Honeywell F120, F120A1015, F120A1007, F120A User Manual

0 (0)
Honeywell F120, F120A1015, F120A1007, F120A User Manual

F120

Room Air Cleaning System

SPECIFICATION DATA

SUPPLY

MODULE

RETURN

MODULE

BLOWER

MODULE

M13442

APPLICATION

The F120 Room Air Cleaning System is designed to collect particles by circulating room air through a media filter. When equipped with an optional CPZ module, the system also adsorbs gaseous contaminants and odors.

The F120 exhaust feature is used to maintain the space at a negative pressurization relative to adjacent spaces to prevent contaminants and odors from moving into nearby areas.

The air supply and return design of the F120 allows air contaminants to be filtered at the center of the room with the filtered air returned toward the sides of the room for maximum room air cleaning.

The Honeywell Trademark is used under license from Honeywell Intellectual Properties, Inc. by Air-Pure Systems.

Honeywell International Inc. makes no representations or warranties with respect to this product.

FEATURES

Specifically designed for use in offices, hospitals, medical clinics, childcare centers, schools, conference rooms, copy centers, laboratories, cafeterias, and hospitality business.

Ultra-quiet operation allows the system to be used in sound sensitive areas such as conference rooms, offices, classrooms and libraries.

Modular design of air supply and return allows maximum flexibility when planning the appropriate air recirculation pattern to maximize overall system performance.

Special return module filter removes both particulates and gaseous contaminants from the air stream.

Convenient roomside service for all filters.

Easy-to-change prefilter extends the media filter life.

Blower module can be mounted remotely from the room to further reduce sound levels.

Two-speed fan motor allows selecting high or low airflow speeds.

Optional exhaust feature allows installations to maintain the space at a negative pressure with respect to surrounding areas to prevent contaminants and odors from moving into nearby areas.

Installation is ideally suited to rooms with either two- by-four or two-by-two foot drop ceiling panels, but can be installed in any wall or ceiling that allows ducting space.

68-3042-2 Revised 11-07

F120 ROOM AIR CLEANING SYSTEM

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

Model:

F120 consists of:

—two filtered return modules with a return grille, prefilter, and

—either a 99.97% HEPA filter or a 95% DOP filter and CPZ module;

—four air supply modules with supply grilles; —a blower module with a two-speed blower, four

recirculating air supply openings, four recirculating air return openings and an optional exhaust opening;

—75 ft (23m) of six-inch diameter flexible duct; 75 ft (23m) of eight-inch diameter flexible duct;

Air Flow Capacity:

—mounting hardware kit consisting of 12 mounting brackets; 40 ft (12m) of 12-gauge high-tensile strength wire; six standard T- bar mounts; duct tape;

—seven duct collar straps.

Color:

Blower Housing: Unpainted galvanized steel.

Return and Supply Grilles: Off-white

Electrical Ratings:

 

 

120 Vac, 60 Hz

240 Vac, 60 Hz

 

 

Fan Speeda

Fan Speeda

 

 

II (high)

I (low)

II (high)

I (low)

Current

(A)

7.0

5.5

3.5

2.8

Power

(W)

800

695

800

695

aOff is “O”.

 

 

Efficiency

 

 

Air Vol cfm

 

 

Particulates at 0.3

VOC/Odors

Gas, VOC, Odor

Air Vol cfm

Model

Voltage

micron (DOP Test)

(First Pass Average)

Control Module (2)

(cu m/hr)

(cu m/hr)a

F120A 1023

120 Vac 60 Hz

95%

85%

CPZ

900 (1530)

1050 (1780)

 

 

 

 

 

 

 

F120A 1031

120 Vac 60 Hz

99.97%

900 (1530

1000 (1700)

 

 

 

 

 

 

 

F120A 1015

120 Vac 60 Hz

b

b

b

 

 

 

 

 

 

 

aWith exhaust option installed.

bPurchase filters separately.

Filters:

HEPA: High efficiency particulate air (HEPA) filter is 99.97 percent efficient for 0.3 micron particulates when measured with Military Standard 282 DOP test.

DOP: Hospital-grade DOP filter is 95 percent efficient for 0.3 micron particulates when measured with Military Standard 282 DOP test.

CPZ: Sorbent modules contain 11 pounds of sorbent. Adsorbs higher molecular weight hydrocarbons and oxidizes acid gases and lower molecular weight hydrocarbons.

Ambient Temperature Rating:

Shipping and Storage: -20°F to +150°F (-29°C to +66°C). Operating: Ambient temperatures ≥90°F (32°C).

Can tolerate 104°F (40°C) for brief periods.

Sound Output Rating at 3.3 ft (1m):

High Speed: 52 dBA (below ASHRAE noise criteria (NC) curve specifications for NC45 over speech recognition frequency range of 500 to 2000 Hz).

Low Speed: 45 dBA (below ASHRAE noise criteria (NC) curve for NC35 over speech recognition frequency range of 500 to 2000 Hz).

Installation Weight:

Blower Module: 63 lb (28.6 kg).

Supply Module: (4 required): 8 lb (3.6 kg).

Return Module without filter (2 required): 24 lb (10.9 kg). 95% DOP Filter/CPZ Module (2 required): 21 lb (9.5 kg). 99.97% HEPA Filter (2 required): 10 lb (4.5 kg).

Shipping Weight:

F120 with 95% DOP Filter and CPZ Module: 207 lb (94 kg). F120 with 99.97% HEPA Filter: 182 lb (83 kg). F120A1015: 152 lb (69 kg).

F120A1007: 70 lb (32 kg).

Dimensions:

See Fig. 1.