Honeywell RA89A, R847A, R845A, R182J, RA832A User Manual

...
5 (1)

TRADELINE®

R182J, R482J, R845A, R847A, RA89A, RA832A Switching Relays

Application

These relays can be used for a variety of switching applications. Typically they provide control of lineor low-voltage devices by a low voltage controller. See Table 1.

TABLE 1—SWITCHING RELAY SPECIFICATIONS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

Contact

 

 

 

 

 

Voltage

Relay Coil

 

 

Voltage

Switch

Control

(Vac at

Current

Ratings (A)

Models

Application

(50/60 Hz)

Action

Circuit

50/60 Hz)

(A)

AFL

ALR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R182J

For 24V thermostat

120

Dpdt

3-wire

24

0.40a

7.4

44.4

 

control of line voltage

240

 

 

 

 

3.7

22.2

 

devices.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R482J

Controlled by a line

120

 

2-wire

120

0.08

7.4

44.4

 

voltage controller

208/240

 

 

208/240

0.04

3.7

22.2

 

 

 

 

 

 

 

 

 

 

 

 

 

R845A

For hot water zone control

120

Dpst

 

24

0.40

7.4

44.4

 

systems or spst control of

 

 

 

 

 

 

 

 

two separate loads.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R847A

Provides switching for

120

 

 

 

 

22

100

 

high-current loads such as

240

 

 

 

 

10

50

 

cooling compressors.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RA89A

For switching one line

120

Spst

 

 

 

10.2

61.2

 

voltage load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RA832A

For switching two line

120

Dpst

 

 

 

7.4

44.4

 

voltage loads with a

240

 

 

 

 

3.7

22.2

 

common power source.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a IMPORTANT: The transformer on the R182 can overheat when used with a series 20 thermostat if the total resistance of the thermostat circuit exceeds 2.5 ohms. If the measured resistance of the thermostat (including thermostat wire and thermostat contact resistance) exceeds 2.5 ohms, add a 100 ohm, 10 watt resistor between the W and R terminals. Table 2 gives maximum thermostat wire runs; if longer runs are necessary, measure the resistance or add a 100 ohm, 10 watt resistor across terminals W and R.

TABLE 2—LENGTH OF WIRE.

 

 

 

 

 

AWG

 

 

Length of Run

Wire

Total Wire

to Thermostat

Size

Length

(Wires)

(Number)

Feet

Meters

Feet

Meters

 

 

 

 

 

22

120

38.0

60

18.0

 

 

 

 

 

20

200

61.0

100

30.5

 

 

 

 

 

18

300

91.5

150

45.5

 

 

 

 

 

16

500

152.5

250

76.0

 

 

 

 

 

14

800

244.0

400

122.0

 

 

 

 

 

J.H. • Rev. 101-94 • ©Honeywell Inc. 1994 • Form Number 69-0791—3

Honeywell RA89A, R847A, R845A, R182J, RA832A User Manual

Installation

WHEN INSTALLING THIS PRODUCT…

1.Read these instructions carefully. Failure to follow instructions can damage product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Make sure installer is a trained, experienced service technician.

4.After completing installation, use these instructions to check out product operation.

WARNING

ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.

Transformer core not bonded.

Disconnect power supply before wiring to prevent electrical shock or equipment damage.

MOUNTING

For replacement, mount the relay in the same location as the old relay. If this is a new installation, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service.

NOTE: To reduce the possible transformer hum and relay noise that is sometimes amplified by mounting surfaces such as sheetmetal, plasterboard, and similar materials, place rubber or felt washers between the case and the mounting surface.

1.Position the relay and mark the mounting holes. See Fig. 1.

2.Start a screw for the keyhole type mounting hole in the upper right corner. Screw it down within about 1/8 in. [3 mm] of the surface.

3.Hang the relay on the screw, position the case, and start the bottom screw.

4.Tighten both screws.

WIRING

All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow any instructions furnished with the controlled equipment.

IMPORTANT: The switching relay terminals are approved for use with copper wires only.

See Figs. 2 through 9 for hookup diagrams for these relays. When two or more devices are to be controlled in parallel, the total current must not exceed the relay load rating. Fig. 11 is an internal view of the RA832A showing terminal locations and barriers.

Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay.

Fig. 1—Approximate mounting dimensions in in. [mm].

 

 

 

 

 

 

4

1

[108]

 

 

 

 

 

1

5

[29]

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

7

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

[48]

 

 

 

 

 

 

 

 

 

 

 

 

7

[22] DIAMETER

 

 

 

 

 

3

[2] DIAMETER

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

32

 

 

KEYHOLE TYPE

 

 

 

2

[13] DIAMETER

MOUNTING HOLE

 

 

 

 

 

 

 

 

 

 

4

1

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

[114]

 

 

 

 

 

 

 

 

 

 

 

 

 

5

1

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

[133]

 

 

 

 

3

1

[89]

 

 

3

[10]

 

 

 

7

 

 

 

 

2

 

 

 

8

 

3

[10]

 

[6] DIAMETER MOUNTING HOLE

 

 

 

 

 

8

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

215

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

[75]

 

 

 

 

 

 

 

 

 

 

1

7

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

[48]

 

 

 

25

[20]

13

[35]

 

 

KNOCKOUT FOR

 

 

 

32

 

 

8

 

 

 

 

1/2 (13) CONDUIT (3)

M3823

Fig. 2—Internal schematic and typical hookup for RA89A.

 

 

 

LOW VOLTAGE (CLASS 2)

 

 

 

 

 

 

 

2-WIRE THERMOSTAT

 

 

 

 

 

T

 

T

RA89A (SPST)

 

2

 

 

RA89A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JUMPER REMOVED

 

 

 

 

 

2

 

1

3

4

 

 

JUMPER

 

 

 

 

 

 

2

 

1

3

4

L2

1

L1

 

TO LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT

 

 

 

 

 

 

 

CONTROLLER

 

1

 

 

 

 

 

(IF USED)

 

 

L2

1

L1

TO LOAD

 

 

 

 

 

 

HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.

2 COMPLETE WIRING AS SHOWN ABOVE.

M3819

 

 

69-0791—3