Heat & Glo LifeStyle TIARAP-CES User Manual

Size:
5.4 Mb
Download

Owner’s Manual

Installation and Operation

TIARA PETITE B

DIRECT VENT ROOM HEATER

Model:

TIARAP-BK

TIARAP-BR

TIARAP-CES

TIARAP-CTO

Tested and

O-TL

Portland

Listed by

Oregon USA

 

C

US

OMNI-TestLaboratories, Inc.

CAUTION

DO NOT DISCARD THIS MANUAL

• Important operating and •

Read, understand and

• Leave this manual with

maintenance instructions

follow these instructions

party responsible for use

included.

for safe installation and

and operation.

 

operation.

 

DO DISCARDNOT

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

What to do if you smell gas

-Do not try to light any appliance.

Do not touch any electrical switch. Do not use any phone in your building.

-Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

-If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Installation and service of this appliance should be performed by qualified personnel. Hearth & Home Technologies suggests NFI certified or factory-trainedprofessionals, or technicians supervised by an NFI certified professional.

WARNING

HOT SURFACES!

Glass and other surfaces are hot during operation AND cool down.

Hot glass will cause burns.

Do not touch glass until it is cooled

NEVER allow children to touch glass

Keep children away

CAREFULLY SUPERVISE children in the same room as appliance

Alert children and adults to hazards of high

temperatures

High temperatures may ignite clothing or other flammable materials.

Keep clothing, furniture, draperies and other combustibles away.

In the Commonwealth of Massachusetts:

installation must be performed by a licensed plumber or gas fitter.

See Table of Contents for additional Commonwealth of Massachusetts requirements.

This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer's instructions and the manufactured home construction and safety standard, Title 24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH.

This appliance is only for use with the type(s) of gas indicated on the rating plate.

www.heatnglo.com

7026-101K

August 1, 2008

Read this manual before installing or operating this appliance. Please retain this owner's manual for future reference.

Congratulations

Congratulations on selecting a Heat & Glo gas appliance - an elegant and clean alternative to wood burning appliances. The Heat & Glo gas appliance you have selected is designed to provide the utmost in safety, reliability, and efficiency.

As the owner of a new appliance, you'll want to read and carefully follow all of the instructions contained in this Owner's Manual. Pay special attention to all Cautions and Warnings.

This Owner's Manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.

The information contained in this Owner's Manual, unless noted otherwise, applies to all models and gas control systems.

Your new Heat & Glo gas appliance will give you years of durable use and trouble-freeenjoyment. Welcome to the Heat & Glo family of gas appliance products!

SAMPLE OF RATINGS LABEL LOCATION: Hang tag attached to rear of appliance.

 

 

 

 

 

 

 

 

Serial No / Numéro du

 

 

Tested and

O-TL

Portland

 

 

MODEL / MODÈLE: TIARA PETITE (B)

 

007

 

 

 

 

 

VENTED GAS FIREPLACE HEATER

 

 

 

 

Listed by

Oregon USA

 

 

 

 

 

 

 

C

US

 

NOT FOR USE WITH SOLID FUEL

 

 

 

 

 

OMNI-TestLaboratories, Inc.

 

 

 

A division of Hearth & Home Technologies Inc.

 

 

Report No. / Rapport Numéro

 

 

 

 

 

 

 

FOURNAISE AU GAZ AVEC VENTILATION

 

 

20802 Kensington Boulevard

 

 

 

061-S-47b-5

 

NE PAS UTILISER AVEC LE COMBUSTIBLE SOLIDE

 

 

Lakeville, MN 55044

 

 

 

 

 

 

 

 

 

 

 

 

APPROVED FOR CANADAAND USATO: ANSI Z21.88b-2003 /CSA2.33b-2003Vented Gas Fireplace Heaters, and applicable sections of UL307b Gas Burning HeatingAppliances for Manufactured Homes and Recreational Vehicles,CAN/CGA2.17-M91Gas FiredAppliances for use at HighAltitudes. This appliance is manufactured for operation with Natural Gas. For conversion to propane Manufacturer's instructions must be used. This appliance may be installed in a bedroom or bedsitting room; in Canada remote thermostat installation is required.

APPROUVÉ-POURLE CANADAET LESÉTATS-UNIS:ANSI-Z21.88b-2003 /CSA2.33b-2003Fournaises au Gaz avec Ventilation, et les sections applicable de UL 307bAppareils de ChauffageAu Gaz our les Maisons Mobiles et les Vehicules Motoriss,CAN/CGA2.17-M91Gas FiredAppliances for use at HighAltitudes. Cet appareil est manufactur pour l'operation avec le Gaz Naturel. Pour une conversion au gaz propane les pices du Manufacturier et ses instructions doivent tre utilises. Cet appareil peut tre utilis dans une chambre à coucher ou salle de sjour, au Canada, l'installation d'un thermostat à distance est exige.

FAN TYPE VENTED CIRCULATOR / VENTILATEUR CIRCULATOIRE

Blower Electrical Rating / Evaluation du Ventilateur

115 V., .55 Amps, 60 Hz, 150 Watts

 

P.4.1-02Canada Minimum pipe(P.4.1-02Le Canada tuyau minimum) 67.38% NG / 69.52% LP

Blower is Optional. Order Part #844-9370

 

 

 

Route power cord away from unit. Do not route

 

 

 

power cord under or over stove./Éloignez le fil électrique

 

 

 

de l'appareil. Ne pas faire passer le fil électrique au dessus

For use with Natural Gas

For use with Propane

 

ou en dessous de l'appareil.

Usage Au Gaz Naturel

Usage Au Gaz Propane

 

 

0-2000FT’

0-2000FT

 

Input Rate on “HI” (BTU/Hr)

17,000

17,000

Puissance Évaluée à “HI” (BTU/Hr)

Input Rate on “LO” (BTU/Hr)

12,000

13,000

Puissance Évaluée à “LO” (BTU/Hr)

Maximum Output (BTU/Hr)**

14,500

13,500

Puissance Maximum (BTU/Hr**

Main Burner Orifice

49

56

Orifice du Brûleur Principal

Minimum Inlet Pressure (Inches W.C.)

4.5”

11”

Pression Minimum de la Valve (pouces W.C.)

Maximum Inlet Pressure (Inches W.C.)

7.0”

14”

Pression Maximum de la Valve (pouces W.C.)

Manifold Pressure on “HI” (Inches W.C.)

3.5”

10”

Pression du Collecteur d’ Échappement à “HI” (pouces W.C.)

**Max Venting, Blower On

 

 

E

 

 

**Ventilation Maximum, Ventilateur Allumé

This appliance equipped for altitudes 0-2000’(0-610m)in USA; and in Canada for altitudes of0-4500’P(0-1370m)L.In USA for Altitudes above 2000’, the vent configuration, orifice or combination of both may need to be changed. See Owner’s Manual for information on making these changes. This appliance must be installed in accordance with local codes, if any (and Commonwealth of Massachusetts approved); if none, follow ANSI Z223.1 in USA, CAN1-B149in Canada. Install and use only in accordance with manufacturer’s installation and operating instructions. NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.) / Cet appareil est équipé pour les altitudes de0-2000’(0-610m)auxÉtats-Unis;et au Canada pour les altitudes de0-4500’(0-1370m).Pour les altitudes au dessus de 2000’ auxÉtats-Unis,la configuration du ventilateur, son orifice ou les deux peuvent possiblement avoir à être changé. Voyez le manuel du propriétaire pour les informations sur ces changements. Cet appareil doit être installé en accord avec les codes locaux,s’il-y-alieu (et approuvé par dans la République de Massachusetts); sinon lisez ANSI Z223.1/CAN1-B149.Installez et utilisez en accords avec les instructions d’installation et d’opération du manufacturier. REMARQUE: Le conduit gaz doit être installé conformément aux codes de construction locaux. L'installation doit être effectuée par un technicien qualifeé et/ou muni d'une licence de manière à respecter les règlements municipaux. (Dans la République de Massachusetts, l'installation doit être effectuée par un plombier ou un installateur d'appareils à gaz agrée.)

M

MINIMUM CLEARANCES TO COMBUSTIBLES

/ ESPACE MINIMUM AUX COMBUSTIBLES

Minimum clearances required from combustible construction for all Aappliance surfaces. /

Espaces minimum exigés de la construction combustible aux surfaces de l’appareil.

 

F

S

 

 

 

 

B

C

H

 

 

Right

 

 

 

 

G

A

A

A

A

 

D

 

 

E

 

 

 

 

 

C

 

 

 

 

 

Left

 

 

 

"A" measurement is from

 

 

 

 

stove top, not side

 

 

 

 

A.

Side of stove top to side wall

6" (15cm)

Du coté du poêle au coté du mur

 

B.

Rear of stove to back wall

2" (5cm)

Le contrôle arrière au mur arrière

 

C.

Corner of stove top to side wall-Left

2" (5cm)

Du coin arrière du poêle au mur de coté gauche

C.

Corner of stove top to side wall-Right

2" (5cm)

Du coin du dessus du poêle au mur de coté droit (acces a la valve)

D.

Minimum Alcove Height

 

43" (109cm)

Hauteur minimum du plancher au plafond

 

E.

Maximum Alcove Depth

 

36" (91cm)

Profondeur maximum de l'alcove

 

F.

Minimum Alcove Width

 

30" (76cm)

Largeur minimum de l'alcove

 

G.

Mantle Clearance from stove top

19-1/2"(50cm)

Espace libre du poêle au manteau

 

H.

Top of Stove to Alcove Ceiling

20-1/4"(51cm)

Dessus de fourneau au plafond de chambrette

HEARTH: A non-combustiblehearth pad is not required. However, the floor beneath the stove must be stable, level, and strong enough to support the stove without a tipping hazard.

CHEMINÉE: Un coussinet non-combustiblede cheminée n’est pas exigé. Cependant, le plancher en dessous du poêle doit être droit, à niveau et assez fort pour supporter le poêle sans le hasard de basculer.

Date of Manufacture /

Date du Manufacturier

 

 

2008 2009 2010 Jan Feb Mar Apr

May

Jun

Jul

Aug Sep

Oct Nov Dec

 

 

 

 

 

102

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER L’ÉTIQUETTE

 

Made in U.S.A. / Fait Aux États-Unis

7026-

Serial No.

Barcode

Model Name

Test Lab & Report No.

Manufactured Date

Page 2

Heat & Glo · Tiara Petite B · 7026-101J

August 1, 2008

- TABLE OF CONTENTS -

Section 1: Listing and Code Approvals

 

A.

Appliance Certifications ......................

4

B.

Glass Specifications............................

4

C.

Specifications......................................

4

D.

High Altitude Installations....................

4

E.

Non-CombustibleMaterials.................

4

F.

Combustible Materials ........................

4

G.

Requirements for the

 

 

Commonwealth of Massachusetts ......

5

Section 2: Getting Started

 

A.

Design & Installation

 

 

Considerations....................................

6

B.

Tools and Supplies Needed................

6

C.

Inspect Appliance & Components.......

6

Section 3: Appliance Location & Clearances

 

A.

Selecting Appliance Location..............

7

B.

Clearances to Combustibles...............

7

Section 4: Termination Locations

 

A.

Vent Termination Minimum

 

 

Clearances..........................................

8

Section 5: Vent Information

 

A.

Venting Components ..........................

10

B.

Use of Elbows.....................................

10

C.

Measuring Standards..........................

10

D.

How to Use the Vent Graph ................

11

E.

Venting Guidelines..............................

11

F.

Horizontal Termination........................

12

G.

Vertical Termination ............................

15

H.

Slim Line Wall Thimble .......................

23

Section 6: Gas Information

 

A.

Fuel Conversions................................

25

B.

Gas Pressures....................................

27

C.

Gas Connection.. ................................27

Section 7: Electrical Information

 

A.

Recommendation for Wire ..................

29

B.

Connecting to the Appliance ...............

29

C.

Standing Pilot Ignition System

 

 

Wiring..................................................

29

D.

Ignition Module Access and

 

 

Battery Replacement ..........................

30

Section 8: Appliance Setup

 

A.

Remove Shipping Materials ................

31

B.

Accessories.........................................

31

B.

Leg Leveling System...........................

31

C.

Flue Restrictor Installation ..................

32

D.

Intake Damper Operation....................

32

E.

Intake Air Shutter Adjustment .............

32

F.

Positioning the Logs............................

32

G.

Mineral Wool .......................................

33

H.

Accessories.........................................

33

I.

Blower Installation...............................

34

J.

Warming Shelves Installation..............

37

K.

Glass Replacement.............................

37

Section 9: Operating Instructions

 

A.

Before Lighting Appliance ...................

38

B.

Controls...............................................

38

C.

Lighting Appliance...............................

39

D.

After Appliance is Lit ...........................

40

E.

Frequently Asked Questions...............

40

Section 10: Troubleshooting...............................

41

Section 11: Maintaining & Servicing Appliance

 

A. Maintenance Tasks .............................

43

Section 12: Reference Materials

 

A.

Appliance Dimension Diagram ...........

45

B.

Vent Components Diagram ................

46

C.

Vent Components List ........................

47

D.

Service Parts List................................

49

E.

Accessories ........................................

53

F.

Service and Maintenance Log ............

54

G.

Warranty Policy...................................

55

H.

Contact Information ............................

56

= Contains updated information.

 

 

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 3

1Listing and Code Approvals

A. Appliance Certification

C. Specifications

 

MODEL

Tiara Petite B

LABORATORY

OMNI-TestLaboratories, Inc.

 

061-S-47b-5

TYPE

Vented Gas Fireplace Heater

STANDARD

ANSI Z21.88b-2003ּ CSA2.33b-2003ּ

 

UL307b ּ CAN/CBA2.17-M91

The product is listed to ANSI standards for “Vented Gas Appliance Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles” and "Gas Fired Appliances for use at High Altitudes".

Manufactured Home or Mobile Home installation may occur only after the home is site located and must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.

When installed, the appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.

