725

580

0.90

225

1970

930

1120

1835

865

830

1680

795

690

1540

725

545

 

 

 

 

 

 

 

 

 

 

NOTES −

All air data is measured external to unit without filter (not furnished − field provided).

 

 

 

 

 

 

Page 6

Lennox G61MP User Manual

 

 

G61MP PARTS ARRANGEMENT

 

 

 

TOP CAP

 

 

 

DuralokPlusTM

 

 

 

HEAT EXCHANGER

 

 

 

ASSEMBLY

 

 

 

 

CABINET

 

BURNER BOX

 

 

 

ASSEMBLY

 

 

 

GAS VALVE

 

 

 

AND MANIFOLD

 

 

FLUE

 

 

 

COLLAR

 

 

COMBUSTION

 

 

AIR PROVE PROVE

 

WARM HEADER

 

SWITCHES*

 

(COLLECTOR)

 

 

 

BOX

 

COMBUSTION AIR

 

 

 

INDUCER

 

 

 

 

 

CONDENSER COIL

BURNER

 

 

PRIMARY LIMIT

ACCESS

 

 

 

 

 

PANEL

 

 

 

 

 

 

COLD HEADER

 

 

 

(COLLECTOR)

 

 

 

BOX

BLOWER

 

DOOR

 

ACCESS

 

INTERLOCK

 

DOOR

 

SWITCH

SECONDARY

 

 

 

 

 

 

LIMITS (2)

*G61MP−090 shown.

 

 

 

G61MP−045 and −070

SIGHT

 

BLOWER

are equipped with

GLASS

 

ASSEMBLY

two switches.

 

 

 

 

 

CONTROL BOX

 

FIGURE 1

Page 7

I−UNIT COMPONENTS

G61MP unit components are shown in figure 1. The gas valve, combustion air inducer and burners can be accessed by removing the burner access panel. Electrical components are in the control box (figure 2) found in the blower section.

G61MP units are factory equipped with a bottom return air panel in place. The panel is designed to be field removed as required for bottom air return. Markings are provided for side return air and may be cut out in the field.

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

3. Circuit Breaker (CB8)

A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the transformer (T1). The breaker is rated 3A at 32V. If the current exceeds this limit the breaker will trip and all unit operation will shutdown. The breaker can be manually reset by pressing the button on the face. See figure 3.

CIRCUIT BREAKER CB8

PRESS TO RESET

CAUTION

Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.

A−Control Box

1. Control Transformer (T1)

A transformer located in the control box provides power to the low voltage section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V secondary.

2. Door Interlock Switch (S51)

A door interlock switch rated 14A at 125VAC is wired in series with line voltage. When the blower door is removed the unit will shut down.

CONTROL BOX G61MP

 

CIRCUIT

 

BREAKER

DOOR INTERLOCK

 

SWITCH

TRANSFORMER

 

SURELIGHT

 

CONTROL

 

BOARD

 

FIGURE 2

FIGURE 3

WARNING

Shock hazard.

Disconnect power before servicing. Integrated

Control Board is not field repairable. If control is inoperable, simply replace entire control.

Can cause injury or death. Unsafe operation will result if repair is attempted.

4. Integrated Control Board (A92)

All G61MP units are equipped with the Lennox Two−Stage Integrated control board. The system consists of a ignition control board (figure 4 with control terminal designations in tables 3, 4 and 5) and ignitor (figure 7). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The board controls all major furnace operations. The board features two LED lights, DS1 and

DS2 for troubleshooting. The board also has two accessory terminals rated at (1) one amp. See table 6 for troubleshooting diagnostic codes.

Electronic Ignition

At the beginning of the heat cycle, SureLight control monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by−passed). Likewise the control will not begin the second stage heating cycle if the second stage prove switch is closed, and will allow first stage heat only. However if the second stage prove switch closes during the first stage pre−purge, the control will respond to second stage heat. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period.

After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up time between trials of 35 sec-

Page 8

onds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again.

The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.

Two Stage Operation / Thermostat Selection Jumper

The control can be utilized in two modes: SINGLE−STAGE thermostat or TWO−STAGE thermostat. The thermostat selection jumper E20, located just below dip switches 1 through 4 (figure 4), must be positioned for the particular application. The jumper is factory set on TWO" for use with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.

