Honeywell V8944L, V8944B, V8944N, V8943C, V8944C User Manual

...
5 (1)

V4943/V8943B,C,N;

V4944/V8944B,C,L,N

Regulating Diaphragm Gas Valves

PRODUCT DATA

FEATURES

APPLICATION

The V4943/V8943B and N (single stage) and V4944/V8944B and N (two stage) are solenoid-operated diaphragm valves suitable for natural gas only. The V4943/V8943C and V4944/V8944C and L are solenoid-operated diaphragm valves suitable for Liquefied Petroleum (LP) gas only. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters.

Models are available for natural or liquid petroleum (LP) gases.

Valve models L, N are rapid opening (less than six seconds) and fast closing, and are available for LP and natural gases, respectively.

Line voltage with two-wire thermostat or controller is used with V4943; V8943 is used with 24V thermostat or controller.

V4944 is used with line voltage dual-stage thermostat or controller; V8944 is used with 24V dual-stage thermostat or controller.

Slow opening B,C valve models are available for natural and LP gases respectively.

Valve closes on power failure; recommended for final shutoff service.

Valve closing time: 2 seconds maximum at 7 inches wc inlet pressure.

Valves rated for 0.5 pound per square inch (psi) (3.4 kPa).

Leadwires and cover for electrical conduit connections are provided.

 

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

6

Operation ..........................................................................

9

Checkout and Troubleshooting .........................................

10

Service Information ..........................................................

12

65-0214-08

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES

SPECIFICATIONS

Models:

All models are solenoid-operated regulating diaphragm gas valves. Details are shown in Table 1.

Table 1. Model Availability.

 

 

 

Power

 

 

Maximum

 

 

 

 

 

 

 

 

 

Operating

Opening

 

 

Number

 

Voltage

 

Consumption

 

 

 

 

 

and

Maximum

(VA

Pipe Size

Thread

Pressure

Time

Pressure

Type of

of Lead-

Model

Frequency

Current

Maximum)

(in.)

Type

psi

kPa

(sec.)

Regulation

Gas

wires

 

 

 

 

 

 

 

 

 

 

 

 

V4943B

120V

0.055A

6.6

1, 1-1/4,

NPT

0.5

3.4

3 to 25

Single

Naturala

2

 

(+10%,

 

 

1-1/2, 2

 

 

 

 

stage

 

 

 

-15%),

 

 

 

 

 

 

 

 

 

 

V4943N

 

 

1, 1-1/4,

 

 

 

<6

 

 

 

 

60 Hz

 

 

1-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V8943B

24V,(+10%,

0.363A

9.0

1, 1-1/4,

 

 

 

3 to 25

 

 

 

 

-15%)

 

 

1-1/2, 2

 

 

 

 

 

 

 

 

50/60 Hz

 

 

 

 

 

 

 

 

 

 

V8943C

 

 

1, 1-1/4

 

 

 

 

 

LP

 

 

 

 

 

 

 

 

 

 

 

 

 

V8943N

 

 

 

1, 1-1/4,

 

 

 

<6

 

Naturala

 

 

 

 

 

1-1/2

 

 

 

 

 

 

 

V4944B

120V

0.077A

9.0

 

 

 

3 to 25

Two stage

 

3

 

 

 

 

 

 

(+10%,

 

 

 

 

 

 

 

 

 

 

V4944C

 

 

 

 

 

 

 

 

LP

 

 

-15%)

 

 

 

 

 

 

 

 

 

 

V4944L

 

 

1-1/4

 

 

 

<6

 

 

 

60 Hz

 

 

 

 

 

 

 

 

V4944N

 

 

 

1, 1-1/4,

 

 

 

 

 

Naturala

 

 

 

 

 

1-1/2, 2

 

 

 

 

 

 

 

V8944B

24V

0.470A

11.3

 

 

 

3 to 25

 

 

 

 

 

 

 

 

 

 

 

(+10%,

 

 

 

 

 

 

 

 

 

 

V8944C

 

 

1, 1-1/4,

 

 

 

 

 

LP

 

 

-15%)

 

 

1-1/2

 

 

 

 

 

 

 

 

50/60 hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V8944L

 

 

1, 1-1/4

 

 

 

<6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V8944N

 

 

 

1, 1-1/4,

 

 

 

 

 

Naturala

 

 

 

 

 

1-1/2, 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a Includes natural gas, mixed air-natural gas, LP gas-air.

Flow Capacity: See Table 2.

Table 2. V4/8943 and V4/8944 Flow Capacity.

 

CSA

 

Regulation Capacities

 

Certified

Btuh per

0.64 sp gr Natural Gas

 

1.0 in. pd

1000 cfh

 

 

 

Maximum

Minimum

Pipe Size

Natural

Natural

(in.)

Gas cfh

gas

cfh

cfh

 

 

 

 

 

1

1,000

1,000,000

1,000

300

 

 

 

 

 

1-1/4

1,600

1,600,000

1,600

480

 

 

 

 

 

1-1/2

2,300

2,300,000

2,300

780

 

 

 

 

 

2

3,000

3,000,000

3,000

870

 

 

 

 

 

Valve Pattern:Straight-through, non offset.

Valve Body Material:Die-cast aluminum.

Electrical Terminations:1/4 in. (6 mm) spade terminals (quick connects). Leadwires and cover for electrical conduit connections are provided.

Valve Closing Time: On power failure, a maximum of 2 seconds at 7 in. wc inlet pressure.

Ambient Temperature Ratings: -40°F to +150°F (-40°C to +66°C).

Maximum Fluid Temperatures: 150°F (66°C).

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).

2.Honeywell Customer Care 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

3.http://customer.honeywell.com or http://customer.honeywell.ca

International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

65-0214—08

2

 

 

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES

Pressure Reference Port Vent: 5/16–24 UNF internal

Weight:

 

 

tapping.

