ADEMCO LYNXR Series
Security Systems
LYNXR/LYNXR24 and LYNXR-EN
Installation and Setup Guide
AWAY
OFF
STA Y
AUX
LIGHTS ON
RECORD
LIGHTS OFF
STATUS
TEST
VOLUME
CODE
NO DELAY
BYPASS
PLAY
CHIME
FUNCTION
DELETE
ESCAPE
ADD
SELECT
ARMED
READY
4
5
6
7
8
9
0
#
1
2
3
K5963V3bx 5/04 Rev. A
–2–
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations f or the Location of Fir e and Burglary Det ection Devices Help Provide
Proper Cover age for the Protec ted Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and plac ement of smoke/hea t detectors, we sub scribe to the recomm endations
contained in the National Fire Protection Association's (NFPA) Standa rd #72 noted below.
• Earl y warning fire detection is bes t achieved by the installation of fire detection equipment in a ll rooms and areas of
the household as f ollows: For minimum p rotection a smoke detector sh ould be installed outsid e of each separate sleepi ng
area, and on ea ch additional floor of a multi-floor famil y living unit, includin g basements. The installa tion of smoke
detectors in kitchens, attics (finished or unfinished), or in garages is not no rmally recommended.
• For ad ditional protection the NFPA recommen ds that you install heat
or smoke detectors in the living room, dining
room, bedroom(s), kitche n, hallway(s), attic, furnace room, utility and st orage rooms, basements and attache d garages.
In addition, w e recommend the f ollowing:
• In stall a smoke detector insi de every bedroom where a smoker s leeps.
• In stall a smoke detector insi de every bedroom where som eone sleeps with the do or partly or completely clos ed. Smoke
could be blocked by th e closed door. Also, an al arm in the hallway outside ma y not wake up the sleeper if the door is
closed.
• In stall a smoke detector insi de bedrooms where electrical appliances (such as portabl e heaters, air conditioners or
humidifiers) are used.
• Install a smoke detector at both ends of a hallw ay if the hallway is more than 40 fe et (12 meters) long.
• In stall smoke detectors i n any room where an ala rm control is located, or in any room where a larm control connection s
to an AC source or ph one lines are made. If dete ctors are not so located, a fir e within the room could pre vent the control
from reporting a fire or an i ntrusion.
THIS CONTROL COMPLIE S WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF F IRE NOTIFICATION APPLIANCES.
DINING
KITCHEN
BEDROOM
BEDROOM
.
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BEDROOM BEDROOM
BEDROOM
BEDROOM
LIVING
ROOM
TV ROOM
DINING
LIVING ROOM
LIVING ROOM
BASEMENT
BEDROOM BEDROOM
BEDROOM
CLOSED
DOOR
GARAGE
KTCHN
KITCHEN
TO
BEDROOM
01000-002-V0
Recommendations For Proper Intrusion Protection
• For prop er intrusion coverage, sensors s hould be located at every possible poin t of entry to a home or premises. This
would include any skylig hts that may be present, and the upper windows in a multi-leve l building.
• In additio n, we recommend that radio back up be used in a security system. This w ill ensure that alarm signals c an be
sent to the alarm mon itoring station in the event that the tel ephone lines are out of order (ala rm signals are normally
sent over the phone l ines, if connected to an alar m monitoring station).
–3–
Table of Contents
SYSTEM FEATURES ...............................................................................................................................................4
MOUNTING THE CONTRO L..................................................................................................................................5
WIRING CONNECTIONS ........................................................................................................................................6
AC POWER AND BACKUP BA TTERY...................................................................................................................9
INSTALLING WIRELESS ZONES ........................................................................................................................11
MECHANICS OF PROGRAMMING .....................................................................................................................14
ZONE RESPONSE TYPE DEFINITIONS ............................................................................................................15
DATA FIELD DESCRIPTIONS .............................................................................................................................17
✻55 ENABLING THE 5842 WIR LESS DIALER ..................................................................................................25
✻56 ENHANCED ZONE PROG RAMMING MODE .............................................................................................27
✻80 DEVICE PROGRAMMING MENU MODE ...................................................................................................31
✻81 ZONE LIST MENU MO DE.............................................................................................................................34
✻83 ENHANCED SEQUENTIAL MODE .............................................................................................................35
✻84 ASSIGN ZONE VOICE DESCRI PTORS .......................................................................................................38
✻85 RECORD CUSTOM VOICE D ESCRIPTORS ................................................................................................40
VOICE PROMPT PROGRAM MING......................................................................................................................41
REMOTE PROGRAMMING /CONTROL (DOWNLOADING) .............................................................................45
SYSTEM OPERATION ...........................................................................................................................................47
TESTING THE SYSTEM ........................................................................................................................................53
SYSTEM COMMUNICATIO N ...............................................................................................................................54
TROUBLESHOOTING GUID E .............................................................................................................................56
CONTACTING TECHNICAL SUP PORT..............................................................................................................58
REGULATORY AGENCY STA TEMENTS ...........................................................................................................59
SPECIFICATIONS ..................................................................................................................................................60
LYNXR/LYNXR24 PRO GRAMMING DEFAULT TABLES .................................................................................61
LYNXR-EN PROGRAMMI NG DEFAULT TABLES ............................................................................................62
INDEX ......................................................................................................................................................................65
LIMITATIONS OF THIS SYSTEM ST ATEMENT...............................................................................................69
WARRANTY ............................................................................................................................................................70
SUMMARY OF CONNEC TIONS DIAGRAM .......................................................................................................71
–4–
System Features
U
U U
U
L
L L
L
LYNXR and LYNXR-EN are n ot intended for UL985 Household Fire appli cations unless a 24-hour backup
battery (P/N LYNXRCHKIT -HC) is installed.
Powerline Carrier Devices a re not UL Listed for fire or burglary functions and ar e intended for home
automation.
The LYNXR-Series c ontrols are self-contained, rechargeable wireless cont rol/communicators that fea ture easy
installation and usage. A built-in speaker prov ides voice annunciation of system status along with voice descriptors of
each zone (LYNXR-EN if prog rammed). The following illustratio n highlights the main features of th is system.
AWAY
OFF
STA Y
AUX
LIGHTS ON
RECORD
LIGHTS OFF
STATUS
TEST
VOLUME
CODE
NO DELAY
BYPASS
PLAY
CHIME
FUNCTION
DELETE
ESCAPE
ADD
SELECT
ARMED
READY
4
5
6
7
8
9
0
#
1
2
3
ZONES and DEVICES
• 1 hardwire zone
• Up to 24 wireless zones
(5800 Series Transmitters)
• Up to 16 wir eless button zones
• Up to 8 Powerline Carrier Devices
• Supports wireless keypads
8 USER CODES
• Installer code
• Master code
• 5 Secondary codes
• Duress code
• 3 Panic functions
OTHER FEATURES
• Exit error feature (detects differ ence between an
actual alarm and exit alarm caused b y leaving a
door open after the exit delay expires)
• Event log st ores up to 84 events
• Macro/ 1-bu tton paging
• RF Jam Detection
• Remote phone con trol
• Compatibl e with 5842 Wireless Dialer
• Compatible wi th encrypted (high-security) devic es
ALARM OUTPUT
• Built-in sounder
• Piezo output
(30mA max.)
• Bell output
(120mA max. )
• Steady output for
burglary/panic
• Temporal pulse
output for fire alarms
• Long Range
Radio/Alarm audio
verification
PROGRAMMING
• Options stored in EEROM
• Can be uploaded, downloaded or
controlled via IBM-compatible
computer using Compass
downloader software and sp ecified
HAYES modem
• Voice Prompt programming mode
COMMUNICATION
• Ademco Low Speed
• Sescoa/Radionics
• Ademco Express
• Ademco Contact ID
• Paging feature
SYSTEM POWER
• Primary Power: Ademco
1332/1332X10 Plug -in Transformer,
110VAC to 9VAC, 15VA ou tput
(1332CN i n Canada)
• Backup batt ery: Six 1.2V
rechargeable nickel-metal hydride
batteries.
