IBM 4QX, 42X, 200, 42E, 900 User Manual

...
0 (0)
IBM 4QX, 42X, 200, 42E, 900 User Manual

Hardware Maintenance Manual

IBM

IBM PC Server/Enterprise Racks

Hardware Maintenance Manual

IBM

IBM PC Server/Enterprise Racks

Note:

Before using this information and the product it supports, be sure to read the general information under “Notices” on page 195.

Sixth Edition (November 1999) Updated April 2001

The following paragraph does not apply to the United Kingdom or any country where such provisions are inconsistent with local law:

INTERNATIONAL BUSINESS MACHINES CORPORATION PROVIDES THIS PUBLICATION "AS IS" WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow disclaimer of express or implied warranties in certain transactions, therefore, this statement may not apply to you.

This publication could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new editions of the publication. IBM may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time.

This publication was developed for products and services offered in the United States of America. IBM may not offer the products, services, or features discussed in this document in other countries, and the information is subject to change without notice. Consult your local IBM representative for information on the products, services, and features available in your area.

Requests for technical information about IBM products should be made to your IBM reseller or IBM marketing representative.

© Copyright International Business Machines Corporation 2001. All rights reserved.

US Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.

About this supplement

This supplement contains diagnostic and service information for the IBM PC Server Rack Enclosure and the IBM Rack enclosures:

IBM PC Server Rack Enclosure models:

Type 9306 19-inch and 24-inch Models:

4QS, 4QX, 9QS

9QX, 9TS, 9TX

IBM Rack enclosure models:

Type 9306 Models 200, 900

Type 9308 Models 42P, 42X, 42S, 42E, 4SA, 4SB (NetBAY42 Enterprise)

IBM NetBAY3 enclosure

IBM NetBAY3E enclosure

This supplement should be used with the related service information in the IBM PC Servers Hardware Maintenance Manual (part number 70H0751, form number S30H- 2501-01).

Important: This manual is intended for trained servicers who are familiar with IBM PC Server and IBM Server products.

Before servicing an IBM product, be sure to review “Safety information” on page 183.

Related publications

The following publications are available for IBM products. For more information, contact IBM or an IBM Authorized Dealer.

© Copyright IBM Corp. 2001

iii

For information about

See publication

 

 

PC Servers

IBM PC Servers Hardware Maintenance Manual

 

(S30H-2501)

 

 

PS/2 Computers

IBM Personal System/2 Hardware Maintenance

 

Manual (S52G-9971)

 

 

PS/ValuePoint Computers

IBM PS/ValuePoint Hardware Maintenance Service

 

and Reference (S61G-1423)

 

 

Laptop, Notebook, Portable, and

IBM Mobile Systems Hardware Maintenance

ThinkPad Computers (L40, CL57, N45,

Manual Volume 1 (S82G-1501)

N51, P70/P75, ThinkPad 300, 350, 500,

 

510, 710T, Expansion Unit, Dock I,

 

Dock II)

 

 

 

ThinkPad Computers (ThinkPad 340,

IBM Mobile Systems Hardware Maintenance

355, 360, 370, 700, 701, 720, 750, 755)

Manual Volume 2 (S82G-1502)

 

 

ThinkPad Computers (ThinkPad 365,

IBM Mobile Systems Hardware Maintenance

760)

Manual Volume 3 (S82G-1503)

 

 

Monitors (Displays) (February 1993)

IBM PS/2 Display HMM Volume 1 (SA38-0053)

 

 

Monitors (December 1993)

IBM Color Monitor HMM Volume 2 (S71G-4197)

 

 

IBM Monitors (P Series) (February

IBM Monitor HMM Volume 3 (S52H-3679)

1996)

 

 

 

IBM 2248 Monitor (February 1996)

IBM Monitor HMM Volume 4 (S52H-3739)

 

 

Disk Array technology overview and

Configuring Your Disk Array booklet (S82G-1506)

using the IBM RAID Configuration

 

Program

 

 

 

Installation Planning for Personal

Personal System/2 Installation Planning and

System/2 computers

Beyond (G41G-2927)

 

 

Installation Planning for Advanced

Advanced PS/2 Servers Planning and Selection

Personal System/2 Servers

Guide (GG24-3927)

 

 

iv Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Contents

About this supplement . . . . . . . . . . . . . . . iii

Related publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii

IBM PC Server/Enterprise rack enclosures 1

General checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Power checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Powering off the rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 IBM PC Server expansion rack models. . . . . . . . . . . . 5 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Server selector console . . . . . . . . . . . . . . . . . . . . . . . . . 6 Server selector unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Power distribution unit. . . . . . . . . . . . . . . . . . . . . . . . . 7 Cooling fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sliding trays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Sliding rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Keyboard tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Parts listing (Type 9306 – 19-inch) Models 9QS, 9TS and 9QX, 9TX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Parts listing (Type 9306 – 24-inch) Models 4QS, 4QX . 17