 

 

1 in., 1-1/4 in. valves: 4 lb (1.8 kg).

 

Standard Factory Settings: See Table 3.

1-1/2 in., 2 in. valves: 5 lb (2.3 kg).

 

 

 

 

Dimensions: See Fig. 1.

 

 

 

 

 

 

Table 3. Factory Settings and Regulation Ranges.

 

 

 

 

 

 

 

 

 

Natural Gas (i.e. B, N models)

LP Gas (i.e. C, L models)

 

 

 

 

 

 

Firing stagesa

 

Factory Setting

Adj. Rangeb

Factory Setting

Adj. Rangeb

Low Fire:

 

 

 

 

 

 

 

 

 

 

 

Standard Models

 

0.8” wc

0.8” to 2” wc

1.4” wc

1.4” to 4.2” wc

 

 

 

 

 

 

Special Models (Group 1)

 

1.6” wc

1.6” to 4.2” wc

 

 

 

 

 

 

 

 

Special Models (Group 2)

 

0.8” wc

0.8” to 2” wc

 

 

 

 

 

 

 

 

Special Models (Group 3)

 

0.8” wc

0.8” to 2” wc

 

 

 

 

 

 

 

 

High Fire:

 

 

 

 

 

 

 

 

 

 

 

Standard Models

 

3.5” wc

3” to 4.5” wc

10” wc

8.8” to 11.5” wc

 

 

 

 

 

 

Special Models (Group 1)

 

3.5” wc

3” to 4.5” wc

 

 

 

 

 

 

 

 

Special Models (Group 2)

 

3.5” wc

1.4” to 4.2” wc

 

 

 

 

 

 

 

 

Special Models (Group 3)

 

5” wc

4.0” to 7” wc

 

 

 

 

 

 

 

 

aV4943 is a single-stage valve, please refer to “High Fire” for spring specifications.

bDo not adjust or operate valve outside of the specified ranges.

CAUTION

DO NOT adjust or operate valve outside of the specified ranges. Valve will not regulate or work properly.

Special Models (Group 1): V4944B1075, V4944B1083, V4944B1091, V8944B1092, V8944B1100, V8944B1118

Special Models (Group 2): V4944B1109, V4944B1125, V4944B1141, V4944B1166; V4943B1050, V4943B1068, V4943B1076, V4943B1084

Special Models (Group 3): V4944B1117, V4944B1133, V4944B1158; V4943B1092, V4943B1100, V4943B1118

Approvals:

Underwriters Laboratories Listed: File Number MH1639

CSA Certified: Report Number C2030020 (except those listed as Special Models Group 2 and Special Models Group 3) Commonwealth of Massachusetts Product Certification Number: G1-12-05-22

Mounting Position:

Accessories:

Standard Position: Upright (horizontal).

AT72D Transformer (40 VA) for all 24 Vac models.

NOTE: V4944B1059, V4944N1052 and V4944N1060 can

204480 Vent Pipe Adapter

 

be mounted upright to 90 degrees from the

 

upright on the horizontal axis with respect to the

 

inlet connection.

 

3

65-0214—08

Honeywell V8944L, V8944B, V8944N, V8943C, V8944C User Manual

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES

SIDE VIEW

TOP VIEW

6 (152)

6-9/16 (167)

FOR 1, 1-1/4

6 OR (152)

7-3/8 (187) FOR 1-1/2, 2

INLET

OUTLET

PRESSURE

PRESSURE

TAP

TAP

 

Fig. 1. V4943/44 and V8943/44 dimensions in in. (mm).

PRESSURE REGULATOR ADJUSTMENT CAPS

ATMOSPHERIC PRESSURE REFERENCE PORT WITH INTERNAL VENT LIMITER

M23375

Gas Valve Sizing

1.Check the burner nameplate for:

a.the type of gas used, and

b.the gas flow capacity. The capacity will be listed in British thermal units per hour (Btuh) or in cubic feet per hour (cfh).

2.Contact the local gas utility for information regarding:

a.the specific gravity (sp gr) and

b.the Btu per cubic foot (Btucf) for the type of gas used.

3.Find the capacity in cf/h. If the capacity is listed in Btu, convert to cf/h using the following formula:

Capacity in cfh = Btuh (burner nameplate)

Btu/cf (gas utility)

4.For gases with specific gravities other than 0.64, multiply the burner cf/h using the proper conversion factor in Table 4.

Table 4. Gas Conversion Factors.

Type of Gas

sp gr (average)

Multiply cfh by

Manufactured

0.60

0.968

Mixed

0.70

1.046

LP-Propane

1.53

1.546

LP-Butane

1.98

1.759

5.Use the corrected burner capacity in cfh when determining the gas valve size in Figs. 2–9.

6.Determine the maximum pressure drop across the valve and draw a vertical line at this pressure in Figs. 2–9.

7.At the point of intersection of the vertical line and the curve, draw a horizontal line to intersect the flow (capacity) scale. The point of intersection indicates the capacity that can be obtained with the maximum pressure drop.

8.If the capacity at the maximum pressure drop is insufficient, use the capacity vs. pressure drop curve for the next larger valve size and repeat steps 6 and 7.

 

 

1 INCH V4/8944B/N REGULATION AREA

 

 

100

 

 

WC)

10

PO > 2 IN.

 

DROP (IN.

 

 

ANY PO

 

PRESSURE

1

PO < 2.5 IN.

 

 

 

 

 

 

 

0.1

 

 

 

100

1000

10000

 

 

FLOW NATURAL GAS (CFH)

M23376

Fig. 2. Capacity vs. pressure drop of Natural Gas curves for 1 in. valve.

65-0214—08

4