While in the single−stage thermostat mode (single jumper setting), the burners will always fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a 10 minute recognition period, the unit will switch to second stage heat. While in the two−stage thermostat mode (two jumper setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second−stage heat on call from the indoor thermostat. If there is a simultaneous call for first and second stage heat, the unit will fire on first stage heat and switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.

Dip Switch Settings

Dip Switches 1 and 2 − Heating Fan off Delay − The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches 1 and 2 located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. For customized comfort, monitor the supply air temperature once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de− energized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air temperature). See table 1 for dip switch settings.

TABLE 1

Heating Fan Off Delay

Delay (Seconds)

Switch 1

Switch 2

 

 

 

 

60

Off

Off

 

 

 

90

Off

On

 

 

 

120

On

Off

 

 

 

180

On

On

Switch 3 − Second Stage Delay (Used with Single−Stage

Thermostat Only) −− This switch is used to determine the second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON position, which provides a 10−minute delay before second−stage heat is initiated. If the switch is toggled to the OFF position, it will provide a 15−minute delay before second−stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE−stage thermostat use.

Switch 4 − Cooling Fan off Delay − The fan on delay time of 2 seconds is not adjustable. Fan off time (time that the blower operates after the cool demand has been satisfied) can be adjusted by flipping dip switch 4. The unit is shipped with a factory fan off setting of 45 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. See table 2 for cool fan off time settings.

TABLE 2

Cooling Fan Off Delay

Delay (Seconds)

Switch 4

 

 

2

Off

 

 

45

On

 

 

Diagnostic LED’s (DS1 and DS2)

Two diagnostic LED’S are located on the two−stage integrated control board. See figure 4. These light flashes correspond with the codes detailed in table 6.

Factory Installed Jumper Y1 to Y2

A factory−installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be clipped for two−stage cooling.

Page 9

TWO−STAGE INTEGRATED CONTROL BOARD

LEDs

DIP

SWITCHES 1 − 4

W915 FACTORY INSTALLED JUMPER (MUST CLIP FOR 2 STAGE COOL)

THERMOSTAT CONNECTIONS (TB1)

DIP SWITCH(ES)

FUNCTION

 

 

1 and 2

Blower Off Delay (Heating Mode)

3

Second Stage ON Delay (Single−stage t’stat)

4

Blower Off Delay (Cooling Mode)

FIGURE 4

TABLE 3

Integrated Control Board Terminals

120VAC Neutral

LINE

Line

 

 

XFMR

Transformer

 

 

EAC

Electronic Air Cleaner

 

 

CIRC

Indoor Blower

 

 

HUM

Humidifier

 

 

 

120VAC Line

 

 

HUM

Humidifier

 

 

XMFR

Transformer

 

 

LINE

Line

 

 

PARK

For Unused Leads

 

 

COOL

Cooling Speed

 

 

EAC

Electronic Air Cleaner

 

 

HI HEAT

HIigh Heat Speed

 

 

LO HEAT

Low Heat, Low Cool and Continuous Fan

 

Speed

 

 

TABLE 4

Integrated Control Board 5 Pin Terminal

PIN #

Function

 

 

1

Ignitor

2Combustion Air Inducer High Speed

3Combustion Air Inducer Low Speed

4

Combustion Air Inducer Neutral

 

 

5

Ignitor Neutral

 

 

TABLE 5

Integrated Control Board 12Pin Terminal

PIN #

Function

 

 

1

Gas Valve 2nd Stage (High Fire)

 

 

2

Second Stage Prove Switch

 

 

3

Not Used

 

 

4

Ground

 

 

5

24V Hot

 

 

6

Primary Limit In

 

 

7

Gas Valve 1st stage (Low Fire)

 

 

8

Gas Valve Common

 

 

9

24V Neutral

 

 

10

Ground

 

 

11

Primary Limit Out

 

 

12

1st Stage Prove Switch

 

 

Page 10

 

 

TABLE 6

 

 

DIAGNOSTIC CODES

 

Diagnostic LEDs are labeled DS1 and DS2. See figure 4 for location of diagnostic LEDs.

 

 

 

DS1

DS2

DESCRIPTION

SIMULTANEOUS

SIMULTANEOUS

Power on − Normal operation.

SLOW FLASH

SLOW FLASH

Also signaled during cooling and continuous fan.

SIMULTANEOUS

SIMULTANEOUS

Normal operation − signaled when heating demand initiated at thermostat.

