PACKAGE GAS ELECTRIC UNITS
TGC SERIES HIGH EFFICIENCY 13-SEER
NOMINAL SIZES 3-5 TONS
C VINTAGE
ENGINEERING DESIGN GUIDE
TABLE2 OF CONTENTS
Model Identification........................................................................................... |
3 |
Engineering Features ............................................................................... |
4 |
Introduction ............................................................................................. |
5 |
Selection Procedure ................................................................................. |
6 |
General Data ... ................................................................................ |
7-10 |
Performance Data.............................................................................. |
11-12 |
Airflow Performance........................................................................... |
13-16 |
Electrical Data ...................................................................................... |
17 |
Dimensional Data ............................................................................. |
18-20 |
Accessories ...................................................................................... |
21-28 |
Typical Wiring .................................................................................... |
29-35 |
Heat Controller, Inc.
-2-
3 |
MODEL IDENTIFICATION |
MODEL NOMENCLATURE - TGC SERIES
T G C |
|
036 |
|
C |
- |
1 |
|
K |
- |
120 |
|
|
|
|
|
|
|
|
|
|
|
Heating Input (BTUH)
120 = 120,000
135 = 135,000
Drive Package
K = Direct Drive
Electrical Designation
1 = 208-230 V, 1 PH, 60 Hz
4 = 460 V, 3 PH, 60 Hz
3 = 208-230 V, 3 PH, 60 Hz
Vintage
Cooling Capacity (BTUH Nominal)
036 = 36,000
042 = 42,000
048 = 48,000
060 = 60,000
Package Gas Electric Rooftop
Heat Controller, Inc.
-3-
ENGINEERING4 FEATURES
ENGINEERING FEATURES
TGC Series Package Gas Electric Units
1.All models feature Copeland® Scroll® compressors offering maximum reliability, efficiency, and quiet operation.
2.Aluminized steel heat exchanger with in-shot burners helps eliminate corrosion.
3.Integrated blower/burner control board with built-in diagnostic capability permits on-site trouble shooting.
4.One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" raised flanges for supply/return air connections provides superior water management.
5.Convertible horizontal and vertical airflow design allows maximum field flexibility and minimizes inventory requirements.
6.Standard full perimeter forkable 14 gauge baserail with lifting holes for easier maneuvering and installations.
7.Factory installed one-inch throw away filter with provisions for two-inch filter.
8.Direct drive blowers to accommodate a wide range of design conditions.
9.Easily removable filter, blower, gas heat, and compressor/control access panels permits prompt service.
10.Number and color coded wiring helps facilitate service and maintenance.
11.Common cabinet and components allows for installation flexibility and fewer parts to inventory.
12.Standard freezestat control offers evaporator coil freeze protection.
13.Optional field installed high and low pressure controls.
14.Externally mounted refrigerant gauge ports for easy service diagnostics.
15.Side and base electric power and gas connection entry helps minimize roof penetrations.
16.Quick assembly common roof curbs helps save field labor and maximize size flexibility.
17.Easy to install, plug-in, slip-in, 100% fully modulating economizers.
18.Quality powder paint finish offers long lasting protection against extreme weather conditions and is able to withstand 1000 HR salt spray test.
Heat Controller, Inc.
-4-
5 |
INTRODUCTION |
These quality features are included in the Heat Controller Package Gas Electric Unit
Evaporator Coil/Filter Access
•Return air filters, normally provided, are removed in this photo.
•Corrosion resistant plastic condensate pan
Tubular Heat Exchanger
•Aluminized steel (viewed from supply air side panel.)
•Stainless steel available
Control Box Access
Compressor Access
Blower Access
•Belt drive model shown.
(On 460 volt 3-phase 5 ton model only.)
Heating Compartment Access
Heat Controller, Inc.
-5-
SELECTION6 PROCEDURE EXAMPLE
1.Determine cooling and heating requirements at design conditions.
Example:
Total cooling capacity ........................ |
43,600 BTUH |
Sensible cooling capacity .................. |
34,000 BTUH |
Heating capacity ................................ |
96,000 BTUH |
Condenser entering air ...................... |
95°F |
Evaporator entering air ...................... |
63°F wbt/76°F dbt |
Indoor air flow .................................... |
1600 CFM |
External static pressure...................... |
0.6 in wg |
Required efficiency ............................ |
13 SEER |
2.Select unit to meet cooling requirements.
Since total cooling is within the range of 4 ton unit and
requires 13 SEER efficiency level, enter cooling performance from the TGC048C at 95°F outdoor temperature, 63°F wbt
entering indoor air, and 1550 CFM:
Total capacity |
....................................47,300 BTUH |
Power input ........................................ |
3.5 kW |
And also, at 76°F db indoor entering air, and using the formula
at the bottom of the table: |
|
Sensible capacity .............................. |
41,708 BTUH |
3.Select heating capacity of the unit.
In the general data tables, note that the heating capacity of the 4 ton model with the 135,000 input heater can deliver 106,500
BTUH, which is suitable for this application.