FEATURES
• Real-time Cloc k display and Fixed-Word display
• Message Center (for user recorded messages)
• Voice announcement of system and zone status
• Voice chime
• Alarm Cloc k
• Reminder
• X-10 Scheduling
• Latch Key Re ports
• Automatic Sta y Arming
• Remote Phone Control
• “Follow Me” Reminder and System Announcements
SPECIAL FEATU RES
LYNXR24
• 24-hour backup
LYNXR-EN
• Two-way voice communication
• Speaker phone operation
–5–
Mounting the Control
Wall Mounting
The illustration below sho ws the front assembly separat ed from the back plate.
!
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the
front assembly board.
Certain features differ be tween the LYNXR/LYNXR24 and the LYNXR-EN model s. Verify the specific model
being installed p rior to programming the system .
DISCONNECT
THIS END ONL Y!
01009-003-V0
MXXXX
K5108
RED WIRE
MARKING
16
1
LOCKING TABS
PC BOARD
PART NUMBER
LOCATION
PC BOARD
PART NUMBER
LOCATION
Desktop Mounting
If desired, an opti onal mounting base (model LY NX-DM, purchased separately) al lows the LYNXR-Series control s to be
used on a desktop.
ADD
ESCAPE
DELETE
SELECT
AWAY
OFF
STAY
AUX
01009-004-V1
WIRE ENTRY
KNOCKOUT
(1 of 3)
1. Separate the front assembly from the
back plate by pressing on the two
locking tabs at the t op of the unit.
2. Carefully disconnect t he ribbon cable
from the front assembly, leaving the
ribbon cable connected to the
terminal block PC board. The back
plate contains the terminal block for
making wiring connec tions.
3. Mount the back plate to a st urdy wall,
feeding the field wiring through the
appropriate openings in the back
plate.
4. After wiring connectio ns are made,
carefully reconnect th e ribbon cable to
the front assembly PC board
connector (properly aligning t he red
wire).
5. Before closing the assembly, verify
which LYNXR model is be ing installed
by checking the model number printed
on the PC Boards. ( Example:
SALYNXREN indicates the unit bei ng
installed is a LYNXR-EN .)
6. Snap the front assembly to the back
plate so it is secured by th e locking
tabs.
1. S lide the control panel onto the
mounting base loc king tabs
.
2. Bring all wiring through the bottom of
the mounting base, using one of the
three wire entry locations, before
making connections to t he control
panel.
3. Use tie-wraps to secure the wiring to
the built-in wire loops as nee ded. Use
the two supplied screws to secure the
control panel to the mo unting base.
–6–
Wiring Connections
Wiring Overview
The following summarizes the c onnections required. Refer to the Wiring Conne ctions paragraph and the Summary of
Connections diagram on the inside back cover when making connections.
MXXXX
K5108
01009-005-V0
Wiring Connections
1. Make Earth Ground Connection - The designate d earth ground terminal (1) must be terminated in a go od earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a non-c orrosive metal strap (copper is recommended) to the pipe t hat is electrically
connected and secured t o which the ground lead.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most e lectrical supply stores.
a. Connect terminal 1 to a good earth ground.
EARTH GROUND
See Earth Ground paragraph.
PHONE LINES
Use either the plug -in jacks or
the screw terminals.
HARDWIRE ZON E
Supports 1 EOLR superv ised zone using either closed
circuit or open circuit sensors.
SOUNDERS
The system includes a built-in sounder in t he master keypad. If
desired, an external bell or piez o sounder can be connected.
Bell: Use a 6-14V bell with maximu m current drain of 120mA.
Piezo: Use a 6-14V piezo sounder with maximum curre nt drain of
30mA.
This control complies wi th NFPA requirements for tempora l pulse
sounding of fire notification applia nces.
Temporal pulse sounding for a fire alarm consists of the fo llowing:
3 pulses – pause – 3 p ulses – pause – 3 pulses. . .
POWERLINE CAR RIER DEVICES
Supports up to 8 Powerline Carrier
Devices for turning on/off lights and
appliances. Requir es the use of an
ADEMCO 1332X10 transform er.
AC TRANSFORMER
Use the suppl ied
ADEMCO 133 2X10
9VAC, 15VA Plug-in
Transformer (1332CN in
Canada
.
LOCAL SOUND ER DISABLE JUMPER
Remove the shorting jumper (shunt) to disable local
sounder, leaving only the external sounder active.
UL NOTE: Do not remove the shorting jumper (the shunt)
for UL installations.
LONG RANGE RADIO
Compatible with the AL ARMNET 7845C and 7720
Devices.
TWO-WAY VOICE
The LYNXR-EN supports the two-wa
voice feature/Alar m Audio Verification.
The LYNXR and LYNXR2 4 require the
installation of the LYNXAVM.
–7–
Wiring Connections
Wiring Connections
2. Make Phone Line Connections - For loc al or full line
seizure proceed to the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either t he
8-position jack or terminal s 2 (TIP) and 3 (RING) on
the Lynx.
b. Connect the handset phone lines to either the RJ11
jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The cont rol must be placed in
series with the incoming p hone line. Plugging the
Direct Connect Cord di rectly into the RJ31X jack, allows
the control to seize the phone line when an alarm
occurs and normal phone line usage by the premises
phones if the plu g needs to be removed.
a. Cut the incoming RING and TIP phone lines
(typically red and green, respectively) and connect
them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown)
respectively.
c. Wire the fly ing lea ds of a D irec t Conne ct Cord to the
control’s phone terminals as shown in the diagram
or plug into the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
RJ31X
1
2
3
45
6
7
8
RING
TIP
INCOMING
PHONE LINE
TO
PREMISES PHONES
TIP RING TIP RING
BROWN
GREY
RED
GREEN
INCOMING
PHONE LINE
TO
PREMISES
PHONES
}
}
GREEN RED
GREY
BROWN
RING
TIP
DIRECT
CONNECT
CORD
OR
OR
8-POSITION
JACK
01000-008-V0
Full Line Seizure Connection s
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will no t be properly
supervised, and the system may not respond to an open circuit on the zone.
3. Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circ uit and closed
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contact s to the hardwired zone terminals 6 (+) and 7 (–). Refer to t he Summary of Connections
diagram.
b. Connect closed circuit device s in series in the high (+) s ide of the loop. The EOL resis tor must be connected in
series with the devices, following the last device.
c. Connect open circuit d evices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
4. Make External Sounder Connections - The control panel supports either a 6 -14VDC piezo sounder (30mA max.) or
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Con nect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sou nder can be disabled by
removing the shorting jumper (shunt) on the terminal b oard. If disabled, however, no sounding
will occur upon AC loss, since the external so under does not operate when AC power is lost.
U
U U
U
L
L L
L
Do not remove shorting jumper (the shunt) for UL installations.
5. Disable Local Sounder Opti on - If required the Master Keypad’s built-in piezo sounder can be disabled.
a. Remove the shorting jumper (shunt) o n the terminal board.
6. Make Powerline Carrier Device Connections - The co ntrol panel supports up t o 8 Powerline Carrier Devices. If using
these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the S UMMARY OF
CONNECTIONS diagram.
a. Conn ect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied A demco connection cable, you may need to revers e the black and yellow wire connections. Refer to the
✻80 Device Programming Men u Mode section for details on programming Powerline Carrier Devices.
–8–
Wiring Connections
INCOMING
PHONE
LINE
TO
HANDSET
PHONE
LINE
WARNING:
TO PREVENT RISK OF SHOCK
DISCONNECT TELEPHONE LINE
A T TELECOM JACK BEFORE
SERVICING THIS UNIT .
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO
DISABLE
WEEKL Y TESTING IS
REQUIRED TO ENSURE
PROPER OPERA TION
OF THIS SYSTEM
ALL OUTPUT CIRCUITS ARE POWER LIMITED.
PREMISES
TELEPHONE
2k OHMS
EOLR
1
2
3
4
8 6 5
11
7
10
12
15
16
13
14
PHONE
ZONE
AAV / LRR
TRIGGER
(L YNXR/L YNR24)
LRR
TRIGGER
(L YNXR-EN)
SOUNDERS
PLCD
AC
EARTH
GROUND
EARTH
GROUND
HARD
WIRED
ZONE
INCOMING
TELEPHONE
LINE
RING
TIP
RING
TIP
( )
( )
(+)
(+)( )
(+)
PIEZO
6-14VDC
120mA max.
(e.g. W AVE2EX)
6-14VDC
30mA max.