Model

Maxi-

Mini-

Orifice

*Steady

**P.4

mum

mum

Size

State

(US or Canada)

%

 

Input

Input

(DMS)

Efficiency

 

 

BTU

BTU

 

%

 

Tiara Petite B (NG)

17,000

12,000

49

73.93

57.30

Tiara Petite B (LP)

17,000

13,000

56

78.19

63.22

*Maximum Vent Blower On **Canada Only

D. High Altitude Installations

Omni-TestLaboratories, Inc. listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2000 feet in the U.S.A. and 0 to 4500 feet in Canada.

When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A. If the heating value of the gas has been reduced, these rules do not apply. To identify the proper orifice size, check with the local gas utility.

If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.

E. Non-CombustibleMaterials

B. Glass Specifications

This appliance is equipped with 5mm ceramic glass behind the curved glass. Replace glass only with 5mm ceramic glass. Please contact your dealer for replacement glass.

Materials that are reported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C, shall be considered non-combustiblematerials.

NOTE: This installation must conform with local codes. In the absence of local codes you must comply with theNational Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and theCAN/CGA B149 Installation Codes in Canada.

F. Combustible Materials

Materials made of or surfaced with wood, compressed paper, plant fibers, plastics, or other materials that can ignite and burn, whether flame proofed or not, or whether plastered or unplastered shall be considered combustible materials.

WARNING

Do NOT use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

Page 4

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.

G.Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-upis installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half(1/2) inch in size,“GAS VENT DIRECTLY

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separated from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting system” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Commonwealth of Massachusetts requirements.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 5

2 Getting Started

A. Design & Installation Considerations

Heat & Glo direct vent gas appliances are designed to operate with all combustion air drawn from outside of the building and all exhaust gases expelled to the outside. No additional air source is required.

CAUTION

Check building codes prior to installation.

Installation MUST comply with local, regional, state and national codes and regulations.

Consult local building, fire officials or authorities having jurisdiction about restrictions, installation inspection, and permits.

When planning an installation, it is necessary to determine the following information before installing:

Where the appliance is to be installed.

The vent system configuration to be used.

Gas supply piping.

Electrical wiring.

Whether optional accessories - devices such as a blower, thermostat or remote control - are desired.

WARNING

Keep appliance dry.

Mold or rust may cause odors.

Water may damage controls.

B.Tools and Supplies Needed

Before beginning the installation be sure that the following tools and building supplies are available. Note: Not all tools will apply to every installation.

Reciprocating saw

Variable Speed Drill/Driver

Pliers

Wrench Set

Hammer

Framing Square

Phillips Screwdriver

Framing Material

Flat Blade Screwdriver

Hi temp caulking material

Plumb Line

Voltmeter

Level

Gloves

Manometer

Safety Glasses

Tape Measure

Non-corrosiveLeak Check Solution

 

or combustible gas detector

C. Inspect Appliance & Components

WARNING

Inspect appliance and components for damage. Damaged parts may impair safe operation.

Do NOT install damaged components.

Do NOT install incomplete components.

• Do NOT install substitute components.

Report damaged parts to dealer.

Carefully remove the appliance and components from the packaging.

Remove cast door and glass door, and set aside on protective surface.

Remove log set and component pack from firebox.

Report to your dealer any parts damaged in shipment, particularly the condition of the glass.

Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit.

WARNING

Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:

Installation and use of any damaged appliance or vent system component.

Modification of the appliance or vent system.

Installation other than as instructed by Hearth & Home Technologies.

Improper positioning of the gas logs or the glass door.

Installation and/or use of any component part not approved by Hearth & Home Technologies.

Any such action may cause a fire hazard.

Page 6

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

3

Appliance Location and Clearances

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

WARNING

 

· Illustrations reflect typical installations and areFOR

 

 

 

Fire Risk

DESIGN PURPOSES ONLY.

Provide adequate clearance:

· Illustrations/diagrams are not drawn to scale.

Around air openings

· Actual installation may vary due to individual design

To combustibles

preference.

For service access

Locate appliance away from traffic areas.

A. Selecting Appliance Location

When selecting a location for your appliance it is important to consider the required clearances to wall (see Figure 3.1).

NOTE: For actual appliance dimensions refer to Section 12.

WARNING

Fire Risk.

Locate and install appliance to all clearance specifications in manual.

B. Clearances to Combustibles

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

G -Alcove

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

A

 

A

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

A

E

C

 

 

 

 

 

 

D

 

 

 

 

 

 

 

"A" measurement is from

 

 

 

 

 

 

 

 

 

 

stove top, not side

 

 

 

 

 

 

 

 

 

 

Model

 

A

B

C

D

E

F

G

H

Tiara

Inches

 

6

2

2

43

36

30

20-1/4

19-1/2

Petite B

Millimeters

152

51

51

1092

914

762

527

495

 

Figure 3.1

 

 

 

 

 

 

 

 

 

 

It is permissable to place the appliance on carpet.

CAUTION

Some carpet materials may be sensitive to radiant heat from the appliance causing discoloration or odor.

NOTE: Flooring beneath appliance may reach 90 degrees plus room ambient temperature. Check with flooring manufacturer for maximum temperature allowed on flooring surfaces.

WARNING

Fire Risk.

Odor Risk.

Tipping Risk

Install appliance on a stable, level platform/ floor strong enough to support appliance without tipping.

USE wood flooring, ceramic tile, brick hearth or high pressure laminate flooring applied directly over thesub-flooringmaterial.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 7

4Termination Locations

A. Vent Termination Minimum Clearances

HORIZONTAL

OVERHANG

WARNING

Fire Risk.

MIN.

20 INCHES MIN.

VERTICAL

 

2 FT.

 

Explosion Risk.

 

LOWEST

WALL

 

 

Maintain vent clearance to combustibles

 

DISCHARGE

 

 

OPENING

 

as specified.

GAS DIRECT VENT

 

 

• Do not pack air space with insulation or

TERMINATION CAP

 

 

 

 

 

other materials.

 

 

X

Failure to keep insulation or other materials

12

away from vent pipe may cause fire.

 

 

 

 

ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

Measure vertical clearances from this surface.

 

 

 

Roof Pitch

H (Min.) Ft.

 

 

 

Flat to 6/12 ........................................................

1.0*

 

 

 

Over 6/12 to .......................................................7/12

1.25*

 

 

 

Over 7/12 to 8/12 ..............................................

1.5*

 

 

 

Over 8/12 to 9/12 ..............................................

2.0*

 

 

 

Over 9/12 to 10/12 ............................................

2.5*

 

 

 

Over 10/12 to 11/12 ..........................................

3.25

Measure horizontal clearances from this surface.

Over 11/12 to 12/12 ..........................................

4.0

Over 12/12 to 14/12 ..........................................

5.0

 

(See Figure 4.4 for specific clearances.)

Over 14/12 to 16/12 ..........................................

6.0

 

Over 16/12 to 18/12

7.0

Figure 4.1 Termination Clearances

Over 18/12 to 20/12 ..........................................

7.5

 

 

 

Over 20/12 to 21/12 ..........................................

8.0

 

 

 

* 3 foot minimum in snow regions

 

GAS, WOOD OR FUEL

 

 

 

 

OIL TERMINATION

B

Figure 4.3 Minimum Height from Roof to Lowest Discharge

 

 

 

 

 

 

GAS

 

Opening

 

C

TERMINATION

 

 

 

 

 

 

 

Figure 4.3 specifies minimum vent heights for various

pitched roofs.

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

Wood & Fuel Oil

Comments

 

Termination

Termination

 

 

 

 

 

 

 

 

A

 

6 in.

20 in. min.

Horizontal distance between terminations

 

 

 

 

 

 

B

 

20 in.

24 in. min.

Distance to perpendicular wall

 

 

 

 

 

 

C

 

18 in.

18 in.

Vertical distance between terminations

 

 

 

 

 

 

Figure 4.2 Multiple Vertical Temination

Page 8

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

GRv

D AH

E

v

M

N

P

Q

(See Note 2)

L

B

 

 

 

U.S.

 

 

V

 

 

 

 

B

 

 

 

 

 

 

 

v

 

 

 

 

T

 

 

 

v

B

(3 FT)

 

 

 

 

 

v

 

S

 

S

 

 

 

 

 

V

Electrical

V

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

Service

 

 

v

 

v

 

M

 

 

 

 

 

 

I

 

 

D*

 

 

 

 

 

 

 

v

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

J or K

 

V

 

 

 

V

= VENT TERMINAL

X = AIR SUPPLY INLET

A

=

12 inches .............

clearances above grade, veran-

 

 

 

(See Note 1)

da, porch, deck or balcony

B

=

12 inches ............

clearances to window or door

 

 

 

 

that may be opened, or to per-

 

 

 

 

manently closed window. (Glass)

D*

=

18 inches .............

vertical clearance to unventilat-

 

 

 

 

ed soffit or to ventilated soffit lo-

 

 

 

 

cated above the terminal

 

 

 

*30 inches ............

for vinyl clad soffits and below

 

 

 

 

electrical service

F= 9 inches .............. clearance to outside corner

G= 6 inches ............... clearance to inside corner

H= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulatorassemblywithin 3 feet (90cm) horizontally from the center-lineof the regulator

I = 3 ft. ....................... clearance to gas service regula- tor vent outlet

J = 9 inches (U.S.A.)

12 inches (Canada)clearance to non-mechanicalair supply inlet to building or the combustion air inlet to any other appliance

**a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor, or meets Note 2.

NOTE 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap is suggested. (See vents components pages.)

NOTE 2: Termination in an alcove space (spaces only open on one side and without an overhang) are permitted with the dimensions specified for vinyl ornon-vinylsiding and soffits.1. There must be at least 3 feet minimum between termination caps.2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap.3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.

= AREA WHERE TERMINAL IS NOT PERMITTED

K

=

3 ft. (U.S.A.)

 

 

 

6 ft. (Canada) .........

clearance to a mechanical

 

 

 

(powered) air supply inlet

L**

=

7 ft. .........................

clearance above paved

 

 

(See Note 1)

sidewalkor a paved driveway

 

 

 

located on public property

M*** =

18 inches ..............

clearance under veranda ,

 

 

 

porch, deck, balcony or over-

 

 

 

hang

 

 

42 inches ..............

vinyl

S

=

6 inches .................

clearance from sides of

 

 

(See Note 3)

electrical service

T

=

12 inches ................

clearance above electrical

 

 

(See Note 3)

service

Alcove Applications

N

=

6 inches .................

 

non-vinylsidewalls

 

 

12 inches ...............

 

vinyl sidewalls

P

=

8 ft.

 

 

 

 

 

 

 

QMIN

 

RMAX

 

1 cap

 

3 feet

 

2 x Q ACTUA L

 

2 caps

 

6 feet

 

1 x Q ACTUA L

 

3 caps

 

9 feet

 

2/3 x Q ACTUA L

 

4 caps

 

12 feet

 

1/2 x Q ACTUA L

QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL

NOTE: Local codes or regulations may require different clearances.

NOTE: Termination caps may be hot. Consider their proximity to doors or other traffic areas.

WARNING: In the U.S.: Vent system termination isNOT permitted in screened porches. You must follow side wall, overhang and ground clearances as slated in the instructions.

In Canada: Vent system termination isNOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow side wall, overhang and ground clearances as stated in the instructions.

Quadra-Fireassumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.

NOTE 3: Location of the vent termination must not interfere with access

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING,

Figure 4.4

 

IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

 

 

 

 

 

 

 

 

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 9

5 Vent Information

A. Venting Components

In order to comply with applicable codes and product warranties, use only following venting components:

Hearth & Home Technologies (HHT)

Simpson Dura-Vent

Selkirk Direct-Temp

Amerivent Direct

Security Secure Vent

DO NOT USE FIELD-FABRICATEDVENTING COMPONENTS. Refer to the venting manufacturer’s instructions.

This product is approved to be vented either horizontally, through the side wall or vertically through the roof. You may vent through a Class A or masonry chimney if an approved adapter is used.

This appliance is a direct vent heater. All combustion air must come directly from the outside of the building. The vent pipe for this unit consists of an inner and an outer pipe. The inner pipe carries the appliance exhaust out of the system, and the outer pipe brings fresh combustion air into the appliance.

A round support box/wall thimble or heat shield is required when the venting passes through a combustible wall.

A support box or ceiling firestop is required when the venting passes through a ceiling.

Roof flashing and a storm collar are required when venting passes through the roof.

Follow instructions provided with the venting for installation of these items.

B. Use of Elbows

CAUTION

ALL vent configuration specifications MUST be followed.

This product is tested and listed to these specifications.

Appliance performance will suffer if specifications are not followed.

Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. (See Figure 5.1.)

Two 45° elbows may be used in place of one 90° elbow. On 45° runs, one foot of diagonal is equal to 8-1/2in. (216mm) horizontal run and8-1/2in. (216mm) vertical run. A length of straight pipe is allowed between two elbows. (SeeFigure 5.1.)

Vertical

 

 

.

 

 

in

 

.

1/2

12

in

 

8

 

 

-

8-1/2in.

Horizontal

Figure 5.1

WARNING

Fire Hazard. Explosion Risk. Asphyxiation Risk.

Do NOT connect this gas appliance to a chimney flue serving a separate solid-fuelor gas burning appliance.

Vent this appliance directly outside.

Use separate vent system for this appliance.

May impair safe operation of this appliance or other appliances connected to the flue.

C. Measuring Standards

Vertical and horizontal measurements were made using the following standards.

Pipe measurements are from center line to center line.

Horizontal terminations are measured to the outside of the mounting surface (flange of termination cap). See

Figure 4.1 on page 8.

Vertical terminations are measured to the top of the last pipe before termination cap.

Horizontal pipe installed level with 1/4 in. rise.

Page 10

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

D. How to Use the Vent Graph

E. Venting Guidelines

1. Measure the distance from the top of appliance to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

Example 1: If the vertical dimension from the top of the appliance to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the outer wall flange must not exceed 9

ft.-8in. (3m).