4.Determine blower speed and power to meet the system
requirements.
At the given external static pressure of 0.6 in wg, the belt model must be selected. Enter the belt drive blower performance data at 1580 CFM and 0.6 in wg ESP:
Watts........ |
635 |
5.Calculate indoor blower BTUH heat effect.
BTUH = Watts x 3.413 = 2168
6.Calculate net cooling capacities.
Net total cooling = 47,300 – 2168 = 45,132 BTUH
Net sensible cooling = 41,708 – 2168 = 39,540 BTUH
Heat Controller, Inc.
-6-
GENERAL7 DATA
NOMINAL 3 TONS
Model |
TGC036C-1K-120 |
TGC036C-3K-120 |
TGC036C-4K-120 |
Cooling Performance1 |
|
|
|
Gross Cooling Capacity Btuh |
37400 |
37400 |
37400 |
EER/SEER2 |
11.7/13 |
11.7/13 |
11.7/13 |
Nominal CFM/ARI Rated CFM |
1200/1200 |
1200/1200 |
1200/1200 |
ARI Net Cooling Capacity Btuh |
36000 |
36000 |
36000 |
Net Sensible Capacity Btuh |
26400 |
26400 |
26400 |
Net Latent Capacity Btuh |
9600 |
9600 |
9600 |
Net System Power kW |
3.08 |
3.08 |
3.08 |
Heating Performance (Package Gas/Electric) 3 |
|
|
|
Heating Input Btuh |
120000 |
120000 |
120000 |
Heating Output Btuh |
94500 |
97200 |
97200 |
Temperature Rise ºF |
50-80 |
50-80 |
50-80 |
AFUE (%) |
80 |
80 |
80 |
Steady State Efficiency (%) |
81 |
81 |
81 |
Qty of Burners |
6 |
6 |
6 |
Qty of Stages |
1 |
1 |
1 |
Gas Connection Pipe Size, in. |
.5 |
.5 |
.5 |
Compressor |
|
1/Copeland Scroll |
|
Qty/Type |
|
|
|
Outdoor Sound Rating (dB) |
78 |
78 |
78 |
Outdoor Coil—Fin Type |
|
Louvered |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. OD |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
16.91 |
16.91 |
16.91 |
Rows / Fins per inch |
1/22 |
1/22 |
1/22 |
Indoor Coil—Fin Type |
|
Corrugated |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
5.17 |
5.17 |
5.17 |
Rows / Fins per inch |
2/17 |
2/17 |
2/17 |
Refrigerant Control |
TXV |
TXV |
TXV |
Drain Connection Qty/Size, in. |
1/0.75 |
1/0.75 |
1/0.75 |
Outdoor Fan—Type |
|
Propeller |
|
Qty Used/Diameter in. |
1/24 |
1/24 |
1/24 |
Drive Type/Speeds |
Direct/1 |
Direct/1 |
Direct/1 |
CFM |
3680 |
3680 |
3680 |
Qty Motors-HP |
1-1/3 |
1-1/3 |
1-1/3 |
Motor RPM |
1075 |
1075 |
1075 |
Indoor Fan—Type |
|
Forward Curved Centrifugal |
|
Qty Used/Diameter in. |
1/10x10 |
1/10x10 |
1/10x10 |
Drive Type/Speeds |
Direct/3 |
Direct/3 |
Direct/3 |
Motor Qty |
1 |
1 |
1 |
Motor HP |
1/2 |
1/2 |
1/2 |
Motor RPM |
1075 |
1075 |
1075 |
Motor Frame Size |
48 |
48 |
48 |
Filter—Type |
|
Disposable |
|
Furnished |
Yes |
Yes |
Yes |
(Qty) Size Recommended in. |
(2)16x25x1 |
(2)16x25x1 |
(2)16x25x1 |
Refrigerant Charge Oz. |
93 |
93 |
93 |
Weights |
|
|
|
Net Weight lbs. |
543 |
543 |
543 |
Ship Weight lbs. |
550 |
550 |
550 |
Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.
2.EER/SEER are rated ARI condition and accordance with DOE test procedures.
3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
Heat Controller, Inc.