DATA
OUT
SYNC
IN
POWERLINE
CARRIER DEVICES
RJ11
8
POS
JACK
AC
AC
SYNC
COM
DATA
9
BELL
TRIGGER
SIGNAL
(NEG)
THE L YNX SERIES CONTROLS ARE
EQUIPPED WITH AN INTEGRAL
RECHARGEABLE BA TTERY P ACK.
L YNXR: P/N L YNXRCHKIT-SC
L YNXR24: P/N L YNXRCHKIT-HC
L YNXR-EN: P/N L YNXRCHKIT-SC
OR
P/N L YNXRCHKIT -HC
01009-009-V0
NOTE
USE ONL Y 1332/1332X10 OR 1332CN
TRANSFORMERS PROVIDED
1332/
1332X10/
1332CN
PLUG-IN
TRANSFORMER
9VA C, 15VA
1332X10
ONL Y
CONNECTIONS
REPLACE EVERY FOUR YEARS
–9–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA P lug-in Transformer, ADEMCO 1332/1332X10 (1332CN in
Canada). Refer to the wiring table below fo r wire gauge and length.
Use only the provided ADEMCO
1332/1332X10 or 13 32CN Transformer
Distance from Transformer
to Control
Wire Gauge
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Wiring to the AC Transformer must not exceed 30 0 feet using 16-gauge wire. The voltage reading betwee n
terminals 15 and 16 of the contro l must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery. In the event of an AC power loss, the system is supp orted by a long life bac kup battery that
is supervised f or connection and for l ow voltage conditions. I f the battery is missin g, or a low battery con dition
is detected, a “lo w battery” message is displayed and a report is se nt to the central station. In addition, t he
system will b eep once every 45 se conds to audibly i ndicate a low battery c ondition (press any key to stop the
beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the 1332/1332X10 (1332CN i n
Canada) AC Transformer to terminals 15 and 16 as
shown in the wir ing diagram.
2. Remove battery retainer.
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
6. Connect battery connector to receptacle on
terminal block PC b oard.
7. After all wiring connections have been m ade, snap
the front assembly t o the back plate and plug the
transformer into a 24-hour, 110VAC unswitch ed
outlet.
Note: Rechargeable batteri es may take up to 48-hours to
fully charge. The “LOW BAT” message should cle ar
within four hours or by entering Test Mode.
01009-007-V0
1
BATTERY
RECEPTACLE
WIRING
TERMINALS
M
XXXX
K5108
TAPE
RETAINER
BATTERY
PACK
16
NOTE
LYNXRCHKIT -HC
BATTER Y PACK SHOWN
Ensure the cover is snapped closed prior to applying AC power.
–10–
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR Series i s equipped with an integr al, replaceable, rechargeable b attery pack com posed of six (6)
rechargeable 1 .2-volt nickel-metal hy dride batteries. S elect the appropriat e battery pack, based on the
installation’s requ irement, and install the b attery pack.
Model
Part Number
Batter
Standb
Time
Low Batter
Notification
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour befor e battery depletion
LYNXRCHKIT-HC 24-hour s (minimum) At least 1-hour before battery depletion
Replacing the Rechargeable Ba ttery
01009-006-V0
LYNXRCHKIT -HC OR LYNXRCHKIT -SC
M
XXXX
K5108
RETAINER
BATTERY
RECEPTACLE
BATTERY
CONNECTOR
BATTERY
PACK
TAPE
Ensure the control panel assembly is snapped closed prior to applying AC power.
1. When battery replacement is required, unplug
the transformer from the wall outlet, and open
the control panel cover.
2. Remove the battery retainer and disconn ect the
battery pack connector from the receptacle on
the terminal block PC board.
3. Remove the battery pack from the back plat e.
4. If required, replace t he tape that secures the
battery pack.
5. Install a replacement battery pack (P/N
LYNXRCHKIT-SC or LYNXRCHKIT-HC) into the
back plate.
6. Install the battery retainer.
7. Connect the battery connector to the
receptacle on the te rminal block PC board.
8. After the wiring connection has been made,
snap the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
10. Rechargeable batteries may take up to 48-
hours to fully charge. The “LOW BAT” message
should clear within four hour s or by entering
Test Mode.
–11–
Installing Wireless Zones
General Information
Zones: The contr ol supports up to 24 wireles s zones using 5800 Series transmit ters, and up to 16
wireless buttons.
Range: The built-in RF receiv er can detect signals from wirele ss transmitters within a nomina l
range of 200 f eet.
Transmitter s: 5800 Series transmi tters have built-in serial num bers that must be enter ed into the
system using th e ✻ 56 or ✻ 83 interactive mode, or input to the control via the downloader . 5800
Series transmit ters (except the 5800 RL and 5827, described s eparately) do not hav e DIP switches.
Each transmitter's zone number is programmed into the system in ✻ 56 mode. Some transm itters,
such as the 58 16 and 5817, can sup port more than one "zone" (referred to as loops or inputs) . On the
5816, for example, th e wire connection terminal bl ock is loop 1,the reed contact i s loop 2. Each loop
must be assigned a different zone number.
U
L
The 5816 and 5817 Transmitters d o not have EOL supervision of their loop wiri ng. Therefore, for
UL Household Burglary installa tions, the loop wiring may not exceed 3 feet.
The 5800RL, 5802MN, 5802MN2, 5804, 5804B D, 5804BDV, 5804E, 5 804WATCH, 5814, 5816TE MP,
5819, 5819S(WHS & BRS), a nd 5850(GBD) transmitters are not intended for any UL installations.
For button transmitt ers (RF "keys") such as the 5804 and 5801, you must assign a unique z one
number to each ind ividual button used on th e transmitter. Each button on the transmitter als o has
a pre-designated loop or input number, which i s automatically displayed.
House Identification
If you are using a 5 804BD/5804BDV, or 5827 Wireless K eypad with
the system, you must p rogram a House ID Code (01–31) in fi eld ✻24
to establish pr oper communication, and the keypad must be s et to
the same ID. House ID 00 d isables all wireless keypads. An RF
House ID is not necessar y for other 5800 Series transmitters; the
entry should be left at “00” (defau lt) in those cases. The 5827 reports
low batte ry status as zo ne “00”.
Transmitter Supe rvision
Except for some transmitters/keypads that may be carried off-
premises (5804, 5804BD , 5804BDV, 5804E, 5804WATCH, an d
5827), each transmitter is sup ervised by a check-in signal that is
sent to the rece iver at 70–90 minute int ervals. If at least one ch eck-
in is not received fr om each supervised transmitt er within a 12-
hour period, the "missing" transmitter numb er(s) and "FAULT" will
be displayed. Th e supervision for a particul ar transmitter in the
system that may al so be carried off the premise s (5801, 5802MN)
may be turned off by entering it as a " UR" (unsupervised RF) type,
as described in th e ✻56 Enhanced Zone Programming Mode sect ion.
5800 Series transmitt ers have built-in tamper protection and will
annunciate as a fault condition if covers are removed.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5806/5807/5808 5890 / 5890PI 5816
5827 5804BD/5804BDV
01009-010-V1
1
2
3
4
5
6
7
8
9
0
*
#
Transmitter In put Types
Each of the follow ing transmitters has on e or more unique factory -assigned input (loop) I D codes.
Each of the inp uts requires a programm ing zone
(e.g., a 5804's four inputs requir e four button zones).
Transmitters c an be entered as one of the following typ es
(see transmitter’s ins tructions for appropriate
input type)
:
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery signals. The
transmitter must remain within the receiver's range.
"UR" (U nsupervised RF ) Sends all the signals that the "RF" type does, but the control does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
"BR" (Uns upervised But ton RF) These only send fault signals. The y do not send low battery signals until they are
activated. The transmitter may be carried off-premises.
–12–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wirele ss transmitters may last from 4–7 years,
depending on th e environment, usage, and the specific wireless d evice
being used. Factors such as humidity, high or low temperatur es, as well
as large swings in temperature may all reduce the actual battery life in a
given installati on. The wireless syst em can identify a true l ow battery
situation, thus a llowing the dealer or user of the system time to arran ge
a change of bat tery and maintain pro tection for that point w ithin the
system.
• Button-type tran smitters should be peri odically tested for battery lif e.
The 5801, 5802MN, 5802MN2, 5 804, 5804BD, 5804BDV, 5804E, and
5804WATCH button transmitters have replaceabl e batteries.
