Honeywell L6064A User Manual

4 (1)
L6064A Universal Two Speed Fan and Limit Controllers
PRODUCT DATA
APPLICATION
These combination warm air fan and limit controllers are suitable for all types of forced air heating systems. The controllers have 2 switches with 3 individually ad­justable set points. One switch opens the limit circuit if the plenum temperature exceeds the preset safety limit; most models reset automatically. The other switch changes fan speeds. On all the L6064 the fan speed is switched from low to high and vice versa according to the plenum temperature. The fan speed is switched to low if the plenum temperature falls below the fan off set point. All the L6064 models are intended for use with conventional warm air systems. All models may be used as limit controls by wiring only the limit side. Limit controls are suitable for line voltage, low volt­age, or millivoltage circuits.
INSTALLATION When installing this product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Follow furnace or burner manufacturer’s instruc­tions, if available. Do not exceed the ratings and limi­tations given in this section.
ELECTRICAL RATINGS: NOTE: The electrical rating is at maximum case tem-
perature of 88
O
C (190OF). Use high temperature insu­lating material, or a mounting bracket when mounting surface temperature exceeds 88OC (190OF).
CAUTION
!
1. Disconnect power supply before beginning in­stallation to prevent electrical shock or equipment damage.
2. When connecting cable or conduit to control, avoid straining the control case.
LOCATION
If this is a replacement installation, locate the L6064 in the same location as the control being re­placed. The L6064 sensing tube length should be the same as the old control. If this is a new installa­tion, the element should be installed only by a trained, experienced service technician according to the furnace manufacturer’s instructions. The ele­ment must not touch any internal part of the furnace.
MOUNTING
The device may be mounted as follows: All models -- Surface or Bracket.
SURFACE MOUNTING
Hole in plenum should be just large enough to accommodate the 20 mm (3/4 in.) diameter element tube.
1. Remove cover by squeezing sides and pulling off. Insert element in plenum and mark location of mounting holes. Make sure the case is snug against the plenum before marking the mounting holes.
2. Punch or drill holes for mounting screws.
3. Place insulation between plenum and case if necessary, or use a mounting bracket.
4. Fasten controller securely with mounting screws.
90OC field wiring may be required. NOTE: For applications under DIN or BEAB juris­diction ambient temperatures must not exceed
O
70
C (158OF).
FAN
24 Vac
LIMIT
2
Full Load (Amps) Locked Rotor
(Amps) Max. Amp.
FAN LOW
6 14
120 Vac 240 Vac
FAN HIGH
LIMIT
FAN LOW
8
48
84
FAN HIGH
3
LIMIT
4
7
42
24
Pilot Duty: 2 A at 24 Vac; 0.25 to 12 Vdc. (Limit) Maximum Combined Connected Load: 2000 VA. ac. Load capacity at terminal points must not exceed the rated capacity of connected wire at its rated insulation temperature. 75
O
C minimum field wiring is required.
FURNACE
MA
T
RIAU
THERMO-ISOLANT
SI N
CESSAIRE
PL
NUM DE
L’APP
AREIL
DE
CHAUFF
AGE
2697C
!
VIS DE MONT
AGE
APPAREIL
DE
CHAUFF
AGE
PL NUM
SUPPORT RIGIDE
50
100
150
200
250
ON/OFF
FAN LIMIT
FAN
LIMIT
BORNES-
PRESSION POUR
CONDUCTEURS
STANDARDS
(4)
PRISE FEMELLE
POUR LE
RACCORDEMENT
D’UNE BORNE ¸
COSSE M LE DE
6,4 MM (1/4 PO)
(4)
PROTØGE-FILS
POUR RETIRER UN
CONDUCTEUR
STANDARD,
POUSSER AVEC UN
TOURNE-VIS ET
TIRER LE FIL
CONDUCTEUR
STANDARD DE
COMMANDE
D’ QUIPEMENT
CONDUCTEUR AVEC
BORNE ¸ COSSE M LE
DE 6,4 MM (1/4 PO)
(POUSSER LA COSSE AU
FOND DE LA CAVIT .)