-7-
8
NOMINAL 3.5 TONS
GENERAL DATA
Model |
TGC042C-1K-120 |
TGC042C-3K-120 |
TGC042C-4K-120 |
Cooling Performance1 |
|
|
|
Gross Cooling Capacity Btuh |
43000 |
43000 |
43000 |
EER/SEER2 |
11.45/13 |
11.45/13 |
11.45/13 |
Nominal CFM/ARI Rated CFM |
1400/1450 |
1400/1450 |
1400/1450 |
ARI Net Cooling Capacity Btuh |
41000 |
41000 |
41000 |
Net Sensible Capacity Btuh |
30000 |
30000 |
30000 |
Net Latent Capacity Btuh |
11000 |
11000 |
11000 |
Net System Power kW |
3.59 |
3.59 |
3.59 |
Heating Performance (Package Gas/Electric) 3 |
|
|
|
Heating Input Btuh |
120000 |
120000 |
120000 |
Heating Output Btuh |
94500 |
97200 |
97200 |
Temperature Rise ºF |
50-80 |
50-80 |
50-80 |
AFUE (%) |
80 |
80 |
80 |
Steady State Efficiency (%) |
81 |
81 |
81 |
Qty of Burners |
6 |
6 |
6 |
Qty of Stages |
1 |
1 |
1 |
Gas Connection Pipe Size, in. |
.5 |
.5 |
.5 |
Compressor |
|
1/Copeland Scroll |
|
Qty/Type |
|
|
|
Outdoor Sound Rating (dB) |
78 |
78 |
78 |
Outdoor Coil—Fin Type |
|
Louvered |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. OD |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
16.91 |
16.91 |
16.91 |
Rows / Fins per inch |
1.53/22 |
1.53/22 |
1.53/22 |
Indoor Coil—Fin Type |
|
Corrugated |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
5.17 |
5.17 |
5.17 |
Rows / Fins per inch |
3/13 |
3/13 |
3/13 |
Refrigerant Control |
TXV |
TXV |
TXV |
Drain Connection Qty/Size, in. |
1/0.75 |
1/0.75 |
1/0.75 |
Outdoor Fan—Type |
|
Propeller |
|
Qty Used/Diameter in. |
1/24 |
1/24 |
1/24 |
Drive Type/Speeds |
Direct/1 |
Direct/1 |
Direct/1 |
CFM |
3680 |
3680 |
3680 |
Qty Motors-HP |
1-1/3 |
1-1/3 |
1-1/3 |
Motor RPM |
1075 |
1075 |
1075 |
Indoor Fan—Type |
|
Forward Curved Centrifugal |
|
Qty Used/Diameter in. |
1/10x10 |
1/10x10 |
1/10x10 |
Drive Type/Speeds |
Direct/3 |
Direct/3 |
Direct/3 |
Motor Qty |
1 |
1 |
1 |
Motor HP |
1/2 |
1/2 |
1/2 |
Motor RPM |
1725 |
1725 |
1725 |
Motor Frame Size |
48 |
48 |
48 |
Filter—Type |
|
Disposable |
|
Furnished |
Yes |
Yes |
Yes |
(Qty) Size Recommended in. |
(2)16x25x1 |
(2)16x25x1 |
(2)16x25x1 |
Refrigerant Charge Oz. |
117 |
117 |
117 |
Weights |
|
|
|
Net Weight lbs. |
579 |
579 |
579 |
Ship Weight lbs. |
586 |
586 |
586 |
Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.
2.EER/SEER are rated ARI condition and accordance with DOE test procedures.
3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
Heat Controller, Inc.
-8-
GENERAL9 DATA
NOMINAL 4 TONS
Model |
TGC048C-1K-135 |
TGC048C-3K-135 |
TGC048C-4K-135 |
Cooling Performance1 |
|
|
|
Gross Cooling Capacity Btuh |
49000 |
49000 |
49000 |
EER/SEER2 |
11.4/13.1 |
11.4/13.1 |
11.4/13.1 |
Nominal CFM/ARI Rated CFM |
1600/1550 |
1600/1550 |
1600/1550 |
ARI Net Cooling Capacity Btuh |
47000 |
47000 |
47000 |
Net Sensible Capacity Btuh |
33600 |
33600 |
33600 |
Net Latent Capacity Btuh |
13400 |
13400 |
13400 |
Net System Power kW |
4.15 |
4.15 |
4.15 |
Heating Performance (Package Gas/Electric) 3 |
|
|
|
Heating Input Btuh |
135000 |
135000 |
135000 |
Heating Output Btuh |
106500 |
109400 |
109400 |
Temperature Rise ºF |
50-80 |
50-80 |
50-80 |
AFUE (%) |
80 |
80 |
80 |
Steady State Efficiency (%) |
81 |
81 |
81 |
Qty of Burners |
6 |
6 |
6 |
Qty of Stages |
1 |
1 |
1 |
Gas Connection Pipe Size, in. |
.5 |
.5 |
.5 |
Compressor |
|
1/Copeland Scroll |
|
Qty/Type |
|
|
|
Outdoor Sound Rating (dB) |
78 |
78 |
78 |
Outdoor Coil—Fin Type |
|
Louvered |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. OD |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
16.56 |
16.56 |
16.56 |
Rows / Fins per inch |
2/22 |
2/22 |
2/22 |
Indoor Coil—Fin Type |
|
Corrugated |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
5.17 |
5.17 |
5.17 |
Rows / Fins per inch |
3/15 |
3/15 |
3/15 |
Refrigerant Control |
TXV |
TXV |
TXV |
Drain Connection Qty/Size, in. |
1/0.75 |
1/0.75 |
1/0.75 |
Outdoor Fan—Type |
|
Propeller |
|
Qty Used/Diameter in. |
1/24 |
1/24 |
1/24 |
Drive Type/Speeds |
Direct/1 |
Direct/1 |
Direct/1 |
CFM |
3680 |
3680 |
3680 |
Qty Motors-HP |
1-1/3 |
1-1/3 |
1-1/3 |
Motor RPM |
1075 |
1075 |
1075 |
Indoor Fan—Type |
|
Forward Curved Centrifugal |
|
Qty Used/Diameter in. |
1/10x10 |
1/10x10 |
1/10x10 |
Drive Type/Speeds |
Direct/3 |
Direct/3 |
Direct/3 |
Motor Qty |
1 |
1 |
1 |
Motor HP |
1/2 |
1/2 |
1/2 |
Motor RPM |
1075 |
1075 |
1075 |
Motor Frame Size |
48 |
48 |
48 |
Filter—Type |
|
Disposable |
|
Furnished |
Yes |
Yes |
Yes |
(Qty) Size Recommended in. |
(2)16x25x1 |
(2)16x25x1 |
(2)16x25x1 |
Refrigerant Charge Oz. |
167 |
167 |
167 |
Weights |
|
|
|
Net Weight lbs. |
585 |
585 |
585 |
Ship Weight lbs. |
592 |
592 |
592 |
Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.