Using the Trans mitter Sniffer Mode
Use this mode aft er all transmitters have b een entered to check th at all
transmitters h ave been properly pr ogrammed.
1. Enter Insta ller code (4112) + [#] + 3.
O
N
O
F
F
5802MN
5804 /5804E
5801
01009-011-V0
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
If so, wait a few minutes and t ry again.
2. The keypad will display all zone num bers, which have a non-zero Zone Type (even if serial
numbers were n ot learned yet). Fault each transmitter in turn, cau sing each one to send a
signal. As the system receives a sig nal from each of th e transmitters, th e zone number of th at
transmitter will disappear from the display . The transmitters may be checked upon
installation, or in an installed system.
3. When all tran smitters have been checked, exit Snif fer mode. Enter Installer Code (4112) +
OFF.
Notes: (1) Sniffer mode does not automaticall y expire. You must manually exit (I nstaller Code + OFF) Sni ffer mode to return to norm al
operation.
(2) All BR-type units must physically be activated to clear the display, since they do not automatically send check-in signals.
(3) When one button of a tran smitter (RF, UR, or B R) is activated, all zon es assigned to other but tons on that transmi tter are
cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
(4) Any transmitter tha t is not “entered” will no t turn off its zone number .
Go/No Go Test Mode
Note: Encrypted (high-securi ty) devices must be activa ted while the system is in G o/No Go Test Mode. Refer to the transmitter’s
installation instruc tions for complete deta ils.
The Go/No Go tests will verify adequate RF signal strength from th e proposed transmitter location,
and allow you to r eorient or relocate transmi tters if necessary, before mou nting the transmitters
permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced.
This will enabl e you to make sure that the RF signal fr om each transmitter is received with
sufficient si gnal amplitude when th e system is in the nor mal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitter s in their desired loc ations and the appr oximate length of wire
to be run to sen sors is connected to the transmitter's screw terminals (if used ), fault each
transmitter.
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
Note: On button t ype transmitters tha t have been programmed t o set ARM AWAY, ARM STAY , or DISARM, pressi ng a button will take the
system out of the Go/No Go Test mod e and cause the progra mmed action.
a. The keypad w ill beep three times ind icating signal reception an d will display the approp riate
zone number.
b. If the keypad does not beep, r eorient or move the transmi tter to another location. Usually a
few inches in either d irection is all that is r equired.
4. If each transmitter produces the proper k eypad response when it is fau lted, you can then
permanently m ount each of the transmi tters according to the ins tructions provided with them.
5. Exit the G o/No Go Test mode by enter ing: Installer Code ( 4112) + OFF.
–13–
Installing Wireless Zones
5800 Series Transmitter Loop Number s (Refer to this information when pro gramming transmitters)
The following illus tration shows the compatible transmitters, their associated input ty pes and loop
designat ions.
LOOP 1
5806/5807/5808/5808LST
ENROLL AS
"RF"
5804WATCH
LOOP 1
5809
ENROLL AS
"RF"
5818
ENROLL AS
"RF"
LOOP 1
LOOP 1
5814
ENROLL AS
"RF"
01009-012-V3
5828V
PROGRAM
HOUSE ID
5827BD
PROGRAM
HOUSE ID
1
4
7
2
5
8
0
3
6
9
#
*
LOOP 1
(MOTION)
5890/5890PI
ENROLL AS
"RF"
LOOP
1
5802 MN
ENROLL AS
"UR" OR "RF"
5804BD/5804BDV
ENROLL AS
"BR"
PROGRAM HOUSE ID
LOOP 4
YOU MUST
ENROLL
THIS BUTTON
LOOP 3
LOOP 1
LOOP 2
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5804/5804E
ENROLL AS "BR"
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
O
F
F
LOOP 3
O
N
5816TEMP
ENROLL AS
"RF"
LOOP 1
(TEMP
SENSOR)
5817
ENROLL AS
"RF"
LOOP 2
(AUX.
CENTER)
LOOP 1
(PRIMARY)
LOOP 3
(AUX.
RIGHT)
5816
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
LOOP 2
(REED)
5816MN
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
ALTERNA TE
POSITION
FOR LOOP 2
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5819S (WHS & BRS)
ENROLL AS
"RF"
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 2
(REED)
5819
ENROLL AS
"RF"
LOOP 2
(REED)
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5827
PROGRAM
HOUSE ID
1
2
3
4
5
6
7
8
9
0
*
#
5800RL
SET
HOUSE ID
5801
ENROLL AS
"UR" OR "RF"
LOOP 3
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 3
1:1 5:0 0
1:1 3: 1 6
5849
ENROLL AS
"RF"
LOOP 1
(SOUND)
5802 MN2
ENROLL AS
"UR" OR "RF"
LOOP
1
5850 (GBD)
ENROLL AS
"RF"
(G
re
en
)
(R
e
d
)
(Y
e
llow
)
ARM
ED
READ
Y
MESSAGE
MIC
Note: Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV, 5804 E and 5804WATCH transmitters, whether or not the loop is used.
U
L
The 5800RL, 5802MN, 5802MN2, 5804, 5804B D, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEM P, 5819, 5819S(WHS
& BRS), and 5850(GBD) wireless transmitters are n ot intended for any UL installations.
Setting DIP Switches on the 5800RL and 5827 Transmitter(s)
Set the 5800RL and 5827 Transmitters to the p rogrammed House ID, by us ing the DIP switches.
(OFF position is indicated by ---)
Notes: (1) The 5827 transmitter cannot be used in conjunction with the ✻58 RF Jam Detection feature.
(2) The 5800RL cannot be used in co njunction with the Auto Arm (scheduled arming) feature.
01000-014-V1
2345 61
SW-6 SETS
MODE
2-6 SETS HOUSE ID
SW-1 ACTIV A TES
MODE SETTING
SWITCH DOWN
FOR "OFF"
SHOWN SET FOR HOUSE ID# 12
SWITCH UP FOR "ON"
5800RL DIP SWITCH TABLE
DIP SWITCH POSITIONS DIP SWITCH POSITIONS House
ID
2 3 4 5 6
House
ID
2 3 4 5 6
0 --- --- --- --- --- 16 ON --- --- --- ---
1 --- --- --- --- ON 17 ON --- --- --- ON
2 --- --- --- ON --- 18 ON --- --- ON ---
3 --- --- --- ON ON 19 ON --- --- ON ON
4 --- --- ON --- --- 20 ON --- ON --- ---
5 --- --- ON --- ON 21 ON --- ON --- ON
6 --- --- ON ON --- 22 ON --- ON ON ---
7 --- --- ON ON ON 23 ON --- ON ON ON
8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- ON ---
11 --- ON --- ON ON 27 ON ON --- ON ON
12 --- ON ON --- --- 28 ON ON ON --- ---
13 --- ON ON --- ON 29 ON ON ON --- ON
14 --- ON ON ON --- 30 ON ON ON ON ---
15 --- ON ON ON ON 31 ON ON ON ON ON
Setting 5800RL DIP Switches
1
2
3
4
5
HOUSE ID
SWITCH UP FOR "ON"
SWITCH DOWN FOR "OFF"
SHOWN SET FOR HOUSE ID# 30
01000-013-VO
5827 WIRELESS KEYPAD DIP SWITCH TABLE
DIP SWITCH POSITIONS DIP SWITCH POSITIONS House
ID
1 2 3 4 5
House
ID
1 2 3 4 5
1 --- --- --- --- ON 17 ON --- --- --- ON
2 --- --- --- ON --- 18 ON --- --- ON ---
3 --- --- --- ON ON 19 ON --- --- ON ON
4 --- --- ON --- --- 20 ON --- ON --- ---
5 --- --- ON --- ON 21 ON --- ON --- ON
6 --- --- ON ON --- 22 ON --- ON ON ---
7 --- --- ON ON ON 23 ON --- O N ON ON
8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- O N ---
11 --- ON --- ON ON 27 ON ON --- ON ON
12 --- ON ON --- --- 28 ON ON ON --- ---
13 --- ON ON --- ON 29 ON ON ON --- ON
14 --- ON ON ON --- 30 ON ON ON ON ---
15 --- ON ON ON ON 31 ON ON ON ON ON
16 ON --- --- --- ---
Setting 5827 DIP Switches
–14–
Mechanics of Programming
General Programmin g Information
Programming options are stor ed in non-removable, electrically erasable, nonv olatile EEROM memory. The
system can be pr ogrammed at any time, even at the installer' s premises prior to the ac tual installation.