 

 

FAST FLASH

FAST FLASH

 

SLOW FLASH

ON

Primary, secondary, backup secondary or rollout limit switch open. Limits must

close within 3 minutes or unit goes into 1 hour Watchguard.

 

 

 

 

Low prove switch open;

OFF

SLOW FLASH

OR: Blocked inlet/exhaust vent;

 

 

OR: Low prove switch closed prior to activation of combustion air inducer.

 

 

 

 

 

High prove switch open;

OFF

FAST FLASH

OR: Blocked inlet/exhaust vent;

 

 

OR: High prove switch closed prior to activation of combustion air inducer.

 

 

 

ALTERNATING

ALTERNATING

Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;

OR lost flame sense 5 times in one heating cycle;

SLOW FLASH

SLOW FLASH

OR pressure switch opened 5 times in one heating cycle.

 

 

 

 

 

SLOW FLASH

OFF

Flame sensed without gas valve energized.

ON

ON

 

ON

OFF

Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.

OFF

ON

 

 

 

 

FAST FLASH

SLOW FLASH

Main power polarity reversed. Switch line and neutral.

SLOW FLASH

FAST FLASH

Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.

 

 

The following conditions are sensed during the ignitor warm−up period only:

 

 

1) Improper main ground;

ALTERNATING

ALTERNATING

2) Broken ignitor; OR: Open ignitor circuit;

FAST FLASH

FAST FLASH

3) Line voltage below 75 volts.

 

 

(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on

 

 

call from thermostat, and will not respond.

 

 

 

NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).

Low flame sense current = 0.17−0.22 microAmps.

B−Blower Compartment

1. Blower Motor (B3) and Capacitor (C4)

All G61MP units use direct drive blower motors. All motors are 120V permanent split capacitor motors to ensure maximum efficiency. Ratings for capacitors will be on motor nameplate. See SPECIFICATIONS section for motor specifications.

NOTE − Shafts on 1 HP motors have 2 flat sides and are matched with blower wheels with 2 set screws.

2. Secondary Limit Controls (S21)

The secondary limits (S21) on G61MP units are located in the blower compartment on the back side of the blower housing.

See figure 5. All G61MP units are equipped with two secondary limts. When excess heat is sensed in the blower compartment, the limit will open. If the limit is open, the furnace control energizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set to open at 125°F and cannot be adjusted.

SUPPLY AIR BLOWER

AND SECONDARY LIMITS

SECONDARY

LIMIT (S)

MOTOR/BLOWER ASSEMBLY

CAPACITOR

To Remove Blower From Unit: Disconnect Power, Remove Control Box, Remove Bolts and Unplug Motor Wires From Control Board.

Then Slide Out Front of Unit.

FIGURE 5

Page 11

C−Heating Components

3. Flame Sensor

A flame sensor is located on the left side of the burner support. See figure 6. The sensor is mounted through the bottom of the burner box and the tip protrudes into the flame envelope of the left−most burner. The sensor can be removed for service without removing any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed.

4. Ignitor

The SureLight ignitor is made of durable silicon nitride. Ignitor longevity is enhanced by controlling voltage to the ignitor. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor. Due to this feature of the board, voltage cannot be measured so ignitor must be ohmed. Ohme value should be 10.9 to 19.7. See 7 for ignitor location.

NOTE − The G61MP furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

NORMAL FLAME SIGNAL > 0.23 MICROAMPS

LOW FLAME SIGNAL

< 0.22 MICROAMPS

DROP OUT SIGNAL

= 0.16 MICROAMPS

5/16"

FIGURE 6

5. Burners (Figure 7)

All units use inshot burners. Burners are factory set and do not require adjustment. The manifold brackets are slotted so burners can be removed as an assembly for service. Burner maintenance and service is detailed in the MAINTENANCE section of this manual. Each burner uses an orifice which is precisely matched to the burner input and is threaded into the burner manifold. All G61MP natural gas units are fitted with

.089" sized orifices. See SPECIFICATIONS" tables for LP kits and high altitude.

A flame retention ring in the end of each burner maintains correct flame length and shape and keeps the flame from lifting off the burner head. In addition, the burner entrance to each clamshell is fitted with a corbel cup (orifice) used to direct the flow of combustion products.

 

SureLight Ignitor Location

 

5/8"

MEASUREMENT IS TO I.D.

