Heat & Glo LifeStyle 6000 XLS, 6000 GDVFL User Manual

4 (1)

Heat-N-Glo Fireplace

Models:

6000 GDVFL

6000 XLS

Installers Guide

U.S. Patents 4,793,322; 4,875,464; 5,000,162 and Patents Pending Canadian Patent 1,297,746

A.G.A. Design Certified/CGA Certified and Underwriters Laboratories Listed. See Approvals Tabel on Page 1.

WARNING

IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.

-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

-What to do if you smell gas

Do not try to light any appliance.

Do not touch any electrical switch.

Do not use any phone in your building.

Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

-Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Printed in U.S.A.

Copyright 1997,

Heat-N-Glo Fireplace Products, Inc.

6665 West Highway 13, Savage, MN 55378

READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE. THIS

INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE.

WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER, SERVICE AGENGY, OR THE GAS SUPPLIER.

1.This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.

2.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

Please contact your Heat-N-Glo Fireplace dealer for any questions or concerns. For the number of your nearest Heat-N-Glo dealer, please call 612-890-8367.

446-982-A 8/97

SAFETY AND WARNING INFORMATION

READ and UNDERSTAND all instructions carefully before starting the installation. FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty.

Prior to the first firing of the fireplace, READ the Using Your Fireplace section of the

Owners Guide.

DO NOT USE this appliance if any part has been under water. Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been underwater.

THIS UNIT IS NOT FOR USE WITH SOLID FUEL.

Installation and repair should be PERFORMED by a qualified service person. The appliance and venting system should be INSPECTED before initial use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is IMPERATIVE that the unit’s control compartment, burners, and circulating air passageways BE KEPT CLEAN to provide for adequate combustion and ventilation air.

Always KEEP the appliance clear and free from combustible materials, gasoline, and other flammable vapors and liquids.

NEVER OBSTRUCT the flow of combustion and ventilation air. Keep the front of the appliance CLEAR of all obstacles and materials for sevicing and proper operations.

Due to the high temperature, the appliance should be LOCATED out of traffic areas and away from furniture and draperies. Clothing or flammable material SHOULD NOT BE PLACED on or near the appliance.

Children and adults should be ALERTED to the hazards of high surface temperature and should STAY AWAY to avoid burns or clothing ignition. Young children should be CAREFULLY SUPERVISED when they are in the same room as the appliance.

These units MUST use one of the vent systems described in the Installing the Fireplace section of the Installers Guide. NO OTHER vent systems or components MAY BE USED.

This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance MUST USE a separate vent system. Common vent systems are

PROHIBITED.

INSPECT the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.

The glass door assembly MUST be in place and sealed, and the trim door assembly MUST be in place on the fireplace before the unit can be placed into safe operation.

DO NOT OPERATE this appliance with the glass door removed, cracked, or broken. Replacement of the glass door should be performed by a licensed or qualified service person. DO NOT strike or slam the glass door.

The glass door assembly SHALL ONLY be replaced as a complete unit, as supplied by the gas fireplace manufacturer. NO SUBSTITUTE material may be used.

DO NOT USE abrasive cleaners on the glass door assembly. DO NOT ATTEMPT to clean the glass door when it is hot.

Turn off the gas before servicing this appliance. It is recommended that a qualified service technician perform an appliance check-up at the beginning of each heating season.

Any safety screen or guard removed for servicing must be replaced before operating this appliance.

i

Safety and Warning Information ......................

i

Section 1: Approvals and Codes .....................

1

Approval Listings and Codes ................................

1

Appliance Certification ......................................

1

Installation Codes ...............................................

1

High Altitude Installations ................................

1

Section 2: Getting Started ................................

2

Introducing the Heat-N-Glo Gas Fireplaces........

2

Pre-installation Preparation ...................................

2

Section 3: Installing the Fireplace ..................

5

Step 1

Locating the Fireplace .............................

5

Step 2

Framing the Fireplace ..............................

6

Step 3 Installing the Vent System ......................

7

A. Vent System Approvals ................................

7

B. Installing Vent Components ......................

13

C. Vent Termination .........................................

18

Step 4 Positioning, Leveling, and

 

 

Securing the Fireplace ...........................

23

Step 5 The Gas Control Systems ......................

23

Step 6 The Gas Supply Line .............................

24

Step 7

Gas Pressure Requirements ..................

25

Step 8

Wiring the Fireplace ..............................

26

Step 9

Finishing ..................................................

28

Step 10

Installing Trim, Logs, and

 

 

Ember Material .......................................

29

Installing the Trim.............................................

29

Positioning the Logs .........................................

30

Placing the Ember Material .............................

30

Step 11 Before Lighting the Fireplace ..............

32

Step 12

Lighting the Fireplace ..........................

32

After the Installation .............................................

32

Section 4: Maintenance and Servicing ........

33

Section 5: Replacement Parts

 

 

and Accessories .............................

35

Replacement Parts .................................................

35

Accessories .............................................................