Type 9306 Model 200 . . . . . . . . . . . . . . . . . 21

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Side panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Selector switch locations . . . . . . . . . . . . . . . . . . . . . . . 22 Power Distribution Unit . . . . . . . . . . . . . . . . . . . . . . . 26 Blank bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Fixed shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Keyboard tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Installing a flat panel monitor rack mount kit. . . . . 29 Removing the existing flat panel monitor stand . . . 29 Installing the new monitor stand. . . . . . . . . . . . . . . . 31 Starting the system. . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Configuring the selector switch . . . . . . . . . . . . . . . . . 35 Switching among servers . . . . . . . . . . . . . . . . . . . . . . 36 Advanced selector switch functions . . . . . . . . . . . . . 37 Resetting the selector switch . . . . . . . . . . . . . . . . . . . 45 Making connections under power. . . . . . . . . . . . . . . 46 Parts Listing (Type 9306 Model 200). . . . . . . . . . . . . . . . 47

Type 9306 Model 900/910 . . . . . . . . . . . . . 51

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Parts listing (Type 9306 Model 900/910) . . . . . . . . . . . . 77

NetBAY 42 Enterprise Rack (Type 9308 Models 42P, 42X, 4SA, 4SB, 42S, 42E) . . 81

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Removing and installing panels . . . . . . . . . . . . . . . . 85 Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Removing and installing the top 6U portion of the rack

91

Installing the stabilizer bracket . . . . . . . . . . . . . . . . . 92

Attaching rack cabinets in a suite . . . . . . . . . . . . . . . 92 Installing L-channel support rails to rack mounting

brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Installing a server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Fixed shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Keyboard tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Monitor shelf. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Installing a flat panel monitor rack mount kit . . . . 103 Removing the existing flat panel monitor stand . . 103 Installing the new monitor stand. . . . . . . . . . . . . . . 105 Blank filler panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Parts listing (Type 9308 Model 42P, 42X) . . . . . . . . . . . 111

NetBAY3 enclosure . . . . . . . . . . . . . . . . . 115

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Casters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Foot pads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Front cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Device side rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Stacking NetBAY3 enclosures. . . . . . . . . . . . . . . . . . 118 Parts Listing (NetBAY3) . . . . . . . . . . . . . . . . . . . . . . . . . 121

NetBAY3E enclosure . . . . . . . . . . . . . . . . 123

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Casters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Front cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Device side rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 Stacking NetBAY3E enclosures . . . . . . . . . . . . . . . . 126 Parts listing (NetBAY3E). . . . . . . . . . . . . . . . . . . . . . . . . 127

IBM NetBAY console switch . . . . . . . . . . 129

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

Tool requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Installation overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Installing a console switch in a monitor shelf . . . . 132 Installing a console switch vertically in a rack. . . . 134 Installing a console switch horizontally in a rack . 137 Parts listing (NetBAY Console Switch). . . . . . . . . . . . . 139

NetBAY Power Distribution Units . . . . . . 141

NetBAY rack Power Distribution Unit introduction . 141 Tool requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Installation overview . . . . . . . . . . . . . . . . . . . . . . . . . 142 Installing devices vertically . . . . . . . . . . . . . . . . . . . 142 Installing a single device horizontally . . . . . . . . . . 144 Installing two devices horizontally . . . . . . . . . . . . . 146 Cabling your PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . 148

NetBAY front-end Power Distribution Unit introduction . 156

Tool requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 Installation overview . . . . . . . . . . . . . . . . . . . . . . . . . 157 Installing a single device vertically . . . . . . . . . . . . . 157 Installing two devices vertically . . . . . . . . . . . . . . . 160 Rack PDU specifications . . . . . . . . . . . . . . . . . . . . . . 164

© Copyright IBM Corp. 2001

v

Line cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

NetBAY server dual-cord Power Distribution Unit introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166

Tool requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Installation overview. . . . . . . . . . . . . . . . . . . . . . . . . 167 Installing devices vertically . . . . . . . . . . . . . . . . . . . 167 Installing a single device horizontally . . . . . . . . . . 169 Installing two devices horizontally . . . . . . . . . . . . . 171 Cabling your PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 Line cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181

Parts listing (Power Distribution Units) . . . . . . . . . . . 181

Related service information . . . . . . . . . . 183

Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 Safety notice (multi-lingual translations) . . . . . . . . 191 Safety inspection guide . . . . . . . . . . . . . . . . . . . . . . . 192 Handling electrostatic discharge-sensitive devices 193 Grounding requirements. . . . . . . . . . . . . . . . . . . . . . 194

Problem determination tips . . . . . . . . . . . . . . . . . . . . . . 194 Notices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Send us your comments! . . . . . . . . . . . . . . . . . . . . . . . . 196 Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197

vi Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

IBM PC Server/Enterprise rack enclosures

General checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Powering off the rack. . . . . . . . . . . . . . . . . . . . . . . . .