 

OF RETENTION RING

 

13/32’

 

 

 

5/16"

 

IGNITOR

BRACKET

 

 

 

BURNERS FRONT VIEW

BURNERS TOP VIEW

FIGURE 7

Page 12

6. Clamshell Heat Exchanger

G61MP units use an aluminized steel primary and stainless steel secondary heat exchanger assembly. Heat is transferred to the air stream from all surfaces of the heat exchanger. The shape of the heat exchanger ensures maximum efficiency.

The combustion air inducer pulls fresh air through the air intake box. This air is mixed with gas in the burner venturi and at the corbel orifices. The gas / air mixture is then burned at the entrance of each clamshell. Combustion gases are then pulled through the primary and secondary heat exchangers and exhausted out the exhaust vent pipe.

7. Flame Rollout Switches (S47)

Flame rollout switch S47 is a high temperature limit located on each side of the burner box. Each furnace is equipped with two identical switches. The limit is a N.C. SPST manu- al-reset limit connected in series with the primary limit S10. When S47 senses rollout, the circuit breaks and the ignition control immediately stops ignition and closes the gas valve.

If unit is running and flame rollout is detected, the gas valve will close and ignition control will be disabled. Rollout can be caused by a blocked heat exchanger, flue or lack of combustion air. The switch is factory set to trip (open) at 250°F and cannot be adjusted. The switch can be manually reset. To manually reset a tripped switch, push the reset button located on the control.

8. Primary Limit Control (S10)

Figure 8 shows the primary limit (S10) used on G61MP units located in the heating vestibule panel. S10 is provided with a shield on some models (figure 8) and must not be removed. Note orientation of shield and limit if limit is replaced. When excess heat is sensed in the heat exchanger, the limit will open.

Once the limit opens, the furnace control energizes the supply air blower and de−energizes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted.

9.Backup Secondary Limit Control (S113) (G61MP−090, 110, 135 only)

Backup secondary limit control S113 is a N.C. auto−reset switch located on the combustion air inducer. S113 acts as a backup to primary limit S10 in the event of an indoor blower failure. S113 contacts open when temperature on the CAI reaches 142°.

10. Gas Valve (GV1)

The G61MP uses a two−stage gas valve manufactured by Honeywell (figure 35) or White Rodgers (figure 36). The valves are internally redundant to assure safety shut−off. If the gas valve must be replaced, the same type valve must be used.

24VAC terminals and gas control knob or switch are located on the valve. All terminals on the gas valve are connected to wires from the electronic ignition control. 24V applied to the terminals energizes the valve.

Inlet and outlet pressure taps are located on the valve. A regulator adjustment screw is located on the valve.

LPG change over kit s are available from Lennox. Kits include burner orifices and a gas valve regulator conversion kit.

The burner box is sealed and operates under a negative pressure. A pressure hose is connected from the burner box to the gas valve. The gas valve senses the pressure in the burner box and changes gas valve outlet (manifold) pressure based on changes in the burner box pressure.

The intent is to compensate for different vent configurations which can greatly affect the rate of the unit.

PRIMARY LIMIT LOCATION

limit shield 090, −110 and

−135 only

limit faces shield

FIGURE 8

11. Combustion Air Inducer Prove Switch (S18)

All G61MP units are equipped with combustion air prove switches located on the combustion air inducer housing.

G61MP−045 and −070 (figure 10) units have two combustion air proving switches. G61MP−090, −110 and −135 units are equipped with two dual prove switch assemblies" consisting of two switches acting as one. See figure 9. The switches are connected to the cold end header box by means of a flexible hose that monitors negative air pressure in the cold end header box.

The switches are a single-pole single-throw proving switch electrically connected to the furnace control. The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the flue becomes obstructed.

Page 13

On heat demand (first or second stage) the switch senses that the combustion air inducer is operating. It closes a circuit to the furnace control when pressure inside the cold end header box decreases to a certain set point.

Set points vary depending on unit size. See tables 8, 9 and 10. The pressure sensed by the switch is negative. If the air intake vent pipe or outlet vent pipe becomes obstructed during operation, the switch senses a change of negative pressure and opens the circuit to the furnace control and gas valve. A bleed port on the switch allows relatively dry air in the vestibule to purge switch tubing, to prevent condensate build up.

The switch is factory set and is not field adjustable. It is a safety shut-down control in the furnace and must not be by− passed for any reason. If switch is closed or by−passed, the control will not initiate ignition at start up.