38

Table of

Contents

ii

1

Approvals

and Codes

1

Approval Listings Appliance Certification

and Codes

The Heat-N-Glo fireplace models discussed in this

 

 

Installers Guide have been tested to certification

 

 

standards and listed by the applicable laboratories.

 

 

 

 

 

 

 

 

 

CERTIFICATION

MODEL

 

LABORATORY

TYPE

STANDARD

 

 

 

 

 

6000GDVFL

 

A.G.A./CGA

Direct Vent

ANSI Z21.50•CGA2.22

 

 

and

Decorative

 

 

 

Underwriters

 

 

 

 

Laboratories

 

 

 

 

 

 

 

6000XLS

 

A.G.A./CGA

Direct Vent

ANSI Z21.44/IR#41/CAN1-2.19

 

 

and

Wall Furnace

 

 

 

Underwriters

 

 

 

 

Laboratories

 

 

 

 

 

 

 

Installation Codes

The fireplace installation must conform to local codes. Before installing the fireplace, consult the local building code agency to ensure that you are in compliance with all applicable codes, including permits and inspections.

In the absence of local codes, the fireplace installation must conform to the National Fuel Gas Code ANSI Z223.1 (in the United States) or the CAN/CGAB149 Installation Codes (in Canada). The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes with the National Electric Code ANSI/NFPA No. 70 (in the United States), or to the CSA C22.1Canadian Electric Code (in Canada).

These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.

High Altitude Installations

A.G.A./CGA Design Certified and U.L. Listed gas fireplaces are tested and approved for elevations from 0 to 2,000 feet in the U.S.A. and from 0 to 4,500 feet in Canada.

When installing this fireplace at an elevation above 2,000 feet (in the United States), it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Input should be reduced four percent (4%) for each 1,000 feet above sea level, unless the heating value of the gas has been reduced, in which case this general rule will not apply. To identify the proper orifice size, check with the local gas utility.

When installing this fireplace at an elevation between 2,000 and 4,500 feet (in Canada), the input rating must be reduced by ten percent (10%).

When installing this fireplace at an elevation above 4,500 feet (in Canada), check with local authorities.

Consult your local gas utility for assistance in determining the proper orifice for your location.

Introducing the

Heat-N-Glo

Gas Fireplaces

Pre-installation

Preparation

Heat-N-Glo direct vent gas fireplaces are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.

The information contained in this Installers Guide, unless noted otherwise, applies to all models and gas control systems.

Gas fireplace diagrams, including the dimensions, are shown in this section.

This gas fireplace and its components are tested and safe when installed in accordance with this Installers Guide. Report to your dealer any parts damaged in shipment, particularly the condition of the glass. Do not install any unit with damaged, incomplete, or substitute parts.

The vent system components and trim doors are shipped in separate packages. The gas logs are factory installed (Model 6000GDVFL) and are packaged separately and must be field installed (Model 6000XLS). Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit. Failure to follow these instructions will void the owner’s warranty and may present a fire hazard.

The Heat-N-Glo Fireplace Products, Inc. Warranty will be voided by, and Heat-N-Glo Fireplace Products, Inc. disclaims any responsibility for, the following actions:

Installation of any damaged fireplace or vent system component.

Modification of the fireplace or direct vent system.

Installation other than as instructed by Heat-N-Glo Fireplace Products, Inc.

Improper positioning of the gas logs or the glass door.

Installation and/or use of any component part not manufactured and approved by Heat-N-Glo Fireplace Products, Inc., not withstanding any independent testing laboratory or other party approval of such component part or accessory.

ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARD.

2

Getting

Started

2

Heat & Glo LifeStyle 6000 XLS, 6000 GDVFL User Manual

When planning a fireplace installation, it’s necessary to determine:

Where the unit is to be installed.

The vent system configuration to be used.

Gas supply piping.

Electrical wiring.

Framing and finishing details.

Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.

If the fireplace is to be installed on carpeting or tile, or on any combustible material other than wood flooring, the fireplace should be installed on a metal or wood panel that extends the full width and depth of the fireplace.

3Figure 1. Diagram of the6000 Series

Step 1

The diagram below shows space and clearance

Locating the

requirements for locating a fireplace within a room.

Fireplace

 

Figure 2. Fireplace Dimensions, Locations, and

Space Requirements

Clearance Requirements

The top, back, and sides of the fireplace are defined by stand-offs.

Minimum Clearances from the Fireplace to

Combustible Materials

Glass

 

Back of

Sides of

Top of

 

Front

Floor

Fireplace

Fireplace

Fireplace

Ceiling

 

 

 

 

 

 

36 inches

0

1/2 inch

1/2 inch

3-1/2 inches

31 inches

(914 mm)

 

(13 mm)

(13 mm)

(89 mm)

(787 mm)

 

 

 

 

 

 

The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch (25 mm).

For 6000 Series Models, the back of the fireplace may be recessed 21-1/2 inches (546 mm) into combustible construction.