Low
CONNECTEUR
M LE RAPIDE
POUR LE
RACCORDEMENT
D’UNE BORNE ¸
COSSE FEMELLE
DE 6,4 MM (1/4 PO)
CONDUCTEUR
AVEC BORNE
EMBROCHABLE
M LE DE 6,4 MM
(1/4 PO) (POUSSER
LA COSSE AU FOND
DE LA CAVIT .)
LOAD
LINE
HIGH LINE
STRIPE GAUGE
ERS
BORNE-PRESSION
VERROUILLABLE
ORIFICE
POUR FIL
PLENUM
HEAT INSULATING MATERIAL IF
NEEDED
2697C
Fig. 1 - Surface mounting L6064. Requires hole 20 mm (3/4 in.) diameter in the plenum.
RIGID BRACKET MOUNTING
All models of the L6064 may be mounted using a rigid bracket. The rigid bracket requires a hole 20 mm (3/4 in.) diameter for mounting.
1. Use bracket as a template to mark the location of mounting holes in plenum. Drill or punch holes for mounting screws.
2. Fasten bracket in place with screws furnished. Tighten the screws securely.
3. Insert element tube through bracket, straighten controller, and fasten by tightening setscrew.
WARNING
!
Be sure screw strikes tube frame and does not strike inner sensing element.
WIRING
Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. All wiring must comply with local electrical codes and ordinances. See Fig. 5 for typical hookups.
1. To remove the slotted knockouts, bend down and break off with a long hose pliers. See Fig. 3.
Fig. 3 - Removing slotted knockouts.
2. Pass wires through bushing before connecting.
3. Connect wire to push-in terminals, and insert the bushing into knockout slot.
PUSH-IN TERMINALS
1. No. 14, 16, or 18 solid or No. 14 or 16 fused stranded
wire may be connected to the terminals.
2. Strip insulation from wires the distance shown by the strip guage on the controller.
3. Solid or solder dipped wire may be inserted by push­ing into the terminal holes. If stranded wire is used, in­sert a small screwdriver into the slot next to the termi­nal. Push in and hold while inserting wire in terminal. Then remove screwdriver.
All wires must be clear of rotating scaleplate.
IMPORTANT
RIGID BRACKET
SETSCREW
Fig. 2 - Rigid bracket mounting requires a hole 20 mm (3/4 in.) diameter for mounting.
FURNACE
PLENUM
FEMALE RECEPTACLE FOR CONNECTION OF
6.4MM (1/4 ") MALE FLAG TERMINAL
(4)
STANDARD WIRE PUSH IN CONNECTORS
(4)
MALE
QUICKCONNECT
FOR CONNECTION
OF 6.4MM (1/4")
FEMALE FLAG
TERMINAL
LEADWIRE WITH
1/4 IN. (6.4MM)
MALE FLAG
TERMINAL (FORCE
FLAG TO BOTTOM
OF CAVITY)
WIRING GUARD
50
FAN LIMIT
ON/OFF
100
200
150
LINE
FAN
HIGH LINE
Low
250
LOAD
LIMIT
STRIPE GAUGE
ERS
TO RELEASE
STANDARD WIRE -
PUSH SCREW
DRIVER IN AND PULL
WIRE OUT
STANDARD
WIRE TO
CONTROLLED
EQUIPMENT
LEADWIRE WITH 1/4 IN.
(6.4 MM) MALE SPADE
TERMINAL (FORCE
FLAG TO BOTTOM OF
CAVITY)
Fig. 4 - Internal view of L6064 showing use of screwdriver to connect or disconnect wires at push-in terminals. NOTE: Because the dial turns when the element temperature changes, the lettering on the dial may not be horizontal.
2
PUSH-IN
LOCK
TERMINAL
HOLE
FOR WIRE
A
L6064
LIMIT
FAN
SIDE
SIDE
(HOT)
L1
1
L2
LOW SPEED
HIGH SPEED
L1
(HOT)
2
1
ADD DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
TO CONTROL LOW VOLTAGE EQUIPMENT
2
1
L2
Fig. 5 - A: Limit in low voltage circuit. B: Limit in line voltage circuit.
OPERATION
During normal operation, the L6064 sensing element will rotate and close the fan switch for high speed once plenum temperature reaches the factory-set fan on set point.