3

Power checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

 

 

General checkout

Use the following procedure for diagnosing keyboard, mouse, and video problems for the IBM PC Server Rack Enclosure and the IBM Rack enclosures (Type 9306 and Type 9308).

For power problems, see “Power checkout” on page 2.

Attention:

For Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX only:

Ensure that the voltage selector switch on each server installed in the server rack is set to 230 V ac.

For Models 200, 900 only:

Ensure that the voltage selector switch on each server installed in the server rack is set to the proper voltage as supplied by the Power Distribution Unit, PDU.

1.Check the following:

Ensure the external power cord is in good condition and properly connected to a known-good power source.

Ensure the internal power cables are in good condition and properly connected. (The internal power cables connect between the power distribution unit and the servers installed in the server rack.)

Ensure the following devices are powered on.

a.Power distribution unit

b.Server selector unit

c.All system units

d.Display

2.If the items/conditions specified in step 1. are not okay, correct the problem and verify that the server rack is operating correctly.

3.If the items/conditions specified in step 1. are okay, then, using the server selector keypad buttons, check the operation of the failing device for all of the servers that are installed in the rack.

4.Did the failure occur on more than one server?

NO: Go to the Hardware Maintenance manual for the server that was selected when the failure occurred. Disconnect the keyboard and mouse from the server selector unit and connect them directly to the failing server. Then, run the server diagnostic programs on the failing server.

If the problem still remains, disconnect the keyboard and mouse from the failing server and reconnect them to the server selector unit. Then, replace the server rack components in the following order until the problem goes away.

a.Device cable (connects between the server selector unit and the server that was selected when the failure occurred).

© Copyright IBM Corp. 2001

1

b.Server selector cable (connects between the server selector keypad and the server selector unit).

c.Server selector keypad.

d.Server selector unit.

YES: Power-off the server rack and replace the server rack components in the following order until the problem goes away. See “Powering off the rack” on page 3.

a.Device extender cable (connects between the device and the server selector unit)

b.Failing device

c.Server selector cable (connects between the server selector keypad and the server selector unit)

d.Server selector keypad

e.Server selector unit

Power checkout

Use the following procedure for diagnosing power problems for the IBM PC Server Rack Enclosure and IBM Rack enclosure (Type 9306).

Attention:

For Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX only:

Ensure that the voltage selector switch on each server installed in the server rack is set to 230 V ac.

For Models 200, 900 only:

Ensure that the voltage selector switch on each server installed in the server rack is set to the proper voltage as supplied by the Power Distribution Unit, PDU.

1.Check the following:

Ensure the external power cord is in good condition and properly connected to a known-good power source.

Ensure the internal power cables are in good condition and properly connected. (The internal power cables connect between the power distribution unit and the servers installed in the server rack.)

Ensure the following devices are powered on.

a.Power distribution unit

b.Server selector unit

c.All system units

d.Display

2.If the items/conditions in step 1. are not okay, correct the problem and verify correct operation of the server rack.

3.If the items/conditions specified in step 1. are okay, then, using the server selector keypad buttons, check for correct operation of all the servers installed in the rack.

4.Did the failure occur on more than one server?

No: Go to the Hardware Maintenance manual for the server that was selected when the failure occurred and run the server diagnostic programs. If the problem still remains, replace the power distribution unit.

2 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Yes: Power-off the server rack and replace the server rack components in the following order until the problem goes away. See “Powering off the rack” on page 3.

a.Power distribution unit fuse.

b.Power distribution unit.

Powering off the rack

Before performing service on the rack, follow this procedure to prevent personal injury and to avoid damaging the rack and the installed servers.

To power-off the IBM PC Server Rack:

1.Shut down and power-off all installed servers.

2.Power-off the server selector unit.

3.If a UPS system is installed in the rack, power-off the UPS system.

4.Disconnect power from the IBM PC Server Rack.

If the rack is plugged into a wall-mounted power supply, disconnect the power cord plug from the wall socket.

If the power cord is wired directly into the installed location's power supply, open the rear door of the rack cabinet and disconnect the power plug from the base of the power distribution unit.