.

Example 2: If the vertical dimension from the top of the appliance is 21 ft. (6m), the horizontal run to the outer wall flange must not exceed 4ft.-3in. (1m).

Notes:

The maximum horizontal vent run is 15 ft. (5m) when the vertical vent rise is 10 ft. (3m).

Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.

Exterior vent diameter = 6-5/8in. (168mm); Inner vent diameter = 4 in. (102mm).

Horizontal sections require noncombustible support every 3 ft. (914mm) , e.g. wall straps.

For any vertical termination a minimum of 6 ft. (2m) vertical must be used.

EXCEPTIONS FOR HORIZONTAL INSTALLATIONS: *The maximum horizontal vent run is 30 in. (762mm).

4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent *The maximum horizontal vent run with a 45° elbow is

pipe and each 45° elbow is equivalent to 1 ft. (305mm) of vent pipe, and must be subtracted from vent pipe run. A single vertical to horizontal 90° elbow is already calculated into the allowable 15 ft. (5m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).

Example: The use of three elbows would reduce the allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.)

18 in. (457mm).

*No external minimum rise is required.

*The minimum horizontal vent run is 6 in. (152mm).

Termination cap

25 ft. (8m)

25'

 

 

 

 

 

 

 

 

Maximum Vertical

 

 

 

 

 

 

 

 

24'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 2

22'

 

 

 

 

 

 

 

 

 

20'

Adjust

 

 

 

 

 

 

 

 

18'

 

 

 

 

 

 

 

 

Intake

 

 

 

 

 

 

 

VERTICAL DISTANCE

16'

Damper

 

 

 

 

 

 

 

FROM APPLIANCE TO

 

 

 

 

 

 

 

 

90° ELBOW

14'

 

 

Install Flue

 

 

 

 

 

12'

 

 

 

 

 

 

 

 

 

Restrictor

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

Example 1

8'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 ft. (2m) Minimum

6'

 

 

 

 

 

 

 

 

Vertical Termination

4'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

L

 

2'

4'

6'

8'

10'

12'

14'

15'

 

 

NOTE: In the Commonwealth of Massachusetts the word damper shall be replaced with the words flue restrictor.

Termination cap

SLK-01TRDor an approved Termination Cap

6 in. (152mm) Minimum starter pipe

30 in. (762mm) Maximum Horizontal run with no vertical pipe and with 1/4 in.

(6mm) rise per foot. Must use approved Termination Cap.

Figure 5.2

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 11

F. Horizontal Termination

Type A - Up & Out Installation

TERMINATION CAP

90° ELBOW

CENTER LINE

PIPE LENGTH

WALL THIMBLE

WALL THIMBLE COVER

PIPE LENGTH

Type B - Straight Out Installation

TERMINATION CAP

CENTER LINE

16-5/8in.

 

 

 

 

WALL THIMBLE

(42 cm)

 

 

 

 

WALL THIMBLE COVER

Type C - 45° Elbow in Corner Installation

WALL THIMBLE

45° ELBOW

2 in. (51mm) CLEARANCE FROM STOVE CORNER TO COMBUSTILE WALL

2 in. (51mm) CLEARANCE FROM STOVE CORNER TO COMBUSTIBLE WALL

Figure 5.3

Step 1.

Determine the desired location of the appliance. Check to ensure that wall studs or roof rafters are not in the way when the venting system is attached. If this is the case, you may want to adjust the location of the appliance.

WARNING

Fire Hazard.

Exhaust Fume Risk.

Impaired Performance of Appliance.

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

Step 2.

Direct vent pipe is designed with a locking connection. To connect the venting system to the appliance flue outlet, a twist-lockadapter is built into the appliance at the factory. Wall thickness may vary. Remember to include wall thickness in minimum clearances when figuring venting lengths for your installation needs.

Note: Female ends of direct vent pipe/elbows are designed to slide straight onto the male ends of adjacent pipes by orienting the pipe indentations so they match and slide into the entry slots on the male ends, seeFigure 5.4. Push the pipe sections completely together, thentwist-lockone section clockwise approximatelyone-quarterturn, until the two sections are fully locked. The female locking lugs may not be visible from the outside. They may be located by examining the inside of the female ends.

Female Locking Lugs

Male Locking Lugs

Figure 5.4

WARNING

Fire Risk. Explosion Risk.

Combustion Fume Risk.

Use vent run supports per installation instructions. Connect vent sections per installation instructions.

Maintain all clearances to combustibles.

Do NOT allow vent to sag below connection point to appliance.

Maintain specified slope (if required).

Improper support may allow vent to sag or separate.

Page 12

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

Step 3.

For installations using a round support box/wall thimble (check pipe manufacturer's instructions), mark the wall for a 10 in. x 10 in. (254mm x 254mm) square hole. The center of the square hole should line up with the center line of the horizontal pipe, as shown in Figure 5.5. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or concrete, a 7 in. (178mm) diameter hole is acceptable.

CENTER OF

HOLE

CENTER

LINE

CENTER LINE

WALL

THIMBLE

Figure 5.5

NOTE:

(1)Installation requires a minimum of 6 in. (152mm) horizontal run of vent with a 1/4 in. (6mm) rise run towards the termination. Each 1 ft. (305mm) of horizontal venting must include a 1/4 in. (6mm) rise. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.

(2)The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be easily blocked or obstructed, see Figure 4.4 on page 9.

(3)For installations requiring a vertical rise on the exterior of the building, a snorkel kit is available with a 14 in. (356mm) and a 36 in. (914mm) tall snorkel termination cap. Follow the same installation procedures as used for standard horizontal terminations. If the snorkel termination must be installed below grade (i.e. basement application), proper drainage must be provided to prevent water from entering the snorkel termination. Do not backfill around snorkel termination.

Step 4.

Position the horizontal termination cap in the center of the 10 in. x 10 in. (254mm x 254mm) square hole and run a bead of non-hardeningmastic around its outside edges, so as to make a seal between it and the wall, attach termination cap to the exterior wall with the four wood screws provided. The arrow on the vent cap should be pointing up (Figure 5.6).

WOOD

SCREW

HOT

WALL THIMBLE

Figure 5.6

NOTES:

(1)The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

(2)A termination cap with a built-invinyl siding standoff is highly recommended on a building with vinyl siding. The pilot hole will be 2 in. (51mm) closer to the bottom of the square than the top. Using a framing square, draw a 14 in. x 14 in. (356mm x 356mm) square around the pilot hole in the siding. SeeFigure 5.7.

8 in.

 

(203mm)

 

 

7 in.

 

(178mm)

7 in.

6 in.

(178mm)

 

(152mm)

Figure 5.7

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 13

(NOTE: Some termination caps may cause the vent pipe to be off center on flashing). Ensure that proper clearances to combustible materials are maintained. If you are not using an approved termination cap with abuilt-instandoff on a building with vinyl siding, a vinyl siding standoff should be installed between the termination cap and the exterior wall (Figure 5.8). Follow manufacturer’s instructions for attaching the vinyl siding standoff to the horizontal termination cap. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. The vent terminal cap shall not be recessed into a wall or siding. Remove siding from the area where the standoff will be located.

Note: The attachment from the vent pipe to the vent termination cap must be sealed with silicone. Termination caps shall not be recessed into a wall or siding.

WARNING

Fire Hazard.

Exhaust Fume Risk.

Impaired Performance of Appliance.

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

VINYL SIDING

Apply sealant to all four sides

SCREWS

Bolt horizontal top to vinyl standoff

SCREWS

WALL THIMBLE COVER

Vinyl siding standoff with siding beneath removed

WALL THIMBLE

Figure 5.8

WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping flue section found on the termination cap.

WARNING

Burn Risk.

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

Step 5.

Place the wall thimble cover over the pipe assembly and slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the vent termination cap assembly. It is important that the vent pipe extend into the vent termination cap a sufficient distance so as to result in a minimum pipe overlap of 1-1/4in. (32mm). Secure the connection between the vent pipe and the vent termination cap by attaching the two sheet metal strips extending from the vent termination cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section (Figure 5.9).

1/4 in. (6mm)

Fold Strap Here

Sheet Metal Screw

Wall Thimble

Wall Thimble Cover/Ceiling

 

Firestop as Required by Local

 

Jurisdiction

Strap

 

Figure 5.9

Page 14

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

G. Vertical Termination

1. Direct Vent Pipe

VERTICAL

TERMINATION

CAP

STORM

COLLAR

FLASHING

FIRESTOP

SUPPORT BOX

PIPE LENGTH

Figure 5.10

Step 1.

Check the installation instructions for required 1 in. (25mm) clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. See page 17, Figure 5.16. Check the instructions below for maximum vertical rise of the venting system, and any maximum horizontal offset limitations. All offsets must fall within the set parameters of the vent graph (Figure 5.2) located on page 11.

NOTE: Maximum vertical rise allowable is 25 ft. (8m),

Figure 5.11.

NOTE: Maximum number of 45° elbows permitted for a vertical installation is eight, provided their installation does not decrease maximum allowable horizontal run (as specified by vent graph, on page 11).

WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as speci-

fied.

• Do not pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

25 ft. (8m) MAXIMUM

Figure 5.11

Step 2.

Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, as shown inFigure 5.12 to avoid cutting loadbearing members.

Plumber’s Tape connected to Wall Strap

Wall Strap

Two 45˚ Elbows

Figure 5.12

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 15

Step 3.

To install the round support box/wall thimble cover in a flat ceiling, cut a 10 in. (254mm) square hole in the ceiling, centered on the hole drilled in Step 2. Frame the hole as shown in Figure 5.13.

Ceiling

Joists

Framing

1 - 1/2 in. (38mm) Long

Wood Screws

Figure 5.13

Step 4.

Assemble the desired lengths of pipe and elbows necessary to reach from the appliance up through the round support box. Ensure that all pipe and elbow connections are in their fully twist-lockedposition. Assemble as instructed.

Step 5.

Cut a hole in the roof centered on the small drill hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles, as specified. Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support box/wall thimble up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well as above the roofline. The galvanized finish is desirable above the roofline, due to its higher corrosion resistance.

NOTE:

(1) If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 ft. (914mm) to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose, Figure 5.12, page 15.

(2)Whenever possible, use 45° elbows, instead of 90° elbows. The 45° elbow offers less restriction to the flow of flue gases and intake air.

Step 6.

Slip the flashing over the pipe section(s) protruding through the roof. Secure the base of the flashing to the roof with roofing nails. Ensure the roofing material overlaps the top edge of the flashing as shown in Figure 5.14. Verify that the chimney is the required height above the roof. See roof pitch table,Figure 4.3, on page 8.

Shingles overlap on

CAP AND STORM

COLLAR NOT SHOWN

top edge of flashing

FOR CLARITY

 

Figure 5.14

Step 7.

Continue to assemble pipe sections until the height of the vent (before adding the termination cap) meets the minimum code requirements as outlined in the current CAN/CGA-B149Installation Codes (in Canada), the National Fuel Gas Code NFPA 54/ANSI Z223.1 (in USA), or local codes. Note that for steep roof pitches, the vent height must be increased. See roof pitch table (Figure 4.3, on page 8). In high wind conditions, nearby trees adjoining rooflines, steep pitched roofs, and other similar factors can result in poor draft, or down drafting. In these cases increasing the vent height or switching to the high wind termination cap may solve this problem.

Step 8.

Slip the storm collar over the pipe, and push it down to the top of the flashing (Figure 5.15). Usenon-hardeningsealant above and below the joint between the storm collar and the pipe.

Optional High Wind Termination Cap

Secure Flashing with Non-Hardening

Sealant and Roofing Nails

Figure 5.15

Page 16

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

Step 9.

Twist-lockthe vent cap and seal.

Note: Formulti-storyvertical installations, a ceiling firestop is required at the second floor, and any subsequent floors (Figure 5.16). The opening should be framed to 10 in. x 10 in. (254mm x 254mm) inside dimensions, in the same manner as shown inFigure 5.13 on page 16.

NAILS

CEILING FIRES TOP

MIN. 1 in. (25mm)

CLEARANCE

MIN. 1 in. (25mm)

CLEARANCE

MIN. 1 in. (25mm)

CLEARANCE

MIN. 1 in. (25mm)

CLEARANCE

Figure 5.16

WARNING

Fire Risk.

Explosion Risk.

Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passed through must be enclosed. The enclosure may be framed and sheetrocked with standard construction materials; however, refer to these installation instructions for the minimum allowable clearance between the outside of the vent pipe and the combustible surfaces of the enclosure. Do not fill any of the required air space with insulation.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 17

2. Cathedral Ceiling

Step 1.

Follow installation Steps 1 and 2 under vertical installation section, page 15.

Step 2.

Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Cut the hole 1/8 in. (3mm) larger than the support box outline.

Step 3.

Lower the support box through the hole in the roof until the bottom of the support box protrudes at least 2 in. (51mm) below the ceiling (Figure 5.17). Align the support box both vertically and horizontally with a level. Temporarily tack the support box in place through the inside walls and into the roof sheathing.

Figure 5.18

Level

Cathedral Ceiling

Support Box

2 in. (51mm) Min. below finished ceiling

Cut hole 1/8 in. (3mm) greater in size than pattern of support box as it is projected onto roof line

Figure 5.17

Step 4.

Using tin snips, cut the support box from the top corners down to the roofline, and fold the resulting flaps over the roof sheathing (Figure 5.18). Before nailing it to the roof, run a bead ofnon-hardeningmastic around the top edges of the support box to make a seal between it and the roof. Clean out any combustible material from inside the support box.

Step 5.

Assemble the desired lengths of pipe and elbows necessary to reach from the appliance up through the round support box. Ensure that all pipe and elbow connections are in their fully twist-lockedposition. Assemble as instructed.

Step 6.

Place the support clamp (provided with the support box) inside the support box (at the bottom), and secure to the pipe section. The clamp allows the support box to support the weight of the pipe sections. Continue to add pipe sections until you are above the roofline.

Step 7.