2.EER/SEER are rated ARI condition and accordance with DOE test procedures.
3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
Heat Controller, Inc.
-9-
GENERAL10 DATA
NOMINAL 5 TONS
Model |
TGC060C-1K-135 |
TGC060C-3K-135 |
TGC060C-4K-135 |
Cooling Performance1 |
|
|
|
Gross Cooling Capacity Btuh |
60000 |
60000 |
60000 |
EER/SEER2 |
11.6/13 |
11.6/13 |
11.6/13 |
Nominal CFM/ARI Rated CFM |
2000/1900 |
2000/1900 |
2000/1900 |
ARI Net Cooling Capacity Btuh |
58000 |
58000 |
58000 |
Net Sensible Capacity Btuh |
42000 |
42000 |
42000 |
Net Latent Capacity Btuh |
16000 |
16000 |
16000 |
Net System Power kW |
5 |
5 |
5 |
Heating Performance (Package Gas/Electric) 3 |
|
|
|
Heating Input Btuh |
135000 |
135000 |
135000 |
Heating Output Btuh |
106500 |
109400 |
109400 |
Temperature Rise ºF |
40-70 |
40-70 |
40-70 |
AFUE (%) |
80 |
80 |
80 |
Steady State Efficiency (%) |
81 |
81 |
81 |
Qty of Burners |
6 |
6 |
6 |
Qty of Stages |
1 |
1 |
1 |
Gas Connection Pipe Size, in. |
.5 |
.5 |
.5 |
Compressor |
|
1/Copeland Scroll |
|
Qty/Type |
|
|
|
Outdoor Sound Rating (dB) |
83 |
78 |
78 |
Outdoor Coil—Fin Type |
|
Louvered |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. OD |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
16.56 |
16.56 |
16.56 |
Rows / Fins per inch |
2/22 |
2/22 |
2/22 |
Indoor Coil—Fin Type |
|
Corrugated |
|
Tube Type |
Rifled |
Rifled |
Rifled |
Tube Size in. |
0.375 |
0.375 |
0.375 |
Face Area sq. ft. |
5.17 |
5.17 |
5.17 |
Rows / Fins per inch |
3/15 |
3/15 |
3/15 |
Refrigerant Control |
TXV |
TXV |
TXV |
Drain Connection Qty/Size, in. |
1/0.75 |
1/0.75 |
1/0.75 |
Outdoor Fan—Type |
|
Propeller |
|
Qty Used/Diameter in. |
1/24 |
1/24 |
1/24 |
Drive Type/Speeds |
Direct/1 |
Direct/1 |
Direct/1 |
CFM |
3930 |
3930 |
3930 |
Qty Motors-HP |
1-1/3 |
1-1/3 |
1-1/3 |
Motor RPM |
1075 |
1075 |
1075 |
Indoor Fan—Type |
|
Forward Curved Centrifugal |
|
Qty Used/Diameter in. |
1/10x10 |
1/10x10 |
1/10x10 |
Drive Type/Speeds |
Direct/3 |
Direct/3 |
Belt/Variable |
Motor Qty |
1 |
1 |
1 |
Motor HP |
1 |
1 |
3/4 |
Motor RPM |
1075 |
1075 |
1725 |
Motor Frame Size |
48 |
48 |
56 |
Filter—Type |
|
Disposable |
|
Furnished |
Yes |
Yes |
Yes |
(Qty) Size Recommended in. |
(2)16x25x1 |
(2)16x25x1 |
(2)16x25x1 |
Refrigerant Charge Oz. |
160 |
160 |
160 |
Weights |
|
|
|
Net Weight lbs. |
597 |
597 |
597 |
Ship Weight lbs. |
604 |
604 |
604 |
Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.