Simply apply p ower temporarily to the C ontrol and then prog ram the unit as desired . There are two
programming modes:
•
Data field programming (used for set ting various system options)
• Interactive menu mode programming (used for program ming zone information, programming Powerline Ca rrier
Devices, and for entering tra nsmitter serial numbers)
The system can also be programmed re motely, using an IBM Personal Computer, a modem, and Compass Downlo ader
for Windows. See the R emote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the
feedback announcements or system beeps in the Programm ing Mode, of the system’s built-in sp eaker. To adjust the volume, press
FUNCTION + VOLUME+ [3 ] or [6]. Upon exiting the Program Mode, the system will reset the volum e to the default value (mid level).
!
Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model being
installed prior to the system programming.
Entering Program Mode - Use one of th e following meth ods to enter Progra mming Mode:
1. Press both the [✻ ] and [#] keys at the same time, within 50 se conds after power is ap plied to the Control o r from
exiting Programming mode, OR
2. After power-up, ent er the Installer Code (4112) + 800 (This method disabled if Program mode is exited using
✻98.)
to enter Expert Programming mode or Installer Code (4112) + 888 to enter Voice Prompt Programming
mode.
Notes: 1. If a different Insta ller Code has been programmed, use tha t code to enter the Programming mode. Once you have en tered the
Program mode, data fiel d
✻20 (the first data field in the s ystem) will be displayed and both keypa d LEDs will flash.
2. Ent ering Programming mode may take up to 18 seconds if the 5842 Wireless Dialer has bee n enabled. The system will display
“ - - “ until the Lynx enters Programming m ode.
Programming a Data Field
1. Press [✻ ] + Field No. (for example, ✻ 21), followed b y the required entry.
2. When you have co mpletely programmed a data fie ld, the keypad will “beep” three times and then automatically
display the next data field in sequence. To go to a different field, press [
✻] plus the desired field number.
3. If the number of digits that will be ente red in a data field is less than the maximum number of digits available (e.g.
phone number fiel d), enter the desired data, then pres s [
✻] to advance to the next data f ield.
4. If a nonexistent field has been e ntered, the keypad will display “ EE”. Simply re-enter [
✻] plus a valid field number.
To view a data field without making changes: Enter [#] + Field No. Data will be displayed for that field.
To delete an entry in a field: Ente r [
✻] + Field No. + [ ✻]. (Applies only to fields ✻40– ✻44, ✻88 and ✻94).
Interactive Mode Programming (✻ 56, ✻ 80, ✻ 81, ✻ 83, ✻ 84, ✻ 85)
Press [✻ ] + interactive mode No. (for example, ✻ 56). The keypad will display the first of a series of pro mpts.
A detailed procedur e (with displays of prompts) is provide d in later sections of this manual.
Interactive Mode Used to Program
✻
56 Enhanced Zone Programming Mode
Zone characteristics, report codes, and serial numbers
✻80 Device Programming Menu Mode
Powerline Carrier Devices
✻81 Zone List Menu Mode
Zone Lists for powerline carrier activation
✻
83 Enhanced Sequential Mode
5800 Series transmitter serial numbers
✻84 Assign Zone Voice Descriptors
Voice descriptors for each zone
✻85 Record Custom Voice Descriptors
Up to 5 custom voice descriptors for zones
Loading Factory Defaults
To load the factory defau lts, enter the Programming m ode, press ✻ 97, then press number 1, 2, 3, or 4 to select from
default tables 1-4 at the bac k of this manual, or press “0” if yo u are not selecting a default table.
!
If a default table is loaded, any data that has already been programmed into the system will be changed according to
the default table selected!
✻96 resets all subscriber account numbers and CSID in pre paration for an initial download.
Exiting Program Mode
✻
98 inhibits re-entry into the Expert or Voice Prompt Programming modes using the Installer Code .
✻99 allows re-entry int o the Expert Program mode usi ng Installer Code (4112) + 800 or into th e Voice Prompt
Programming mode using Installer Code (4112) + 888 .
Note: After exiting program mode (or up on power-up), the system takes up to a m inute to reset. To bypass the reset delay, pr ess [#] + [0].
–15–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types a re defined below.
Type 00
Zone Not Used
Zone type 00 is used to program a zone that is no t used.
Type 02
Entry/Exit Burglary #2
01000-017-V0
Zone type 02 is usually assig ned to sensors or contacts on which sec ondary entry and
exit doors that might be further from the keypad (typically used for a garage, loading
dock, or basement doo r).
Zone Characteristics:
• Entry delay #2 is prog rammable from 0-99 seconds (field ✻ 36).
• Exit delay is independen tly programmable from 0-99 secon ds (field
✻34).
• Secondary entry delay, if arme d in the AWAY or STAY mode.
• No entry delay when armed in the STAY NO D ELAY or AWAY NO DELAY mode.
• Exit delay beg ins regardless of the arming mod e selected.
01000-018-V0
Type 03
Perimeter
Burglary
Zone type 03 is usua lly assigned to all sensors or contac ts on exterior doors and
windows. Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY mode.
Type 04
Interior, Follower
5890 / 5890PI
01000-019-V1
Zone type 04 is usually assigned t o a zone covering an entry area (i.e.: foyer, lobby, or
hallway) that one m ust pass upon entry (after fa ulting the entry/exit zone) to reach
the keypad. It provides an instant alarm if the entry/ex it zone is not violated first,
and protects an area i n the event an intruder has hidden on the prem ises before the
system is armed, or gains access to the premises throu gh an unprotected area.
Zone Characteristics:
• Delayed alarm (usi ng the programmed entry/exit ti me) if entry/exit (types 01 or
02) or interior-with-de lay (type 10) zone is faulted first.
• Instant alarm in all other situations.
• Active when armed in AWAY or AWAY NO DELAY mode.
• Bypassed automatically w hen armed in STAY or STAY NO DELAY mode.
Type 05
Trouble by Day/
Alarm by Night
Zone type 05 is usually assigned to a zone that contains foil-protected doors or
windows or covers a s ensitive area (i.e.: stock room, drug supply room, etc.) It can also
be used on a sensor o r contact in an area where imm ediate notification of an entry i s
desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY (night) mode.
• Provides a latched t rouble sounding from th e keypad and, if desired, a central
station report during the dis armed state (day).
Type 06
24-hour
Silent Alarm
Zone type 06 is usually assig ned to a zone containing an Emergency
button (silent emergency).
Zone Characteristics:
• Sends a report to the centra l station but provides no keypad di splay or
sounding.
Type 01
Entry/Exit Burglary #1
01000-017-V0
Zone type 01 is usua lly assigned to sensors or contacts on primary entry and exit
doors.
Zone Characteristics:
• Entry delay #1 is programma ble from 0-99 seconds (field
✻35).
• Exit delay is indep endently programmable from 0-9 9 seconds (field
✻34).
• Exit and entry delays when armed in AWAY or S TAY mode.
• No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode .
• Exit delay regar dless of the arming mode select ed.
–16–
Zone Response Type Definitions
Type 07
24-hour
Audible
Alarm
Zone type 07 is usually assigned to a zone containing an Emergency
button (audible emergency).
Zone Characteristics:
• Sends a report to the central station, and prov ides alarm sounds
externally and at the key pad.
Type 08
24-hour
Auxiliary Alarm
Zone type 08 is usually assig ned to a zone containing a button for use
in personal emergencie s or to a zone containing monitoring devices
(i.e.: water or tempera ture sensors, etc.).
Zone Characteristics:
• Sends a report to the central station and pr ovides an alarm sound at
the keypad. (No bel l output is provided and there is no keypad
timeout.)
5806/5807/5808
01000-020-V0
Type 09
Supervised
Fire
Zone type 09 can be assigned to any wireless zone used as a
fire zone. This zone type is always active and cannot be
bypassed.
Zone Characteristics:
• Bell output will pulse when this zone type is alarme d.
Type 10
Interior w/Delay
Zone type 10 is bypassed when the panel is armed in the STAY or STA
NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programm ed entry time) when armed in the
AWAY mode.