IBM PC Server/Enterprise rack enclosures 3

4 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 IBM PC Server expansion rack models . . . . . . . . . . 5 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Server selector console . . . . . . . . . . . . . . . . . . . . . . . . 6 Server selector unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Power distribution unit . . . . . . . . . . . . . . . . . . . . . . . 7 Cooling fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sliding trays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Single latch rail tray . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Dual latch rail tray . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Sliding rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Keyboard tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Parts listing (Type 9306 – 19-inch) Models 9QS, 9TS and 9QX, 9TX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Parts listing (Type 9306 – 24-inch) Models 4QS, 4QX 17

Features

The 9306 IBM PC Server Rack Enclosure, models 4QS, 9QS, 9TS come in three primary models.

19-inch Quad Primary Server Rack, Model 9QS

19-inch Tri Primary Server Rack, Model 9TS

24-inch Quad Primary Server Rack, Model 4QS

A Quad Primary Server Rack can house up to four IBM PC Servers. The Tri Primary Server Rack can house up to three IBM PC Servers.

Both Quad and Tri Primary Server Racks provide a built in server selector which connects to one set of console devices (monitor, keyboard, and mouse.) The server selector works independently from the server's operating systems, enabling the connected servers to run different operating systems.

These IBM 9306 PC Server Rack Enclosure models are shipped preassembled and precabled.

IBM PC Server expansion rack models

Three optional IBM PC Server Rack Expansion models are available to expand the capacity of the IBM PC Server Rack Primary Enclosure. The optional IBM PC Server Rack Expansion models are:

19-inch Quad Expansion Rack, Model 9QX

19-inch Tri Expansion Rack, Model 9TX

24-inch Quad Expansion Rack, Model 4QX

The IBM PC Server Rack Expansion models allow the installation of up to four more servers using the Primary IBM PC Server Rack monitor, keyboard, and mouse.

Locations

The following sections contain information on specific equipment locations.

Note: For instructions on how to power-off the rack, see “Powering off the rack” on page 3.

© Copyright IBM Corp. 2001

5

Server selector console

To remove the Server Selector Console:

1.Power-off the rack.

2.Use an 1/8-inch allen wrench to remove screws.

3.Disconnect the server selector cable from the back of the server selector console.

4.Remove the server selector console from the cabinet.

 

Server

Monitor

Selector

Console

Bezel

 

Server

Server

Server

Selector

Selector

Selector

Keypad

Electronics

Cable

 

 

 

Server selector unit

The server selector unit is located in the upper rear of the rack cabinet. The server selector unit can only be accessed or removed from the rear of the IBM Rack cabinet.

CAUTION:

The server selector unit is heavy. You will need two people to safely remove the server selector unit. See “Safety notice (multi-lingual translations)” on page 191.

To remove the server selector unit:

1.Power-off the rack.

2.Unplug the keyboard, mouse, video cables, and the power cord.

3.Remove the server selector console.

4.With one person bracing the server selector unit from below, have the second person use a 5/16-inch wrench to remove the four nuts that secure the server selector unit to the rack cabinet.

5.Remove the server selector unit from the cabinet.

Note: When replacing the server selector unit, be sure that the Server Selector cable is fed through the indentation along the left side of the server selector unit.

6 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Server

 

 

 

 

Server

 

 

 

 

Selector

Selector

 

 

 

 

 

 

 

 

Unit

Cable

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

AC Power

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

Server Rack

Server

Server Selector

Monitor

Monitor

Unit On-Off

Connection

Connections

Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

V

V

V

V

V

V

V

V

O

G

G

G

G

G

G

G

G

N

A

A

A

A

A

A

A

A

O

1

2

3

4

5

6

7

8

K M

B O K M K M K M K M K M K M K M K M

O U 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8

Server Rack

 

Mouse

Server Keyboard

Connection

and Mouse

 

Server Rack

Connections

Keyboard

 

Connection

 

Power distribution unit

Note: For information and installation instructions for the IBM NetBAY Rack Power Distribution Units, see “NetBAY Power Distribution Units” on page 141".

Note: To remove the power distribution unit, you might need to remove the right side cabinet panel, the server installed in sliding tray 2 (in the primary IBM PC Server Rack), or sliding tray 5 (in the IBM PC Server Expansion Rack).

To remove the power distribution unit:

1.Power-off the rack.

2.Disconnect all power plugs from the power distribution unit.

3.Using a Phillips screwdriver, remove the four screws from the front of the power distribution unit.

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 7

Note: These screws are held in place by nuts and washers. Hold the nut while you are unscrewing the screw to prevent the nut and washer from falling into the bottom of the cabinet.

4.Remove the power distribution unit from the cabinet.