DUAL COMBUSTION AIR PROVE SWITCH

G61MP−090, −110 & −135

first stage

negative

pressure

 

second stage

positive pressure

FIGURE 9

To troubleshoot the prove switches, temporarily jumper them.

The unit will not fire with the switches jumpered. Therefore, the prove switches must be bypassed after the combustion air inducer is activated. This will determine if the prove switches and furnace are operating properly. However, this may not indicate if the sealed combustion system is operating properly.

Checks of pressure differential can aid in troubleshooting. When measuring the pressure differential, readings should be taken at the prove switch. Lack of differential usually indicates problems in the intake or exhaust piping, but may indicate problems in the heat exchanger, condensing coil, header boxes, combustion inducer or other components.

Measuring pressure differential

The differential pressure is the difference in pressure measured across the cold end header box orifice.

1 − Remove thermostat demand and allow unit to cycle off.

2 −

Install a tee in the negative (−) line and a tee in the positive

 

(+) line running from one of the prove switches to the cold

 

end header box.

3 −

Install a manometer with hose from the negative (−)

 

side of the manometer to the tee installed in the nega-

tive (−) line and with hose from the positive (+) side of the manometer to the tee in the positive (+) line.

NOTE − Both sides of the cold end header box are negative.

However the (+) port reads less negative pressure than the

(−) port.

CAI & COLD END HEADER BOX ASSEMBLY

(−045 & 070 SHOWN)

 

Install tee’s in the

 

negative line and

 

positive line then

 

connect hoses to

 

manometer.

_ +

+ _

cold end header box

prove switches orifice size

FIGURE 10

4 − Operate unit and observe manometer reading. Readings will change as heat exchanger warms.

a.Take one reading immediately after start-up.

b.Take a second reading after unit has reached steady state (approximately 5 minutes). This will be the pressure differential.

The pressure differential should be greater than those listed in table 8, 9 or 10.

5 − Remove thermostat demand and allow to cycle off.

6 − Remove manometer and tee’s. Reinstall combustion air sensing hoses to the prove switch.

7 − Repeat steps 1 through 6 for the other prove switch.

Page 14

12. Combustion Air Inducer (B6)

All G61MP units use a combustion air inducer to move air through the burners and heat exchanger during heating operation. The blower uses a PSC 120VAC motor. The motor operates during all heating operation and is controlled by the ignition control A3. Blower operates continuously while there is a call for heat. The burner ignition control will not proceed with the ignition sequence until combustion air inducer operation is sensed by the proving switches.

The CAI is installed on the cold end header box. The cold end header box is a single piece made of hard plastic. The box has an internal channel where the combustion air inducer creates negative pressure at unit start up. The channel contains an orifice used to regulate flow created by the CAI. The box has pressure taps for the CAI prove switch hoses.

The prove switches measure the pressures across the CAI orifice or difference in the channel and the box. A window is provided on the bottom right hand side of the box to indicate orifice size. See figure 10. See table 7 for orifice size per unit. If replacement is necessary the gaskets used to seal the box to the vestbule panel and the CAI to the box, must also be replaced.

 

TABLE 7

 

 

 

G61MP Unit

 

C.A.I. Orifice Size

 

 

 

−045

 

.719"

 

 

 

−070

 

.938"

 

 

 

−090

 

1.063"

 

 

 

−110

 

1.313"

 

 

 

−135

 

1.688"

 

 

 

TABLE 8 0’ to 4500’

G61MP Unit

Set Point

Set Point

Second Stage

First Stage

 

 

 

 

−045

0.95"

0.95"

 

−070

 

 

 

 

 

−090

0.85"

0.50"

 

−110

 

 

 

 

 

−135

0.60"

0.35"

 

 

 

 

TABLE 9*

 

 

4501’ to 7500’

 

 

 

 

G61MP Unit

Set Point

Set Point

Second Stage

First Stage

 

 

 

 

−045

0.95"

0.95"

 

−070

 

 

 

 

 

−090

0.75"

0.50"

 

 

 

−110

0.85"

0.50"

 

 

 

−135

0.55"

0.35"

 

 

 

*Unit may require conversion kit at this altitude. See High Altitude table.