Complete the cathedral ceiling installation by following the same procedures outlined in steps 7 through 9 for vertical installations, pages 16-17.

Step 8.

Install the black trim collar around the outside of the cathedral ceiling support box (Figure 5.19). The two pieces of the trim collar slide over one another to allow for easy adjustment around the support box. Using the six screws provided, secure the four corners and the overlapping sections of the trim collar to the ceiling. You may want to predrill the holes for the overlapped sections for ease of installation.

Trim Collar

Cathedral

Ceiling

Support Screws

Box

Figure 5.19

Page 18

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

3. Class A Metal Chimney

TERMINATION

CAP

TOP

ADAPTOR

FLASHING

EXISTING

METAL

CHIMNEY

SYSTEM 4 in. (102mm) FLEX PIPE

RETRO CONNECTOR

DIRECT VENT PIPE

Figure 5.20

Step 4.

Pass the flex pipe down through the center of the chimney system, and center the top adapter on the top of the chimney pipe. Drill four 1/8 in. (3mm) diameter holes through the top adapter, and into the chimney top. Ensure that you are drilling into the metal on the chimney. Twist lock the high wind termination cap onto the top adapter (Figures 5.22 and 5.23).

Figure 5.22

CAUTION

Ensure that existing chimney is functionally sound and clean.

Have inspection done by qualified chimney sweep or professional installer BEFORE converting to direct vent appliance.

Step 1.

Remove existing chimney cap.

Step 2.

Measure the distance from the top of the chimney to the bottom of the ceiling support box, add 3 in. (76mm) to this measurement, and cut a section of 4 in. (101mm) flex pipe to that length (the flex should be fully extended).

Step 3.

Connect the end of the flex pipe section to the underside of the top adapter, using four sheet metal screws (Figure 5.21).

Top Adapter

Flex Pipe

Sheet Metal Screws

Figure 5.21

High Wind Termination

Cap

Sheet Metal Screws

Drill Four 1/8 in. (3mm) Diamater Holes

Figure 5.23

Step 5.

Pull the flex pipe down through the ceiling support box, until it protrudes approximately 3 in. (76mm). Connect the flex pipe to the retro connector, and attach with sheet metal screws.

Step 6.

Push the flex pipe back up into the ceiling support box, center the retro connector, and attach it to the support box with sheet metal screws.

Step 7.

The connection between the appliance and the retro connector may be completed with sections of direct vent pipe.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 19

4. Existing Masonry Chimney

Type A & B Co-AxialtoCo-Linear

CHIMNEY LINER

 

CHIMNEY LINER

TERMINATION

 

TERMINATION CAP

CAP

 

 

 

 

 

 

 

 

 

 

CO-AXIALTO

3 in. (76mm)

FLEX LINER

 

CO-LINEAR

 

 

CO-AXIALTO

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CO-LINEAR

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

PIPE LENGTH

PIPE LENGTH

OPTIONAL

OPTIONAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOWING TWO

25 ft. (8m)

SECTIONS OF

FLEX LINER

25 ft. (8m) OF 3 in. (76mm) FLEX LINER EXHAUST SECTION

THIS SECTION OF

THE CHIMNEY MUST

BE SEALED

THE CHIMNEY MUST BE

SEALED FROM THE 4 ft. (1m)

SECTION TO TERMINATION

USING A SMOKE SHELF OR A

DAMPER. THE SEAL SHOULD

BE 6 in. (152mm) BELOW THE

END OF THE 4 ft. (1m) AIR

INTAKE SECTION.

4 ft. (1m) OF 3 in. (152mm) FLEX LINER AIR INTAKE SECTION

Type C - Up & Out Installation

TERMINATION

CAP

TOP ADAPTOR

FLASHING

RETRO

4 in. (1m) FLEX

LINER

CONNECTOR

 

90 DEGREE ELBOW

DIRECT

VENT PIPE

Type D - Hearth Mount

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHIMNEY LINER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINATION CAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 ft. (8m) OF 3 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(76mm) FLEX LINER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THIS SECTION OF THE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHIMNEY MUST BE

ALCOVE CLEARANCE

 

 

 

 

 

 

 

 

 

 

SEALED

 

 

 

 

 

 

 

 

 

 

 

TO COMBUSTIBLES

 

 

 

 

 

 

 

 

 

 

 

MUST BE MAINTAINED.

 

 

 

 

 

 

 

 

 

 

CHIMNEY MUST BE SEALED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FROM 4 ft. (1m) SECTION TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINIATION USING A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SMOKE SHELF OR A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DAMPER*. SEAL SHOULD BE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 in. (152mm) BELOW END OF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 ft. (1m) AIR INTAKE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECTION.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 ft. (1m) OF 3 in. (76mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CO-AXIALTOCO-LINEAR

FLEX LINER AIR INTAKE

 

SECTION

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.

Figure 5.24

Page 20

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

CAUTION

Ensure that existing chimney is functionally sound and clean.

Have inspection done by qualified chimney sweep or professional installer BEFORE converting to direct vent appliance.

Step 1.

Before cutting any holes, assemble the desired sections of direct vent pipe to determine the center of the masonry penetration.

Step 2.

Once the center point of the penetration has been determined, cut a 6 in. (152mm) diameter hole in the masonry. If the hole is too large, the retro connector might not mount properly; if the hole is too small, the appliance might starve for intake air. If there is a frame wall in front of the masonry wall, cut and frame a 10 in. (254mm) square opening in the wall (centered around the 6 in. (152mm) masonry opening). If there is sheet rock only (no studs) in front of the masonry the 10 in. (254mm) opening is still needed, but does not need to be framed. If the hole is framed a round support box/wall thimble is required. This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles (Figure 5.25).

Studwall

10 in. x 10 in. (254mm x 254mm)

framed opening in wall Masonry Chimney

Retro Connector

Wall Thimble Cover

(4) Masonry Bolts

(Not Included)

NOTE: For hearth applications refer to page 19, Figure 5.24 for the use of a co-axialtoco-linearappliance connector.

Figure 5.25

Cut and bend flashing as needed to fit

Figure 5.26

Sealant adhesive

 

Step 4.

To determine the length of flex needed, measure from 3 in. (76mm) above the top of the flashing down to the level of the opening. Add the distance from the center of the chimney out through the wall. Cut a piece of 4 in. (102mm) flex to this length (extended to its nominal length). Be sure to leave 2-3in.(51-76mm)of flex above the existing chimney to allow for connection to the termination kit.

Step 5.

Connect the flex liner to the top adapter using three sheet metal screws (Figure 5.21 page 19).

Step 6.

Feed the flex liner through the flashing into the chimney. Carefully feed the flex liner down the chimney to the bottom and out the opening in the masonry wall, forming an angle to line up the flex liner with the vent opening on the appliance.

WARNING

Fire Risk.

Explosion Risk.

Do not let the flex liner sag below the level at which it will connect to the appliance or connector. This could allow hot gas to become trapped and potentially become a fire hazard. The flex liner path should always be sloped up toward the termination cap.

Step 3.

Secure the flashing to the top of the masonry chimney using a bead of non-hardeningsealant-adhesive.If the flashing is larger than the top of the chimney, cut and fold flashing as needed to fit chimney(Figure 5.26).

Step 7.

If additional lengths of flex liner are needed to span the chimney height, use a flex coupler to connect the pieces of flex liner together. Connect the flex to the coupler by using four sheet metal screws for each side (Figure 5.27, on the next page).

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 21

Flex Liner

Flex Coupler

Sheet Metal Screws

Figure 5.27

Step 8.

Secure the top adapter to the flashing. Use three sheet metal screws through the side of the top adapter into the flange on the flashing (Figure 5.28). Twist lock the high wind termination cap on to the top adapter.

High Wind

Termination Cap

Top Adaptor

(3) Sheet Metal Screws

Flashing

Figure 5.28

6 in. (152mm) diameter opening in masonry wall

Retro Connector

(3) Masonry Bolts (Not included)

Figure 5.29

Step 10.

Slide wall thimble cover over retro connector and secure with masonry bolts (Figure 5.30). If you have a framed wall in front of the masonry, use wood screws to mount wall thimble cover to framed wall, over retro connector and 10 in. (254mm) square framed opening (Figure 5.25, page 21). If needed, add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble cover.

Retro Connector

Wall Thimble Cover

(4) Masonry Bolts

(Not included)

Figure 5.30

Step 9.

Attach the flex to the retro connector. Use three sheet metal screws to attach the flex liner to the connector (Figure 5.29). Mount the retro connector to the masonry wall using masonry bolts. Redrill larger holes on connector as needed. Be careful to ensure that the connector is centered in the opening and the mounting holes line up with the masonry wall.

Step 11.

The connection between the appliance and the retro connector may be completed with sections of direct vent pipe.

Page 22

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

H. Slim Line Wall Thimble

BEFORE YOU BEGIN:

Review the venting configurations in Figures A, B andC onthe next page.

1. Assembling Slim Line Trim Ring and Heat Shield

Figure 5.31 Lay the trim ring on flat surface and bend up the six welded brackets into a 90 degree position. The brackets along the outer edge of the ring are for locating the ring in the center of the hole.

Figure 5.32 The heat shield is shipped flat and must be hand bent into a half circle before attaching it to the trim ring. Bend the heat shield as shown.

NOTE: Wear leather gloves when bending the heat shield to prevent injury.

CAUTION

Sharp Edges

• Wear protective gloves and safety glasses during installation.

Figure 5.33 Attach the heat shield to the trim ring with the four screws provided. Screws go through the heat shield and into the brackets on the trim ring.

2. Installing Slim Line Trim Ring and Heat Shield

Measure from the floor to the center of the vent pipe. Cut out a 9-1/2in. (241mm) hole in the wall. Hold the trim ring/heat shield assembly in place and put a mark on the shield with a black marker where it protrudes through the exterior wall. SeeFigure A on the next page.

Use that mark as a guide to trim off excess heat shield with a pair of sheet metal shears.

3/4

3/4

3/4

Figure 5.34 When installing the trim ring/heat shield assembly make sure the trim ring is centered in the hole and that the shield is above the pipe. There must be a minimum of 3/4 in. (19mm) minimum clearance maintained to combustibles from the top of the heat shield.

Ensure that framing on the inside of the wall is a minimum inner framing diameter of 10 in. x 10. in. (254mm x 254mm).

The four trim ring mounting screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 23

FIG. A 90 DEGREE ELBOW

PLACE MARK WHERE PROTRUDES THROUGH

EXTERIOR WALL TO CUT OFF EXCESS

90° ELBOW CENTER LINE

TERMINATION CAP

PIPE LENGTH

HEAT SHIELD

OVER PIPE

TRIM RING

 

PIPE LENGTH

FIG. B 45 DEGREE ELBOW

TRIM RING

HEAT SHIELD OR WALL

THIMBLE OVER PIPE

45° ELBOW

2 in. (51mm) CLEARANCE FROM STOVE CORNER TO COMBUSTILE WALL

2 in. (51mm) CLEARANCE FROM STOVE CORNER TO COMBUSTIBLE WALL

FIG. C MINIMUM CLEARANCE

INTERIOR WALL (2 in. (51mm) clearance from rear of stove)

CENTER LINE

Figure 5.34

MINIMUM OF 6 in. (152mm) OF PIPE

THROUGH THE WALL

WALL THIMBLE

TERMINATON CAP

HEAT SHIELD OVER TOP HALF

OF PIPE

TRIM RING

Page 24

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

6 Gas Information

A. Fuel Conversions

Before making gas connections ensure that the appliance being installed is compatible with the available gas type.

Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a qualified technician using Hearth & Home Technologies specified and approved parts.

PILOT HOOD

MILLIVOT GENERATOR

THERMOCOUPLE

ALIGNMENT NOTCH

1. Converting to LP Gas

NOTE: Gas conversions should only be performed by a qualified service person, and/or where required by state and local codes, licensed installer/service technician. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.

Any damaged valve components should not be installed. If a valve or regulator has been dropped or appears to have been modified, the valve or regulator should not be installed.

KIT CONTENTS: Replacement orifice; replacement pilot injector; valve regulator; and conversion label.

TOOLS REQUIRED: #2 Phillips head screwdriver, slotted screwdriver or Torx TH20; 5/32 in. Allen wrench; 3/8 in. open end wrench.

Remove 2 screws

Figure 6.1 Remove top and front (if installed), glass, and logs (if installed). Remove burner by removing ONLY the two screws indicated. DO NOT remove the screws from the burner top. Lift the burner up and out of the firebox.

Figure 6.2 Pull off pilot hood and set aside.Do not remove the wire clip.

5/32 in. Allen wrench

Figure 6.3 Use a 5/32 in. Allen wrench to remove the pilot injector. Replace pilot injector with the one supplied with the appliance (#35 for Propane, #62 for Natural Gas).

Replace pilot hood, snapping into position.

Figure 6.4 Remove main burner orifice using a 3/8 in. wrench. Be sure to align notch on left side of pilot hood, shown. Replace orifice with the proper size as indicated below for your gas type and venting.

PROPANE

NATURAL GAS

#56

#49

Reinstall burner.

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 25

2. Valve Regulator Replacement

WARNING

Fire Risk.

Explosion Risk.

Disconnect any electrical cords and turn off gas supply to unit before proceeding if converting fuel on an appliance already fully installed.

Remove upper and lower back shield. Loosen the set collars on the extension rods with the 3/32 in. Allen wrench. Remove the rods and adapter cap.

AMounting Screws

BPressure Regulator Tower

CDiaphragm

Figure 6.5 Turn control knob to the OFF position, ensure that gas supply to the valve has been turned off. Using a Torx TH20, or slotted screwdriver, remove the three pressure regulator mounting screws(A), pressure regulator tower(B), and diaphragm(C).

E Screws

D

Rubber Gasket

Identification Label F

Figure 6.6 Ensure that the rubber gasket(D) is properly positioned and install the new HI/LO pressure regulator assembly to the valve using the new screws(E) supplied with the kit. Tighten screws securely. (Reference torque = 25 in./lb.) Install the enclosed identification label(F) to the valve body where it can be seen.