 

AC Power

 

Input

AC Fuse

 

Circuit

 

Breaker

 

115V AC

AC Power

Output

Power-On

 

Indicator

 

Voltage

 

Selection

 

Switch

 

230V AC

 

Power-On

 

Indicator

 

Cooling fan

To remove the cooling fan:

1.Power-off the rack.

2.Open the rear door of the rack cabinet.

3.Disconnect the power plug from the rear of the cooling fan.

4.Use a 5/16-inch wrench to remove the eight nuts that secure the cooling fan to the top of the rack cabinet.

5.Remove the cooling fan from the cabinet.

Note: When installing the fan, make sure that the green and yellow ground wire is attached to one of the top fan mounting screws and that the strain-relieving clamp is attached to another. The power cable should be secured by the strainrelieving clamp.

8 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Ground

Wire

Power

Plug

Sliding trays

Models 4QS and 4QX come with either single latch slide rails or dual latch slide rails. Single latch slide rails have a front latch release on the right rail only. Dual latch slide rails have a front latch release on both rails. The slide rail FRU number for the 24-inch rack replaces the single latch slide rail with the dual latch slide rail.

Note: If a server is installed on a tray being removed, first remove the server.

Single latch rail tray

To remove a sliding tray with single latch rails:

1.Power-off the rack.

2.Open the rear door of the rack cabinet and remove the pin 1 that secures the sliding tray to the cable management arm

3.Loosen the thumbscrews 2 on the sliding tray and fully extend the sliding tray.

4.Use a 3/32-inch allen wrench to remove the five screws 3 from the left side of the sliding tray.

5.Lift the rear locking tab 4 and push the sliding tray approximately two inches into the cabinet.

6.Release the forward locking tab 5. Then, while holding the sliding tray in place, use your other hand to grasp the outside sliding rail 6 and push it into the rack cabinet until it disconnects from the sliding tray.

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 9

Dual latch rail tray

To remove a sliding tray with dual latch rails:

1.Power-off the rack.

2.Open the rear door of the rack cabinet and remove the pin 1 that secures the sliding tray to the cable management arm.

3.Loosen the thumbscrews 2 on the sliding tray and fully extend the sliding tray.

4.Push in on the spring of the right rear locking tab 3 and push the sliding tray approximately two inches into the cabinet.

5.Release both left and right forward locking tabs 4. Then, while holding the sliding tray in place, push both left and right outside sliding rails 5 into the rack cabinet until it disconnects from the sliding tray.

Note: Left side view for 4 and 5 are not shown.

Sliding rails

This procedure is for single latch sliding rails and dual latch sliding rails.

For single latch sliding rails, the right rail is the one that has the front latch. The left rail does not have a front latch.

For dual latch sliding rails, the right rail is the one that has the rear latch. The left rail does not have a rear latch.

To remove the sliding rails:

1.Power-off the rack.

2.Remove the sliding tray that is attached to the sliding rails that you want to remove. See “Sliding trays” on page 9.

3.Use a 3/32-inch allen wrench to remove the four screws that secure each of the sliding rails to the rack cabinet.

10 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Note: You will need to adjust the position of the sliding rail in order to line up the access holes over the locations of the screws.

Keyboard tray

To remove the keyboard tray:

1.Power-off the rack.

2.Disconnect the keyboard and mouse cables from the keyboard and mouse extension cables.

3.Remove the keyboard and mouse from the keyboard tray.

4.Pull the keyboard tray straight out of the rack cabinet.

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 11

Parts listing (Type 9306 – 19-inch) Models 9QS, 9TS and 9QX, 9TX

This parts listing is for Models 9QS, 9TS and 9QX, 9TX

4

 

 

7

 

8

9

 

 

 

 

 

5

6

 

 

 

 

 

 

 

 

10

3

 

 

 

 

11

1

2

 

 

 

13

 

 

 

 

 

12

 

 

30

 

 

14

28

29

 

 

 

 

 

 

 

 

 

 

 

 

27

 

 

 

 

 

 

 

24

 

 

 

 

 

23

 

 

 

 

 

 

 

20

19

 

 

 

 

 

 

 

 

22

21

 

 

 

 

 

 

 

 

25

 

18

15

26

17

16

12 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Index

19-Inch Rack Enclosure (Type 9306)

FRU

1

Adapter Plate Options:

 

 

PS/2 Server 85/95

76H3733

 

Model 300

76H3734

 

Model 500, 700

76H3734

2

Monitor Stand

07H0061

3

Server Selector Cable

07H0036

4

Blank Bezel (9QX, 9TX Expansion units only)

76H0379

5

Monitor Bezel with button label

76H0378

6

Server Selector Keypad

07H0097

7

Monitor Housing (19-inch)

76H0377

8

Server Selector Unit Electronics

07H0034

 

See “Safety inspection guide” on page 192.