2.EER/SEER are rated ARI condition and accordance with DOE test procedures.
3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
Heat Controller, Inc.
-10-
|
11 |
|
|
|
|
|
|
|
|
|
|
|
|
SYSTEM PERFORMANCE |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GROSS SYSTEM PERFORMANCE DATA—TGC036C |
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE |
|
|
|
|
|
|
|
|
|||||||
|
|
|
wbE |
|
|
|
71°F [21.7°C] |
|
|
|
|
67°F [19.4°C] |
|
|
|
|
63°F [17.2°C] |
|
|
||||
|
CFM [L/s] |
1500 [707.9] |
|
1200 [566.3] |
900 [424.8] |
1500 [707.9] |
1200 [566.3] |
|
900 [424.8] |
1500 [707.9] |
1200 [566.3] |
900 [424.8] |
|||||||||||
|
|
DR |
|
.16 |
|
|
.12 |
|
.06 |
|
.16 |
|
.12 |
|
|
.06 |
|
.16 |
|
.12 |
|
.06 |
|
|
75 |
|
Total BTUH [kW] |
45.5 [13.33] |
|
43.5 [12.75] |
41.6 [12.19] |
42.7 [12.51] |
40.9 [11.99] |
|
39.0 [11.43] |
40.3 [11.81] |
38.6 [11.31] |
36.8 [10.79] |
|||||||||
|
|
Sens BTUH [kW] |
27.9 |
[8.18] |
|
24.9 |
[7.30] |
22.0 |
[6.45] |
33.1 |
[9.70] |
29.7 |
[8.70] |
|
26.2 |
[7.68] |
37.6 [11.02] |
33.7 |
[9.88] |
29.8 |
[8.73] |
||
|
[23.9] |
|
|
|
|||||||||||||||||||
O |
|
Power |
|
2.2 |
|
|
2.2 |
|
2.1 |
|
2.2 |
|
2.1 |
|
|
2.1 |
|
2.2 |
|
2.1 |
|
2.1 |
|
|
|
Total BTUH [kW] |
44.6 [13.07] |
|
42.6 [12.48] |
40.7 [11.93] |
41.8 [12.25] |
40.0 [11.72] |
|
38.1 [11.17] |
39.4 [11.55] |
37.7 [11.05] |
35.9 [10.52] |
||||||||||
|
|
|
|
||||||||||||||||||||
U |
80 |
|
|
|
|||||||||||||||||||
T |
|
Sens BTUH [kW] |
27.2 |
[7.97] |
|
24.4 |
[7.15] |
21.5 |
[6.30] |
32.5 |
[9.52] |
29.1 |
[8.53] |
|
25.7 |
[7.53] |
37.0 [10.84] |
33.2 |
[9.73] |
29.3 |
[8.59] |
||
[26.7] |
|
|
|
||||||||||||||||||||
D |
|
Power |
|
2.3 |
|
|
2.3 |
|
2.2 |
|
2.3 |
|
2.3 |
|
|
2.2 |
|
2.3 |
|
2.3 |
|
2.2 |
|
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O |
85 |
|
Total BTUH [kW] |
43.7 [12.81] |
|
41.8 [12.25] |
39.9 [11.69] |
40.9 [11.99] |
39.1 [11.46] |
|
37.4 [10.96] |
38.5 [11.28] |
36.8 [10.79] |
35.1 [10.29] |
|||||||||
R |
|
Sens BTUH [kW] |
26.7 |
[7.83] |
|
23.9 |
[7.00] |
21.1 |
[6.18] |
32.0 |
[9.38] |
28.7 |
[8.41] |
|
25.3 |
[7.41] |
36.5 [10.70] |
32.7 |
[9.58] |
28.9 |
[8.47] |
||
|
[29.4] |
|
|
|
|||||||||||||||||||
D |
|
Power |
|
2.5 |
|
|
2.4 |
|
2.4 |
|
2.4 |
|
2.4 |
|
|
2.3 |
|
2.4 |
|
2.4 |
|
2.3 |
|
R |
90 |
|
Total BTUH [kW] |
42.9 [12.57] |
|
41.0 [12.02] |
39.1 [11.46] |
40.1 [11.75] |
38.3 [11.22] |
|
36.6 [10.73] |
37.6 [11.02] |
36.0 [10.55] |
34.4 [10.08] |
|||||||||
Y |
|
|
|
||||||||||||||||||||
|
Sens BTUH [kW] |
26.3 |
[7.71] |
|
23.6 |
[6.92] |
20.8 |
[6.10] |
31.6 |
[9.26] |
28.3 |
[8.29] |
|
25.0 |
[7.33] |
36.1 [10.58] |
32.3 |
[9.47] |
28.5 |
[8.35] |
|||
|
[32.2] |