Fill out the conversion label and attach it to the valve cover.

WARNING

Fire Risk.

Explosion Risk.

Gas Leak Risk.

Rubber gasket must be seated properly on valve face.

Do no install a valve or regulator that has been dropped.

WARNING

Fire Risk.

Explosion Risk.

If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life.

The qualified service agency is responsible for the proper installation of this conversion kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

Page 26

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

B. Gas Pressures

Proper input pressures required for optimum appliance performance, gas line sizing requirements need to be followed from NFPA51.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

C. Gas Connection

NOTE: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI Z223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.)

NOTE: A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm)T-handlemanualshut-offvalve and flexible gas connector are connected to the 1/2 inch (13mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

WARNING

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.

PRESSURE

NG

LP

Minimum Inlet Pressure

5 inches w.c.

11 inches w.c.

Maximum Inlet Pressure

10 inches w.c.

13 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10 inches w.c.

If the pressure is not sufficient, ensure:

1)the piping used is large enough.

2)the supply regulator is adequately adjusted.

3)that the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

WARNING

Gas Leak Risk.

Support control when attaching pipe to prevent bending gas line.

NOTE: The gap between the supply piping and gas access hole may be plugged withnon-combustibleinsulation to prevent cold air infiltration.

Leak test all gas line joints and the gas control valve prior to and after starting the appliance.

Before making the gas connection, ensure that the appliance you are installing is designed for the type of gas being supplied. This information can be found on the ratings label under the appliance. If the appliance has been converted to propane (LP), the valve cover should have a label stating that the appliance has been converted to propane.

Connect the gas line at the 3/8 in. (10mm) pipe connector on the valve at the back of appliance. We recommend connecting the appliance with an approved flex gas line. If flex gas lines are not approved in your area, you must connect a hard pipe to the gas hookup.

You must supply a manual shut-offvalve in a visible location within 3 ft. (914mm) of the appliance.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 27

WARNING

Fire Risk or Explosion Hazard.

Gas build-upduring line purge may ignite.

Purge should be performed by a qualified technician.

Ensure adequate ventilation.

• Ensure there are no ignition sources such as sparks or open flame.

A small amount of air will be in the gas supply lines. When first lighting appliance it will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

Air only needs to be purged again if gas valve has been turned to the OFF position.

WARNING

CHECK FOR GAS LEAKS

Explosion Risk.

Fire Risk.

Asphyxiation Risk.

Check the fittings and connections

Do not use open flame.

After the gas line installation is complete, all connections must be tightened and checked for leaks with a commercially-available,noncorrosive leak check solution. Be sure to rinse

off all leak check solution following testing. Fittings and connections may have loosened during shipping and handling.

WARNING

Fire hazard.

Do NOT change the valve settings.

This valve has been preset at the factory.

Changing valve settings may result in fire hazard or bodily injury.

HIGH ALTITUDE INSTALLATIONS

Omni-TestLaboratories, Inc. listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2000 feet in the U.S.A. and 0 to 4500 feet in Canada.

When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A. If the heating value of the gas has been reduced, these rules do not apply. To identify the proper orifice size, check with the local gas utility.

If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.

Page 28

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

7 Electrical Information

A. Recommendation for Wire

See B5 below for recommended maximum lead length (two wire) when using wall thermostat/switch.

NOTE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, withNational Electric Code ANSI/NFPA 70-latest edition or theCanadian Electric Code, CSA

C221.1.

B. Connecting to the Appliance

WARNING

Wire 110v to electrical junction box.

Do NOT wire 110v to the valve.

Do NOT wire 110V to wall switch.

Incorrect wiring will damage millivolt systems.

1.This appliance may be used with a wall switch, wall mounted thermostat and / or a remote control.

2.If using thermostat, use one compatible with a millivolt gas valve system.

3.Follow parameters for locating thermostat (see individual thermostat instructions) to ensure proper operation of appliance.

4.Use low resistance thermostat wire for wiring from ignition system to the wall switch and thermostat.

5.Use the following chart for wire sizing.

Wire Size

Max. Length

16 gauge

65 feet

18 gauge

40 feet

20 gauge

25 feet

22 gauge

18 feet

8.Ensure the thermostat is mounted level for accurate readings.

9.The thermostat should be mounted on an inside wall and not in direct line with the appliance convection air.

10.If the thermostat is located too close to the appliance, you may need to set the temperature setting slightly higher to maintain the desired temperature in your home.

Do not connect this appliance to a thermostat serving any other appliance.

Bedroom installation in Canada requires this appliance to be connected to a thermostat.

WARNING

Shock hazard.

This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle. Do not cut or remove the grounding prong from this plug.

C.Standing Pilot Ignition System Wiring

This appliance DOES NOT require 110 VAC supply for operation. A wiring diagram is shown inFigure 7.1 on the next page.

This appliance is equipped with a millivolt control valve.

6.Keep wire lengths as short as possible by removing any excess wire length.

7.Low voltage and 110 VAC voltage cannot be shared within the same wall box.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 29

Thermopile

Ignition Module

Black

ON/OFF

Switch

Black TH

IgniterPilot

Thermocouple

Gas

 

PILOT ASSEMBLY

 

 

TPTH

 

 

TP

 

TPTH

 

A

E

 

 

 

TP

 

 

 

TH

HI

LO

 

 

N

O

 

 

O

F

 

 

 

F

 

 

 

TOLIP

 

P

 

 

 

TOLI

 

 

VALVE

Figure 7.1

CAUTION

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

CAUTION

Shock hazard.

Replace damaged wire with type 105O C rated wire.

Wire must have high temperature insulation.

D.Ignition Module Access and Battery Replacement

The Ignition Module is located under the appliance attached to the decorative cover.

To access the module:

1.Lift off the appliance top and place it on a flat surface, with the porcelain side up to prevent damage.

2.Remove the appliance front by sliding it upwards in the grooves, being careful not to chip the porcelain. Lay the front face up on a flat surface.

3.With the cast iron front removed, remove the decorative cover located under the apliance. To remove the cover, remove the two screws on the front of the appliance that hold the cover in place. Pull the cover forward, down and out. The module will then be accessible for service and battery replacement.

The single "AA" 1.5V battery that powers the ignitor is located in the module. To replace the battery, open the battery compartment and remove the old battery. Replace the battery making sure the polarity is correct.

Figure 7.2

CAUTION

Battery polarity must be correct or module damage will occur.

Page 30

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

 

 

Appliance Setup

 

A.

Remove Shipping Materials

C. Flue Restrictor Installation

8

 

Remove shipping materials from inside or underneath the firebox.

When your installation falls within a shaded area on the vent graph (page 11), a flue restrictor must be installed for proper operation.

B. Leg Leveling System

Figure 8.1 Thread Allen bolts through nuts until flush. The Allen bolts and nuts are included in the component pack inside the appliance firebox.

Figure 8.2 Slide assembled nuts and bolts into the slots on the legs with the nuts on the bottom.

Figure 8.3 Use a 5/32 in. 4mm) Allen wrench to adjust legs up and down to desired level.

Figure 8.4 Installation of the flue restrictor requires the removal of the baffle located inside the firebox. Remove the baffle by first removing the two screws holding the baffle in place (one on each side).

Lift the baffle out of the bracket along the back of the firebox, angle the baffle slightly and remove it from the firebox.

Figure 8.5 With the baffle removed, remove the two screws located in the back of the firebox. Reuse the screws to install the flue restrictor. Reinstall the baffle using the two screws previously removed.

The flue restrictor should be used in all situations that fall within the shaded area on the vent graph.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 31

D. Intake Damper Operation

F. Positioning the Logs

The intake damper can be used with or without the flue restrictor to adjust the air flow. Opening the damper makes the flames shorter and more active. Closing the damper makes the flames taller and less active.

Figure 8.6 Loosen the wingnut that secures the damper. The wingnut is located on the underside of the appliance, to the right of the pilot assembly.

To CLOSE the intake damper, pull the wingnut forward.

To OPEN the damper, push the wingnut back. Adust the damper in 1/4 in. increments until the desired flame is achieved. After adjustment, tighten the wingnut.

NOTE: In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.

E. Intake Air Shutter Adjustment

OPEN CLOSE

Figure 8.7 The shutter is located on the underside of the appliance, on the right side. To adjust the shutter, loosen the wingnut.

Moving the shutter bolt to the right closes the shutter. Moving the shutter bolt to the left, will open the shutter. Opening the shutter causes flames to become shorter and blue. Closing the shutter creates taller orange/yellow flames.

NOTE: Do not close so much as to cause a sooty flame. Improper adjustment can cause sooting in the firebox and/ or on the outside of a house with a horizontal termination.

Retighten the wingnut after adjustment.

While still breakable, the logs do not become fragile until after the appliance is burned and they have cured. After curing, any handling must be done with care as breakage can easily occur.

PLEASE NOTE: Logs have been designed to work specifically with the burner of this appliance. Exact placement will ensure proper operation of your gas appliance and reduce sooting.

Figure 8.8 Gently remove the top of the appliance and set aside. Remove the cast face by sliding straight up and set it aside.

Remove the glass by releasing the latch located on the top of the appliance. Lean the glass frame forward and lift it out.

Place the left log on the log shelf along the back of the firebox with thefront resting on the burner.

Figure 8.9 Place the right log on the log shelf along the back of the firebox with the front of the log resting on the burner.

Page 32

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

Figure 8.10

Place the twig with the center resting on the flat area in the center of the burner and both ends positioned as shown.

G. Mineral Wool

WARNING

Explosion Risk.

Follow ember placement instructions in manual.

Do NOT place embers directly over burner ports.

Replace ember material annually.

Improperly placed embers interferes with proper burner operation.

Figure 8.11 Apply dime size pieces sparingly along front edge of burner. Do not completely block ports.

H. Accessories

Install approved accessories per instructions included with accessories. Refer to Section 12 for appropriate accessories.

WARNING

Shock or fire risk.

Use ONLY optional accessories approved for this appliance.

Using non-listedaccessories voids warranty.

• Using non-listedaccessories may result in a safety hazard.

Only Hearth & Home Technologies approved accessories may be used safely.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 33

I. Blower Installation

KIT CONTENTS:

1 - Blower Mounted in Housing

2 - Speed Control Knob

3 - Pal Nut

4 - Ceramic Snap Disk

5 - Speed Control (Rheostat)

6 - Wire Harness (attached to Blower)

7 - 12 Screws

8 - 12 inch Glass Tape

9 - 1 Zip Tie

10 - Bracket #1

11 - Snap Disc Bracket

TOOLS REQUIRED: Short #2 Philips screwdriver; 11/16" wrench.

10

11

Figure 8.12 Open and inspect contents of the blower kit. The contents of the kit are listed above. If any of the parts are missing or damaged, please contact your dealer for replacements.NOTE: Not all parts will be used for this install.

Figure 8.13 Lift off the appliance top and place it on a flat surface, with the porcelain side up to prevent damage. Remove the back shield by removing the two screws along the top of the shield.

Place the blower on the floor behind the appliance and route the ends of the wiring harness through the rubber grommet on the underside.

Figure 8.14 Holding the blower in place, attach it to the appliance with four of the screws provided.

SNAP DISC

SNAP DISC

 

BRACKET

SPADE

TERMINALS

Figure 8.15 Install the snap disc. A snap disc bracket is located in the appliance's component bag. Bend the two spade teminals on the snap disc from a horizontal to a vertical position. Insert the snap disc through the hole in the snap disc bracket and attach the two white wires from the wiring harness to the snap disc.

NOTE: The mounting flange is on top of the bracket.

Page 34

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

Figure 8.16 With the cast iron front of the appliance removed, remove the decorative cover located under the appliance. To remove the cover, remove the two screws on the front of the appliance that hold the cover in place. Pull the cover forward, down and out.

Figure 8.17 Attach the snap disc bracket to the stud located under the left side of the appliance using the10-32nut also located in the appliance component bag.

Figure 8.18 Install the speed control (rheostat). The speed control mounts to the decorative cover removed in Step 5. Insert the stem of the speed control through the hole located on the right side of the cover. Secure with the pal nut using an 11/16 in. (17.5 mm) wrench. Attach the black and white wires routed under the appliance indicated inFigure 8.13, on page 34, to the two speed control wires. Push the speed control knob onto the stem andre-attachthe decorative cover. Secure the wires up and out of the way using the zip tie provided.

Plug in the blower.

The blower will not run until the appliance has heated up enough to activate the snap disc. This can take up to 15 minutes depending on the temperature of the room. Likewise, the blower will not automatically turn off until the appliance has cooled off enough to turn off the snap disc.

Turning the control knob to the left (counterclockwise) until you hear an audible click will turn the blower "OFF". Turning the control knob to the right (clockwise) until you hear a click will turn the blower "ON". Turning the control knob further to the right will reduce the speed of the blower.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 35

 

 

VARIABLE SPEED CONTROL

 

 

BLACK

 

BLACK

JUNCTION BOX

 

 

 

 

 

BLACK

BLACK

 

BLACK

 

BLOWER RECEPTACLE

BLACK

 

 

BLACK

WHITE

BLACK

BLACK

 

 

BLACK

 

 

 

 

 

 

WHITE

 

 

 

 

 

TEMPERATURE SENSOR SWITCH

 

 

GROUND

 

 

 

BLACK

 

GREEN

BLOWER

 

 

 

WHITE

 

 

 

 

 

 

 

 

110 - 120 VAC

 

 

 

 

POWER SUPPLY

 

Figure 8.19 Complete Assembly

 

 

 

 

Page 36

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

J. Warming Shelves Installation

KIT CONTENTS: (2) Warming shelves, (2) brackets, and (4) 1/4 in. Phillip head screws.

TOOLS NEEDED: Phillips head screwdriver.

Figure 8.20 Remove warming shelves and hardware from packaging. Install leveling bolt to each warming shelf.