 

9

Internal Cables

06P6007

 

See Cable Kit Shelf Server

 

10

Cable Management Arm

76H0386

11

Cable Management Arm Single Server Tray

76H0387

12

Pin, Cable Management Arm

07H0089

13

Fan 220 V ac with Power Cord

07H0063

14

Latch, Rear Door

76H0376

15

Rear Door (19-Inch)

76H0373

15

Hinge Set for Rear Door

76H0389

16

External Power Cord:

 

 

Australia

14F1559

 

Europe

14F1554

 

Israel

14F1561

 

Italy

14F1560

 

New Zealand

14F1558

 

South America, India

14F1557

 

U.K./Denmark

14F1555

 

USA

14F1553

 

External Power Cord Option - 6 Ft.

07H0094

17

Left/Right Side Panel

76H0374

18

Caster

76H3626

19

NetBAY Rack Power Distribution Unit

09N9668

19

NetBAY Front-end Power Distribution Unit

09N9670

 

3-phase NEMA L21-30P line cord (200-250 Vac) for NetBAY Front-end PDU

00N7720

 

3-phase IEC 309-3P+N+Gnd line cord (380-415 Vac) for NetBAY Front-end PDU

00N7721

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 13

Index

19-Inch Rack Enclosure (Type 9306)

FRU

 

1-phase NEMA L5-30P line cord (100-127 Vac) for NetBAY Front-end PDU

00N7722

 

1-phase NEMA L6-30P line cord (200-240 Vac) for NetBAY Front-end PDU

00N7723

 

1-phase IEC 309-2P+Gnd line cord (200-240 Vac) for NetBAY Front-end PDU

00N7724

19

NetBAY Server Dual-cord Power Distribution Unit

09N9669

 

Hardware Kit for NetBAY Power Distribution Units

09N9671

 

Power Distribution Unit

07H0424

19

250 V Slow Blow Fuse

0303549

20

Keyboard Slides, (one pair)

07H0038

21

Leveling Foot (Qty. 1)

76H0390

22

Stabilizing Bar

76H0375

23

Keyboard Tray, 19-Inch

76H0381

24

Slide Rails, Server Tray (one pair)

07H0083

24

Slide Rails, Dual Tray (one pair)

76H0383

25

19-inch Front Compartment Door (19-Inch by 26-Inch) Includes Hinge Set and Screws

76H0371

26

Door Hinge Set

76H0372

27

Door Valance (9QX, 9TX, Expansion units only)

76H0380

28

Mouse Table

07H0079

29

Dual Server Tray

76H0382

29

Dual Server Shelf

76H0385

30

Single Server Tray

76H0384

 

19-Inch Single Slide Shelf for an Industry Standard 19-Inch Rack.

76H3628

 

Cable, SVGA-Video (15 Feet) Option

76H3736

 

Monitor Power Cable (connects from monitor to Power Distribution Unit)

07H0075

 

Rack Keyboard Cable (connects from Keyboard Drawer to Server Selector Unit)

07H0067

 

Rack Mouse Cable (connects from Keyboard Drawer to Server Selector Unit)

07H0069

14 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Rack Enclosure Kits (Type 9306)

FRU

Bolt-Together Kit (19-Inch to 24-Inch, 24-Inch to 19-Inch)

76G3627

19-Inch Attachment Bracket (2 each)

Screw 1/4-20 x 1/2 Button Head Socket Cap Allen (8 each)

Screw 1/4-20 x 1-1/4 Socket Cap (4 each)

Flanged Nut 1/4-20 (12 each)

24-Inch Attachment Bracket (4 each)

Cable Kit Shelf Server (12foot cables)

06P6007

Monitor Cable

Keyboard Cable

Mouse Cable

Internal Power Cable

Cable Kit Top Shelf Server (7-foot cables)

06P6006

Monitor Cable

Keyboard Cable

Mouse Cable

Internal Power Cable

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 15

Rack Enclosure Kits (Type 9306)

FRU

Miscellaneous Parts Kit

07H0057

Rack Nut/Holder 10-32 (8 each)

Keeper Nut 8-32 Zinc (8 each)

Keeper Nut 10-32 (6 each)

Screw 6-32 x 5/16 (2 each)

Screw 6-32 x 1/4 Button Head Socket Cap Allen (8 each)

Screw 10-32 x 3/8 Button Head Socket Cap (8 each)

Screw 6-32 x 3/8 Button Head Socket Cap (2 each)