• Entry delay begins wh enever sensors in this zone are vi olated,
regardless of whether an entry/exit delay zone was trippe d first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regar dless of the arming mode selec ted.
Type 20
Arm–Stay
Zone type 20 is a special-pur pose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• Exit delay regar dless of the arming mode selec ted.
• System is armed in the STAY mode whe n the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Type 21
Arm–Away
Zone type 21 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Type 22
Disarm
Zone type 22 is a special-purpose zone ty pe used with 5800 series
wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Type 23
No Alarm Response
Zone type 23 can be used on a zone when a Powerline Carrier Device
(e.g., X-10) action is desire d, but with no accompanying alarm (e.g.,
front door light).
Type 24
Silent Burglary
Zone type 24 is usually assigned se nsors or contacts on exterior doors
and windows where bel ls and/or sirens are NOT desi red.
Zone Characteristics:
• Instant alarm, with NO au dible indication when is armed in t he
AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note: Keypad beeps if the zone is faulted when system is disarmed and Chime
mode is on.
–17–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pag es list all data fields in this Control (in numerical ord er). Use the blank programming f orm
to record the dat a for this installation . Note that both keypad LED s flash while in Program ming mode.
Note: Entering a number other than the one specified will give unpredictable res ults.
✻
20
Installer Code
Enter 4 digits, 0-9
The Installer Code is used to e nter the 4-digit Master Security Code. See
"Master Code" in the System Operation section for procedure.
✻21
Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
If enabled, security code is not re quired to arm the system. The user
simply presses and holds down the AWAY or ST AY key to arm.
✻22
Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inac tivity
This opt ion allows th e choice of ei ther always ba cklighting th e keypad or
turning the ba cklighting off afte r 10 seconds of keypad inactivity.
✻23
Forced Bypass
0 = no forced bypass
1 = provide automatic bypa ss of all open (faulted)
zones
All zones bypasse d by this function will be displayed after the bypass is
initiated.
Note: UL installations: must be 0 (no forced bypass)
✻24
RF House ID Code
00 = disable all wireless key pad usage
01-31 = House ID
The House ID identifies receivers an d wireless keypads.
If a 5827 Wireless Keypad or 5804BD/5804BDV Tra nsmitter is to be
used, a House ID Code MUST be entered, and the ke ypad should be set
to the same ID.
✻25
Powerline Carrier Device (X-10) House ID
0 = A 4 = E 8 = I # + 12 = M
1 = B 5 = F 9 = J # + 13 = N
2 = C 6 = G # + 10 = K # + 14 = O
3 = D 7 = H # + 11 = L # + 15 = P
Powerline Carrier Devices require a House ID. This field identifies this
House ID to the Control. The Power line Carrier Devices are
programmed in field ✻80.
✻26
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activ ated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime m ode on)
This option allows the installer to define the s pecific zones intended to
chime when faulted while t he system is in Chime mode. If enabled , these
zones are defi ned in zone list 3 (se e ✻81 Zone List Menu Mode ).
✻27
Real Time Clock Display
0 = do not display the time
1 = display the time
Refer to the User’s Manual for settin g the clock time and date.
✻29
Daylight Savings Time Start/End Mon th
0, 0 = no daylight saving time used
1-12 = start month and end mon th
Enter # + 10 for 1 0, # + 11 for 11, and # + 12 for 12.
✻30
Daylight Savings Time Start/End Week
0 = disable 4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend 6 = next to last
3 = third weekend 7 = 3
rd
from last
Enter the appropriate start and end weekend of the month.
✻31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arm ing period for
a given zone
LYNXR/LYNXR24 - Applies to Long Range Radio Output if “0”
is selected in field ✻91
LYNXR-EN - Applies to Long Range Radio Output if Long Range
Radio is connected to the Trigger Single (Neg.) terminal #8.
UL installations: must be 0 (no limit)
This field applies only to burglary zones (zone response types 1-5, 10),
and affects long range radio reporting but does not affect central station
reporting.
Note: This fie ld applies only to the bell a nd does not affect keypad
sounds.
✻32
Fire Sounder Timeout
0 = yes, fire sounder timeout a fter time programmed in
field
✻33
1 = no fire sounder timeout; continue sounding until
manually turned off
This Control compl ies with NFPA requirements for temporal pulse
sounding of fire noti fication appliances.
Temporal pulse sou nding for a fire alarm cons ists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses . . .
✻33
Alarm Bell Timeout
0 = No timeout 2 = 8 min 4 = 16 min
1 = 4 min 3 = 12 min
This field determines whether the external sounder will shut off after
time allowed, o r continue until manually tu rned off.
UL installations : must be set for a minim um of 4 min (option 1)
✻34
Exit Delay
00-99 = exit delay time in second s
The system will wait the time entered before sounding an alarm if the
exit door is left open after t he system has been armed.
UL installations: must be set for a maximum of 60 seconds
–18–
Data Field Descriptions
✻35
Entry Delay 01
00-99 = entry delay time in secon ds.
The system will wait the time entered before sounding alarm up on entering
if system is not disarmed. UL installations: must be set for a ma ximum of
45 seconds
✻36
Entry Delay 02
00-99 = entry delay time in secon ds.
The system will wait the time entered before sounding alarm up on
entering. UL installations: must be set for a maximum of 45 seconds
✻37
Audible Exit Warning/Quick Exit
Exit Warning Quick Exit
0 = no exit warning
sound
0 = no quick
exit
1 = provide exit
warning sound
when armed AWAY
1 = allow quick
exit
Exit Warning: So und consists of slow co ntinuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of ex it delay.
Quick Exit: If en abled, user can restart t he exit delay time after armi ng in
STAY mode by enter ing the user code and pressi ng the STAY key, or by
pressing the STAY key if Quic k Arm is enabled. This avoi ds having the
user disarm then re-arm the system after al lowing someone to enter or exit
✻38
Confirmation of Arming Ding
0 = no ding
1 = confirmation ding after ar ming system
2 = confirmation ding after arm ing from RF button or
RF keypad only
Confirmation o f arming is provided by a 1/2 second external sounder “ding”
that sounds when closing rep ort is sent, or at the end of exit delay.
If Option 2 is selected the externa l sounder “ding” occurs immediately after
the system receives the RF transmission.
✻39
Power Up In Previous State
0 = always power up in a disarme d state
1 = assume the system sta tus prior to power-down
When the system powers up ar med, an alarm will occur 1 minute a fter
arming if a zone is faulted, and any bypas sed zones will be unbyp assed.
Note: If the previous stat e was armed AWAY or STAY , the system will not
respond to sensor changes for 1 minute, which allows time for sensors such
as PIRs to stabiliz e. UL installations: must be 1 (power up in previo us
state)
DIALER PROGRAMMING (
✻
40–
✻
50)
Fields
✻
40,
✻
41,
✻
42: Enter up to the number o f digits shown. Enter 0–9, # + 11 for ‘
*
’
;
# + 12 for ‘#’; # + 13 for a pa use
(2 seconds)
NOTE: Whenever AAV is used, primary (field ✻41) and secondary (field ✻42) phon e numbers sho uld be preceded with the call w aiting
disable command. Otherwise, there is the possibility of connection of the third party t o LYNX during AAV mode.
✻40
PABX Access Code
Enter up to 6 digits if PA BX is needed to access an
outside line.
If fewer than 6 digits need to be entered, exit b y pressing [
✻
]. To clear
entries from field, press
✻
40
✻
.
✻41
Primary Phone No.
Enter up to 20 digits.
If fewer than 20 digits entered, ex it by pressing [
✻
]. To clear entries from
field, press
✻
41
✻
.
Note: Backup reporting (8 attempts are mad e to the secondary phone
number if no kiss off is received after 8 att empts to the primary
number) is automatic only if there is a secondary phone number
(field
✻
42).
✻42
Secondary Phone No.
Enter up to 24 digits.
If fewer than 24 digits entered, ex it by pressing [
✻
]. To clear entries from
field, press
✻
42
✻
. See backup reporting note for field
✻
41. If using the
paging feature, enter the pag er phone number here.
!
All four digits of the Subscriber Account number must be entered in Fields
✻
43 and
✻
44. If ten digit format is
selected in
✻
48 (option 5), all ten digits of the Subscriber Account number must be entered.