Figure 8.21 Install warming shelf bracket loosely to each warming shelf using the bolt provided.

Figure 8.23 Align bracket to firebox and gently tighten the screw to hold it in place.

Reassemble the appliance.

K. Glass Replacement

Turn the appliance OFF and let it cool down before replacing the glass. Lift off the appliance top and place it on a flat surface with the porcelain side up to prevent damage.

Remove the appliance front by sliding it upwards in the grooves being careful not to chip the porcelain. Lay the front face up on a flat surface.

Unhook the latch now exposed on top of the appliance. Pull the top of the glass frame toward you and lift it out of the retainer along the bottom of the firebox.

Replacement is the reverse of the removal.

Figure 8.22 Gently lift cast top off of unit and set aside.

Install warming shelf to unit gently aligning the shelf with the tabs that are in place on the side of the unit. Use the leveling bolt in the located in the center of the warming shelf to adjust the shelf to it's desired position.

CAUTION

Handle glass assembly with care.

Inspect the gasket to ensure it is undamaged.

Inspect the glass for cracks, chips or scratches.

Do NOT strike, slam or scratch glass.

Do NOT operate appliance with glass door removed, cracked, broken or scratched.

Replace glass assembly as a complete assembly.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 37

9 Operating Instructions

A. Before Lighting Appliance

Read this entire manual prior to using the appliance. Failure to follow the instructions may result in property damage, bodily injury, or even death.

Remove all shipping materials from inside and/or underneath the firebox.

Review proper placement of logs, mineral wool.

Check the wiring.

Check the baffle adjustment.

Ensure that there are no gas leaks.

Ensure that the glass is sealed and in the proper position.

Ensure that the flow of combustion and ventilation air is not obstructed (front grilles and vent caps).

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or the gas supplier.

WARNING

Do NOT use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

WARNING

Glass door must be in place when appliance is operating.

Risk of:

Combustion Fumes

Fire

Do NOT operate appliance with glass door removed.

Open viewing glass for servicing only.

Glass door MUST be in place and sealed before operating appliance.

Only use glass door certified for use with appliance.

Glass replacement should be done by qualified technician.

WARNING

HOT! DO NOT TOUCH.

SEVERE BURNS MAY RESULT.

CLOTHING IGNITION MAY RESULT.

Glass and other surfaces are hot during operation and cool down.

Keep children away.

CAREFULLY SUPERVISE children in same room as appliance.

Alert children and adults to hazards of high temperatures.

Do NOT operate with protective barriers open or removed.

Keep clothing, furniture, draperies and other combustibles away.

B. Controls

FAN SPEED: The blower is optional installed on the appliance and this knob controls the speed of the blower that pushes the heated air into the room.

MAIN BURNER: This control is used to turn the appliance on and off.

PILOT IGNITOR: The pilot ignitor is used only to start the pilot. When the valve control knob is turned to the pilot position and fully depressed, it sends an electrical charge to the pilot assembly. The appliance is equipped with an electric igniter and should begin sparking right away.

VALVE CONTROL: This knob is used to control gas to the appliance and for starting the pilot. There are three positions,ON, OFF, & PILOT. The indicator on the valve indicates the position of the knob.

COMFORT CONTROL: This knob controls the flame height from low (“LO”) to high (“HI”).

NOTE: If using a remote control wall switch, or thermostat, the On/Off Switch must be left “OFF”. Turning the On/Off Switch to “ON” will keep the appliance on continually.

Page 38

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

C. Lighting Appliance

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life

A.This appliance has a pilot that must be lit manually. When lighting the pilot, follow these instructions exactly.

B.BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

*Do not try to light any appliance.

*Do not touch any electric switch, do not use any phone in your building.

*Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

*If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

 

LIGHTING INSTRUCTIONS

1.

STOP! Read the safety information above on this label.

 

2.

Set the thermostat to the lowest setting (if applicable) and turn off

 

the switch at the control panel.

 

3.

Disconnect the power from the appliance.

 

4.

Open the door of the appliance. May need to remove face/front first.

5.

Push in gas control knob slightly and turn clockwise

to the "OFF"

 

position. Do not force.

 

6.Wait five (5) minutes to clear out any gas. Smell for gas, including near the floor. If you smell gas, STOP! Follow "B" of the safety information above. If you don't smell gas go to the next step.

7.Push gas control knob in and turn counterclockwise to the pilot position. NOTE: Knob cannot be turned unless knob is pushed in slightly. Do not force.

8.PIEZO IGNITER: Press down on the gas control knob in pilot position and simultaneously press the piezo igniter.

(This may take many repetitions for lighting.)

ELECTRONIC IGNITER: If the unit is equipped with an electronic igniter it should begin sparking right away.

9.The pilot should be visible through the door opening.

10.After the pilot is lit, continue holding control knob down for approximately

30 seconds. Release the knob and it will pop back up. Pilot should remain lit.

MILLIVOLT

PILOT HOOD

THERMOCOUPLE

If it goes out, repeat steps 7 through 9.

GENERATOR

* If the knob does not pop up when released, stop and immediately call your

 

 

service technician or gas supplier.

 

 

* If the pilot will not stay lit after several tries, turn the gas control knob

 

 

clockwise

to "OFF" and call your service technician or gas supplier.

 

 

11. Reinstall door and face. Wait five minutes to allow pilot flame to stabilize and establish proper draft.

12.Push down and turn gas control knob counterclockwise to "ON".

13.Push burner rocker switch on the control panel to "ON". If thermostat is to be used, leave switch in "OFF" position and set the thermostat to desired setting.

14.Reconnect electrical power to appliance.

TO TURN OFF GAS TO APPLIANCE

1.Set the thermostat to lowest setting.

2.Turn off all electric power to the appliance if service is to be performed.

3.Push in gas control knob slightly and turn clockwise to "OFF" position.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 39

D. After Appliance is Lit

Initial Break-inProcedure

When you light your appliance, you may notice that it produces heat which does have an associated odor or smell. If you feel this odor is excessive it may require the initial three to four hour continuous burn on high followed by a second burn up to 12 hours to fully drive off any odor from paint and lubricants used in the manufacturing process. Condensation on the inside of the glass is normal.

NOTE: The appliance should be run three to four hours on the initialstart-up.Turn it off and let it cool completely. Remove and clean the glass. Replace the glass and run the appliance for an additional 12 hours. This will help to cure the products used in the paint and logs.

During this break-inperiod it is recommended that some windows in the house be opened for air circulation. This will help avoid setting off smoke detectors, and help eliminate any odors associated with the appliance’s initial burning.

WARNING

Fire Risk.

High Temperatures.

Keep combustible household items away from appliance. Do NOT obstruct combustion and ventilation air.

Do NOT place combustible items on top of or in front of appliance.

Keep furniture, draperies away from appliance.

CAUTION

Prevent accidental appliance operation when not attended.

Unplug or remove batteries from remote control if absent or if appliance will not be used for an extended period

of time.

Property damage possible from elevated temperatures.

CAUTION

Smoke and odors released during initial operation.

Open windows for air circulation.

Leave room during initial operation.

Smoke may set off smoke detectors.

Smoke and odors may be irritating to sensitive individuals.

WARNING

Fire Hazard.

Keep combustible materials, gasoline and other flammable vapors and liquids clear of appliance.

Do NOT store flammable materials in the appliance’s vicinity.

Do NOT use gasoline, lantern fuel, kerosene, charcoal lighter fluid or similar liquids in this appliance.

Combustible materials may ignite.

E. Frequently Asked Questions

ISSUE

SOLUTIONS

Condensation on the glass

This is a result of gas combustion and temperature variations. As the appliance warms,

 

this condensation will disappear.

Blue flames

This is a result of normal operation and the flames will begin to yellow as the appliance

 

is allowed to burn for 20 to 40 minutes.

Odor from appliance

When first operated, this appliance may release an odor for the first several hours.

 

This is caused by the curing of the paint and the burning off of any oils remaining from

 

manufacturing.

Film on the glass

This is a normal result of the curing process of the paint and logs. Glass should be

 

cleaned within 3 to 4 hours of initial burning to remove deposits left by oils from the

 

manufacturing process. A non-abrasivecleaner such as gas appliance cleaner may be

 

necessary. See your dealer.

Metallic noise

Noise is caused by metal expanding and contracting as it heats up and cools down,

 

similar to the sound produced by a furnace or heating duct. This noise does not affect

 

the operation or longevity of the appliance.

Page 40

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

10 Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-freeservice. If you do experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1. After repeated trig-

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode

gering of the piezo

 

wire is properly connected, replace the ignitor.

button, the spark ignitor

 

 

b. Defective pilot or

Using a match, light the pilot. If the pilot lights, turn off the pilot and

will not light the pilot.

misaligned electrode

trigger the piezo button again. If the pilot lights, an improper gas/air

 

 

(spark at electrode).

mixture caused the bad lighting and a longer purge period is recom-

 

 

mended. If the pilot will not light, ensure the gap at the electrode and

 

 

pilot is one-eighth(1/8) inch to have a strong spark. If the gas is OK,

 

 

replace the pilot.

 

c. No gas or low gas

Check the remote shut-offvalve from the appliance. Usually, there is

 

pressure.

a valve near the gas main. There can be more that one (1) valve from

 

 

the appliance and the main.

 

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2. The pilot will not stay

a. Defective thermo-

Check that the pilot flame impinges on the thermocouple. Clean and /or

lit after carefully follow-

couple.

adjust the pilot for maximum flame impingement.

ing the lighting instruc-

 

 

tions.

 

Ensure that the thermocouple connection at the gas valve is fully

 

 

inserted and tight (hand tighten plus 1/4 turn).

 

 

Disconnect the thermocouple from the valve, place one millivolt lead

 

 

wire on the tip of the thermocouple and the other meter wire on the

 

 

thermocouple copper lead. Start the pilot and hold the valve knob in. If

 

 

the millivolt reading is less than 15mV, replace the thermocouple.

 

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty

 

 

valve.

3. The pilot is burning,

a. ON/OFF switch or

Check the ON/OFF switch and wires for proper connections. Place the

there is no gas to the

wires defective.

jumper wires across the terminals at the switch. If the burner comes on,

burner, the valve knob is

 

replace the defective switch. If the switch is OK, place the jumper wires

in the ON position, and

 

across the switch wires at the gas valve. IF the burner comes on, the

the ON/OFF switch is in

 

wires are faulty or connections are bad.

the ON position.

 

 

b. Thermopile may

If the pilot flame is not close enough physically to the thermopile, adjust

 

 

not be generating

the pilot flame.

 

sufficient millivoltage.

Be sure the wire connections from the thermopile at the gas valve ter-

 

 

 

 

minals are tight and that the thermopile is fully inserted into the pilot

 

 

bracket.

 

 

Check the thermopile with a millivolt meter. Take the reading at TH-

 

 

TP&TP terminals of the gas valve. The meter should read 325 millivolts

 

 

minimum, while holding the valve knob depressed in the pilot position,

 

 

with the pilot lit, and the ON/OFF switch in the OFF position. Replace

 

 

the faulty thermopile if the reading is below the specified minimum.

 

 

With the pilot in the ON position, disconnect the thermopile leads from

 

 

the valve. Take a reading at the thermopile leads. The reading should

 

 

be 325 millivolts minimum. Replace the thermopile if the reading is

 

 

below the minimum.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 41

 

Symptom

Possible Cause

Corrective Action

3.

(Continued)

c. Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the

 

 

 

ON position. Check the millivolt meter at the thermopile terminals. The

 

 

 

millivolt meter should read greater than 125mV. If the reading is accept-

 

 

 

able, and if the burner does not come on, replace the gas valve.

 

 

d. Plugged burner

Check the burner orifice for stoppage. Remove stoppage.

 

 

orifice.

 

 

 

e. Wall switch or

Follow the corrective action in Symptom and Possible Cause 1.a.

 

 

wires are defective.

Check the switch and wiring. Replace where defective.

4.

Frequent pilot outage

a. Pilot flame may

Clean and adjust the pilot flame for maximum flame impingement on

problem.

be too high or too

thermocouple. Follow lighting instructions carefully.

 

 

low, or blowing

 

 

 

(high), causing safety

 

 

 

pilot to drop out.

 

5.

The pilot and main

a. No LP in tank.

Check the LP (propane) tank. Refill the fuel tank.

burner extinguish while

b. Inner vent pipe

Check for proper vent connection at flue collar and all vent joints.

in operation.

leaking exhaust

 

 

 

gases back into the

 

 

 

system.

 

 

 

c. Horizontal vent

The horizontal vent cap should slope down only enough to prevent any

 

 

improperly pitched.

water from entering the appliance.

 

 

d. Bad thermopile or

Replace if necessary.

 

 

thermocouple.

 

 

 

e. Improper vent cap

Check for proper installation and freedom from debris or blockage.

 

 

installation.

 

6.

Glass soots.

a. Flame impinge-

Adjust the log set so that the flame does not excessively impinge on it.

 

 

ment.

Check that logs are placed according to installation instructions.

 

 

b. Improper shutter

Adjust the air shutter at the base of the burner.

 

 

setting.

 

 

 

c. Debris around

Inspect the opening at the base of the burner. NO MATERIAL SHOULD

 

 

opening at base of

BE PLACED IN THIS OPENING.

 

 

burner.

 

7.

Flame burns blue

a. Insufficient

Ensure that the vent cap is installed properly and free of debris. Ensure

and lifts off burner.

oxygen being sup-

that the vent system joints are tight and have no leaks.

 

 

plied.

Ensure that no debris has been placed at the base of, or in the area of

 

 

 

 

 

 

the air holes in the center of the base pan beneath the burner.

 

 

 

Ensure that the glass is tightened properly on the appliance, particu-

 

 

 

larly on top corners.

Page 42

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

11 Maintaining and Servicing Appliance

Although the frequency of your appliance servicing and maintenance will depend on use and the type of installation, a qualified service technician should perform an appliance check-upat the beginning of each heating season.

WARNING

Risk of injury or property damage.