|
|
|
|||||||||||||||||||
B |
|
Power |
|
2.6 |
|
|
2.5 |
|
2.5 |
|
2.6 |
|
2.5 |
|
|
2.5 |
|
2.6 |
|
2.5 |
|
2.5 |
|
U |
|
|
Total BTUH [kW] |
42.0 [12.31] |
|
40.2 [11.78] |
38.3 [11.22] |
39.2 [11.49] |
37.5 [10.99] |
|
35.8 [10.49] |
36.8 [10.79] |
35.2 [10.32] |
33.6 |
[9.85] |
||||||||
|
|
|
|
||||||||||||||||||||
L |
95 |
|
|
|
|||||||||||||||||||
B |
|
Sens BTUH [kW] |
25.9 |
[7.59] |
|
23.2 |
[6.80] |
20.5 |
[6.01] |
31.1 |
[9.11] |
27.9 |
[8.18] |
|
24.6 |
[7.21] |
35.7 [10.46] |
31.9 |
[9.35] |
28.2 |
[8.26] |
||
[35] |
|
|
|
||||||||||||||||||||
|
|
Power |
|
2.7 |
|
|
2.6 |
|
2.6 |
|
2.7 |
|
2.6 |
|
|
2.6 |
|
2.7 |
|
2.6 |
|
2.6 |
|
T |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
E |
100 |
|
Total BTUH [kW] |
41.1 [12.05] |
|
39.3 [11.52] |
37.5 [10.99] |
38.3 [11.22] |
36.6 [10.73] |
|
34.9 [10.23] |
35.8 [10.49] |
34.3 [10.05] |
32.7 |
[9.58] |
||||||||
M |
|
Sens BTUH [kW] |
25.4 |
[7.44] |
|
22.8 |
[6.68] |
20.1 |
[5.89] |
30.7 |
[9.00] |
27.5 |
[8.06] |
|
24.3 |
[7.12] |
35.2 [10.32] |
31.5 |
[9.23] |
27.8 |
[8.15] |
||
P |
[37.8] |
|
|
|
|||||||||||||||||||
E |
|
|
Power |
|
2.8 |
|
|
2.8 |
|
2.7 |
|
2.8 |
|
2.8 |
|
|
2.7 |
|
2.8 |
|
2.8 |
|
2.7 |
R |
105 |
|
Total BTUH [kW] |
40.0 [11.72] |
|
38.3 [11.22] |
36.5 [10.70] |
37.2 [10.90] |
35.6 [10.43] |
|
34.0 |
[9.96] |
34.8 [10.20] |
33.3 |
[9.76] |
31.8 |
[9.32] |
||||||
A |
|
Sens BTUH [kW] |
24.9 |
[7.30] |
|
22.3 |
[6.54] |
19.7 |
[5.77] |
30.1 |
[8.82] |
27.0 |
[7.91] |
|
23.8 |
[6.98] |
34.7 [10.17] |
31.0 |
[9.09] |
27.4 |
[8.03] |
||
T |
[40.6] |
|
|
|
|||||||||||||||||||
U |
|
Power |
|
3.0 |
|
|
2.9 |
|
2.8 |
|
3.0 |
|
2.9 |
|
|
2.8 |
|
2.9 |
|
2.9 |
|
2.8 |
|
R |
|
|
Total BTUH [kW] |
38.8 [11.37] |
|
37.1 [10.87] |
35.4 [10.37] |
36.0 [10.55] |
34.4 [10.08] |
|
32.8 |
[9.61] |
33.6 |
[9.85] |
32.1 |
[9.41] |
30.6 |
[8.97] |
|||||
|
|
|
|
||||||||||||||||||||
E |
110 |
|
|
|
|||||||||||||||||||
|
Sens BTUH [kW] |
24.2 |
[7.09] |
|
21.7 |
[6.36] |
19.1 |
[5.60] |
29.4 |
[8.62] |
26.4 |
[7.74] |
|
23.3 |
[6.83] |
33.6 |
[9.85] |
30.4 |
[8.91] |
26.9 |
[7.88] |
||
°F |
[43.3] |
|
|
|
|||||||||||||||||||
|
Power |
|
3.1 |
|
|
3.0 |
|
3.0 |
|
3.1 |
|
3.0 |
|
|
3.0 |
|
3.1 |
|
3.0 |
|
2.9 |
||
[°C] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
115 |
|
Total BTUH [kW] |
37.3 [10.93] |
|
35.7 [10.46] |
34.1 |
[9.99] |
34.5 [10.11] |
33.0 |
[9.67] |
|
31.5 |
[9.23] |
32.1 |
[9.41] |
30.7 |
[9.00] |
29.3 |
[8.59] |
||||
|
|
|
|
||||||||||||||||||||
|
|
Sens BTUH [kW] |
23.3 |
[6.83] |
|
20.9 |
[6.13] |
18.4 |
[5.39] |
28.6 |
[8.38] |
25.6 |
[7.50] |
|
22.6 |
[6.62] |
32.1 |
[9.41] |
29.6 |
[8.67] |
26.2 |
[7.68] |
|
|
[46.1] |