Fields
✻
43 and
✻
44:
Enter [
✻
]
as the fourth digit if a 3-digit account number (for 3+1 dialer re porting format) is used. Enter 0 as the fir st
digit of a 4-digit account number for Nos. 0000–0999. Ent er [
✻
] as the fifth digit if a 4-digit account number (for 3+1,
CID®) is used. Exit f ield by pressing [
✻
] if only 3 digi ts are used. To clear en tries from field, press
✻
43
✻ or ✻
44
✻
. See
blank Programmi ng Form for examples of account num ber entries. If using the p aging feature, do not enter a lea ding 0
in the subscriber account number, and do no t use digits A-F anywhere in the number. Some paging systems provide
voice mail capability, w hich is activated by a leading 0 in the message. Enter digits 0–9; # +11= B; # +12=C; # +13=D; #
+14=E; or # +15=F.
✻43
Primary Subs Account No.
Enter a four or ten digit account n umber.
Enter the primary subscriber account number.
To clear entries from field, press
✻
43
✻
.
✻44
Secondary Subs Account No.
Enter a four or ten digit account n umber.
Enter the secondary subscriber account number.
To clear entries from field, press
✻
44
✻
.
–19–
Data Field Descriptions
Field 46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for a pause (2 sec onds).
✻46
“Follow Me Reminder” Phone Number
Enter up to 24 digits.
This option allows the user to schedule a time driven me ssage. When
activated the system will dial the phone number programmed and deliver a
voice message (custom words 72, 73 and 74). This option is only supported
when the pager or fo llow me feature is enable d in field
✻
49 (option 6-9 or
10-13).
If using the Fo llow Me Reminder feat ure, enter the pho ne number here. If
fewer than 24 digits are e ntered, exit by pressing [
✻
]. To clear entries from
the field press
✻
46
✻
.
The telephone message can b e terminated (acknowledged) by pressi ng any
key on the telephone keyp ad. Pressing any key on the local LYNXR keypad
will terminate (acknowledge) bot h the follow me and the local reminder
announceme nts.
Note: The follow me remin der announcement will be terminat ed if any
other event requires the system to d ial out or if and audible alarm
has occurred.
✻47
Phone System Select
Note: For LYNXR/LYNXR24 o nly options 0, 1, 2, and 3
are applicable. For LYNXR-EN all options apply.
Central Dialing Mode
Station Pulse Tone Pulse Tone
No WATS 0 = No
Speaker
Phone
1 = No
Speaker
Phone
4 = With
Speaker
Phone
5 = With
Speaker
Phone
WATS 2 = No
Speaker
Phone
3 = No
Speaker
Phone
6 = With
Speaker
Phone
7 = With
Speaker
Phone
This opt ion is used to en ter the corre ct type of phon e dialing (pul se or tone),
and to select the correct WATS line option for the Central Station. For
LYNXR-EN this option is used to activate the speaker phone opti on.
Note: If using pulse dialing, you must e nter the numbers slowly in order to
allow the pulse dia ler time to operate.
✻48
Report Format for Primary/Secondary
Primary Secondary
See choices below See choices below
0 = 3+1; 4+1 A DEMCO Low Speed Standard
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMC O Low Speed Stan dard
3 = 4+2 Radioni cs Standard
5 = ADEMCO Contact ID® Repo rting with 10- digit
subscri ber account numb er
6 = 4+2 ADEM CO Express
7 = ADEMCO Con tact ID® Reporting with 7-digit
subscri ber account numb er
8 = 3+1; 4+1 A DEMCO Low Speed Expanded
9 = 3+1; 4+1 Ra dionics Expande d
Enter
✻
as the 4th digit of
✻
43 through
✻
44, if 3+1 dialer r eporting is to be
used. (For an explanation of these formats, see the System Communicatio n
section of this manual.)
Notes: (1) The maximum number of alarm and alarm restore report s
during one armed period is determined by field
✻
92.
(2) If Option 5 is selected a 10-digit acc ount number must be
entered in Fields
✻
43 or
✻
44.
(3) Option 5 or 7 (A DEMCO Contact ID® Reporting) must be
selected for AVM.
(4) Option 5 or 7 (A DEMCO Contact ID® Reporting) must be
selected if installing the 5842 Wireless Dialer.
✻49
Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary
fails, then all
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All reports All
To Primary To Paging Nu mber
6 = All reports except Open/Clo se Alarms, Open/C lose
‡
,
Troubles
7 = All reports Alarms, Troubles
8 = All reports Alar ms, Open/Close
‡
,
Troubles
9 = All reports except Open/Clo se Open/Close
‡
To Primary To Follow Me Sy stem
Phone Number
10=All reports except Open/Clo se Alarms, Open/C lose
‡
,
Troubles
11 = All reports Alarms, Troubles
12=All reports Alarms, Open/Close
‡
,
Troubles
13=All reports except Open/Clo se Open/Close
‡
‡
Will report Users 0, 5-8, and, if using wireless button-type
devices, will re port the zone number o f the arm or disarm
button 26-33. All other zones and users are not reporte d.
This field is used to s elect a reporting option as fo llows:
Enter: 0 - 5 when reporting to telephone receivers.
6 - 9 when reporting to a pager is desired.
10 - 13 when reporting to an auxiliary telephone receiver.
Pager Report Format
Options 6-9 send reports to t he primary phone number, in a format defined
in Field
✻
48, and send reports to a pager, which has its p hone number
entered as the secondary phone number in Field
✻
42. The pager report is a
7-digit code, wit h optional 16-digit prefix, i n the following format:
AAAAAAAAAAAAAAAA-EEE–0 0NN where:
AAA = Optional 16 digits for PIN number, etc. See Field
✻
88 for full
description of these characters.
EEE = 3-digit Event Code as follows:
911 = Alarm ( NN = zone number)
101 = Open, system disarmed (NN = user no.)
102 = Close, system armed (NN = user no.)
811 = Trouble (NN = zone no.)
00 = Always disp layed before 2-digit user/zone no.
NN = 2-digit user number or z one number, depending on the t ype of
event (EEE) that occurred. NN=00 indicates AC loss , system low
battery, or low batt ery in 5827.
Follow Me System Report Format
Options 10-13 sen d reports to the primary p hone number, in a format
defined in Field
✻
48, and sends voice message to t he secondary phone
number entered in Field
✻
42.
The message is a re peatable system status anno uncement. If the manual
paging option has been programmed in Field
✻
87, the message will repeat
“system, system…..”.
The message can be terminated b y pressing any key on the telephone
keypad.
–20–
Data Field Descriptions
✻50
15-Second Dialer Delay (Burglary)
0 = no dialer delay
1 = provide 15-second delay o f burglary alarm report
when armed away
If enabled, provides communication delay to the c entral station and allows
the subscriber time t o avoid a false alarm transm ission. Delay does not
apply to zone type 6, 7, 8, and 9 alarms, wh ich are always sent as soo n as
they occur. UL installatio ns: must be 0 (no delay)
✻51
Periodic Test Report
0 = no test report 2 = weekly
1 = once every 24 hrs 3 = once every 30 da ys
Test report code entered in field
✻
64 is sent.
✻52
First test Report Offset
0 = 24 hrs after exit program m ode or download
1 = 6 hours after exit program m ode or download
2 = 12 hrs after exit program m ode or download
3 = 18 hrs after exit program m ode or download
This is the time to first report fr om programming or downloading.
✻53
Sescoa/Radionics Select
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats.
✻
54
Lack of Usage Notification
0 = Disabled 4 = 90 days
1 = 1 day 5 = 180 days
2 = 7 days 6 = 365 days
3 = 27 days
Note: There will be no local annuncia tion indicating that
this report has been s ent to the Central Station.
If enabled, notifies the ce ntral station if an end user is not o perating their
security system by sending a System Inactivity report 654. The report will
be sent only to the Pr imary phone number and on ly if Contact ID® format
was selected.
Note: The report will follow the
✻
49 = 0 rules, no mat ter which selection
was made in
✻
49.
✻58
RF Jam Detection
0 = no jam detection
1 = RF jam detection with event l ogging, but no
central station report
2 = RF jam detection with event l ogging and with
central station report (if trouble/restore report i s
enabled in fields ✻60, ✻71)
For Event Logging, Optio n 2 must be selected.
If the control detects an RF jam condition, a “FAULT” message appears for
zone 90. The Cont act ID® code for RF Jam is 3 44.