Screw 1/4-20 x 1/2 Button Head Socket Cap (2 each)

Screw 8-32 x 1/4 Button Head Socket Cap Allen (4 each)

Screw 10-32 x 1/4 Button Head Socket Cap (2 each)

Screw 8-32 x 1/4 Button Head Socket Cap (8 each)

Pull-ring, 3-Inch (2 each)

Shoulder Screw 8-32 x 3/8 (2 each)

Standoff,.25 Hex, 6-32 FF,.5-Inch (2 each)

Screw 8-32 x 3/8 Button Head Socket cap (2 each)

Screw 10-24 x 1/4 Button Head Socket Allen (2 each)

Screw 10-24 x 5/16 Button head Socket Allen (2 each)

Keeper Nut 8-32 (2 each)

Nut 8-32 (2 each)

Captive Weld Nut (2 each)

Whiz-Lock Flange Nut 1/4-20 (2 each)

Keeper Nut 10-32 (2 each)

Bumpers (2 each)

Cable Ties (8 each)

Server Tray Interlock Kit

07H0091

Cam (1 each)

Spring (1 each)

16 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Parts listing (Type 9306 – 24-inch) Models 4QS, 4QX

This parts listing is for Models 4QS and 4QX.

4

6

7

8

 

10

11 12

5

9

 

 

 

13

14

1

2

3

 

 

30

29 28

27

26

23

 

 

15

 

 

 

 

 

19

 

22

21

18

 

 

 

20

 

24

 

17

16

25

 

 

 

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 17

Index

24-Inch Rack Enclosure (Type 9306)

FRU

1

Adapter Plate Options:

 

 

PS/2 Server 85/95

76H3733

 

Model 300

76H3734

 

Model 500, 700

76H3735

2

Monitor Stand

07H0061

3

Server Selector Cable

07H0036

4

Blank Bezel (4QX Only)

07H0066

5

Monitor Housing (24-Inch)

07H0065

6

Server Selector Keypad

07H0097

7

Rack Frame

N/A

8

Spacer (see Spacer Kit, right side at end of this FRU list)

07H0059

9

Server Selector Unit Electronics See "Safety Notice (Multi-lingual Translations) See “Safety

07H0034

 

notice (multi-lingual translations)” on page 191.

 

10

Internal Cables (see Cable Kit Top Shelf Server and Cable Kit Bottom Shelf Server)

 

11

Cable Management Arm

07H0087

12

Pin, Cable Management Arm

07H0089

13

Fan 220 V ac with Power Cord

07H0063

14

Rear Door Latch/Lock with Key and Bracket

07H0055

15

Rear Door (24-Inch)

07H0047

16

External Power Cord:

 

 

Australia

14F1559

 

Europe

14F1554

 

Israel

14F1561

 

Italy

14F1560

 

New Zealand

14F1558

 

South America, India

14F1557

 

U.K./Denmark

14F1555

 

USA

14F1553

 

External Power Cord Option - 6 Ft.

07H0094

17

Left/Right Side Panel

07H0049

18

NetBAY Rack Power Distribution Unit

09N9668

18

NetBAY Front-end Power Distribution Unit

09N9670

18

NetBAY Server Dual-cord Power Distribution Unit

09N9669

 

Hardware Kit for NetBAY Power Distribution Units

09N9671

18

Power Distribution Unit

07H0424

 

250 V Slow Blow Fuse

0303549

19

Keyboard Slides, 24-Inch (one pair)

07H0038

18 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Index

24-Inch Rack Enclosure (Type 9306)

FRU

20

Leveling Feet (Qty. 4)

07H0053

21

Stabilizing Leg

07H0051

22

Keyboard Drawer, 24-Inch (with Slides and Brackets)

07H0077

23

Slide Rails, Server Tray (one pair)

07H0083

24

24-Inch Front Compartment Door (24-Inch by 26-Inch)

07H0058

25

Door Hinge Set

07H0045

26

Door Valance (4QX Only)

07H0068

27

Handle, Server/Keyboard Tray

07H0085

28

Server Tray

07H0081

29

Mouse Table

07H0079

30

Shelf, Server Tray, 24-Inch

07H0093

 

Cable, SVGA-Video (15 Feet)

76H3736

 

Monitor Power Cable (connects from monitor to Power Distribution Unit)

07H0075

 

Rack Keyboard Cable (connects from Keyboard Drawer to Server Selector Unit)

07H0067

 

Rack Mouse Cable (connects from Keyboard Drawer to Server Selector Unit)

07H0069

Rack Enclosure Kits 24-inch (Type 9306)

FRU

Bolt-Together Kit (19-Inch to 24-Inch, 24-Inch to 19-Inch) – includes: 19-Inch Attachment