|
|
|
|||||||||||||||||||
|
|
|
Power |
|
3.2 |
|
|
3.1 |
|
3.1 |
|
3.2 |
|
3.1 |
|
|
3.1 |
|
3.2 |
|
3.1 |
|
3.1 |
GROSS SYSTEM PERFORMANCE DATA—TGC042C |
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE |
|
|
|
|
|
|
|
|
|||||||
|
|
|
wbE |
|
|
|
71°F [21.7°C] |
|
|
|
|
67°F [19.4°C] |
|
|
|
|
63°F [17.2°C] |
|
|
||||
|
CFM [L/s] |
1810 [854.2] |
1450 [684.3] |
1090 [514.4] |
1810 [854.2] |
1450 [684.3] |
|
1090 [514.4] |
1810 [854.2] |
1450 [684.3] |
1090 [514.4] |
||||||||||||
|
|
DR |
|
.23 |
|
|
.2 |
|
.15 |
|
.23 |
|
.2 |
|
|
.15 |
|
.23 |
|
.2 |
|
.15 |
|
|
75 |
|
Total BTUH [kW] |
53.2 [15.59] |
50.9 [14.92] |
48.6 [14.24] |
49.3 [14.45] |
47.1 [13.80] |
|
45.0 [13.19] |
46.0 [13.48] |
44.0 [12.90] |
42.0 [12.31] |
||||||||||
|
|
Sens BTUH [kW] |
32.4 |
[9.50] |
29.1 |
[8.53] |
25.7 |
[7.53] |
38.2 [11.20] |
34.2 [10.02] |
|
30.2 |
[8.85] |
43.6 [12.78] |
39.0 [11.43] |
34.5 [10.11] |
|||||||
|
[23.9] |
|
|
||||||||||||||||||||
O |
|
Power |
|
2.5 |
|
|
2.5 |
|
2.4 |
|
2.5 |
|
2.5 |
|
|
2.4 |
|
2.5 |
|
2.5 |
|
2.4 |
|
|
|
Total BTUH [kW] |
51.9 [15.21] |
49.6 [14.54] |
47.4 [13.89] |
48.0 [14.07] |
45.9 [13.45] |
|
43.8 [12.84] |
44.7 [13.10] |
42.7 [12.51] |
40.8 [11.96] |
|||||||||||
U |
80 |
|
|
||||||||||||||||||||
T |
|
Sens BTUH [kW] |
31.9 |
[9.35] |
28.6 |
[8.38] |
25.2 |
[7.39] |
37.7 [11.05] |
33.8 |
[9.91] |
|
29.8 |
[8.73] |
43.0 [12.60] |
38.5 [11.28] |
34.0 |
[9.96] |
|||||
[26.7] |
|
|
|||||||||||||||||||||
D |
|
Power |
|
2.7 |
|
|
2.6 |
|
2.6 |
|
2.7 |
|
2.6 |
|
|
2.6 |
|
2.7 |
|
2.6 |
|
2.6 |
|
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O |
85 |
|
Total BTUH [kW] |
50.8 [14.89] |
48.6 [14.24] |
46.4 [13.60] |
46.8 [13.72] |
44.8 [13.13] |
|
42.8 [12.54] |
43.6 [12.78] |
41.7 [12.22] |
39.8 [11.66] |
||||||||||
R |
|
Sens BTUH [kW] |
31.3 |
[9.17] |
28.0 |
[8.21] |
24.7 |
[7.24] |
37.1 [10.87] |
33.2 |
[9.73] |
|
29.3 |
[8.59] |
42.4 [12.43] |
38.0 [11.14] |
33.5 |
[9.82] |
|||||
|
[29.4] |
|
|
||||||||||||||||||||
D |
|
Power |
|
2.8 |
|
|
2.8 |
|
2.7 |
|
2.8 |
|
2.7 |
|
|
2.7 |
|
2.8 |
|
2.7 |
|
2.7 |
|
R |
90 |
|
Total BTUH [kW] |
49.8 [14.59] |
47.6 [13.95] |
45.4 [13.31] |
45.8 [13.42] |
43.8 [12.84] |
|
41.9 [12.28] |
42.6 [12.48] |
40.7 [11.93] |
38.9 [11.40] |
||||||||||
Y |
|
|
|||||||||||||||||||||
|
Sens BTUH [kW] |
30.6 |
[8.97] |
27.4 |
[8.03] |
24.2 |
[7.09] |
36.4 [10.67] |
32.6 |
[9.55] |
|
28.8 |
[8.44] |
41.7 [12.22] |
37.4 [10.96] |
33.0 |
[9.67] |
||||||
|
[32.2] |
|
|
||||||||||||||||||||
B |
|
Power |
|
3.0 |
|
|
2.9 |
|
2.8 |
|
2.9 |
|
2.9 |
|
|
2.8 |
|
2.9 |
|
2.9 |
|
2.8 |
|
U |
|
|
Total BTUH [kW] |
48.8 [14.30] |
46.7 [13.69] |
44.6 [13.07] |