Note: This feature cannot be used in conjunction with the 5827 wireless
keypad.
SYSTEM STATUS AND RESTOR E REPORT CODES PROGRAMMING (
✻
59 –
✻
76, &
✻
89)
Program Report Codes usi ng the interactive
✻
56 Enhanced Zone Programming Mode, or codes c an be entered in data
fields
✻
59-
✻
76,
✻
89. The following i s a set of guidelines when p rogramming report codes. The actual report code di gits
that you enter depend up on the particular installa tion, and should be in agreement with you and the central station
office receiving the signa ls.
With a 3+1 or 4+1 Standard Format: Enter a code in t he first box: 1–9, A, B, C, D, E, or F. Ente r "#+10" for A
(reports a “0” on some receiv ers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14 " for E, "#+15" for F. Entering "0" in the
first box will disable a repor t. Entering "0" in the second bo x results in automatic advance to the next field.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, o r A–F, as described above.
Entering "0" in the fir st box will disable a repor t. Entering "0" in the second box will eliminate the expand ed message for
that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different
digit for each zone until you have use d up available digits. If the number of zone s exceeds the number of available
digits, begin with digit 1 aga in. This is an "enabling" code only and is not the actual code sent to the central station
office. Entries in the se cond boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all
the system conditions you want to send to the central station. A "0" in the first box disables the report.
–21–
Data Field Descriptions
SYSTEM ST ATUS REPORT CO DES (
✻
59–
✻
68)
✻59
Exit Error Report Code
(See notes abo ve)
If the system is arme d and an entry/exit or interior zone is still open
after the exit delay ti me has expired, an alarm will sound at the
keypad and external sounder. If the system is disarmed before the
end of the entry delay th at immediately follows, the alarm so unding
will stop and no message will be sent to the central station. The
keypad will display “CA (CANCELED ALARM).”
If the system is not disarmed be fore the end of the entry delay
mentioned above, and an entr y/exit or interior zone is still open, an
“exit alarm” mess age will be sent to the ce ntral station if an Exit
Error report code is selected in this field. The keypad will display
“EA (EXIT ALARM),” and the alarm sounding will continue until
the system is disarmed (or timeout oc curs).
An Exit Alarm conditio n will also result if a fault occurs i n an exit or
interior zone within 2 mi nutes following the end of the exit de lay,
and an “Exit Alarm” message will be sent to the central station.
If Contact ID® form at has been programmed, t he message will
contain the zone number and error code 374 (Trouble–Exit Error). If
4+2 format is used, the digit entered in this field will be s ent
followed by the second dig it of the programmed alarm code for th at
zone. If 3+1 or 4+1 for mat is used, only the digit e ntered in this field
will be sent. This messag e will go to the primary phone n o. Under
any of these conditions, no restore m essage will be sent.
If “0” is entered in this field, no special message will b e sent, only
the regular alarm and alarm restore code for the zone.
✻60
Trouble Report Code
(See notes above)
This will be sent if a zo ne goes into trouble.
✻61
Bypass Report Code
(See notes above)
This will be sent when a zone is manually bypassed.
✻62
AC Loss Report Code
(See notes above)
Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no AC restore report.
✻63
Low Battery Report Code
(See notes above)
This will be sent when a low battery condition exists in the system’s
standby battery.
✻64
Test Report Code
(See notes above)
This is sent periodi cally to test that the communicator and ph one
lines are operatio nal (frequency of report is selected in field
✻
51).
✻65
Open Report Code
(See notes above)
This is sent upon disarming o f the system. 2nd digit = user number,
if expanded or 4+2 r eporting is selected.
✻66
Arm AWAY/STAY Report Code
(See notes above)
This opt ion allows fo r independent programming of AWAY and
STAY reports. 2nd digit of report is user number if expanded or 4+2
reporting is selected .
NOTE: OPEN reports are not sent if the associated closing report is
not enabled.
✻67
RF transmitter Low Batt. Report Code
(See notes above)
This is sent in the event that a wireless transm itter low battery
condition exists.
✻68
Cancel Report Code
(See notes above)
This is sent upon disarming of the system aft er an alarm condition
was reported.
RESTORE REPORT CODES (
✻
70–
✻
76)
✻70
Alarm Restore Report Code, 1st Digit
(See notes above)
Sent when the zone that caus ed an alarm is restored to its non-
faulted condition . 2nd digit is automatically sent as the 2nd digit of
the zone alarm report code programmed in field
✻
56, if expanded or
4+2 reporting is sel ected.
✻71
Trouble Restore Report Code
(See notes above)
Sent when a trouble in a zo ne is restored.
✻72
Bypass Restore Report Code
(See notes above)
Sent when a zone that has been bypa ssed is unbypassed.
✻73
AC Restore Report Code
(See notes above)
Sent when AC power has been rest ored after an AC power outage.
✻74
Low Battery Restore Report Code
(See notes above)
Sent when a system low batt ery condition is restored to normal.
–22–
Data Field Descriptions
RESTORE REPORT CODES (
✻
70–
✻
76) Continued
✻75
RF Transmitter Low Batt. Restore Code
(See notes above)
Sent when a transmitter that p reviously sent in a “low battery” message
has sent a messag e indicating it no longer has a low battery cond ition.
✻76
Test Restore Report Code
(See notes above)
Sent when the test mode is exit ed. A restore code entered here will cause
a restore message to be sent when Test mode is exite d.
✻87
AUX Function/1-Button P aging
0 = Aux key performs defined fun ction (macro)
1 = Aux key sends predefined m essage to pager or a
voice message to Follow Me system phone
number
If “0” is entered, user can define a macro function for the AUX key. See
user manual for description of t he use of this key.
If “1” is entered, you m ust also select an option in fie ld
✻
49. The options
are 6-9 for the pager or 10-13 for the follow me s ystem announcement.
The actual pager mess age is 999-9999. Note that t he hyphen may not be
displayed, depending on the pager service. The manual follo w me system
announcement is a repeat able “System, System…..”.
Note: A macro cannot b e run from the Test mode.
✻88
Pager Characters
Enter up to 16 digits that will appea r in front of the 7-
digit pager message.
Enter [#] + [11] for “*”
Enter [#] + [12] for “#”
Enter [#] + [13] for 2-seco nd pause
NOTES: Verify tha t the pager supports [* ] and [#]
characters be fore using them. S ome pagers
require an additional delay [pause] in order to
receive the entire message .
If entered, these digi ts will appear in front of the 7-digit pag er message
sent by the control (either upon a system event or upon pressing the AUX
key [if programm ed for paging]), and duri ng latch key report (if e nabled
during schedu ling). These digits can consist of a PI N number, account
number, pauses or special dig its needed by the pager (these types of
characters are not displayed), or any other characters the user chooses
that will be displa yed (eg., using a charact er code to distinguish bet ween
control panel messages and other pager messages).
You do not need to fill all 16 digits. Press [
✻
] + next field number to exit
the field. To clear the field, press
✻
88
✻.
See field
✻
87 to select the AUX key P aging feature. See field
✻
49, which
must have an option 6-9 sel ected to enable paging messages, for
description of the pager message.
✻89
Event Log 80% Full Report Code
(See notes abo ve)
If an Event Logg ing selection is made in fie ld
✻
90, a message can be sent
to the central stati on receiver when the log is 8 0% full. If the log becomes
full, a new message wi ll overwrite the oldest message i n the log.
Note: All control and reado ut from the log, aside from the selection ma de
by the installer in field
✻
90, is accomplishe d via the downloader.
✻90
Event Logging Options
0 = No event logging
1 = log Alarm/Alarm R estore
2 = log Trouble/Trouble Restor e
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of ev ents (add value of entries )
Example: To select “Alarm/Alarm Re store” and “Open/Close,” enter 9 (1 +
8); to select all e vents, enter #15.
Default “3” = alarm/alarm restore (1) plus trouble/trouble restore (2).
The system has the ability to record various events in a history log (84-
event capacity). The types of events to be logged can be selected as
indicated. At any time , the downloader operator can then upl oad the log
and view or print out al l or selected categories of the log. The log c an also
be cleared by the dow nload operator.
The display/prin tout at the central station will show the date , time, event,
and description o f the occurrences.
Note: System messages are logged whe n any non-zero selection is made.