Before servicing:

Turn off gas.

Turn off electricity to appliance.

Ensure appliance is completely cooled.

After servicing:

Replace any screen or barrier that was removed.

Reseal and reinstall any venting removed for servicing.

WARNING

Annual inspection by qualified technician recommended.

Check:

Condition of glass, glass assembly and glass seal.

Obstructions of combustion and ventilation air.

Obstructions of termination cap.

Burner ignition and operation.

Burner air shutter adjustment

• Gas connections and fittings.

Clean:

Glass

Air passageways, grilles, control compartment

Burner, burner ports

Risk of:

• Fire

Delayed ignition or explosion

Exposure to combustion fumes

Odors

WARNING

Inspect external vent cap regularly.

Ensure no debris blocks cap.

Combustible materials blocking cap may ignite.

Restricted air flow affects burner operation.

CAUTION

Handle glass assembly with care.

NOTE: Clean glass after initial3-4hours operation.Longer operation without cleaning glass may cause a permanent white film on glass.

When cleaning glass door:

Avoid striking, scratching or slamming glass.

Do NOT use abrasive cleaners.

Use a hard water deposit glass cleaner on white film.

Do NOT clean glass when hot.

Turn off appliance after 3-4hours of operation and ALLOW TO COOL.

Remove and clean glass assembly.

Replace glass assembly and operate appliance for additional 12 hours.

Refer to maintenance instructions.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 43

A. Maintenance Tasks

Inspect

 

Maintenance Tasks

Doors

1.

Inspect for scratches, dents or other damage and repair as necessary.

 

2.

Verify no obstructions to air flow.

 

3.

Verify maintenance of proper clearance to combustible household objects.

Gasket Seal, Glass

1.

Inspect gasket seal and its condition.

Assembly and Glass

2.

Inspect glass for scratches and nicks that can lead to breakage when exposed to heat.

 

3.

Confirm there is no damage to glass or glass frame, Replace as necessary.

 

4.

Verify that latches engage properly and glass attachment components are intact and operat-

 

ing properly. Replace as necessary.

 

5.

Clean glass. Replace glass assembly if severely coated with silicate deposits that cannot be

 

removed.

Valve Compartment

1.

Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these

and Firebox Top

areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.

 

2.

Remove any foreign objects.

 

3.

Verify unobstructed air circulation.

Logs

1.

Inspect for broken, damaged, or missing logs. Replace as necessary.

 

2.

Verify correct log placement and no flame impingement causing sooting. Correct as neces-

 

sary.

Firebox

1.

Inspect for paint condition, warpage, corrosion or perforation. Sand and repaint as neces-

 

sary.

 

2.

Replace appliance if firebox has been perforated.

Burner Ignition and

1.

Verify burner is properly secured and aligned with pilot or igniter.

Operation

2.

Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if

 

necessary. USE CAUTION WHEN CLEANING/HANDLING CERAMIC BURNER.

 

3.

Replace ember material with new dime-sizeand shape pieces. Do not block ports or obstruct

 

lighting paths.

 

4.

Check for smooth lighting and ignition carryover to all ports. Verify there is no ignition delay.

 

5.

Inspect for lifting and other flame problems.

 

6.

Inspect orifice for soot, dirt or corrosion.

 

7.

Verify manifold and inlet pressures. Adjust regulator as required.

 

8.

Inspect pilot flame strength. Clean or replace orifice as necessary.

 

9.

Inspect thermocouple/thermopile sensor rod for soot, corrosion and deterioration. Clean with

 

emery cloth or replace as required.

 

10. Verify millivolt output. Replace as necessary.

Venting

1.

Inspect venting for blockage or obstruction such as bird nests, leaves, etc.

 

2.

Confirm that termination cap remains clear and unobstructed by plants, etc.

 

3.

Verify that termination cap clearance to subsequent construction (building additions, decks,

 

fences or sheds) has been maintained.

 

4.

Inspect for corrosion or separation.

 

5.

Verify weather stripping, sealing and flashing remains intact.

Remote Controls

1.

Verify operation of remote.

 

2.

Replace batteries in remote transmitters and battery-poweredreceivers.

Page 44

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

12 Reference Materials

A. Appliance Dimension Diagram

Dimensions are actual appliance dimensions. Use for reference only. For clearances to combustibles refer to Section 3.

 

A

B

 

 

C

D

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

F

 

 

 

 

Location

Inches

Millimeters

Location

Inches

Millimeters

 

A

27-3/8

695

D

17-3/8

441

 

B

18-1/8

460

E

22-3/4

578

 

C

15-3/8

384

F

16-1/4

413

Figure 12.1

Appliance Dimensions

 

 

 

 

 

August 1, 2008

 

 

Heat & Glo · Tiara Petite B · 7026-101K

Page 45

B. Vent Components Diagram

 

 

 

6-3/8in.

 

 

 

6-1/2in.

 

(162mm)

 

 

 

 

 

 

 

(165mm)

 

 

 

 

9-1/4in.

 

 

 

 

 

(235mm)

 

 

 

6-1/2in.

 

 

 

 

 

 

 

 

6-3/8in.

 

(165mm)

9-5/8in.

 

 

 

 

(244mm)

 

6-5/8in.

(162mm)

 

 

 

 

(168mm)

 

 

 

 

SLP45-BK

 

 

 

 

 

 

6-5/8in.

 

 

 

 

 

(168mm)

 

9-5/8in.

 

 

 

SLP90M

 

 

 

(244mm)

17-24in.

 

 

6-1/2in.

 

 

(432-610mm)

 

 

(165mm)

 

 

 

11-3/4in.

 

 

 

 

 

(298mm)

5-3/4in.

 

 

 

 

 

 

 

 

 

 

(146mm)

 

 

 

SLP12AM

 

 

6-5/8in.

 

SLP12M

 

(168mm)

 

 

 

SLP6M

 

 

 

 

 

 

 

 

 

 

 

 

47-3/4in.

 

 

 

 

 

(1213mm)

 

 

 

35-3/4in.

 

 

 

 

 

(908mm)

 

 

 

 

23-3/4in.

 

 

 

 

 

(603mm)

 

 

 

 

12-17in.

 

 

 

 

 

(305-432mm)

 

 

 

 

3-3/4in.

 

 

 

 

 

(95mm)

 

 

 

 

 

SLP4M

SLP6AM

SLP24M

SLP36M

SLP48M

 

4 in. (102 mm) inner pipe 6-5/8in. (168 mm) outer pipe

 

Figure 12.2 SL-DSeries Vent Components

 

 

 

 

Page 46

Heat & Glo · Tiara Petite B · 7026-101K

 

August 1, 2008

C. Vent Components List

Description

HHT SL-P

Simpson

Selkirk®

Amerivent

Security

 

M= Multi Pack (6)

Dura-Vent®

Direct-Temp

Direct ®

Secure Vent®

 

 

DirectVent Pro

 

 

 

4” Pipe Length, Galvanized

SLP4M

-

-

-

-

4” Pipe Length, Black

SLP4-BK

-

-

-

-

6” Pipe Length, Galvanized

SLP6M

46-DVA-06

4DT-6

-

SV4L6

6” Pipe Length, Black

SLP6-BK

46-DVA-06B

4DT-6B

-

SV4LB6

7” Pipe Length, Galvanized

-

-

-

4D7

-

7” Pipe Length, Black

-

-

-

4D7B

-

9” Pipe Length, Galvanized

-

46-DVA-09

4DT-9

-

-

9” Pipe Length, Black

-

46-DVA-09B

4DT-9B

-

-

12” Pipe Length, Galvanized

SLP12M

46-DVA-12

4DT-12

4D12

SV4L12

12” Pipe Length, Black

SLP12-BK

46-DVA-12B

4DT-12B

4D12B

SV4LB12

18” Pipe Length, Galvanized

-

46-DVA-18

4DT-18

-

-

18” Pipe Length, Black

-

46-DVA-18B

4DT-18B

-

-

24” Pipe Length, Galvanized

SLP24M

46-DVA-24

4DT-24

4D2

SV4L24

24” Pipe Length, Black

SLP24-BK

46-DVA-24B

4DT-24B

4D2B

SV4LB24

36” Pipe Length, Galvanized

SLP36M

46-DVA-36

4DT-36

4D3

SV4L36

36” Pipe Length, Black

SLP36-BK

46-DVA-36B

4DT-36B

4D3B

SV4LB36

48” Pipe Length, Galvanized

SLP48M

46-DVA-48

4DT-48

4D4

SV4L48

48” Pipe Length, Black

SLP48-BK

46-DVA-48B

4DT-48B

4D4B

SV4LB48

Adjustable Length, 3”-6”,Black

SLP6A-BK

-

-

-

 

Adjustable Length, 3”-6”,Galvanized

SLP6AM

-

-

-

-

Adjustable Length, 3”-7”,Galvanized

-

46DVA-08A

-

-

-

Adjustable Length, 3”-7”,Black

-

46DVA-08AB

-

-

-

Adjustable Length, 3”-12”,Black

SLP12A-BK

-

-

-

-

Adjustable Length, 3”-12”,Galvanized

SLP12AM

-

-

-

-

Adjustable Length, 3”-14.5”,Galvanized

-

46DVA-16A

-

-

-

Adjustable Length, 3”-14.5”,Black

-

46DVA-16AB

-

-

-

Adjustable Length, 7”, Galvanized

-

-

-

4D7A

-

Adjustable Length, 7”, Black

-

-

-

4F7AB

-

Adjustable Length, 11”-14”,Galvanized

-

-

4DT-AJ

-

-

Adjustable Length, 11”-14”,Black

-

-

4DT-AJB

-

-

Adjustable Length, 12”, Galvanized

-

4DTAJ12

-

4D12A

SV4LA12

Adjustable Length, 12”, Black

-

4DTAJ12-B

-

4D12AB

SV4LBA12

Adjustable Length, 16”, Galvanized

-

46DVA-16A

-

4D16A

-

Adjustable Length, 16”, Black

-

46DVA-16AB

-

-

-

Adjustable Length, 24”, Galvanized

-

-

-

-

SV4LA24

Adjustable Length, 24”, Black

-

-

-

-

SV4LBA24

2’ Flexible Pipe Length

SLP-FLEX-2

-

-

-

-

3’ Flexible Pipe Length

SLP-FLEX-3

-

-

-

-

5’ Flexible Pipe Length

SLP-FLEX-5

-

-

-

-

10’ Flexible Pipe Length

SLP-FLEX-10

-

-

-

-

3” x 35’ Flex Extension

-

2280

-

-

-

4” x 35’ Flex Extension

-

2281

-

-

-

45° Elbow, Galvanized

SLP45M

-

-

-

-

45° Elbow, Black

SLP45-BK

See Swivel

4DT-EL45B

4D45LB

SV4EBR45

45° Elbow, Swivel, Galvanized

-

46DVA-E45

-

-

SV4E45

 

 

 

 

 

 

 

 

 

 

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

 

Page 47

Description

HHT SL-P

Simpson

Selkirk®

Amerivent

Security

 

 

M= Multi Pack (6)

Dura-Vent®

Direct-Temp

Direct ®

Secure Vent®

 

 

 

DirectVent Pro

 

 

 

45° Elbow, Swivel, Black

 

-

46DVA-E45B

-

-

SV4EB45

90° Elbow, Galvanized

 

SLP90M

See Swivel

4DT-EL905

4D90LS

-

90° Elbow, Black

 

SLP90-BK

See Swivel

4DT-EL90SB

4D90LBS

SV4EBR90

90° Elbow, Swivel, Galvanized

-

46DVA-E90

-

-

SV4E90

90° Elbow, Swivel, Black

 

-

46DVA-E90B

-

-

SV4EB90

Adjustable Flashing, 0/12-6/12

SLP-RF6M

46DVA-F6

4DT-AF6

4DF

SV4FA

Adjustable Flashing, 7/12-12/12

SLP-RF12M

46DVA-F12

4DT-AF12

4DF12

SV4FB

Attic Insulation Shield - Cold Climates 36”

-

-

-

4DAIS37

-

Attic Insulation Shield 12”

 

SLP-AS2M

-

-

4DAIS12

SV4RSA

Attic Insulation Shield, Adjustable 11”-20”

-

46-DVA-IS

-

-

-

Cathedral Support Box

 

SLP-CCS-BK

46DVA-CS

4DT-CSS

4DRSB

SV4CSB

Ceiling Support

 

-

46DVA-DC

4DT-CS

4DFSP

SV4SD

Co-AxialtoCo-LinealAppliance Connector

-

46DVA-GCL

-

-

-

Decorative Ceiling Firestop - Black

SLP-DCF-BK

-

-

-

-

Decorative Radius Cover

 

DRC-RADIUS

-

-

-

-

Firestop Spacer/Ceiling Firestop

SLP-FSM

46DVA-FS

4DT-FS

4DFSP

SV4BF

Flex Trap Cap with Firestop

 

SLP-FLEX-TRAP

-

-

-

-

Flex Trap Cap with Firestop and 30’ Flex Pipe

SLP-FLEX-TRAP30

-

-

-

-

Masonry Chimney Conversion Kit

-

46DVA-KMC

-

-

-

Offset Support

 

-

46DVA-ES

4DT-OS

-

SV4SU

Offset Wall Thimble, Black

 

SLP-WT-BK

-

-

-

-

Silicone Roof Flashing, 4” to 8” pipes (6)

RF4-8M

-

-

-

-

Storm Collar

 

SLP-SCM

46DVA-SC

4DT-SC

4DSC

SV4FC

Trim Plate, Black

 

-

-

4DT-TP

4DFPB

SV4LA

Wall Support Band

 

SLP-HVSM

46-DVA-WS

4DT-WS/B

4DWS

SV4BM

Wall Thimble Support Box/Ceiling Support

-

-

-

-

SV4PF

Wall Thimble, Black

 

SLP-WSM

46DVA-WT

4DT-WT

4DWT

SV4RSM

TERMINATION CAPS & KITS

 

 

 

 

 

Basic Horizontal Termination Kit (A)

-

46DVA-KHA

4DT-HKA

4DHTK2

SV-SHK

Chimney Liner Termination Kit

-

46DVA-GK

-

-

-

Horizontal Square Termination Cap

SLP-HHW2

46DVA-HC

4DT-HHC

4DHC

SV4CHC

Horizontal Termination Kit (B)

-

46DVA-KHC

4DT5-HKB

4DHTK1

SV-HK

RHVK Snorkel Kit

 

-

844-8921

-

-

-

Snorkel Termination 14”

 

SLK-SNKD

46DVA-SNK14

4DT-ST14

4D12S

SV4STC14

Snorkel Termination 36”

 

-

46DVA-SNK36

4DT-ST36

4D36S

SV4STC36

*Stove Adaptor Kit (Vertical Cap Kit)

LINK-STOVE

-

-

-

-

Trapezoid Termination Kit

(3-1/8”-4-3/4”)

SLP-TRAP1

-

-

-

-

Trapezoid Termination Kit

(5-1/4”X9-1/4”)

SLP-TRAP2

 

 

 

 

Vertical Termination Cap

 

SLP-TVHW

46DVA-VCH

4DT-VKC

4DVT

SV4CGV

* Stove Adaptor Kit (Vertical Cap Kit) Includes30’-4”flex, adapters, wall thimble, masonry, ZC flashing, 991DA vertical cap.