TABLE 10* 7501’ to 10,000’

G61MP Unit

Set Point

Set Point

Second Stage

First Stage

 

 

 

 

−045

0.95"

0.95"

 

 

 

−070

0.85"

0.85"

 

 

 

−090

0.60"

0.35"

 

 

 

−110

0.85"

0.50"

 

 

 

−135

0.55"

0.35"

 

 

 

*Unit may require conversion kit at this altitude. See High Altitude table.

Page 15

II−PLACEMENT AND INSTALLATION

TABLE 11

OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES

 

 

 

 

Vent Pipe Length Equivalency (feet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

Outdoor

 

 

 

 

 

2" Wall

 

 

VENT

Exhaust

Exhaust

1−1/2"

2" Con-

3" Con-

 

 

 

 

2" Wall

3" Wall

Kit with

2" Wall

 

Accelerator

Accelerator

Concen-

centric

centric

UNIT

PIPE

Plate Kit

Plate Kit

Vent Ex-

Ring Kit

MODEL

DIA.

(Dia. X

(Dia. X

tric Kit

Kit

Kit

 

 

tension

 

 

(in.)

Length)

Length)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1−1/2" X 12"

2" X 12"

71M80

60M29

60L46

22G44

44J40

30G28

15F74

 

 

81J20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

Not

12

Not

Not

4

4*

4

4

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

2−1/2

5

Not

15

Not

Not

5

5*

5

5

 

Allowed

Allowed

Allowed

36B−045

 

 

 

 

 

 

 

3

7

Not

21

Not

Not

7

7*

7

7

 

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

4

14

Not

42

Not

Not

14

14*

14

14

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

2

4

Not

12

Not

Not

4

4*

4

4

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

2−1/2

5

Not

15

Not

Not

5

5*

5

5

 

Allowed

Allowed

Allowed

36B−070

 

 

 

 

 

 

 

3

8

Not

24

Not

Not

8

8*

8

8

 

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

4

14

Not

42

Not

Not

14

14*

14

14

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

2

Not

1

Not

3

3

Not

1

Not

1**

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2−1/2

Not

2

Not

6

6

Not

2

Not

2**

 

Allowed

Allowed

Allowed

Allowed

60C−090

 

 

 

 

 

 

3

Not

2

Not

6

6

Not

2

Not

2**

 

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

4

Not

4

Not

12

12

Not

4

Not

4**

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2−1/2

Not

2

Not

6

6

Not

2

Not

2***

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

60C−110

3

Not

2

Not

6

6

Not

2

Not

2***

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

4

Not

4

Not

12

12

Not

4

Not

4***

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

3

Not

6

Not

Not

15

Not

6

Not

6***

 

Allowed

Allowed

Allowed

Allowed

Allowed

60D−135

 

 

 

 

 

4

Not

10

Not

Not

25

Not

10

Not

10***

 

 

Allowed

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator.

***For use only in non−direct vent applications, when snow riser is

not required. Requires field−provided and installed 2" exhaust accelerator.

Page 16

A−Vent Piping Guidelines

The G61MP can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.

NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors.

In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −−

Size pipe according to tables 12 and 13. Table 12 lists the minimum equivalent vent pipe lengths permitted. Table 13 lists the maximum equivalent pipe lengths permitted.

Maximum vent length is defined as:

Total length (linear feet) of pipe,

Plus Equivalent length (feet) of fittings,

Plus Equivalent length (feet) of termination.

NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.

Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping

Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 14.

*NOTE − The exhaust pipe should be offset a minimum of 12 inches to avoid the possibility of water droplets being released from the exhaust termination. The minimum exhaust vent length is 15 ft. Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 12−inch vertical offset.

Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 5 feet (1.52m) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to 2.5 feet (.76m) of vent pipe of the same diameter. In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact the Application Department for assistance in sizing vent pipe in these applications.

NOTE − The flue collar on all models is sized to accommodate 2" Schedule 40 flue pipe. When vent pipe which is larger than 2" must be used in an upflow application, a 2" elbow must be applied at the flue collar in order to properly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine acceptable vent lengths. Assign an equivalent feet value to this elbow according to the larger size pipe being used. Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.

 

Exhaust Pipe Offset

 

12" Min.

12" Min.

 

Upflow and Downflow Application

Upflow and Downflow Application

Rooftop Termination

Side Wall Termination

12" Min.

12" Min.

 

Horizontal Application

 

Horizontal Application

Rooftop Termination

 

Side Wall Termination

 

 

 

FIGURE 11

Page 17

Loading...
+ 37 hidden pages