3

Installing the

Fireplace

4

Minimum Clearances from the Vent Pipe to

Combustible Materials

 

 

 

 

For Vertical

 

 

 

 

 

For Horizontal Sections

Sections

At Wall Firestops

 

 

 

 

 

 

 

 

 

 

 

Top

Bottom

Sides

 

Top

Bottom

Sides

 

 

 

 

 

 

 

 

 

 

 

3 inches

1 inch

1 inch

1 inch

2-1/2 inches

1/2 inch

1 inch

 

 

(75 mm)

(25 mm)

(25 mm)

(25 mm)

(63.7 mm)

(13 mm)

(25 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step 2

Framing the

Fireplace

For minimum clearances, see the direct vent termination clearance diagrams on pages 19 and 21 in this section.

Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall coverings and fireplace facing material. The diagram below shows framing reference dimensions.

CAUTION

MEASURE FIREPLACE DIMENSIONS, AND

 

VERIFY FRAMING METHODS AND WALL

 

COVERING DETAILS, BEFORE FRAMING

 

CONSTRUCTION BEGINS.

The framing headers may rest on the fireplace stand-offs.

 

 

 

 

B

 

 

 

 

C

 

 

 

 

A

 

 

 

 

Framing should be

 

 

 

 

constructed of 2 X 4

 

 

 

 

lumber or heavier.

Model

A

B

C

D

6000 Models

42

38-1/4

22

26-1/4

NOTE: DIMENSIONS SHOWN IN INCHES

Figure 3. Framing Dimensions

 

 

 

5

Step 3

Installing the

Vent System

A. Vent System Approvals

These appliances are approved to use D-series direct vent pipe components and terminations. Approved vent system components are labeled for identification.

NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE USED. Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide. The drawing below shows vent system components and terminations.

Identifying Vent Components

The vent systems installed on this gas fireplace may include one, two, or three 90° elbow assemblies. The relationships of vertical rise to horizontal run in vent configurations using 90° elbows MUST BE strictly adhered to. The rise to run relationships are shown in the venting drawings and tables. Refer to the diagrams on the next several pages.

Vent system

Vent system components

 

termination kits

 

Figure 4. Vent Components and Terminations

6

DV-45D

7

 

DV-90D

 

 

 

 

6-7/16"

 

 

 

 

6-5/32"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7/16

 

 

 

(156 mm)

 

 

 

 

 

 

(164 mm)

 

 

 

5/32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

881/2-1/2"

 

 

 

 

 

 

 

 

 

 

 

(216 mm)

 

 

 

 

8-1/2"

 

 

 

 

 

 

 

 

 

 

8

/12

11-5/8"

11-1/16"

 

 

 

 

 

 

 

(216 mm)

11 5/8

 

 

 

 

7-3/8" 5-7/8"

 

 

 

(295 mm)

11

1/16

 

 

 

 

 

 

 

(281 mm)

6-1/2"

 

 

 

3/8

5 7/8

 

 

 

 

 

5-1/16"

(187 mm) (149 mm)

 

 

 

 

 

 

6 1/2

 

 

 

 

 

 

 

 

 

(165 mm)

5

1/16

 

8-5/8"

 

 

 

 

(129 mm)

 

 

 

 

 

 

 

 

8

5/8

 

 

 

 

 

 

 

 

 

(220 mm)

 

 

 

 

 

 

 

 

11-15/16"

 

 

 

8-5/8"

 

 

 

11

15/16

 

 

 

8

5/8

 

 

 

(303 mm)

 

 

 

(220 mm)

 

 

 

 

 

 

 

 

 

 

DV-48D

DV-36D

47-3/4"

47

3/4

(1.2 m)

35-3/4"

35

3/4

(908 mm)

DV-12D

DV-09D

 

 

 

 

DV-06D

11-3/4"

 

 

 

11 3/4

 

8-3/4"

 

 

 

 

 

 

(298 mm)

8 3/4

 

5-3/4"

 

 

(222 mm)

 

5 3/4

 

 

 

 

(146 mm)

NOTE: PIPESNOTE:OVERLAPPIPES OVERLAP1 3/8 INCHES1-3/8 INCHES(34.93 mm)(34.93ATmm)EACHAT EACHJOINT.JOINT.

Figure 5. D-Series Direct Vent Component Specifications (5-inch inner pipe/8 5/8-inch outer pipe)

7

HORIZONTALVENTING

 

H

Kit No.

Max. Run

DVK-01D

 

DVK-01TRD

24" (610 mm)

Figure 6. Corner Installation

Models 6000XLS, and 6000GDVFL are tested and approved to use 45° elbows in corner installations. However, 90° elbows will result in better performance.

8

VENTING WITH ONE (1) 90° ELBOW

 

1´ MIN. (305 mm)

2´ MAX. (610 mm)

2´ MIN. (610

mm)

4´ MAX. (1.22 m)

3´ MIN. (914

mm)

6´ MAX. (1.86

m)

4´ MIN. (1.22 m)

8´ MAX. (2.48

m)

40´ MAX. (12.4 m)

8´ MAX. (2.48

m)

Figure 7. Venting with One 90° Elbow

 

 

9