76G3627

Bracket (2 each); Screw 1/4-20 x 1/2 Button Head Socket Cap; Allen (8 each); Screw 1/4-20

 

x 1-1/4 Socket Cap (4 each); Flanged Nut 1/4-20 (12 each); 24-Inch Attachment Bracket (4

 

each)

 

Cable Kit Shelf Server (12 foot cables) – includes: Monitor Cable; Keyboard Cable; Mouse

07H0073

Cable; Internal Power Cable

 

Cable Kit Top Shelf Server (7 foot cables) – includes: Monitor Cable; Keyboard Cable;

07H0071

Mouse Cable; Internal Power Cable

 

Miscellaneous Parts Kit – includes: Rack Nut/Holder 10-32 (8 each); Keeper Nut 8-32 Zinc

07H0057

(8 each); Keeper Nut 10-32 (6 each); Screw 6-32 x 5/16 (2 each); Screw 6-32 x 1/4 Button

 

Head Socket Cap; Allen (8 each); Screw 10-32 x 3/8 Button Head Socket Cap; (8 each);

 

Screw 6-32 x 3/8 Button Head Socket Cap; (2 each); Screw 1/4-20 x 1/2 Button Head

 

Socket Cap; (2 each); Screw 8-32 x 1/4 Button Head Socket Cap; Allen (4 each); Screw 10-

 

32 x 1/4 Button Head Socket Cap; (2 each); Screw 8-32 x 1/4 Button Head Socket Cap; (8

 

each); Pull-ring, 3-Inch (2 each); Shoulder Screw 8-32 x 3/8 (2 each); Standoff, .25 Hex, 6-32

 

FF, .5-Inch (2 each); Screw 8-32 x 3/8 Button Head Socket cap; (2 each); Screw 10-24 x 1/4

 

Button Head Socket Allen; (2 each); Screw 10-24 x 5/16 Button head Socket Allen; (2 each);

 

Keeper Nut 8-32 (2 each); Nut 8-32 (2 each); Captive Weld Nut (2 each); Whiz-Lock Flange

 

Nut 1/4-20 (2 each); Keeper Nut 10-32 (2 each); Bumpers (2 each); Cable Ties (8 each)

 

Server Tray Interlock Kit – includes: Cam (1 each); Spring (1 each)

07H0091

Spacer Kit, Right Side – includes: Rack Joiner (8 each); Spacer, Top and Bottom, 34-Inch (1

07H0059

each); Spacer, Body 70-Inch (2 each); Screw 10-32 x 3/8 Button Head Socket cap; (8 each);

 

Screw 1/4-20 x 1/2 Button Head Socket cap; (8 each); Whiz-Lock Flange Nut 1/4-20 (8

 

each); Screw 6-32 x 3/8 Button Head Socket Cap; (6 each)

 

Type 9306 Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX 19

20 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Type 9306 Model 200

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Side panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Selector switch locations . . . . . . . . . . . . . . . . . . . . . 22 Power Distribution Unit. . . . . . . . . . . . . . . . . . . . . . 26 Blank bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Fixed shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Keyboard tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Installing a flat panel monitor rack mount kit . . . 29

Removing the existing flat panel monitor stand . 29 Installing the new monitor stand . . . . . . . . . . . . . . 31 Starting the system. . . . . . . . . . . . . . . . . . . . . . . . . . 35 Configuring the selector switch . . . . . . . . . . . . . . . 35 Switching among servers . . . . . . . . . . . . . . . . . . . . 36 Advanced selector switch functions . . . . . . . . . . . 37 Resetting the selector switch. . . . . . . . . . . . . . . . . . 45 Making connections under power . . . . . . . . . . . . . 46 Parts Listing (Type 9306 Model 200) . . . . . . . . . . . 47

Features

The IBM NetBAY22, Type 9306, Model 200 Rack enclosure is a 22-U high (38.5-inch) industry-standard, 19-inch rack that houses and controls multiple IBM PC Servers/IBM Servers and related equipment.

Locations

The following sections contain information on specific equipment locations.

Note: For instructions on how to power-off the rack, see “Powering off the rack” on page 3.

Side panel

Locked Unlocked

© Copyright IBM Corp. 2001

21

Selector switch locations

Note: For information about the IBM NetBAY Console Switch, see “IBM NetBAY console switch” on page 129.

Two

One

M

Rese

t

K

 

M

Aux.

K

 

Three

 

 

Two

 

ree

M

Th

K

 

M

K

M

K

Two

Th

ree

M

K

M

K

Three

M K

Important

Information

1 0

Figure 1. Selector switch in monitor compartment

22 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks