Honeywell TH8110U User Manual

0 (0)

TH8110U Touch Screen

Programmable Thermostats

INSTALLATION INSTRUCTIONS

APPLICATION

The TH8110U Universal Programmable Thermostats provide electronic control of 24 Vac heating and cooling systems or 750 mV heating system. See Table 1 for a general description.

Table 1. TH811 Thermostats Description.

 

 

 

 

 

 

Model

Power

Changeover

System Selection

Fan Selection

Comments

Method

 

 

 

 

 

 

 

 

 

 

 

 

TH8110U

Batteries or

Automatic or

Heat-Off-Cool-Auto

On-Auto-Circ

System and Fan

 

common wire

manual

 

 

selection vary based on

 

 

selectable

 

 

system type

 

 

 

 

 

 

RECYCLE NOTICE

If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After completing installation, use these instructions to check out the product operation.

Selecting Location

Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.

NO

 

YES

 

NO

NO

5 FEET

[1.5 METERS]

M19925

Fig. 1. Selecting thermostat location.

Do not install the thermostat where it can be affected by:

Drafts or dead spots behind doors and in corners.

Hot or cold air from ducts.

Radiant heat from sun or appliances.

Concealed pipes and chimneys.

Unheated (uncooled) areas such as an outside wall behind the thermostat.

® U.S. Registered Trademark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2004 Honeywell International Inc. •

• All Rights Reserved

69-1700

 

 

TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

Installing Wallplate

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.

1.Position and level the wallplate (for appearance only).

2.Use a pencil to mark the mounting holes.

WALL

WIRES THROUGH WALL

AND WIRE SLOT

WALL ANCHORS (2)

MOUNTING

HOLES

MOUNTING

SCREWS (2)

M19916

Fig. 2. Mounting wallplate.

3.Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.

4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.

5.Insert the mounting screws into the holes and tighten.

WIRING (FIG. 5-11)

All wiring must comply with local electrical codes and ordinances.

1.Select set of terminal identifications (Table 2) that corresponds with system type (conventional or heat pump) in Fig. 3.

2.Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.

3.Securely tighten each screw.

4.Push excess wire back into the hole.

5.Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

HEAT PUMP

CONVENTIONAL

Y2

Y2

RC

RC

L

 

R

R

E

 

W

O/B

AUX

W2

Y

Y

S1

S1

G

G

S2

S2

C

C

 

SCREW TERMINALS

M19951

Fig. 3. Selecting terminal identifications for system type.

Table 2. Selecting Terminal Identifications for System Type.

 

 

 

 

Wallplate

Wiring

System Type

Terminal

Diagram

Identifications

Reference

 

 

 

Standard Heat/Cool

Conventional

5, 6

 

 

 

Heat Only

Conventional

7

 

 

 

Heat Only with Fan

Conventional

8

 

 

 

Heat Only Series 20

Conventional

9

 

 

 

Cool Only

Conventional

10

 

 

 

Heat Pump with No

Heat Pump

11

Auxiliary Heat

 

 

 

 

 

M19917

Fig. 4. Inserting wires in terminal block.

IMPORTANT

Use 18 gauge thermostat wire.

69-1700

2

Honeywell TH8110U User Manual

TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

 

 

CONTACTOR

 

 

 

 

HEAT RELAY

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19895

Fig. 5. Typical hookup of conventional single-stage heat and cool system with single transformer (1H/1C conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

 

 

CONTACTOR

1

 

 

 

 

HEAT RELAY

C

 

 

 

 

 

 

R

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2REMOVE FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19896

Fig. 6. Typical hookup of conventional single-stage heat and cool system with two transformers (1H/1C conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

HEAT RELAY

 

 

 

 

OUTDOOR/INDOOR

 

 

 

TEMPERATURE

 

 

 

SENSOR

 

 

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19897

Fig. 7. Typical hookup of heat-only system (1H conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

 

 

SENSOR

 

HEAT RELAY

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19898

Fig. 8. Typical hookup of heat only system with fan (1H conventional).

3

69-1700

TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

 

CONVENTIONAL

Y2

RC

2

 

 

 

R

 

1

 

 

 

 

W

 

 

R

W2

Y

 

 

C

S1

G

 

 

 

S2

C

 

 

 

3

 

 

 

 

OUTDOOR/INDOOR

 

W

B

R

TEMPERATURE

 

 

 

 

 

SENSOR

 

 

 

SERIES 20

 

 

 

 

 

 

 

MOTOR OR

 

 

TR

TR

VALVE

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M19899

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

 

RELAY

 

 

 

 

OUTDOOR/INDOOR

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

CONTACTOR

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19900

 

Fig. 10. Typical hookup of cool only system

Fig. 9. Typical hookup of heat only Series 20 system.

(1C conventional).

 

 

HEAT PUMP

 

Y2

RC

1

 

2

R

L

R

C

 

 

E

O/B 3

 

AUX

Y

 

S1

G

OPTIONAL

 

 

S2

C

24 VAC

COMMON

 

 

CONNECTION

 

 

FAN RELAY

4

 

 

OUTDOOR/INDOOR

CHANGEOVER

COMPRESSOR

TEMPERATURE

VALVE

 

SENSOR

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.

4OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS.

WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M19903

Fig. 11. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).

Powering the Thermostat

There are two different ways to power the thermostat:

Batteries (three AAA alkaline).

24 Vac Common wire.

Wiring 24 Vac Common

Wire the common side of the transformer to the C screw of the thermostat wallplate. When installing in a single transformer system, keep jumper wire between the R and Rc screws. When installed in a two-transformer

system, use the common from the cooling transformer to connect to C screw and remove the jumper wire between the R and Rc screws.

Inserting Batteries (Optional)

If not using a 24 Vac Common to power the thermostat, install three AAA alkaline batteries (included) in the back of the thermostat. Make sure the positive and negative terminals are oriented correctly, as marked on the device. See Fig.12.

69-1700

4

Loading...
+ 8 hidden pages