44.9 [13.16] |
42.9 [12.57] |
|
41.0 [12.02] |
41.6 [12.19] |
39.8 [11.66] |
38.0 [11.14] |
||||||||||
|
|
|
|||||||||||||||||||||
L |
95 |
|
|
||||||||||||||||||||
B |
|
Sens BTUH [kW] |
29.9 |
[8.76] |
26.7 |
[7.83] |
23.6 |
[6.92] |
35.7 [10.46] |
31.9 |
[9.35] |
|
28.2 |
[8.26] |
41.0 [12.02] |
36.7 [10.76] |
32.4 |
[9.50] |
|||||
[35] |
|
|
|||||||||||||||||||||
|
|
Power |
|
3.1 |
|
|
3.0 |
|
3.0 |
|
3.1 |
|
3.0 |
|
|
3.0 |
|
3.1 |
|
3.0 |
|
3.0 |
|
T |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
E |
100 |
|
Total BTUH [kW] |
47.8 [14.01] |
45.7 [13.39] |
43.7 [12.81] |
43.9 [12.87] |
42.0 [12.31] |
|
40.1 [11.75] |
40.6 [11.90] |
38.9 [11.40] |
37.1 [10.87] |
||||||||||
M |
|
Sens BTUH [kW] |
29.2 |
[8.56] |
26.1 |
[7.65] |
23.1 |
[6.77] |
35.0 [10.26] |
31.3 |
[9.17] |
|
27.7 |
[8.12] |
40.3 [11.81] |
36.1 [10.58] |
31.9 |
[9.35] |
|||||
P |
[37.8] |
|
|
||||||||||||||||||||
E |
|
|
Power |
|
3.3 |
|
|
3.2 |
|
3.1 |
|
3.2 |
|
3.2 |
|
|
3.1 |
|
3.2 |
|
3.2 |
|
3.1 |
R |
105 |
|
Total BTUH [kW] |
46.8 [13.72] |
44.7 [13.10] |
42.7 [12.51] |
42.8 [12.54] |
41.0 [12.02] |
|
39.1 [11.46] |
39.6 [11.61] |
37.8 [11.08] |
36.1 [10.58] |
||||||||||
A |
|
Sens BTUH [kW] |
28.6 |
[8.38] |
25.6 |
[7.50] |
22.6 |
[6.62] |
34.4 [10.08] |
30.8 |
[9.03] |
|
27.2 |
[7.97] |
39.6 [11.61] |
35.6 [10.43] |
31.4 |
[9.20] |
|||||
T |
[40.6] |
|
|
||||||||||||||||||||
U |
|
Power |
|
3.4 |
|
|
3.3 |
|
3.3 |
|
3.4 |
|
3.3 |
|
|
3.2 |
|
3.4 |
|
3.3 |
|
3.2 |
|
R |
|
|
Total BTUH [kW] |
45.5 [13.33] |
43.5 [12.75] |
41.6 [12.19] |
41.6 [12.19] |
39.8 [11.66] |
|
38.0 [11.14] |
38.3 [11.22] |
36.7 [10.76] |
35.0 [10.26] |
||||||||||
|
|
|
|||||||||||||||||||||
E |
110 |
|
|
||||||||||||||||||||
|
Sens BTUH [kW] |
28.1 |
[8.24] |
25.1 |
[7.36] |
22.2 |
[6.51] |
33.9 |
[9.94] |
30.3 |
[8.88] |
|
26.8 |
[7.85] |
38.3 [11.22] |
35.1 [10.29] |
31.0 |
[9.09] |
|||||
°F |
[43.3] |
|
|
||||||||||||||||||||
|
Power |
|
3.5 |
|
|
3.5 |
|
3.4 |
|
3.5 |
|
3.4 |
|
|
3.4 |
|
3.5 |
|
3.4 |
|
3.4 |
||
[°C] |
|
|
Total BTUH [kW] |
44.1 [12.92] |
42.1 [12.34] |
40.2 [11.78] |
40.1 [11.75] |
38.4 [11.25] |
|
36.7 [10.76] |
36.9 [10.81] |
35.3 [10.35] |
33.7 |
[9.88] |
|||||||||
115 |
|
|
|||||||||||||||||||||
|
|
|
|||||||||||||||||||||
|
|
Sens BTUH [kW] |
27.7 |
[8.12] |
24.8 |
[7.27] |
21.9 |
[6.42] |
33.5 |
[9.82] |
30.0 |
[8.79] |
|
26.5 |
[7.77] |
36.9 [10.81] |
34.8 [10.20] |
30.7 |
[9.00] |
||||
|
[46.1] |
|
|
||||||||||||||||||||
|
|
Power |
|
3.7 |
|
|
3.6 |
|
3.5 |
|
3.6 |
|
3.6 |
|
|
3.5 |
|
3.6 |
|
3.6 |
|
3.5 |
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
Heat Controller, Inc. |
[ ] Designates Metric Conversions |
|
|