SETTINGS AND ADJUSTMENTS
CAUTION
!
When adjusting the fan and limit setting levers, hold the scalepale dial to keep it from turning and straining the sensing element.
Move the setting levers to the control points recom­mended by the burner or furnace manufacturer. Use gentle finger pressure.
1. Move the FAN OFF (continuous low speed) setting lever to the temperature at which the fan is to run low speed for continuous air circulation. All L6064 models - FAN ON (heating fan speed) range is from 8.3
O
C (15OF) above the FAN OFF (continuous low speed) setting to 17OC (30OF) below the LIMIT OFF setting.
2. Move the LIMIT setting lever to the temperature at which the high limit switch is to break the primary con­trol circuit. All L6064 models - limit range is 35
O
to 250
F).
O
C to 120OC (95OF
LIMIT SETTING ADJUSTMENT
These controllers have a limit stop which prevents the limit indicator lever from being adjusted beyond the equip­ment manufacturer’s specifications.
1. Push the small end of Limit Adjust Tool (196722) through hole in scaleplate (located at caution marking) to depress the stop disc not more than 1/16 in. (1.6 mm) to release stop lock (Fig. 10). Stop disc is on back of scaleplate.
2. While depressing the stop disc, insert the long end of Limit Adjust Tool next to limit stop (Fig. 10) and move the stop to desired setting.
If the L4064 is a replacement con­trol, high limit stop setting should be the same as that of the control being replaced.
(Move stop clockwise to lower the setting, counterclockwise to raise it.) Then remove the limit stop adjust tool.
3. Set the LIMIT OFF lever to the temperature at which the high limit switch is to open to stop the burner. If the high limit stop has been properly set, the LIMIT OFF lever should be as high as the stop permits.
B
L6064
LIMIT
FAN
SIDE
SIDE
LIMIT STOP
ADJUSTABLE
LIMIT STOP
O
C)
TOOL
O
F
2
24V
1
LOW SPEED
HIGH SPEED
SCALEPLATE
CAUTION
DO NOT ROTATE - HOLD DIAL
WHEN SETTING POINTERS
50
FAN
AN
F
OFF
OFF
100
ON
FAN OFF SET POINT LEVER
FAN ON SET
POINT LEVER
HOMEOWNER: THIS IS A "SAFETY STOP". DO NOT ALTER
1
150
L1
120V
TO RELEASE STOP, PRESS STIFF WIRE
IN HOLE
250
200
LIMIT SET POINT LEVER (FACTORY-SET AT 200
L2
(93
Fig. 6 - Changing the high limit stop.
CHECKOUT
Always conduct a thorough checkout immediately follow­ing completion of the installation. Operate the system through at least one complete cycle to ensure that the sys­tem operates as intended, especially with respect to the proper function of the limit control. The recommended method of checking out the limit con­trol function without disturbing any of the furnace manu­facturer’s fan or limit settings is as follows:
1. To stimulate fan motor failure, a broken fan belt, or a plugged filter, remove the belt driving the fan. On direct drive fans disconnect the wiring to the fan motor - at the motor terminal panel - and insulate any live conductors which might result.
2. Turn the thermostat to the highest setting to ensure that the burner will run continuously.
3. Watch the operation of the furnace to be sure that the limit control shuts off the burner when the plenum tem­perature reaches the limit setting, and that the fan motor continues to operate. On direct drive fans check to be sure that voltage is evident on the disconnected leads to the fan motor when the limit stops the burner.
4. If the installation checks out satisfactorily, replace the fan belt-or reconnect any direct drive fan wiring-and lower the thermostat temperature adjustment to the normal set­ting.
5. If the installation does not check out satisfactorily, recheck the wiring, correct any wiring discrepancies, and repeat items 1 through 4. If the installation cannot be made to function properly DO NOT LEAVE THE FURNACE OPERATIONAL, PARTICULARLY IF THE LIMIT OR FAN CONTROLS DO NOT FUNCTION CORRECTLY. RE­MOVE THE FUSE IN THE CIRCUIT POWERING THE FURNACE until assistance can be enlisted to correct the installation.
3
95C-10617B 1
Loading...
+ 5 hidden pages