NOTES: 1Before cutting any holes check pipe manufacturers current instructions.2Each pipe manufacturer has their own list of parts for kits.

3SL is not interchangeable with SLP.

Page 48

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

D. Service Parts List

TIARA PETITE B

(NG, LP) Exploded Parts Diagram

Beginning Manufacturing Date: 4-04

 

Ending Manufacturing Date:

 

 

 

IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealer's VIP site. When ordering, supply serial and model numbers to ensure correct service parts.

 

12

 

 

 

10

 

 

 

11

 

 

 

 

8

 

 

 

9

 

 

13

 

 

 

 

 

7

 

 

 

6

14

 

 

 

15

 

 

 

 

 

3

 

 

2

 

4

 

1

 

5

 

 

 

Item

Description

Item

Description

1

Bulkhead with Flex Tube

9

Adapter, DV

2

Air Shutter Assembly

10

Blower Shroud Top

3

Baffle

11

Relief Door Bracket

4

Baffle Back

12

Relief Door Assembly

5

Damper Assembly

13

Latch, Draw

6

Gasket, Adapter, Elbow

14

Door/Glass Assembly

7

Blower Shroud Back

15

Door Retainer

8

Flue Shield

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 49

D. Service Parts List(cont’d.) TIARA PETITE B

(NG, LP) Exploded Parts Diagram

Beginning Manufacturing Date: 4-04

 

Ending Manufacturing Date:

 

 

 

IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealer's VIP site. When ordering, supply serial and model numbers to ensure correct service parts.

 

28

 

 

 

25

 

 

27

 

 

26

 

29

24

 

30

 

 

 

23

 

 

22

1

31

21

2

 

20

 

3

 

 

19

 

16

 

 

17

18

 

Item

Description

Item

Description

 

 

16

Knob, Extension, ON/OFF

24

Side, Left or Right (interchangeable)

 

 

17

Knob, Extension, HI/LO

25

Back Shield

 

 

18

Valve Cover

26

Switch Bracket

 

 

19

Ignition Module

27

Switch, Rocker, ON/OFF

 

 

20

Valve, Gas

28

Top

 

 

21

Burner with Neck Assembly

29

Front

 

 

22

Gasket, Pilot

30

Log Set Assembly

 

 

23

Pilot Assembly

31

Valve Bracket

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 50

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

D. Service Parts List(cont’d.) TIARA PETITE B

(NG, LP) Exploded Parts Diagram

Beginning Manufacturing Date: 4-04

 

Ending Manufacturing Date:

IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealer's VIP site. When ordering, supply serial and model numbers to ensure correct service parts.

Item

Part Description

SKU

#

Alphabetical Order

 

9

Adapter, DV

7000-162

2

Air Shutter Assembly

7016-017

25

Back Shield

7016-140

3

Baffle

7016-125

4

Baffle Back

7016-126

 

Blower Assembly

BK-GAS

7

Blower Shroud Back

7016-132

10

Blower Shroud Top

7016-118

1

Bulkhead with Flex Tube

7000-156

21

Burner with Neck Assembly

BRNR-TPB

 

Burner Stop

7010-152

 

Burner Support

7016-120

 

Cable/Switch Assembly

230-1900

 

Component Pack Assembly, Matte Black (includes warranty card, ON/OFF valve, mineral wool, leveling assembly, snap disc bracket,

MBK: 7026-003

 

restrictor, owner’s manual, fasteners, and Touch-upPaint.)

BR: 7026-008

 

 

CES: 7026-011

 

 

CTO: 7026-012

 

Conversion Kit, LP

LPK-TPB

 

Conversion Kit, NG

NGK-TPB

5

Damper Assembly

7016-006

32

Door Frame

7016-117

14

Door/Glass Assembly

GLA-TPB

15

Door Retainer

7016-134

 

Flex Line 3/8 Flare x 22L

7000-197

 

Flue Collar

7016-122

8

Flue Shield

7016-130

29

Front

See page 52

6

Gasket, Adapter Elbow

460-0610

33

Glass Assembly Only

7016-023

19

Ignition Module

230-1880

 

 

 

17

Knob, Extension, HI/LO

571-533

 

 

 

16

Knob, Extension, ON/OFF

571-534

 

 

 

13

Latch, Draw

229-0640

 

 

 

30

Log Set Assembly

LOGS-TPB

 

 

 

 

ON/OFF Valve

15697A

 

 

 

 

Orifice Insert #49 (NG)

842-1220

 

 

 

 

Paint, Touch-up,Espresso

TOUCHUP-CES

 

 

 

 

Paint, Touch-up,Matte Black

7000-304

 

 

 

 

Paint, Touch-up,Tuscan Olive

TOUCHUP-CTO

 

 

 

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 51

D. Service Parts List(cont’d.) TIARA PETITE B

(NG, LP) Exploded Parts Diagram

Beginning Manufacturing Date: 4-04

 

Ending Manufacturing Date:

IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealer's VIP site. When ordering, supply serial and model numbers to ensure correct service parts.

Item

 

Part Description

 

Part #

#

 

Alphabetical Order

 

 

23

Pilot Assembly (NG)

 

 

230-1781

 

 

 

 

 

 

Pilot Shield

 

 

7016-164

 

 

 

 

 

12

Relief Door Assembly

 

 

7016-005

 

 

 

 

 

11

Relief Door Bracket

 

 

7016-121

 

 

 

 

 

 

Restrictor

 

 

7016-145

 

 

 

 

 

24

Side, Left or Right (interchangeable)

 

 

See chart below

 

 

 

 

 

 

Snap Disc Bracket

 

 

7009-108

 

 

 

 

 

26

Switch Bracket

 

 

7016-143

 

 

 

 

 

27

Switch, Rocker, ON/OFF

 

 

230-0730

 

 

 

 

 

28

Top

 

 

See chart below

 

 

 

 

 

31

Valve Bracket

 

 

7016-142

 

 

 

 

 

18

Valve Cover

 

 

7016-133

 

 

 

 

 

20

Valve, Gas (LP)

 

 

842-0230

 

 

 

 

 

20

Valve, Gas (NG)

 

 

842-0240

 

 

 

 

 

 

Wire Harness

 

 

7010-156

 

 

 

 

 

CAST PARTS - INDIVIDUAL PIECES

Add color code to SKU.

Example 476-0030MBK

Part Description

SKU

 

Color Code

Front

476-0030

 

BK - Matte Black

 

 

 

 

Side

476-0020

 

PBR - Porcelain Brown

Top

476-0010

 

CES - Powder Coat Espresso

 

 

 

CTO - Powder Coat Tuscan Olive

Page 52

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

E. Accessories

TIARA PETITE B

(NG, LP) Exploded Parts Diagram

Beginning Manufacturing Date: 4-04

 

Ending Manufacturing Date:

IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealer's VIP site. When ordering, supply serial and model numbers to ensure correct service parts.

Part Description

Part #

Alphabetical Order

 

Mineral Wool

200-2550

Remote Control 110 VAC

RC-SMART-HNG

Remote Control - Battery Remote Thermostat

SMART-BATT-HNG

Remote Control Thermostat with Timer

SMART-STAT-HNG

Wall Switch Kit, Off-White

WSK-21

Wall Switch Kit, White

WSK-21-W

Wall Thermostat

WH-STAT

Warming Shelves, Matte Black

TPSK-BK

Warming Shelves, Porcelain Almond

TPSK-AL

Warming Shelves, Porcelain Black

844-9520

Warming Shelves, Porcelain Brown

TPSK-BR

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 53

F. Service and Maintenance Log

Date of Service

Performed By

Description of Service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 54

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008

G. Warranty Policy

LIMITED LIFETIME WARRANTY

HEAT & GLO GAS APPLIANCE PRODUCTS

BASIC ONE-YEAR WARRANTY. HEAT & GLO, a brand of HEARTH & HOME TECHNOLOGIES INC., located at 20802 Kensington Boulevard, Lakeville, MN 55044, (“HEAT & GLO”) warrants to the original owner that your new HEAT & GLO Gas Appliance (the “Product”) will be free from defects in materials and workmanship for a period of one year from the date of installation. During the fi rst year, HEAT & GLO will replace or repair, at its discretion, any defective components at its sole cost and expense, including payment of all reasonable labor costs incurred in replacing or repairing such components. This basic warranty is subject to the conditions, exclusions and limitations described below.

EXTENDED LIFETIME COVERAGE. HEAT & GLO warrants that the fi rebox, heat exchanger, log(s), and burner will not be defective in material or workmanship during the period the Product is owned by the original owner, subject to the following conditions, exclusions and limitations described below.

CONDITIONS, EXCLUSIONS AND LIMITATIONS:

1.This warranty applies to the original owner only and is nontransferable.

2.This warranty applies only to Products installed in the United States of America or Canada.

3.This warranty is limited to the replacement or repair of defective components or workmanship and HEAT & GLO may fully discharge all obligations under this warranty by repairing or replacing, at its discretion, the defective components. The maximum amount recoverable under this warranty is limited to the purchase price of the Product and, if HEAT & GLO is unable to provide replacement or repair in an expedient and cost-effectivemanner, HEAT & GLO may discharge all obligations under this warranty by refunding the purchase price of the Product. IN NO EVENT SHALL HEAT & GLO BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES CAUSED BY DEFECTS IN THE PRODUCT.

4.Any labor and related repair charges relating to the costs and expenses of replacing or repairing defective components under the Limited Lifetime Warranty are not covered by this warranty, except as provided for under the Basic One-YearWarranty.

5.Components and parts made by other manufacturers, whether sold with the Product or added thereafter, are NOT covered by this warranty unless expressly authorized and approved by HEAT & GLO in writing.

6.Any damages caused by environmental conditions, inadequate ventilation or drafting caused by tight sealing construction of the structure, air handling devices such as exhaust fans or forced air furnaces, or other such causes are not covered by this warranty.

7.This warranty will be void if:

a)The Product is not installed, operated and maintained in compliance with local building codes and with the instructions in the Installer’s Guide, Owner’s Guide and Listing Agent Identifi cation Label furnished with the Product.

b)Any parts or components made by other manufacturers are added or used in the Product, unless expressly authorized and approved by HEAT & GLO in writing.

c)Any service work is performed on the Product by anyone other than an authorized HEAT & GLO representative.

d)The Product is damaged due to shipping, improper handling, accident, abuse or misuse.

e)Fuels other than those specifi ed in the Installer’s Guide and Owner’s Guide are used.

f ) Modifi cation was made to the Product which was not expressly authorized and approved by HEAT & GLO in writing.

EXCEPT TO THE EXTENT PROVIDED BY LAW, HEAT & GLO MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO THE DURATION OF THE WARRANTY SPECIFIED ABOVE.

Some states do not allow limitations on how long an implied warranty lasts, or do not allow exclusion or limitation of incidental or consequential damages, so those limitations may not apply to you. This warranty gives you specifi c legal rights, and you may also have other rights which vary from State to State.

If warranty service is needed you should contact your installing dealer and if the installing dealer is unable to provide necessary parts or components, contact the nearest authorized HEAT & GLO dealer or supplier.

NOTES TO CUSTOMER:

1.In order to insure proper installation, operation and maintenance HEAT & GLO strongly recommends annual servicing by an authorized HEAT & GLO dealer.

2.Please complete this information and retain this warranty in a safe place for future reference: Installation Date:______

Model #:_________________ Serial #:______________ Installing Contractor:_________________________

3.HEAT & GLO reserves the right to make changes at any time, without notice, in design, material, specifi cations and prices of the Product. HEAT & GLO also reserves the right to discontinue styles and products.

060-981E10/07

© 2007 Hearth & Home Technologies Inc.

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 55

H. Contact Information

CONTACT INFORMATION:

Heat & Glo, a brand of Hearth & Home Technologies, Inc. 20802 Kensington Boulevard

Lakeville, MN 55044

Please contact your Heat & Glo dealer with any questions or concerns. For the number of your nearest Heat & Glo dealer,

please visit our web site at www.heatnglo.com

CAUTION

Do NOT discard this manual.

Important operating and maintenance instructions included.

Read, understand and follow these instructions for safe installation and operation.

Leave this manual with party responsible for use and operation.

Your Records for Model:

Tiara Petite B

 

 

DEALERSHIP WHERE PURCHASED:

SERIAL NUMBER:

__________________

______________________________________

DATE PURCHASED:

__________________

_______________________________________

DATE INSTALLED:

__________________

_______________________________________

 

 

DEALER TELEPHONE: __________________

This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or other U.S. and foreign patents pending.

Page 56

Heat & Glo · Tiara Petite B · 7026-101K

August 1, 2008