Honeywell C7189U User Manual

5 (1)

C7189U Remote Indoor Sensor

(USE WITH VISIONPRO® THERMOSTATS)

INSTALLATION INSTRUCTIONS

APPLICATION

This indoor sensor is designed to sense temperature at a remote location and send this information to the VisionPRO Thermostat. This sensor can be used as a stand alone sensor or as part of an averaging network. Once a remote indoor temperature sensor is connected to the thermostat, the thermostat's sensor is no longer used. The thermostat's installer setup should be modified to tell the thermostat that remote indoor temperature sensor(s) have been used. The Inside temperature reading on the thermostat's display will be the remote sensor(s) temperature location(s).

M24055

Fig. 1. C7189U Remote Indoor Sensor

SPECIFICATIONS

Operating Ambient Temperature Range:

45 to 88°F (7.2 to 32°C).

Display Range:

0 to 99°F (-18 to 37°C).

Sensor Accuracy:

+/-1.5°F at 70°F (+/-.84 at 21°C)

Operating Relative Humidity:

5% to 95% non-condensing.

Finish:

White.

Resistance Characteristics:

Negative temperature coefficient (NTC). Resistance decreases as the temperature increases.

Dimensions in inches (mm):

1 1/2 (38) wide x 2 1/4 (57) high x 3/4 (19) deep.

Distance:

Maximum distance between thermostat and sensor is 200 feet.

Must be installed by a trained, experienced technician

Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Check the specification in this booklet to verify that this product is suitable for the application.

Always test for proper operation after installation

69-1710EFS-1

C7189U REMOTE INDOOR SENSOR

INSTALLATION

Installation Tips

Install the sensor about 5 feet (1.5m) above the floor in an area with good air circulation at average temperature. Maximum distance between remote sensor and the thermostat is 200 feet. See Fig. 2.

CAUTION

Electrical Hazard

Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

YES

NO

NO

5 FEET

(1.5 METERS)

NO

M24115

Fig. 2. Typical location for C7189U Sensor.

Remote Sensor Wallplate Installation

Remove the cover from the remote sensor as shown in Fig. 3.

1.Pull wires through wire hole.

2.Position wallplate on wall, level and mark screw hole positions with pencil.

3.Drill holes at marked positions, then tap in supplied wall anchors.

4.Place wallplate over anchors, insert and tighten mounting screws. See Fig. 4.

M24056

Fig. 3. Remove the cover.

M24057

Fig. 4. Mount wallplate to wall.

69-1710EFS-1

2

Honeywell C7189U User Manual

C7189U REMOTE INDOOR SENSOR

WIRING

The sensor can be used to provide one remote sensor (see Fig. 6) or as a temperature averaging network with multiple sensors connected (see Fig. 7). The thermostat is not part of the average network.

CAUTION

ELECTRICAL HAZARD.

Can cause electrical shock or equipment damage. Disconnect power before wiring.

1.Run the wire cable from the thermostat to the remote sensor location.

2.Loosen screw terminals, insert wires into terminal block (polarity does not matter), then retighten screws.

3.Push excess wire back into the wall opening.

4.Plug the wall opening with non-flammable insulation to prevent drafts from affecting the sensor operation and replace the cover on the remote sensor.

5.Connect the two wires to the thermostat's remote sensor terminals (polarity does not matter) and replace the thermostat back onto the wallplate. See Fig. 6.

M24116

Fig. 5. Terminal block wiring.

 

 

 

C7189

 

 

3

2

 

 

 

Y2

RC

 

1

 

R

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2IF MORE THAN ONE C7189 REMOTE SENSOR IS REQUIRED, REFER TO FIGURE 7.

3WIRES MUST HAVE A CABLE SEPARATE FROM THE

THERMOSTAT CABLE.

M19972A

Y2

 

 

2

2

1

1

C7189

S2

C7189

 

 

 

C7189

C7189

Y2

 

 

2

 

1

12

2C7189 C7189 C7189

C7189 C7189 C7189

Fig. 6. Wiring a single C7189U Sensor.

C7189 C7189 C7189

1 SENSORS MUST BE ARRANGED IN THIS CONFIGURATION TO OPERATE CORRECTLY.

2 WIRES MUST HAVE A CABLE SEPARATE FROM THE

THERMOSTAT CABLE.

M19973

Fig. 7. Wiring Multiple C7189U Sensors.

OPERATION

Once a remote indoor temperature sensor is connected to

.

the thermostat, the thermostat's sensor is no longer used.

 

The thermostat's installer setup should be modified to tell

 

the thermostat that remote indoor temperature sensor(s)

 

have been used. The Inside temperature reading on the

 

thermostat's display will be the remote sensor(s)

 

temperature location(s). See Fig. 8.

 

TUE

FAN

CHANGE FILTER UV LAMP HUMIDIFIER PAD

Inside

Set To

 

AUTO

Heat On

SYSTEM

Following

 

Schedule

HEAT

 

 

AM

SCHED HOLD CLOCK SCREEN MORE

M19974

Fig. 8. Inside Temperature Reading on TH8000 Series Thermostat.

3

69-1710EFS-1

C7189U REMOTE INDOOR SENSOR

CHECKOUT

For best results, allow the sensor to absorb the air moving through the room for a minimum of twenty minutes before taking a resistance measurement.

1.Use an accurate thermometer (+/-1ºF[0.5ºC]) measure the temperature at the sensor location.

2.Remove one wire from one of the sensor's wiring terminals. Use an ohmmeter to measure the resistance across the sensor. Verify the sensor accuracy with the temperature/resistance in Table 1.

CALIBRATION

The sensor is calibrated at the factory and cannot be recalibrated in the field.

Table 1. Sensor Resistance at Room Temperature.

Room Temperature

Ohms of

°F

°C

Resistance

 

 

 

40

4.4

22537

42

5.6

21516

 

 

 

44

6.7

20546

 

 

 

46

7.8

19626

 

 

 

48

8.9

18754

 

 

 

50

10.0

17926

 

 

 

52

11.1

17136

 

 

 

54

12.2

16387

 

 

 

56

13.3

15675

 

 

 

58

14.4

14999

 

 

 

60

15.6

14356

 

 

 

62

16.7

13743

 

 

 

64

17.8

13161

 

 

 

66

18.9

12607

 

 

 

68

20.0

12081

 

 

 

70

21.1

11578

 

 

 

72

22.2

11100

 

 

 

74

23.3

10644

 

 

 

76

24.4

10210

 

 

 

78

25.6

9795

 

 

 

80

26.7

9398

 

 

 

82

27.8

9020

 

 

 

84

28.9

8659

 

 

 

86

30.0

8315

 

 

 

88

31.1

7986

 

 

 

90

32.2

7672

 

 

 

92

33.3

7372

 

 

 

94

34.4

7086

 

 

 

96

35.6

6813

 

 

 

98

36.7

6551

 

 

 

100

37.8

6301

 

 

 

Automation and Control Solutions

 

 

 

 

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

 

 

 

1985 Douglas Drive North

35 Dynamic Drive

 

 

 

Golden Valley, MN 55422

Scarborough, Ontario M1V 4Z9

 

 

 

 

 

 

http://yourhome.honeywell.com

 

 

 

 

 

 

 

 

® U.S. Registered Trademark

© 2005 Honeywell International Inc. Patents Pending.

69-1710EFS-1 M.S. Rev. 10-05

Loading...
+ 8 hidden pages